| 1 | 1 | PART A : SITC of Room AC Machines | BI01010001010000000000000515BI0100001112 | | |
|---|
| 2 | 2 | Supply & Delivery of split type fixed speed, Non-Inverter Air conditioning machine having the following major specification : EER: 3.57 ,Compressor Type: Rotary, Rated Cooling Capacity (Watts): 6600, Rated Power Input (Watts) : 1850, Air volume indoor unit(CFM.): 777, Nano Platium filter, powerful cool and wide & long airflow Air Sleep Cooling Technology, LCD remote control, Electronic metal housing box, 12 hour on and off timer, auto restart, auto swing, fan speed option (low/medium/high) etc. Refrigerant-R410A/R32. Min. BEE Star rating : 3 star,Min.capacity 2 Tr.\n[Make- Mitshubishi Electric, model no- MS/MU GK24VA or eqv. make of General/ Mitsubishi Heavy Industries.] | BI01010001010000000000000515BI0100001113 | 2 | Nos |
|---|
| 3 | 3 | Supply & Delivery of split type fixed speed, Non-Inverter Air conditioning machine having the following specification :Maximum EER: 3.59,Compressor Type: Rotary, Rated Cooling Capacity (Watts): 5200, Rated Power Input (Watts) : 1450, Air Volume indoor unit(CFM.): 777, Nano Platium filter, powerful cool and wide & long airflow Air Sleep Cooling Technology, LCD remote control, Electronic metal housing box, 12 hour on and off timer, auto restart, auto swing, fan speed option (low/medium/high) etc. Refrigerant-R410A/R32. Min. BEE Star rating : 3 star,Min.capacity 1.5 Tr.\n[Make- Mitshubishi Electric, model no- MS/MU GK18VA or eqv. make of General/ Mitsubishi Heavy Industries.] | BI01010001010000000000000515BI0100001114 | 3 | Nos |
|---|
| 4 | 4 | Supply and delivery and fixing of\n (I) Electric cable (3core 2.5sq.mm) \n(II) Copper pipe 3/8\"/1/2\" for liquid as required. (III) Copper pipe 5/8\" / 1/4\"for suction as required (IV) Insulation Foam 3/8\" / 1/2\" for liquid as required. (V) 5/8\" / 1/4\"for suction as required. \n(VI) Drain pipe of PVC for drainage connections for installation of Split A.C. both indoor and outdoor unit. | | 193 | Ft. |
|---|
| 5 | 5 | Installation,Commissioning and testing of 2.0 ton and 1.5 ton split type AC machine both indoor/outdoor including fixing of 40 x 40 x 5 mm MS angle iron frame and mending good the damages and painting with wall matching colour. | BI01010001010000000000000515BI0100001115 | 5 | Each |
|---|
| 6 | 6 | Supply and delivery of R32/R410A (if required due to long strech of outdoor unit from the indoor unit | BI01010001010000000000000515BI0100001116 | 12 | Kg |
|---|
| 7 | 7 | PART B : SITC of Walk in cold Room | BI01010001010000000000000515BI0100001117 | | |
|---|
| 8 | 8 | Walk-in Cold Room Design As per (R.N.T.C.P)\nPurpose: To supply, install, commission and test Walk in Cold Room. In places, where Walk in Cold Room is not available/ cannot be constructed, provision should be made for adequate number of refrigerators for storage purposes.\nDescription:\n1. External Dimensions of Walk in Cold Room: 6 feet x 7 feet x 9 feet high (Size of the walk-in cold room may vary based on the available space as well as storage requirements)\n2. Temperature range: Suitable to maintain temperature of 2 to 4 degree centigrade always | BI01010001010000000000000515BI0100001118 | | |
|---|
| 9 | 8.01 | 3. Panels for walls and ceiling :\n- Panel thickness: 60 mm and Internal & External Finish including ceiling made of PCGI (powder coated galvanized iron) of 0.6mm thickness\n- Insulation: Prefabricated panels made of CFC free Polyurethane Foam (PUF), 60 mm thick, with thermal conductivity: 0.16 K –BTU/HR/DEG F/INCH of Panel Thickness, Co-efficient of Heat Transfer: 0.366 W/m C, Density of PUF: 36-40 KG/CU.M | BI01010001010000000000000515BI0100001119 | | |
|---|
| 10 | 8.02 | 4. Panel Design:- \n- All the wall and ceiling corners will be connected by pre-fabricated double bends of “U” Sect and three-way gasket made of PVC to accept fit of gaps between panels and provide air tight joints without using silicone sealant\n- Corners of the Floors should will be rounded to impeded bacterial growth.\n- Metallic Cam locks for panels designed to withstand 550lbs and uprooting 750lbs maximum. \n(i)Corner Panels will be 12” wide to form L – Shape and corners cove will be rounded \n(ii) Door Dimension: 34” wide and 78” high– 01 Number. \n(iii)Type: Flush Type \n(iv) Door Door thickness: 60mm \n(v)Door sheet :0.6mm PCGI Posi-seal door closer \n(vi)Door Hinge of Positive Cam lift Hardware \n(vii)PVC Wiper Gasket with SS Bracket at Bottom of Door \n(viii) Safety Release Exit device for Opening Door from inside \n(ix) Lock Arrangement from outside with Metallic Cam lock\n(x)Door Frame/leaf perimeter is of fiberglass reinforced polyester (FRP). FRP resists rust, scratches Dents, impacts and distortion. \n(xi) Floor Design: 60mm panel for flooring with ply-board with anti-skid aluminum checkered plate. \n(xii) Temperature Indicator: Digital Type LED Display at suitable eye length outside with sensor probe hanging in air inside the WIC Room. Interior Lamps: 40W, LED, MOISTURE PROOF – 01 Number. | BI01010001010000000000000515BI0100001120 | | |
|---|
| 11 | 8.03 | 5. Refrigeration system: \n(i)Two Sets of Condensing and Evaporating units each of 100% capacity\n(ii)Auto change-over every four hour between both the sets of condensing and evaporating systems.\n(iii)These two units should function such that in case of failure of one unit, the second unit remains operational full time.\n(iv)Refrigeration capacity: 12000/18000 BTU /Hr (1/1.5TR) depending upon the size of cold room\n(v)No. of refrigeration systems: Two Sets\n(vi)Condensing Unit: Complete Two set (of compressors, coil, circuits and condensing fans\n(vii)Compressor Type: Hermetic, Make: Any reputed make (such as Copeland, Kirloskar, DANFOSS), Number of Compressors: 02(Two Nos.), Compressor Setting: Through Thermostat\n(ix) No of Circuit: 02 (Two Nos.)\n(x)No of Condensing Fan: Two\n(xi)Condensing Coil Material: “H” inner Grooved Copper tubes with Slit Aluminum\n(xii)To be located at a place easy to access for repair and with adequate safety to prevent theft/ external damage.\n | BI01010001010000000000000515BI0100001121 | | |
|---|
| 12 | 8.04 | 6.Evaporating Unit:\n(i)Complete two sets including for fan and cooling coil of suitable capacity and other accessories like copper piping, insulation, etc.) location - Ceiling Mounted\n(ii)Piping: Copper Piping and Cabling as required between condensing and evaporating unit\n(iii) Length of Copper Piping between cooling and evaporating units: 15 Feet approx. (depending upon the location of cooling unit from WIC Room)\n(iv) Refrigerant: 100% CFC free\n7. Power Supply: 230±10% V, 50-60 Hz | BI01010001010000000000000515BI0100001122 | | |
|---|
| 13 | 8.05 | 8. Spares and accessories: All required spares and accessories i.e. capacitor, relay contractor, copper tubing, etc. should be supplied to replace immediately by local electrician in case of any breakdown under guidance by vendor. | BI01010001010000000000000515BI0100001123 | | |
|---|
| 14 | 8.06 | 9. Installation and Commissioning: Including nitrogen leak test for refrigeration gas and pressure test for compressor unit. It should be validated through qualified third-party vendor as per NABL requirements with accuracy of ±0.1°C and uniformity of ±1°C. | BI01010001010000000000000515BI0100001124 | | |
|---|
| 15 | 8.07 | 10. Warranty and Service: \n(i)Three years for whole of the unit (including 5 years of warranty for the condensation unit) \n(ii)Warranty starts from installation and commissioning on site. Servicing to be done on a regular basis (minimum 6 monthly and unlimited calls in case of break\n(iii) Calibration once a year through third party with valid traceability | BI01010001010000000000000515BI0100001125 | 1 | Item |
|---|