| 1 | 1 | Taking down carefully existing unserviceable aluminum / copper point wiring of any description & in any position with and including existing steel conduit / PVC Conduit / Casing caping fixed on surface/wall/angle/girder and including all fitting, accessories & fixtures such as switches, ceiling roses, pendants, regulators, sockets, etc including sunken boxes/junction boxes and making good the disturbed surface of walls, floors, ceiling etc to match with the existing surfaces including material complete all as specified and directed. | | 138 | Each Point |
|---|
| 2 | 2 | M&L for point wiring in non metallic PVC conduit of suitable size but not less than 20mm including all fittings such as elbow, bends, junction boxes, saddles, etc. on surface with and including two runs of PVC insulated unsheathed multistranded copper conductor cable (FRLSH) 1.5 sqmm nominal cross sectional area, 1100 volts grade and including one run of 1.5 sqmm (green colour) PVC insulated unsheathed multistranded (FRLSH) copper conductor cable as earth wire to be terminated in and incl MS sheet rectangular block of suitable size for mounting, switches, sockets, fan regulator etc. with 3 mm thick plastic laminated sheet cover for one light point or one fan point controlled by one switch including making good the disturbed wall and painting the same with matching to existing wall all as specified and directed by Engineer in charge. Note: M&L for making good is deemed to be included in quoted rates | | 95 | Each Point |
|---|
| 3 | 3 | All as per Srl item No 2 above but One bell/buzzer point controlled by one push button on the same board with other switches or independent with cables 1.5 sqmm Size. | | 2 | Each Point |
|---|
| 4 | 4 | All as per Srl item No 2 above but point wiring for 5 pin socket outlet, 5 Amps on same board with other switches. | | 25 | Each Point |
|---|
| 5 | 5 | All as per Srl item No 2 above but point wiring for 5 pin socket outlet, 5 Amps on independent board. | | 8 | Each Point |
|---|
| 6 | 6 | All as per Srl item No 2 above but point wiring for one five pin socket outlet, 15 Amps & 5 Amp on independent board using 2.5 sqmm two run and one run 2.5 sqmm (nominal area) stranded copper conductor cable. | | 8 | Each Point |
|---|
| 7 | 7 | Supplying & fixing switch moduler type, 5 Amps, single pole, one way , 230 volts AC circuit complete all as specified & directed. | | 128 | Each |
|---|
| 8 | 8 | Supplying & fixing switch moduler type, 5 Amps, Bell push , flush type , 230 volts AC circuit complete all as specified & directed. | | 2 | Each |
|---|
| 9 | 9 | Supplying & fixing Socket outlet 3 pin, 5A, moduler type, multipurpose, 230 volts AC circuit complete all as specified & directed. | | 33 | Each |
|---|
| 10 | 10 | Supplying & fixing switch moduler type, 15 Amps, single pole, one way , 230 volts AC circuit complete all as specified & directed. | | 8 | Each |
|---|
| 11 | 11 | Supplying & fixing Socket outlet 2 in 1, 3 pin, 5 and 15 amp flush type , flush type, 230 volts AC circuit complete all as specified & directed. | | 8 | Each |
|---|
| 12 | 12 | Supplying & fixing Ding Dong call bell AC 230 Volts single pole to be fixed on surface complete all as specified & directed. | | 2 | Each |
|---|
| 13 | 13 | Supplying & fixing ceiling rose PVC/polycarbonate,insulated body, three terminals, complete all as specified & directed. | | 90 | Each |
|---|
| 14 | 14 | Supply and fixing Lamp Holder white PVC/Polycabonate type with back plate suitable for batten fitting complete all as specified & directed. | | 5 | Each |
|---|
| 15 | 15 | Supply and fixing Stepped type electronic fan regulator flush type suitable for ceiling fans, prewired 230 volts AC 50Hz supply 100Watt complete all as specified & directed. | | 10 | Each |
|---|
| 16 | 16 | Supply, fixing, connecting and testing in replacement Industrial Earth Plug & socket with sheet metal enclosure electric driven single phase including MCB 'C' series SP 20 Amps and supplied with neutral links complete all as specified and directed. | | 5 | Each |
|---|
| 17 | 17 | M & L for Cross arms, bracings, supports, clamps and back plates fabricated from structural steel sections including nuts, bolts, washers, welding, bending colt or hot, drilling holes for bolts, at any height, in any shape or size as indicated or directed and inclusive of one primer coat, one under coat and one finishing coat of paint for mounting Air Circulator / Exhaust Fan / Ceiling Fan for fixing arrangements complete. | | 0.3 | Qtls |
|---|
| 18 | 18 | Dismantling and Taking down unserviceable existing light fittings 1X 40 Watt / 2X 40 Watt/ 70 watt or any other wattage security lihgts of any size and capacity from any location/height after disconnecting of electrical connection complete including all connected accessories all as directed by Engr-in-Charge. | | 115 | Each |
|---|
| 19 | 19 | Supplying, fixing, connecting up to existing/new ceiling rose and testing industrial box type batten LED tube light fitting suitable for and including 1x18 Watt 4 feet white colour tube lamp with polycarbonate/Acrylic diffuser more than 85%efficiency of light with LED lamp efficay as 100 Lum/W THD =15% with operating voltage range 100-300V, driver efficency >85%, surge voltage withstand 2.5 KV , power factor =0.9 including connecting with 23/0.0076 copper conductor flexible twisted three core cable including all accessories for fixing the light fitting to steel trusses / false ceiling / ceing suspended by 2 nos. Ø19/20 mm dia rigid stove enamelled black steel conduit 0.50 to 0.75 mtrs length with bell mouth threaded sockets or with chains at a distance of 700mm complete including dismantling of old fittings all as specified & directed.Make BAJAJ, Cat No. BLRB-DB118 or equivalent in Wipro/CG/Phillips | | 40 | Each |
|---|
| 20 | 20 | Supplying, fixing, connecting in at any height up to existing/new ceiling rose and testing LED luminarie made up of polycarbonate housing provided with SS toggles for fixing (supplied with the luminaire) and CRCA gear tray cum reflector finished in white powder coating, completely prewired with accessories up to terminal block suiatble for twin 18W LED tube 4' long including 02 Nos.18 W LED tube rods and including connecting with 23/0.0076 copper conductor flexible twisted three core cable and fixing arrangements for fixing the light fitting to steel trusses / false ceiling/ ceiling suspended by 2 nos. Ø19/20 mm rigid stove enamelled black steel conduit 0.50 to 0.75 mtrs length with bell mouth threaded sockets or with chains at a distance of 700mm complete including dismantling of old fittings all as specified & directed.Cat No Make BAJAJ, Cat No. BLRB-DB218 or equivalent in Wipro/CG/Phillips NOTEs for item NO 15and16 -1 ; Stove enamelled black steel conduit or cahin only will be measured and paid under relevant items of this schedule. 2 ; Quoted rate is deemed to be inclusive of conduit fittings and bell mouthed threaded sockets.complete all as specified & directed. 3 ; Quoted rate is deemed to be inclusive any misc materials required for fixing new luminaries. | | 40 | Each |
|---|
| 21 | 21 | Supplying, fixing, connecting in at any height up to existing/new ceiling rose and testing LED batten with 20 W LED light source in integral module with polycarbonate/Acrylic diffuser more than 85%efficiency of light with LED lamp efficay as 100 Lum/W THD =15% with operating voltage range 100-300V, driver efficency >85%, surge voltage withstand 2.5 KV , power factor =0.9, and connecting with 23/0.0076 copper conductor flexible twisted three/ two core cable fittings conection complete all as specified & directed all Make Bajaj /Havells/Wipro/CG/Phillips. NOTE - Quoted rate is deemed to be inclusive of any misc materials required for fixing new luminaries. | | 30 | Each |
|---|
| 22 | 22 | Supplying, fixing, connecting in at any height up to existing/new ceiling rose and testing LED batten with 10 W LED light source in integral module with polycarbonate/Acrylic diffuser more than 85%efficiency of light with LED lamp efficay as 100 Lum/W THD =15% with operating voltage range 100-300V, driver efficency >85%, surge voltage withstand 2.5 KV , power factor =0.9, and connecting with 23/0.0076 copper conductor flexible twisted three/ two core cable fittings conection complete all as specified & directed all Make Bajaj /Havells/Wipro/CG/Phillips. NOTE - Quoted rate is deemed to be inclusive of any misc materials required for fixing new luminaries. | | 5 | Each |
|---|
| 23 | 23 | Dismantling and Taking out old unserviceable copper/aluminium sub main wiring/Unarmoured cable (used as Sub main wiring) from any height of any Size and Core with all connecting accessories incld. conduit or casing caping and incld. making good to the disturbed wall and painting the same with matching paint as of existing wall including material all as specified and directed by Engineer in charge. | | 855 | RM |
|---|
| 24 | 24 | Material & Labour for Sub main wiring at any height with 2 single core PVC insulated, multi stranded copper conductor cable (FRLSH), unsheathed, 2.5 sqmm, 1100 volt grade conforming to IS drawn through and including New 20 mm size steel conduit and including one single core PVC insulated multi stranded unsheathed copper conductor cable, 2.5 sqmm,, FRLSH green in colour as continuous earth wire including all accessories and fixing arrengements, supporting clamps, bends, sockets and connecting items etc. all as specified and directed. | | 580 | RM |
|---|
| 25 | 25 | Material and labour for Sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, conforming to IS, FRLSH type, 4.0 Sqmm, 1100 volts grade, drawn through and including New PVC non metallic conduit 20 mm dia including connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable, FRLSH type, 4.0 sqmm, 1100 Volts grade,,green in colour as earth contuinity wire all as specified and directed by Engineer in charge. | | 40 | RM |
|---|
| 26 | 26 | Material and labour for Sub main wiring at any height and surface with and including two single core PVC insulated multi stranded copper conductor cable, conforming to IS FRLSH type, 4.0 Sqmm, 1100 volts grade, drawn through and including New 20 mm size steel conduit and including connected accessories and one single core PVC insulated multi stranded unsheathed copper conductor cable, FRLSH type, 4.0 sqmm, 1100 Volts grade,green in colour , as earth contuinity wire all as specified and directed by Engineer in charge. (Note for item No 2 to 4) :- Two runs of cables & continuous earth wire in new PVC casing and caping / PVC non metallic conduit/ steel Conduit will be measured as one length of sub main wiring). | | 235 | RM |
|---|
| 27 | 27 | Dismantling and drawing out old unserviceable Sub Main Aluminium/copper wiring from Existing Steel/PVC Conduit of any size and any type from any height with all connecting accessaries (excluding conduit or casing caping) and making good the disturbed wall and painting the same with matching to existing wall including material all as specified and directed by Engineer in charge. | | 4845 | RM |
|---|
| 28 | 28 | Material and labour Sub main wiring at any height including using two single core PVC insulated copper conductor cable (FRLSH) of size 1.5 sqmm 1100 volt grade conforming to IS drawn through existing Steel/ PVC conduit including 1.5 sqmm. PVC multi stranded copper conductor cable (FRLSH) green in colour for continuous earthing all as specified and directed. | | 1300 | RM |
|---|
| 29 | 29 | Material and labour Sub main wiring at any height including using two single core PVC insulated copper conductor cable (FRLSH) of size 2.5 sqmm 1100 volt grade conforming to IS drawn through existing Steel/ PVC conduit including 2.5 sqmm. PVC multi stranded copper conductor cable (FRLSH) green in colour for continuous earthing all as specified and directed. | | 3500 | RM |
|---|
| 30 | 30 | Material and Labour for Sub main wiring at any height with four single core PVC insulated copper conductor cable (FRLSH) of size 6 sqmm 1100 volt grade conforming to IS drawn through Existing Steel / PVC conduit including two single core 6.0 sqmm PVC multi stranded copper conductor cable (FRLSH) green in colour for continuous earthing all as specified and directed. (Note for item No28 to 30) - (a). Two/Four runs of wiring cable and One/two runs of earth continuity wire shall be measured as one length. | | 45 | RM |
|---|
| 31 | 31 | Disconnecting and taking down old existing damaged metallic rigid steel conduit of any size and any type from any height with all fittings complete. | | 570 | RM |
|---|
| 32 | 32 | Supply & fixing hot galvanised rigid steel conduit 25 mm dia, light grade, at any height with and incld. of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks, screws, clips, plugs, clamps etc. for securing , conduits etc. to walls,ceiling, steel joists etc. complete all as directed by Engr-in-Charge. Make - Jindal/Kalinga/ BEC. | | 280 | RM |
|---|
| 33 | 33 | Supply & fixing hot galvanised rigid steel conduit 20 mm dia, light grade, at any height with and incld. of all tees, bends, elbows, reducers, bell mouth tube ends and fixing accessories such as couplers, lock nuts, saddles, pipe hooks, screws, clips, plugs, clamps etc. for securing , conduits etc. to walls,ceiling, steel joists etc. complete all as directed by Engr-in-Charge. Make - Jindal/Kalinga/ BEC. | | 290 | RM |
|---|
| 34 | 34 | Disconnecting and taking down old switch fuse type distribution Box with MCB/fuse grip TPN/SPN DB 2 Way to 12 Way old type DB including taking out all cable connections of any description and in any position and M&L for making good the disturbed surface of walls, to match with the existing surfaces complete all as specified and directed by Engineer in charge. | | 9 | Each |
|---|
| 35 | 35 | Supply, fixing, connecting & testing sheet metal enclosures for TPN DBs (DPX 160 type ) for using MCCB as incommer suitable for triple pole and neutral, 12 way with having Copper bus bars suitable for 200 Amps rating complete Suitable for MCCB upto160 Amps as incommer and MCB as outgoing complete all as specified & directed, conforming to IS : cat No 5077 48 Metal Door Make Legrand or equivalent in Havells / C&S / Schneider . Note : MCCB , MCB ,s will be measured and paid separately under relevant item of this schedule. | | 2 | Each |
|---|
| 36 | 36 | Supply, fixing, connecting & testing sheet metal enclosures for TPN DBs (DPX 160 type ) for using MCCB as incommer suitable for triple pole and neutral, 8 way with having Copper bus bars suitable for 200 Amps rating complete Suitable for MCCB upto160 Amps as incommer and MCB as outgoing complete all as specified & directed, conforming to IS : cat No 5077 47 Metal Door Make Legrand or equivalent in Havells / C&S / Schneider . Note : MCCB , MCB ,s will be measured and paid separately under relevant item of this schedule. | | 6 | Each |
|---|
| 37 | 37 | Supply, fixing, connecting & testing double door sheet metal SPN distribution board 8 way with 100 Amps rated copper bus bar, IP 43, IK 09 class, inclusive of Neutral bar, Earthbar complete all as specified & directed. Make - Legrand/L&T/ ABB/Schenider. | | 2 | Each |
|---|
| 38 | 38 | Supply, fixing, connecting & testing double door sheet metal SPN distribution board 12 way with 100 Amps rated copper bus bar, IP 43, IK 09 class, inclusive of Neutral bar, Earthbar all as specified & directed. Make - Legrand/L&T/ ABB/Schenider. | | 2 | Each |
|---|
| 39 | 39 | Supply and fix MCCB thermal magnetic release four pole 25 KA 160 Amps Make Legrand Cat No 420057 /L&T /ABB and making conections to be fixed in DB,s complate all as specifide and directed. | | 8 | Each |
|---|
| 40 | 40 | Supplying & fixing MCB 6 to 32 Amps, single pole and neutral, \"C\" curve 10 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly complete all as specified and directed. Make - Legrand/ABB/L&T/ Seimens. | | 10 | Each |
|---|
| 41 | 41 | Supplying & fixing MCB 6 to 32 Amps, single pole, 10 kA breaking capacity with integrated label holder, sliding bottom clamp, color coded On/Off indication on dolly, complete all as specified and directed. Make - Legrand/ABB/L&T/ Seimens. | | 210 | Each |
|---|
| 42 | 42 | Removing of old HPMV / MH high bay light fittings at 12 to 15 mtr height carefully without dammaging connector or ceiling rose. If any damage made to the government fropety the same shall be repaired by the contractor without any extra cost. | | 230 | Each |
|---|
| 43 | 43 | Supply and fixing at 12 to 15 mtr height New suspended type industrial LED highbay Light Fitting with pressure die cast aluminium housing adoppts best heat dissipation 150 watt energy efficient 14000 to 15000 lumen output with high power LED including connection with and including 1.00 sqmm three core cable from connector or ceiling rose to light fitting complete all as specified and directed by Engineer-in-Charge. Make Bajaj Cat No. BGHBM150WWLED XE or equivalent in CG,C&S NOTE :- The quoted rates are deemed to be included the cost of Nut-bolts washars or clamps required to be replaced if old one are found unserviciable or of diferant size/shape for completion of work. | | 250 | Each |
|---|
| 44 | 44 | Supply & fix in repairs Dimmer Controller 240 volts 50 Hz 400 Watts Suitable for Air circulators all as specified Cat No 38659 Make Anchor Modle Penta or equivalent Cona / Leder / Polycab | | 50 | Each |
|---|
| 45 | 45 | Supply & fix in repairs Switch 16 Amp 240 Volt all as specified & directed Make Anchor penta or equivalent Cona / leader / polycab | | 115 | Each |
|---|
| 46 | 46 | Supplying & fixing Socket outlet 2 in 1, 3 pin, 5 and 15 amp flush type , flush type, 230 volts AC circuit complete all as specified & directed | | 60 | Each |
|---|
| 47 | 47 | S&F of MS box 1.6 mm thick 150 x200 mm size with and including 3 mm thick hylum sheet for mounting/fixing of two No 15 A piano type switgh , one 5/15 A multipupose socket and one 450 watt dimmer duly cutting driling etc including fixing matarial complete all as specified and directed. NOTE :- maximun boxes areto be fix on steel stucture by welding / driling of hoes etc.contractors are advoiced to see the site before quoting the rates. | | 55 | Each |
|---|
| 48 | 48 | S&F of MS box 1.6 mm thick 100 x175 mm size with and including 3 mm thick hylum sheet for mounting/fixing of one No 15 A piano type switgh , and one 450 watt dimmer duly cutting driling etc including fixing matarial complete all as specified and directed. NOTE :- maximun boxes areto be fix on steel stucture by welding / driling of hoes etc.contractors are advoiced to see the site before quoting the rates. | | 7 | Each |
|---|
| 49 | 49 | Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix MCCB thermal magnetic release four pole 25 KA 63 Amps Make Legrand Cat No 420053 /L&T /ABB with one way metal inclosure Cat No 5078 01 /L&T /ABB and making conections of cables with suitable size nutbolt etc including making good the disturbed suface of wall including material complate all as specifide and directed. | | 11 | Each |
|---|
| 50 | 50 | Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix MCCB thermal magnetic release four pole 25 KA 100 Amps Make Legrand Cat No 420055 /L&T /ABB with one way metal inclosure Cat No 5078 01 /L&T /ABB and making conections of cables with suitable size nutbolt etc including making good the disturbed suface of wall including material complate all as specifide and directed. | | 5 | Each |
|---|
| 51 | 51 | Removing of old ICTP main switch/MCCB after disconecting the incoming and out going cables and supply and fix MCCB thermal magnetic release four pole 36 KA 400 Amps with spreader links Make Legrand Cat No 422007 & 6250 08 /L&T /ABB and making conections of cables with suitable size nutbolt etc including making good the disturbed suface of wall including material complate all as specifide and directed. | | 2 | Each |
|---|
| 52 | 52 | Removing of old ICTP main switch/MCCB after disconecting the incoming and out going cables and supply and fix MCCB thermal magnetic release four pole 36 KA 630 Amps with spreader links Make Legrand Cat No 422009 & 6250 08 /L&T /ABB and making conections of cables with suitable size nutbolt etc including making good the disturbed suface of wall including material complate all as specifide and directed. | | 2 | Each |
|---|
| 53 | 53 | Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix Industrial plug and socket board TP32 Amps including plug top and MCB \"C\" curve 10 KA 32 Amps Make Legrand Cat No 5078 18 and 4086 58 /L&T /ABB including making good the disturbed suface of wall including material complate all as specifide and directed. | | 8 | Each |
|---|
| 54 | 54 | Removing of old ICTP main switch after disconecting the incoming and out going cables and supply and fix one way metal inclosure Cat No 5077 93 /L&T/ C&S and MCB \"C\" curve TPN 10 KA 32Amps Make Legrand Cat No 4086 80 /L&T/ C&S including making good the disturbed suface of wall including material complate all as specifide and directed. | | 30 | Each |
|---|
| 55 | 55 | Supply, fixing, connecting & testing sheet metal enclosures for ETPN DBs (Ekinox3 type ) for using MCB ,RCCB,RCBo as incommer suitable for triple pole and neutral, 6 way with having Copper bus bars suitable for 200 Amps ratingIP 43 -IK 09 with metal door complete all as specified & directed, conforming to IS : cat No 5076 71 Make Legrand or equivalent in Havells / C&S / Schneider . Note : MCCB , MCB ,s will be measured and paid separately under relevant item of this schedule. | | 3 | Each |
|---|