| 1 | 1 | ELECTRICAL INSTALLATION OF NEW ACADEMIC BUILDING (G+2) | BI01010001010000000000000515BI0100001112 | | |
|---|
| 2 | 1.01 | S&F of 415V, 100A 4 Pole on load changeover switch sheet metal enclose suitable on flat iron frame with necessary connection. (make L&T cat. No. – CO11000OSOO) (for 2nd Building lighting VTPN | BI01010001010000000000000515BI0100001113 | 1 | item |
|---|
| 3 | 1.02 | S/F 415V, 8 way VTPN with SS enclose double-door with 100A Fore Pole MCCB as incomer (25KA) & 7 nos. 63A TP MC’s (C Series) & 3 nos. 32ASPMCB’s as outgoing, fixed concealed in wall and necessary Intre connection of suitable size of copper wire with earthing attachment & neutral link (Make – Legrand). (For AC & Lighting/Gr. Floor-02 nos) | BI01010001010000000000000515BI0100001114 | 1 | item |
|---|
| 4 | 1.03 | S/F 415V, 4 way 16-32A per way TPN MCB BDB with SS enclose double door with 63A Four Pole isolator as incomer & 6 nos. 32A & 6 nos. 20A SPMCB’s (C Series) as outgoing, fixed concealed in wall & necessary Intre connection of suitable size of copper wire with earthing attachment & neutral link (Make – Legrand) (Computer, Power point, Lighting & AC machine for main building & 2nd building). | BI01010001010000000000000515BI0100001115 | 1 | no |
|---|
| 5 | 1.04 | S/F 250V 2 + 8 way, 6-16A per way SPN MCB BDB with SS enclose double-door with 40A DP isolator as incomer & 4 nos. 16A SPMCB’s (C Series) as outgoing, concealed in wall & necessary intre connection of suitable size of copper wire with earthing attachment & neutral link. (Make – Legrand) | BI01010001010000000000000515BI0100001116 | 6 | no |
|---|
| 6 | 1.05 | S& Drawing 1.1 KV gr. 4 core 50 sq. mm PVC/Al/Ar cable mainly embedded in wall/duct with 2 x 10 SWG G. I. wire etc. mending good damages & painting including necessary inter-connection as to G. S. (From ground floor old building to new building) (Make – Polycab/Havells/KEI) | BI01010001010000000000000515BI0100001117 | 120 | nos |
|---|
| 7 | 1.06 | S & Drawing 1.1 KV gr. 2 core 10 sq. mm PVC/Al/Ar cable mainly embedded in wall/duct with 2 x 10 SWG G. I. wire etc. mending good damages & painting including necessary inter-connection as to G. S. (For Compound Light Loop in Loop out System & SPNBDB) (Make – Polycab/Havells/KEI) | BI01010001010000000000000515BI0100001118 | 145 | nos |
|---|
| 8 | 1.07 | S/F compression type gland complete with brass gland, brass ring & rubber ring for dust and moisture-proof entry & S/F socketing with finishing the end of XLPE/PVC armoured cables for 4 core 50 sq. mm | BI01010001010000000000000515BI0100001119 | 6 | nos |
|---|
| 9 | 1.08 | S/F compression type gland complete with brass gland, brass ring & rubber ring for dust and moisture-proof entry & S/F socketing with finishing the end of XLPE/PVC armoured cables for 4 core 16 sq. mm | BI01010001010000000000000515BI0100001120 | 2 | nos |
|---|
| 10 | 1.09 | S/F compression type gland complete with brass gland, brass ring & rubber ring for dust and moisture-proof entry & S/F socketing with finishing the end of XLPE/PVC armoured cables for 2 core 10 sq. mm | BI01010001010000000000000515BI0100001121 | 10 | mtr |
|---|
| 11 | 1.1 | Distribution wiring in 1.1 KV grade 2x22/0.3 (1.5 sq. mm) single core stranded ‘FR’ insulated & unsheathed copper wire (Make – Polycab/Havells) partly in 20 mm size PVC rigid conduit ‘FR’(precision make) (for ceiling & horizontal portion only) and in 19 mm bore, 3 mm thick polythene pipe (for vertical run embedded in wall), with 1x22/0.3 (1.5 sq. mm) single core stranded ‘FR’PVC insulated and unsheathed copper wire for ECC, to light/fan/call bell points with modular type (Make -Anchor/Crabtree) switch fixed on MS CRC sheet metal (16 SWG) switch board on wall complete with 2 no. “Ph & N” copper bar incl. bakelite/perspex top cover 3 mm thick and incl. 175x100x65 mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish. (Only PVC Rigid Conduit only for horizontal run & above false ceiling and vertical run concealed) Avg. Run – 8 mtr. | BI01010001010000000000000515BI0100001122 | 240 | mtr |
|---|
| 12 | 1.11 | Do do to 250V 5A 3 pin plug point incl. S&F 250V 3 pin flush type plug socket & existing switch board (Modular Type; Make – Crabtree) | BI01010001010000000000000515BI0100001123 | 30 | mtr |
|---|
| 13 | 1.12 | S/F 3 Modular Switch Board with S/F 250V 5 pin 1 no 15A Modular type plug socket/switches (Make – Crabtree) including necessary inter-connection & earthing attachment as per direction of E. I. C. (for power point) | BI01010001010000000000000515BI0100001124 | 8 | mtr |
|---|
| 14 | 1.13 | S/F of 12 Modular switch board with top cover & Modular type 1x15A power socket/switch & 3x5A, 5 pin socket/switch flushed conceal in wall including necessary inter-connection & earthing attachment (Modular Type; Make – Crabtree) & mending good the damages to original flush as to G. S. (for computers) | BI01010001010000000000000515BI0100001125 | 4 | mtr |
|---|
| 15 | 1.14 | S/F of 6 Modular switch board with S/F 250V 5 pin 2 nos SA Modular type plug socket/switches (Modular Type; Make – Crabtree) including necessary inter-connection & earthing attachment as per direction of E. I. C. (for separate plug) | BI01010001010000000000000515BI0100001126 | 12 | nos |
|---|
| 16 | 1.15 | Supplying and Drawing 1.1 KV single core stranded ‘FR’PVC insulated & unsheathed single core stranded copper wire (Make – KEI/Polycab) of the following sizes in the 20 mm/25 mm dia PVC rigid pipe and by the prelaid GI fish wire and making necessary connection as required 2 x 2.5 sq. mm + 1 x 1.5 sq. mm (for power points and computer board) | BI01010001010000000000000515BI0100001127 | 310 | nos |
|---|
| 17 | 1.16 | Supplying and Drawing 1.1 KV single core stranded ‘FR’PVC insulated & unsheathed single core stranded copper wire (Make – KEI/Polycab) of the following sizes in the 20 mm/25 mm dia PVC rigid pipe and by the prelaid GI fish wire and making necessary connection as required 2 x 6 sq. mm + 1 x 4 sq. mm (for VTPN/PBDB to SPNBDB) | BI01010001010000000000000515BI0100001128 | 160 | nos |
|---|
| 18 | 1.17 | S/F of single/twin 20/18 watt LED 4 ft. fluo. fittings suspended 25 cm below the ceiling with 2 nos 20 mm dia EI conduit supports fixed with “L” type MS clamp with the suitable size of fastener & nuts & bolts as per GS, with S/F suitable length of 3x1.5 sq. mm copper wire with painting: Single fittings with 1 no LED fluo. lamp (Make – Philips, Cat. No. – TMC 501 1xLED 18/20W) | BI01010001010000000000000515BI0100001129 | 40 | nos |
|---|
| 19 | 1.18 | S/F of single/twin 20/18 watt LED 4 ft. fluo. fittings suspended 25 cm below the ceiling with 2 nos 20 mm dia EI conduit supports fixed with “L” type MS clamp with the suitable size of fastener & nuts & bolts as per GS, with S/F suitable length of 3x1.5 sq. mm copper wire with painting: Twin fittings with 1 no LED fluo. lamp (Make – Philips, Cat. No. – TMC 501 1xLED 18/20W) | BI01010001010000000000000515BI0100001130 | 80 | nos |
|---|
| 20 | 1.19 | S/F of 1200 mm ceiling fan complete with blades, canopy, fork, rubber bush etc. with necessary Connection of flexible copper wire of 2x24/0.2 mm & app. Paint the down rod upto 30 cm. (Make – USHA Stricker Plus/Crompton AURA) | BI01010001010000000000000515BI0100001131 | 56 | nos |
|---|
| 21 | 1.2 | S/F 250 V 600 watt Electronics step type ceiling fan regular Modular type (Make – Anchor/Crabtree) | BI01010001010000000000000515BI0100001132 | 56 | nos |
|---|
| 22 | 1.21 | S/F following size of exhaust fan after making holes in wall with louver shutter & making good damages and smooth cement finish etc. as practicable as possible and providing necessary length of PVC insulated flexible copper wire for connection (Make – EPC) For 300 mm (12”) Exhaust fan | BI01010001010000000000000515BI0100001133 | 4 | nos |
|---|
| 23 | 1.22 | S/F following size of exhaust fan after making holes in wall with louver shutter & making good damages and smooth cement finish etc. as practicable as possible and providing necessary length of PVC insulated flexible copper wire for connection (Make – EPC) For 230 mm (9”) Exhaust fan | BI01010001010000000000000515BI0100001134 | 4 | nos |
|---|
| 24 | 1.23 | Supplying and Fixing MS fan clamp to two piece type for RC ceiling as per approved specification, fabricated from 40 mm x 9 mm MS flat including making good damages to building roof with satisfactory finishing and painting (As per drawing No. 475 of PWD Specification Book – May 1991) | BI01010001010000000000000515BI0100001135 | 56 | nos |
|---|
| 25 | 1.24 | S & F of required size solderless Cu socket of following Cu wire - 2.5 sq.mm. | BI01010001010000000000000515BI0100001136 | 80 | nos |
|---|
| 26 | 1.25 | S & F of required size solderless Cu socket of following Cu wires - 4 sq.mm. | BI01010001010000000000000515BI0100001137 | 12 | mtr |
|---|
| 27 | 1.26 | S & F of required size solderless Cu socket of following Cu wire - 6 sq.mm. | BI01010001010000000000000515BI0100001138 | 20 | mtr |
|---|
| 28 | 1.27 | S & erection of 80 mm dia, 1.5 mtr. Long G.I. pipe (TATA-M) with base plate in CC foundation including providing muffing 0.45x0.45x0.60 mtrs above roof level incl. S/F 20 cm x 15 cm x 10 cm C.I. loop box in muffing as to G.S. | BI01010001010000000000000515BI0100001139 | 6 | mtr |
|---|
| 29 | 1.28 | S & F 1.5 mtr. Long single G.I. Arm bracket for mini pole etc. | BI01010001010000000000000515BI0100001140 | 6 | mtr |
|---|
| 30 | 1.29 | S & D of 150 watt LED street light luminaire (make Crompton Cat. No. LSTN 1-150-CDL-A/Philips Cat. No. BRP410 LED 100 CW HE NR PC S2 PSU GR) with all other accessories driver, adapter etc. | BI01010001010000000000000515BI0100001141 | 6 | mtr |
|---|
| 31 | 1.3 | S/F of 230 V, 150 W LED flood light fittings including driver on ceiling with existing circular head frame 600 mm dia G.I. pole top arm bracket angle on 9 mtr. Pole including necessary inter connection & earthing attachment (Make – Crompton Cat. LFLN-150-CDL/60) | BI01010001010000000000000515BI0100001142 | 2 | nos |
|---|
| 32 | 1.31 | Supply & Installation of 63A, 4 Bar Cu busbar chamber with sheet metal enclosure flushed on wall and mending good the damages (Make – Havells/Bentec DECB 63) (For compound light) | BI01010001010000000000000515BI0100001143 | 1 | nos |
|---|
| 33 | 1.32 | S/F of 230V 415V 3-Phase 9A-15A MF-I starter on wall with angle iron frame for compound light & necessary inter connection (Make – L & T, Cat. No. SS97210) | BI01010001010000000000000515BI0100001144 | 1 | nos |
|---|
| 34 | 1.33 | Earthing the installation with 50 mm dia G.I. pipe as to G.S. (TATA-M pipe) for soft soil | BI01010001010000000000000515BI0100001145 | 2 | nos |
|---|
| 35 | 1.34 | S/F medium gauge G.I. pipe (ISI-Medium) protection with necessary fittings & joining materials as required – 50 mm dia | BI01010001010000000000000515BI0100001146 | 6 | nos |
|---|
| 36 | 1.35 | S/F 25 mm x 6 mm G.I. earth bus ber as per G.S. | BI01010001010000000000000515BI0100001147 | 2 | nos |
|---|