Military Engineer Services-MES has published Provn Of Gate Light , Garden Light , Led Lights For Helipad And Children Park At Icgs Vadinar And Provn Of Isolation Transformer At Icgs Vadinar And Icgs Pipavav Under Ge ( I ) Cg Porbandar. Submission Date for this Tender is 18-06-2020. LED Light Tenders in ICGS VADINAR, ICGS PIPAVAV Gujarat. Bidders can get complete Tender details and download the document.
Name of Work: PROVN OF GATE LIGHT, GARDEN LIGHT, LED LIGHTS FOR HELIPAD AND CHILDREN PARK AND PROVN OF ISOLATION TRANSFORMER AT ICGS VADINAR AND PIPAVAV UNDER GE (I) CG PORBANDAR | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | SCHEDULE 'A' | BI01010001010000000000000515BI0100001112 | ||
2 | 1.01 | Excavating in post holes (or similar holes) each n exc 0.5 cu. m, getting out, returning, filling in and ramming earth or broken rubble mixed with earth around, in layers not exceeding 25 cm in hard/dense soil complete all as specified and directed. | 4 | Each | |
3 | 2 | Excavation in trenches not exc 1.5 m wide and not exc 1.5m in depth and getting out in hard/dense soil complete all as specified and as directed | 100 | Cum | |
4 | 3 | Returning filling in including spreading levelling watering and well ramming in layers not exc 25 cm thick complete all as specified and as directed | 80 | Cum | |
5 | 4 | Removing excavated materials to a distance not exc 50 m and depositing where directed at a level not exc 1.5 m above the starting point complete all as specified. | 20 | Cum | |
6 | 5 | M&L Wiring with 2.5Sqmm, 3 Core, PVC insulated and FR PVC Round sheathed, copper conductor (flexible) industrial cable, 1100 Volts, conforming to IS-694, drawn through DWC Pipe and connecting light fittings/ terminals with copper lugs complete all as specified and directed.\nNote: DWC pipe shall be measured and paid separetly under relevant item of BOQ.\nMake: Havells, KEI, RR KABLE, RAVIN | 900 | RM | |
7 | 6 | M&L Sub main wiring alongwith earth wire of size of 2 x10 Sqmm for phase & neutral and 1x10 Sqmm earth wire of FR grade, PVC insulated with multistranded copper conductors, single core cable conforming to IS 694,with and including PVC heavy duty (ISI marked), surface conduit of size 32mm dia with all fittings complete all as specified and directed.\nMake: Havells, KEI, RR KABLE, RAVIN | 60 | RM | |
8 | 7 | M&L Sub main wiring alongwith earth wire of size of 2 x 6 Sqmm for phase & neutral and 1x 6 Sqmm earth wire of FR grade, PVC insulated with multistranded copper conductors, single core cable conforming to IS 694,with and including PVC heavy duty (ISI marked), surface conduit of size 25mm dia with all fittings complete all as specified and directed.\nMake: Havells, KEI, RR KABLE, RAVIN | 180 | RM | |
9 | 8 | M&L Sub main wiring alongwith earth wire of size of 2 x 4 Sqmm for phase & neutral and 1x 4 Sqmm earth wire of FR grade, PVC insulated with multistranded copper conductors, single core cable conforming to IS 694,with and including PVC heavy duty (ISI marked), surface conduit of size 25mm dia with all fittings complete all as specified and directed.\nMake: Havells, KEI, RR KABLE, RAVIN | 250 | RM | |
10 | 9 | M&L Cable XLPE Insulated ,screened, PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sq mm 2 core complete all as specified and as directed by Engineer-in-Charge. | 250 | RM | |
11 | 10 | S&F Thermoplastic/ Polycarbonate DB 4 way, 240 Volts, IP-65 protection suitable for single pole and neutral MCB complete all as specified and as directed by Engineer-in-Charge. \nMake: Hensel -KV- 7104 or equivalent in Hager/L&T | 8 | Each | |
12 | 11 | S&F MCB SP 5/16 Amps, 10 KA rupturing capacity, 'C' curve, complete all as specified and as directed by Engineer-in-Charge. Make: L&T/ C&S/ Legrand/ Schneider | 8 | Each | |
13 | 12 | S&F Wall mounted Industrial Plug and socket 32/40Amps with DP MCB of capacity 40A, 'C' curve, along with enclosure all as specified and directed. Make : Legrand/L&T/C&S | 2 | Each | |
14 | 13 | S & F MCB SPN 16-32 Amps, 20 KA rupturing capacity, 'C' curve, complete all as specified and as directed by Engineer-in-Charge.. Make: L&T/ C&S/ Legrand/ Schneider | 8 | Each | |
15 | 14 | S&F LED Bollard light Cool white 6500 K of wattage 14 watt with integrated mounting base plate and driver complete with housing dark grey RAL 7043 with long life time of 50,000 hours (70% lumen maintenance @ Tc = 35ºC), IP65 protection and IK10 impact resistance including PCC (1:2:4) foundation of suitable size for mounting of light fitting including mounting pole with accessories not less than 1.2m height complete all as specified and directed. \nMake : Philips Cat No. BCP400 LED09 D CW PSU GR S1 or its equivalent in Wipro/Osram. \nNote: The Contractor should submit LM 79 & LM 80 certificates for the batch of fittings procured before incorporating fittings in the work. | 30 | Each | |
16 | 15 | S&F LED Bollard light Cool white 6500 K of wattage 17 watt with integrated mounting base plate and driver complete with housing dark grey RAL 7043 with long life time of 50,000 hours (70% lumen maintenance @ Tc = 35ºC), IP65 protection and IK10 impact resistance including PCC (1:2:4) foundation of suitable size for mounting of light fitting including mounting pole with accessories not less than 1.2m height complete all as specified and directed. \nMake : Philips Cat No. BCP400 LED09 T CW PSU GR S1 or its equivalent in Wipro/Osram.\nNote: The Contractor should submit LM 79 & LM 80 certificates for the batch of fittings procured before incorporating fittings in the work. | 40 | Each | |
17 | 16 | S&F LED Bollard Light Cool White of wattage 8.50 Watt 6500 K with with integrated mounting base plate and driver complete with housing dark grey RAL 7043 IP 65 protection, Resistant to corrosion and Better optics for uniform distribution including PCC (1:2:4) foundation of suitable size for mounting of light fitting complete all as specified and directed. \nMake: Philips Cat No. BCP400 LED04 U CW PSU GR or its equivalent in Wipro/Osram \nNote: The Contractor should submit LM 79 & LM 80 certificates for the batch of fittings procured before incorporating fittings in the work. | 110 | Each | |
18 | 17 | S&F LED Post Top lantern of capacity 70 Watt 5700 K , lumen output 5000 lm with integrated mounting base plate and driver complete with long life time of 50,000 hours (70% lumen maintenance @ Tc = 35ºC), IP66 protection and IK10 impact resistance including pole of 3.5 mtr height, hot dipped galvanised MS pole of suitable size and grey UV stabilised PU coating over galvanising, and fixed on and including PCC/RCC foundation as per manufacturer's recommendations, complete all as specified and as directed. \nMake : Philips Cat No. BGP400 LED50Y CW PC S1XT or its equivalent in Wipro/Osram \nNote: The Contractor should submit LM 79 & LM 80 certificates for the batch of fittings procured before incorporating fittings in the work. | 4 | Each | |
19 | 18 | Supply, installation and testing of Isolation transformer 10 KVA single phase with following technical specification as directed by Engr-in-Charge Make : Aplab/AE /Schneider/ITE \n(i) Input-230V, 1 phase 2 wire, 50Hz AC \n(ii) Output-230V, 1 phase 2 wire,50 Hz AC. \n(iii) Acceptable input range-±10%. \n(iv)Mode of Operation-1:1 isolation transformer. \n(v) Common mode noise rejection (Transients & Spikes) : Over 100 db \n(vi) Coupling Capacitance : Less than 0.009pF\n(vii) DC Galvanic Isolation : More than 100 M Ohms between windings & winding to Ground\n(viii)Load Regulation : ±3%\n(ix) Termination : On terminal block/brass studs of adequate rating\n | 2 | Each | |
20 | 19 | Supply and lay double wall corrugated (DWC) high density polythene pipes having corrugation on the outer wall and plain surface on the inner wall confirming to IS 16205 & IS14930 ( Part I and II) for protection of underground calbes of size 63 mm outer dia with all fittings. laid in trenches / road/ nallah or fixed along wall. poles or laid under floor (including cutting floor/Road and making good to match with existing adjoining surface etc for cable protection all as specified (excavation and earth work shall be measured and paid separately) \nMake: ALOM POLY EXTRUSIONS LTD (ALCORR)/ Gemini or equivalent | 650 | RM | |
21 | 20 | Supply and lay double wall corrugated (DWC) high density polythene pipes having corrugation on the outer wall and plain surface on the inner wall confirming to IS 16205 & IS14930 ( Part I and II) for protection of underground calbes of size 63 mm outer dia with all fittings. fixed along wall, poles or along floor complete all as specified and as directed by Engineer-in-Charge. . \nMake: ALOM POLY EXTRUSIONS LTD (ALCORR)/ Gemini or equivalent | 250 | RM | |
22 | 21 | M&L Cutting existing bituminous road to required width and length for laying under ground cables including making good road surface with 250 mm thick PCC type B-1, (1:2:4, using 20 mm graded stone aggregate) and finishing the disturbed surface to existing level, complete all as specified and as directed by Engineer-in-Charge. | 25 | RM | |
23 | 22 | M&L 300mm bore earthing, with 19mm dia and 3m long solid copper earth electrode, connected with earthing lead of size 20mm x 3mm copper strip, to the earth test point (upto 7.5m length) including excavation and earth work,with chemical compound, to reduce soil sensitivity and provision of PCC earth pit of size as shown in electrical plate no 03 includng provision of high quality earth pit cover made of polymer in lieu of CI cover indicated in the electrical plate, all as specified and as directed by Engineer-in-Charge.\nNote: The Compound (earth enhance gel) to reduce soil sensitivity should be suitable for the prevailing soil, IR value should be less than 2.0 ohms | 4 | Each | |
24 | 23 | S&F Cable junction box of size 104 x 104 x 70mm , IP 66 weather proof, suitable for PVC insulated cable of size 2.5sqmm, including provision of brass glands, all as specified and as directed.\nMake: Hensel Model No KF0404G OR Equivalent from Neptune / Hager. | 180 | Each |