Power Government Departments Closing in 0 days TDR #24558027

Annual Maintenance Contract Of Grid Station Delina And 220Kv Zatl Amc Of 220/132/33Kv Delina Grid Station And 220Kv Zdtl

Issued by Government Departments · DELINA, Jammu And Kashmir
Tender Value
Ref. Documents
Estimated cost
Bid Submission
06 Jul 2020
0 days left
EMD
18000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
DELINA → Jammu And Kashmir
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Annual Maintenance Contract of grid station delina and 220kv zatl amc of 220 / 132 / 33kv delina grid station and 220kv zdtl , grid stations , power transformers: general checking / visual inspection of transformers ( i ) checking / arresting of oil leakages ( ii ) checking of auto starting of fans , external cleaning of radiators , cleaning of marshalling boxes of transformer and oltc , ( iii ) tightening of terminations , checking of oltc driving mechanism , electrical checking / testing of prv , buchholz relay , oltc surge relay / checking of alarm & trip and checking / tightening of earthing connections , checking of earth resistance of neutral and ( iv ) replacement of silca gel of breathers for 50mva power transformers , conducting of scheduled preventive tests of power transformer viz . ir , bdv , ppm , tan-delta / capacitane of bushing / winding and dga , checking oil level of conservator tank & topping of oil if required by way of dehydration / filteration including cost transformer oil for 50mva / 20mva , onload oil filteration for 53 . 33mva / 50mva / 20mva transformers , repairing of cooling fans of transformers including replacement of damaged winding , bearing if required , overhualing of circuit breaker :- checking of gas pressure , pressure switch setting etc , checking of healthiness of accumulator by checking the pre-charging pressure when building up pressure from zero , checking of operation of safety valve , cleaning of breaker units , checking of protection equipmentsand replacement of defective ones , i . e . , complete inspection and testing of sf6 type circuit breakers inclusive of operating mechanism . maintaining gas levels , venting of circuit breakers , replacement of o-rings , gas kits including circuit breaker analysis by cba etc . , fixing tripping & closing coils for 220kv / 132kv sf6 cb ( rate shall be quoted per cb ) , fixing tripping & closing coils for 33kv vcb ( rate shall be quoted per cb ) , filling of sf6 gas to maintain requisite pressure of sf6 cbs , fixing latches / remote switches , spring , toggle switch for sf6 cb and vcb , spring charging motor ( rates shall be per 220kv / 132kv cb ) , fixing latches / remote switches , , spring charging motor ( rates shall be per 33kv cb ) , fixing vacuum interrupter of repute make for 33kv vcb ( siemens / cgl / abb / bhel ) , current transformers :- checking of bellow expansion , checking of oil leakage in terminal box , checking of primary connection strips , checking of healthiness of gaskets , checking the tightness of all connections including earthing of pf terminal , cleaning of porcelain , marshalling box and junction box , checking cleanliness / tightness of all electrical connections including earthing of all marshalling boxes , ct secondary terminal , space heater and illumination , healthiness of secondary terminal bushing , checking of oil level , measurement of ir value tightening of jumpers , ct analysis with the help of cta etc . , 220kv / 132kv ct , 33kv ct , cvts / pts :- visual checking of earthing hf point ( in case it is not being used for plcc , checking of any breakage or cracks in cementing joint , cleaning of cvt capacitor stacks and tightness of terminal connections , checking of space heater and illumination in pt mks , checking and tightness of all connections including earth connections cleaning of porcelain , marshalling box and junction box , checking of healthiness of gaskets , checking of neutral earthing in cvt , healthiness of all gaskets and oil level . measurement of ir value and tightening of all connections and droppers . , 220kv / 132kv cvt , 33kv pt , surge arrestors :- checking of leakage current ( third harmonic resistive current ) , testing of counters and leakage current meters , checking of earth connections between surge arrester , surge monitor and earth , checking of leakage current after cleaning of porcelain surface , measurement of ir value and tightening of droppers and testing of counter and leakage of current meters , cleaning of insulators , checking of earth cennections between surge arrester , surge monitor and earth . , 220kv / 132kv la , 33kv la , isolators :- maintenance of linkages including transmission gears , stopper bolts . cleaning of auxiliary switch contacts and greasing with silica grease , cleaning of support insulators , termination contacts , checking of elecctrical / mechanical interlocks with e / s and cb , mounting bolts , alignment , nuts , pins , space heater , illumination , healthiness of gaskets , auxiliary contacts , alignment of earthing blades , operation of earth switch , almunium / copper flexible conductor , earth connections of structures and mb . lubrication of operating mechanism , hinges lock joints , levers , bearings , main contacts , cleaning of post insulators , tightening of clamps , bolts / nuts . , 220kv / 132kv isolator , 33kv isolator , reparing of three phase motors of isolators including replacement of damaged winding and bearing . , providing / replacement of damaged / burnt droppers , jumpers for isolators / breakers / transformers / ct / pt / pi / la etc . 132kv & 33kv switch yards , replacement of damaged clamps & connectors for isolators / breakers / transformers / ct / pt / pi / la etc . for 132kv & 33kv switch yards as per tech specs . & drgs to be provided by the department , post insulators :- checking of insulators for cracks and cleaning of insulators and tightening of droppers for 132kv & 33kv level ( rate shall be per pi ) , fixing of post insulators ( if damaged ) as per tech specs . & drgs to be provided by the department , 220kv / 132kv pi , 33kv pi , checking & tightening of bus bar & its clamps / jumpers / droppers including adjustment of sags . ( rate shall be per meter conductor ) , fixing of bus bar conductors , its droppers / jumpers including requisite clamps ( if damaged ) ( rate shall be per meter conductor ) , provididng and fixing of disc insulators ( 70kn / 90kn / 120kn ) ) , visual inspection & checking & tightening of all bolts , nuts with washers of gi latice towers , beams and equipment pipe structures , 220kv / 132kv bay , 33kv bay , providing and fixing of missing / damaged gi bolts , nuts with washers and gi lattice members of towers , beams and equipment pipe structures , illumination system :- inspection / checking healthiness of fittings & luminaries of control room , office , residential quarters , sentary post . main entry gate and repairing and replacement if required . , out door illumination system :- inspection / checking of healthiness of fittings & luminaries & mcb , lighting panels of outdoor switch yard , including high mast . , providing & replacement of damaged / burnt items . viz . mcb , fuses , fixtures , pvc frls cable , led lamps / tubes / led flood lights , in outdoor yards if required . , battery bank: inspection / checking and cleaning of battery cell terminals , application of petrolium jelly , if required , conduction of battery impendence and discharge test & checking voltage temperature , current , terminals voltage and battery discharge testing etc . , battery charger :- inspection / checking of control cards , measurement of test point voltage values , testing of dc earthfault and u / v relays , ir measurement of charger transformer , cables , checking of earthing etc . checking of charger panel and dcdb for electrical connections , cleanliness etc . , protection system :- inspection / checking of protection relays and application of ccl4 for cleaning , checking of control wiring rate shall be per panel including / installation , commisioning and testing of protective relays ( relay will be provided by department ) , cleaning of cable trenches and cables including of dressing of cables , setting right the cable trays & racks etc , auxilary transformer :- inspection / checking of bush

Corrigendum

Sr No Corrigendum Date Corrigendum Type New Submission Date
1 25-Jun-2020 EXTENSION OF DATES-I Date 06-Jul-2020

BOQ

Name of Work:Stage Contract for Annual Maintenance of Grid Stations,Delina and Associated Transmission Lines
Sl.No.Item DescriptionItem Code / MakeQuantityUnits
11GRID STATIONS
22POWER TRANSFORMERS: General checking /visual inspection of Transformers (i) Checking/arresting of oil leakages (ii) Checking of Auto starting of fans, External cleaning of radiators, Cleaning of marshalling boxes of transformer and OLTC, (iii) Tightening of terminations, Checking of OLTC driving mechanism, Electrical checking/ testing of PRV, Buchholz relay, OLTC surge relay/ checking of alarm & trip and Checking / Tightening of earthing connections, Checking of earth resistance of Neutral and (iv) Replacement of Silca Gel of breathers for 50MVA Power Transformers1No.
33Conducting of Scheduled Preventive Tests of Power Transformer viz. IR , BDV, PPM, Tan-delta /Capacitane of bushing/ winding and DGA1No.
44Checking oil level of conservator tank & topping of oil if required by way of dehydration/Filteration including cost transformer oil for 50MVA /20MVA1Litre
55Onload oil filteration for 53.33MVA/50MVA /20MVA Transformers1No.
66Repairing of cooling fans of transformers including replacement of damaged winding, bearing if required1No.
77Overhualing of Circuit Breaker :- Checking of gas pressure, pressure switch setting etc, Checking of healthiness of accumulator by checking the pre-charging pressure when building up pressure from zero, Checking of operation of safety valve, Cleaning of breaker units, checking of protection equipmentsand replacement of defective ones, i.e., complete inspection and testing of SF6 type circuit breakers inclusive of operating mechanism. Maintaining gas levels, venting of circuit breakers, replacement of o-rings, gas kits including circuit breaker analysis by CBA etc.1No.
88Fixing Tripping & Closing Coils for 220KV/132kv SF6 CB (rate shall be quoted per CB)1No.
99Fixing Tripping & Closing Coils for 33kV VCB (rate shall be quoted per CB)1No.
1010filling of SF6 gas to maintain requisite pressure of SF6 CBs1kg
1111Fixing Latches /remote Switches, Spring, Toggle switch for SF6 CB and VCB ,Spring charging motor(rates shall be per 220KV/132kv CB)1No.
1212Fixing Latches /remote Switches, ,Spring charging motor(rates shall be per 33kv CB)1No.
1313Fixing Vacuum Interrupter of repute make for 33kV VCB (Siemens/CGL/ABB/BHEL)1No.
1414Current Transformers :- Checking of bellow expansion, Checking of oil leakage in terminal box, Checking of primary connection strips, Checking of healthiness of gaskets, Checking the tightness of all connections including earthing of PF terminal, Cleaning of Porcelain, marshalling box and junction box, Checking cleanliness / tightness of all electrical connections including earthing of all marshalling boxes, CT secondary terminal, space heater and illumination, healthiness of secondary terminal bushing, checking of oil level, measurement of IR value tightening of jumpers, CT Analysis with the help of CTA etc.
1515220KV/132kV CT1No.
161633kV CT1No.
1717CVT's / PT's :- Visual checking of earthing HF point (in case it is not being used for PLCC,Checking of any breakage or cracks in cementing joint, Cleaning of CVT capacitor stacks and tightness of terminal connections, Checking of space heater and illumination in PT MKs,Checking and tightness of all connections including earth connections Cleaning of Porcelain, marshalling box and junction box, Checking of healthiness of gaskets, Checking of neutral earthing in CVT, healthiness of all gaskets and oil level. Measurement of IR value and tightening of all connections and droppers.
1818220KV/132kV CVT1No.
191933kV PT1No.
2020Surge Arrestors :- Checking of leakage current (third harmonic resistive current), Testing of counters and leakage current meters, Checking of earth connections between surge arrester, surge monitor and earth, Checking of leakage current after cleaning of porcelain surface, measurement of IR value and tightening of droppers and testing of counter and leakage of current meters, Cleaning of insulators, Checking of earth cennections between surge arrester, Surge monitor and Earth.1No.
2121220KV/132kV LA1No.
222233kV LA1No.
2323Isolators :- Maintenance of linkages including transmission gears, stopper bolts. Cleaning of auxiliary switch contacts and greasing with silica grease, cleaning of support insulators, termination contacts, checking of elecctrical / mechanical interlocks with E/S and CB, mounting bolts, alignment, nuts, pins, space heater, illumination, healthiness of gaskets, auxiliary contacts, alignment of earthing blades, operation of earth switch, almunium / copper flexible conductor, earth connections of structures and MB. Lubrication of operating mechanism, hinges lock joints, levers, bearings, main contacts, cleaning of post insulators, tightening of clamps, Bolts /Nuts.
2424220KV/132kV Isolator1No.
252533kV Isolator1No.
2626Reparing of Three phase motors of isolators including replacement of damaged winding and bearing.1No.
2727Providing / Replacement of damaged / burnt droppers, jumpers for Isolators/ breakers/transformers / CT / PT / PI/LA etc. 132kV & 33kV Switch Yards1m
2828Replacement of damaged Clamps & Connectors for Isolators/ breakers/transformers / CT / PT / PI/LA etc. For 132kV & 33kV Switch Yards as per Tech specs. & Drgs to be provided by the Department1No.
2929Post Insulators :- Checking of insulators for cracks and cleaning of insulators and tightening of Droppers for 132kV & 33kV level (Rate shall be per PI)1No.
3030fixing of Post Insulators (if damaged) as per Tech specs. & Drgs to be provided by the Department
3131220KV/132kV PI1No.
323233kV PI1No.
3333Checking & tightening of Bus Bar & its clamps/ jumpers/ droppers including adjustment of Sags. (Rate shall be per Meter conductor)1mtr
3434fixing of Bus Bar conductors, its droppers / jumpers including requisite Clamps (if damaged) (Rate shall be per meter conductor)1mtr
3535Provididng and fixing of Disc Insulators (70kN /90kN / 120kN))1No.
3636Visual inspection & checking & tightening of all Bolts, Nuts with washers of GI Latice Towers, Beams and equipment Pipe Structures
3737220KV/132kV Bay1No.
383833kV Bay1No.
3939Providing and fixing of missing / damaged GI Bolts, Nuts with washers and GI lattice members of Towers, Beams and equipment Pipe Structures1kg
4040Illumination System :- Inspection/checking healthiness of fittings & Luminaries of Control Room, Office, Residential quarters, Sentary post. main entry gate and repairing and replacement if required.1Job
4141Out Door Illumination System :- Inspection/checking of healthiness of fittings & Luminaries & MCB, lighting panels of outdoor Switch Yard, including High Mast.1Job
4242Providing & replacement of damaged/burnt items. Viz. MCB, Fuses, Fixtures, PVC FRLS cable, LED Lamps/Tubes/LED Flood lights, in outdoor Yards if required.1Job
4343Battery Bank: Inspection/checking and cleaning of battery cell terminals, application of petrolium Jelly, if required, conduction of battery impendence and discharge test & checking voltage temperature, current, terminals voltage and Battery discharge testing etc.1No.
4444Battery Charger :- Inspection/checking of control cards, measurement of test point voltage values, testing of DC earthfault and U/V relays, IR measurement of charger transformer, Cables, checking of earthing etc. Checking of charger panel and DCDB for electrical connections, cleanliness etc.1No.
4545Protection System :- Inspection / checking of Protection Relays and application of CCl4 for cleaning, checking of control wiring Rate shall be per Panel including /Installation, commisioning and testing of protective relays (Relay will be provided by Department)1No.
4646Cleaning of cable trenches and cables including of dressing of cables, setting right the cable trays & racks etc1Rm
4747Auxilary Transformer :- Inspection /checking of Bush Rods, connectors, oil level, Silica Gel condition/colour, measurement of IR, BDV /PPM, safety diaphragm, tightness of earthing connections and cleaning of Bushings \n1Job
4848L.T Switchgear Panel:\nInspection /cleaning of LT Panels, bus bar insulators, Space Heaters, thermostats etc. Tightening of all electrical connections, Checking of indicating meters/LED indicators, Check for change-over facility, check operation /indications in OFF Load condition of MCCB.1Job
4949Earthing Mat :- Measurement of earth resistivity, checking of electrical continuity of equipment earthings, tightening of earthing connectors, removal of rust from bolted earth connectors and tightening. Watering through manholes provided in the Switch Yards
5050220KV/132kV Switch Yard1Job
515133kV Switch Yard1Job
5252DC Distribution Board :- Inspection/checking of Panel, louvers, switches/sockets, MCBs, cables connections, wiring, Space Heaters, Thermostats and checking of healthiness of all emergency DC light and auto change over operation1Job
5353Fire Protection System:- Refilling of fire fighting CO2 and dry chemical powder gas cylinders, providing of Nozzle etc. Setting right Sand Buckets stand & refilling of sand buckets (rate shall be per cylinder)1No.
5454Deweeding of Switch Yards & adjacent areas within premises including Removal/Cutting of unwanted Grass/weeds / Bushes at GSS Kulgam & Mattan1m2
5555General inspection, cleaning, tightening of electrical connections of Control & Relays Pannels and DCDB & ACDB, Rates shall be per Panel1No.
5656Painting/distempering of Control Room Building, Residentail Quarters, Office, Sentry Post (Rate shall be per sq.m including material)1m2
5757Repair/maintenance of Main Gate of Grid Sub-Stations if rquired by way of welding & Painting.1Job
5858Providng and fixing of sign boards at Sub Stations Rate shall be per Board of standard size1No.
5959House Keeping Items: Providing of daily consumeable items (Colin, Harpic, Dish wash Bar, brooms, Microfiber cleaning cloth, kitchen scrub cloth etc.) for house keeping in the entire Grid Sub Station Premises viz. Control Room, Pantry, Wash Rooms, Office, Security post and perphericial areas1Job
6060House Keeping Services: Monthly basis rates for cleaning of Grid Sub Stations as per the direction of concerned In-Charge Engineer at (Rates quoted shall be per Grid Sub Station)1No.
6161Transmission Lines
6262Checking and tightening of jumpers (Rate shall be per Jumper)1No.
6363Replacement of burnt/ damaged Jumpers (Rate shall be per Jumper) including cost of material1No.
6464Replacement of damaged disc insulators1No.
6565Tension string (Rate shall be per Disc.)1No.
6666Suspension string (Rate shall be per Disc.)1No.
6767Repairing of power conductor when lowering of conductor is necessary. Complete job including laying of conductor, making of compression joint, if any, rough sagging tensioning of conductor, fixing dead end assembly etc. upto span of 500 meter tension (Rates shall be per span per phase)1No.
6868Fixing of repair Sleeves compression type for ACSR Panther /Zebra Conductor including cost of material (rate shall be per sleeve)1No.
6969Making Mid Span Compression Joint including cost of material (rates shall be per joint)1No.
7070Tightening of nuts and bolts of tower superstructures Rates shall be per Tower1No.
7171Tower weight upto 4 MT1No.
7272Tower weight more than 4 MT upto 7.5 MT1No.
7373Tower weight more than 7.5 MT1No.
7474Providing & fixing of missing GI Lattice members, Bolts, Nuts & Washers if any for Tower Superstructures1kg
7575Checking / tightening of tower footing earthing bolts and measuring tower footing resistance (Rate shall be per Tower)1No.
7676Branch cutting: In a corridor width of 15 meter for 220KV/132kV D/C1km
7777Repairing damaged conductor by using Helikal Sleeve or Bolted or by shorting method without lowering the conductor (Rate shall be per span per phase)1No.
7878Repairing / re-fixing of anti climbing devices per tower1No.
7979Providing & fixing of anti climbing devices per tower1No.
8080Fixing of Phase Plates/ No. Plates/ Danger Plates per D/C Tower Rates shall be per Tower1No.
8181Providing of Vehicles including POL for meeting urgent field services viz. fault locating, rectification and Restoration of Power Supply including shifting of restoration teams along with requisite T&P items. (Rates shall be per km of journey)1km

AI Tender Summary

OUR REF NO 24558027
AUTHORITY Government Departments
TENDER VALUE Ref. Documents
LAST DATE 06-07-2020
Authority
Authority Name Jammu And Kashmir Power Development Department
Work Description Annual Maintenance Contract of grid station delina and 220kv zatl amc of 220 / 132 / 33kv delina grid station and 220kv zdtl , grid stations , power transformers: general checking / visual inspection of transformers ( i ) checking / arresting of oil leakages ( ii ) checking of auto starting of fans , external cleaning of radiators , cleaning of marshalling boxes of transformer and oltc , ( iii ) tightening of terminations , checking of oltc driving mechanism , electrical checking / testing of prv , buchholz relay , oltc surge relay / checking of alarm & trip and checking / tightening of earthing connections , checking of earth resistance of neutral and ( iv ) replacement of silca gel of breathers for 50mva power transformers , conducting of scheduled preventive tests of power transformer viz . ir , bdv , ppm , tan-delta / capacitane of bushing / winding and dga , checking oil level of conservator tank & topping of oil if required by way of dehydration / filteration including cost transformer oil for 50mva / 20mva , onload oil filteration for 53 . 33mva / 50mva / 20mva transformers , repairing of cooling fans of transformers including replacement of damaged winding , bearing if required , overhualing of circuit breaker :- checking of gas pressure , pressure switch setting etc , checking of healthiness of accumulator by checking the pre-charging pressure when building up pressure from zero , checking of operation of safety valve , cleaning of breaker units , checking of protection equipmentsand replacement of defective ones , i . e . , complete inspection and testing of sf6 type circuit breakers inclusive of operating mechanism . maintaining gas levels , venting of circuit breakers , replacement of o-rings , gas kits including circuit breaker analysis by cba etc . , fixing tripping & closing coils for 220kv / 132kv sf6 cb ( rate shall be quoted per cb ) , fixing tripping & closing coils for 33kv vcb ( rate shall be quoted per cb ) , filling of sf6 gas to maintain requisite pressure of sf6 cbs , fixing latches / remote switches , spring , toggle switch for sf6 cb and vcb , spring charging motor ( rates shall be per 220kv / 132kv cb ) , fixing latches / remote switches , , spring charging motor ( rates shall be per 33kv cb ) , fixing vacuum interrupter of repute make for 33kv vcb ( siemens / cgl / abb / bhel ) , current transformers :- checking of bellow expansion , checking of oil leakage in terminal box , checking of primary connection strips , checking of healthiness of gaskets , checking the tightness of all connections including earthing of pf terminal , cleaning of porcelain , marshalling box and junction box , checking cleanliness / tightness of all electrical connections including earthing of all marshalling boxes , ct secondary terminal , space heater and illumination , healthiness of secondary terminal bushing , checking of oil level , measurement of ir value tightening of jumpers , ct analysis with the help of cta etc . , 220kv / 132kv ct , 33kv ct , cvts / pts :- visual checking of earthing hf point ( in case it is not being used for plcc , checking of any breakage or cracks in cementing joint , cleaning of cvt capacitor stacks and tightness of terminal connections , checking of space heater and illumination in pt mks , checking and tightness of all connections including earth connections cleaning of porcelain , marshalling box and junction box , checking of healthiness of gaskets , checking of neutral earthing in cvt , healthiness of all gaskets and oil level . measurement of ir value and tightening of all connections and droppers . , 220kv / 132kv cvt , 33kv pt , surge arrestors :- checking of leakage current ( third harmonic resistive current ) , testing of counters and leakage current meters , checking of earth connections between surge arrester , surge monitor and earth , checking of leakage current after cleaning of porcelain surface , measurement of ir value and tightening of droppers and testing of counter and leakage of current meters , cleaning of insulators , checking of earth cennections between surge arrester , surge monitor and earth . , 220kv / 132kv la , 33kv la , isolators :- maintenance of linkages including transmission gears , stopper bolts . cleaning of auxiliary switch contacts and greasing with silica grease , cleaning of support insulators , termination contacts , checking of elecctrical / mechanical interlocks with e / s and cb , mounting bolts , alignment , nuts , pins , space heater , illumination , healthiness of gaskets , auxiliary contacts , alignment of earthing blades , operation of earth switch , almunium / copper flexible conductor , earth connections of structures and mb . lubrication of operating mechanism , hinges lock joints , levers , bearings , main contacts , cleaning of post insulators , tightening of clamps , bolts / nuts . , 220kv / 132kv isolator , 33kv isolator , reparing of three phase motors of isolators including replacement of damaged winding and bearing . , providing / replacement of damaged / burnt droppers , jumpers for isolators / breakers / transformers / ct / pt / pi / la etc . 132kv & 33kv switch yards , replacement of damaged clamps & connectors for isolators / breakers / transformers / ct / pt / pi / la etc . for 132kv & 33kv switch yards as per tech specs . & drgs to be provided by the department , post insulators :- checking of insulators for cracks and cleaning of insulators and tightening of droppers for 132kv & 33kv level ( rate shall be per pi ) , fixing of post insulators ( if damaged ) as per tech specs . & drgs to be provided by the department , 220kv / 132kv pi , 33kv pi , checking & tightening of bus bar & its clamps / jumpers / droppers including adjustment of sags . ( rate shall be per meter conductor ) , fixing of bus bar conductors , its droppers / jumpers including requisite clamps ( if damaged ) ( rate shall be per meter conductor ) , provididng and fixing of disc insulators ( 70kn / 90kn / 120kn ) ) , visual inspection & checking & tightening of all bolts , nuts with washers of gi latice towers , beams and equipment pipe structures , 220kv / 132kv bay , 33kv bay , providing and fixing of missing / damaged gi bolts , nuts with washers and gi lattice members of towers , beams and equipment pipe structures , illumination system :- inspection / checking healthiness of fittings & luminaries of control room , office , residential quarters , sentary post . main entry gate and repairing and replacement if required . , out door illumination system :- inspection / checking of healthiness of fittings & luminaries & mcb , lighting panels of outdoor switch yard , including high mast . , providing & replacement of damaged / burnt items . viz . mcb , fuses , fixtures , pvc frls cable , led lamps / tubes / led flood lights , in outdoor yards if required . , battery bank: inspection / checking and cleaning of battery cell terminals , application of petrolium jelly , if required , conduction of battery impendence and discharge test & checking voltage temperature , current , terminals voltage and battery discharge testing etc . , battery charger :- inspection / checking of control cards , measurement of test point voltage values , testing of dc earthfault and u / v relays , ir measurement of charger transformer , cables , checking of earthing etc . checking of charger panel and dcdb for electrical connections , cleanliness etc . , protection system :- inspection / checking of protection relays and application of ccl4 for cleaning , checking of control wiring rate shall be per panel including / installation , commisioning and testing of protective relays ( relay will be provided by department ) , cleaning of cable trenches and cables including of dressing of cables , setting right the cable trays & racks etc , auxilary transformer :- inspection / checking of bush
Basic Detail
Tender No TLMD-VI/06 of 2020-21
Bidding Type Tender
Location
City DELINA
State Jammu And Kashmir
Key Dates
Publish Date 25 Jun 2020
Submission Date 06 Jul 2020
Open Date 08 Jul 2020
Finance
Tender Value Ref. Documents
Tender Fee 500
EMD 18000
Exemption Not Available
Document List
Tendernotice_1.pdf
SBD_Delina.pdf
8EE7F7CC-C7F1-48F1-8B1A-0987583E7BEF.html
BOQ_186444.xls

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Jun 25, 2020
11:30 IST

Tender Published

Tender notice published.

Completed
Jul 06, 2020
18:00 IST

Corrigendum-1 Issued

Clarifications on tender conditions and amendments issued.

Completed
Jul 06, 2020
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Jul 08, 2020

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
pdf

Tendernotice_1.pdf

pdf

SBD_Delina.pdf

html

8EE7F7CC-C7F1-48F1-8B1A-0987583E7BEF.html

xls

BOQ_186444.xls

TenderDetail
Loading tenders