| 1 | 1 | SHIFTING & OVERHAULING OF 2750KVA HINDUSTAN BROWN BOVRI MAKE TRANSFORMER TO INTAKE WELL SUBSTATION\n | | | |
|---|
| 2 | 1.01 | Disconnection and transportation of 2750KVA Hindustan Brown Boveri make transformer from Thermal plant\nto Intake well s/s:\nThe scope of work includes disconnection of cables on HT/MV side, bus & bus trunking on LT side, control cables, earth cables /strips, removing the foundation locks of 2750 KVA transformer ,leading , lifting, loading, transporting and erecting the same at Intake well substation located at FACT-CD Township. The transformer shall be tied firmly with vehicle using chain pulleys etc. The contractor shall take all necessary precautions to ensure that no damage is occured to the transformer during handling or transportation. Minor civil works and clearing of passages for the smooth leading of transformer at Thermal plant and at intake well substation are under the scope of contractor. | CDE-SO-HBBTR-01 | 1 | Nos |
|---|
| 3 | 1.02 | Overhauling and testing of 2750 KVA Hindustan Brown Boveri make transformer:\nThe scope of work includes draining out the existing oil, dismantling all integrals,opening the top cover, cleaning the\nassembly, checking the brazing joints,connections etc, flushing the tank and radiators by using new oil, replacing all gaskets and seals with new ones(Grade RC 70C conforming to IS 4253), painting the transformer and\naccessories after necessary surface preparation with two coats of epoxy paint of identical colour over a coat of\nsuitable primer,assembling the integrals, providing new breather with the same capacity,filling the tank and topping up the transformer up to the required conservator level with new oil, providing new terminal box at 440 V side, testing the transformer as per IS for all the routine tests, etc. New transformer oil required for cleaning the tank and other assemblies and for topping up the transformer (approximately 2400 litres of oil) will be supplied by FACT free of cost..All other materials required for the work such as gaskets, paint, primer, breather ,nuts, bolts, washers etc.shall be supplied by the contractor. Vehicle for the to and fro transportation of oil shall be arranged by contractor. However the forklift for loading / unloading the transformer oil shall be arranged by FACT free of cost subject to availability.The contractor shall furnish all the test report to FACT.Drained oil shall be transported to FACT-CD Phase1 scrap yard | CDE-SO-HBBTR-02 | 1 | Nos |
|---|
| 4 | 1.03 | Installation ,connection and commissioning of 2750 KVA\ntransformer.\nThe scope of work includes leading the transformer to the bay using guides, fixing and positioning on the foundation\nlocks. The scope of work shall also include reconnection of 3x300/400 cable on HT& MV sides using proper end termination kits, all control & earth cables / strips, cleaning the work site, charging and commissioning, All nut, bolts and washers must be replaced by new one. All tools and tackles required for the work shall be brought by the\ncontractor. The material like cable lugs, cable glands etc shall be supplied by the contractor. All the civil/mechanical\nworks including the necessary materials required for the successful completion of the work shall be under the scope of contractor. Minor civil works on the damaged walls/floors while leading the transformer shall be arranged by the\ncontractor. | CDE-SO-HBBTR-03 | 1 | Nos |
|---|
| 5 | 1.04 | End termination of following size of cable\n11KV,3 X 300 sq.mm XLPE.The scope of work includes supply of suitable sized end termination kit also | CDE-SO-HBBTR-04 | 1 | Nos |
|---|
| 6 | 1.05 | End termination of the following sizes of cables\n3.3 KV 3 X 240 sq.mm PVC cable | CDE-SO-HBBTR-05 | 2 | Nos |
|---|
| 7 | 1.06 | Fabrication and supply of LT cable terminal box:\nThe scope of work includes Fabrication; and supply of\n600x600x300 mm M.S terminal box .The thickness of the sheet shall not be less than 3 mm. and the box shall be\nneatly painted. | CDE-SO-HBBTR-06 | 1 | Nos |
|---|
| 8 | 1.07 | Disconnection, leading, loading , transporting and unloading the Kirloskar make 1600 kVA 11/3.3kV\ntransformer from Intake well pump substation to Thermal plant. The scope of work includes disconnection of power & control cables, earth cables /strips, leading the transformer to out side of the bay using guides after removing foundation locks, lifting and loading the transformer to the vehicle arranged by contractor. The transformer shall be tied firmly with vehicle using chain pulleys etc. The scope of work shall also include minor civil works if any for transporting to the thermal plant and unloading at site , leading the transformer to the bay using guides, fixing and positioning to the foundation locks. Clearing the passage from transformer bay to the vehicle shall be in contractor's scope.The contractor should take all necessary precautions to ensure that no damage is occured to the transformer during handling or transportation. The power and control circuit terminations (HV & MV) need not be connected. All tools and tackles required for the work shall be brought by the contractor. | CDE-SO-HBBTR-07 | 1 | Nos |
|---|