8834/E8 Special Repair Of Lt Pannel , Lt Feeder Pillar Pannel And Related Acessories At Diamond Harbour Under Ge ( I ) ( Cgp ) Kolkata, KOLKATA-West Bengal

Military Engineer Services-MES has published 8834/E8 Special Repair Of Lt Pannel , Lt Feeder Pillar Pannel And Related Acessories At Diamond Harbour Under Ge ( I ) ( Cgp ) Kolkata. Submission Date for this Tender is 20-06-2020. Feeder Pillar Tenders in KOLKATA West Bengal. Bidders can get complete Tender details and download the document.




Tender Notice

24450225
Corrigendum : 8834/E8 Special Repair Of Lt Pannel , Lt Feeder Pillar Pannel And Related Acessories At Diamond Harbour Under Ge ( I ) ( Cgp ) Kolkata
Open Tender
Indian
West Bengal
KOLKATA
20-06-2020

Tender Details

8834/E8 Special Repair Of Lt Pannel , Lt Feeder Pillar Pannel And Related Acessories At Diamond Harbour Under Ge ( I ) ( Cgp ) Kolkata

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 04-Jun-2020 BOQ corrigendum 1 BOQ 20-06-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 24400.0 /-
Tender Value
INR 12.20 Lakhs /-

BOQ Items

Name of Work: SPECIAL REPAIR OF LT PANNEL, LT FEEDER PILLAR PANNEL AND RELATED ACESSORIES AT DIAMOND HARBOUR UNDER GE (I) (CG&P) KOLKATA
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Taking down old feeder piller pannel including all necessary items with lifting and carrying complete all as specified and as directed. item1 3 EACH
2 2 Taking down old unserviceable HT / LT cables of any size complete all as specified and as directed. item4 710 RM
3 3 Excavation in trenches, n. exc. 1.5m wide and n. exc. 1.5m in depth; for laying of cable, n. exc 10 sqm on plan and n exc 1.5 m in depth and getting out in soft/loose soil. item5 40 CUM
4 4 Returning, filling in, including spreading, levelling, watering and well ramming in layers not exc 25 cm. item6 30 CUM
5 5 Removing excavated material n. exc. 50 m and depositing where directed at a level n. exc. 1.5 m above the starting point item7 10 CUM
6 6 M&L fine sand, filling in trench for cable cushioning and gently punned down by manually with hands complete all as specified and directed. item8 20 CUM
7 7 Material and labour Brick protection cover to LT underground cable with Sub Class 'B' over burnt laid dry and flat abutting each other with gaps between adjacent bricks not exceeding 10 mm complete specified and directed item9 3000 EACH
8 8 M&L PCC 1:4:8 type D2 type (using 40 mm graded crushed stone aggregate) as in pole foundation complete all as specified and directed. item10 3 CUM
9 9 Supply and laying tubes 40 mm dia steel water tube light grade galvanised with all fittings laid in trenches complete all as specified and as directed. item11 30 RM
10 10 Supply and laying tubes 80 mm dia steel water tube light grade galvanised with all fittings laid in trenches complete all as specified and as directed. item12 20 RM
11 11 Supply and laying in trenches or fixing or passing through pipes or fixed to wall/pole 1100 volts grade PVC/ XLPE insulated armoured heavy duty electric cables (conforming to IS :1554(Part- I) / IS 7098 (Part- I)with aluminium conductor of cross sectional area 150 Sqmm 3.5 core complete all as specified and as directed. item13 290 RM
12 12 Supply and laying in trenches or fixing or passing through pipes or fixed to wall/pole 1100 volts grade PVC/ XLPE insulated armoured heavy duty electric cables (conforming to IS :1554(Part- I) / IS 7098 (Part- I)with aluminium conductor of cross sectional area 95 Sqmm 3.5 core complete all as specified and as directed. item14 200 RM
13 13 Supply and laying in trenches or fixing or passing through pipes or fixed to wall/pole 1100 volts grade PVC/ XLPE insulated armoured heavy duty electric cables (conforming to IS :1554(Part- I) / IS 7098 (Part- I)with aluminium conductor of cross sectional area 50 Sqmm 3.5 core complete all as specified and as directed. item15 220 RM
14 14 M & L Cable jointing kit for 1100 V grade cable for straight though (cold applied insulation and sealing system) heat shrink type joint complete with jointing material and accessories suitable for 3.5 core XLPE armoured aluminium conductor cable of size 120 - 185 sqmm incl cutting of old jointing material including taking down old one complete all as specified and as directed. (Make -Raychem Kit no -RLVJ S3 or equivalent of M-seal / Denson ) item16 3 EACH
15 15 All as per item no. 14 above but cable of size 70 - 95 sqmm incl cutting of old jointing material including taking down old one complete all as specified and as directed. (Make -Raychem Kit no -RLVJ S2 or equivalent of M-seal / Denson ) item17 4 EACH
16 16 All as per item no. 14 above but cable of size 25 - 50 sqmm incl cutting of old jointing material including taking down old one complete all as specified and as directed. (Make -Raychem Kit no -RLVJ S1 or equivalent of M-seal / Denson ) item18 4 EACH
17 17 Supply, Install, design, testing and commissoning outdoor floor mounted pannel of size 1200mm x 800mm x 600mm cubical size near voltage stabilizer Room NCB side. Panel made of 2.0 mm thick MS CRCA sheet and angle iron structure 40 x 40 x 6 mm, CPRI approved varmin proof compartmentalized, type of size as required including loking arrangement and two coat of powder coated paint over a coat of red oxide primer, fixed in floor with MS angle iron 40 x 40 x 6 mm frame structure and grouted with PCC M-15 (Nominal mix) using 20 mm graded stone aggregate with and including 2.5 sqmm single core copper FRLS/HRFR wired connection, brass cable gland for cable entry etc. having following accessories :- (a) Copper bus bar electrolytic grade rectangular 630 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-04 set (b) LED lamps 03 Nos (R, Y, B) - 7 Set (c) Digital Voltmeter 0-500 Volts - 01 No (d) Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed,industrial multistrand copper cable 1100 V grade cable , including provision of lugs/thimbles on either ends of cable. (e) Digital Ammeter - 01 No. (f) Inter connection of MCCBs with bus bar with suitable size copper strip/PVC insulated, unsheathed , multi stranded copper conductor cable, 1100 volts grade. (g) Selector Switch - 02 Nos. INCOMING :MCCB 100 Amps 4 Pole, 25 KA Braking Capacity- 01 Nos Make: Legrand Cat No. 4200 55 or equiv in Siemens/Schneide. OUTGOING : (1) MCB TPN 63 Amps - 01 Nos, Make : Legrand cat No 4086 83 (2) MCB TPN 32 Amps - 02 Nos, Make : Legrand cat No 4086 80 (3) MCB SPN 32 Amps - 01 Nos, Make : Legrand cat No 4086 17 (4) MCB SPN 20 Amps - 03 Nos, Make : Legrand cat No 4086 15 (5) MCB SP 20 Amps - 01 Nos, Make : Legrand cat No 4085 93 (6) Power contractor 4 pole MNX 32 Amps - 01 Nos (7) street light timer FM1 / Quartz Daily 240V AC Base/DIN Mounting analogue type - 01 Nos Make : L & T Cat no. AUTS01ANA00 or equivalent of item19 1 EACH JOB
18 18 Supply, Install, design, testing and commissoning outdoor floor mounted pannel of size 1200mm x 800mm x 600mm cubical size near MES office across the road NCB side. Panel made of 2.0 mm thick MS CRCA sheet and angle iron structure 40 x 40 x 6 mm, CPRI approved varmin proof compartmentalized, type of size as required including loking arrangement and two coat of powder coated paint over a coat of red oxide primer, fixed in floor with MS angle iron 40 x 40 x 6 mm frame structure and grouted with PCC M-15 (Nominal mix) using 20 mm graded stone aggregate with and including 2.5 sqmm single core copper FRLS/HRFR wired connection, brass cable gland for cable entry etc. having following accessories :- (a) Copper bus bar electrolytic grade rectangular 630 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-04 set (b) LED lamps 03 Nos (R, Y, B) - 7 Set (c) Digital Voltmeter 0-500 Volts - 01 No (d) Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed,industrial multistrand copper cable 1100 V grade cable , including provision of lugs/thimbles on either ends of cable. (e) Digital Ammeter - 01 No. (f) Inter connection of MCCBs with bus bar with suitable size copper strip/PVC insulated, unsheathed , multi stranded copper conductor cable, 1100 volts grade. (g) Selector Switch - 02 Nos. INCOMING :MCCB 125 Amps 4 Pole, 36 KA Braking Capacity- 01 Nos Make: Legrand Cat No. 4200 96 or equiv in Siemens/Schneide. OUTGOING : (1)MCCB 100 Amps 4 Pole, 25 KA Braking Capacity- 01 Nos Make: Legrand Cat No. 4200 55 or equiv in Siemens/Schneide(2) MCCB 63 Amps 4 Pole, 25 KA Braking Capacity- 02 Nos Make: Legrand Cat No. 4200 53 or equiv in Siemens/Schneide (3) MCB TPN 32 Amps - 01 Nos, Make : Legrand cat No 4086 80 (4) MCB SPN 20 Amps - 02 Nos, Make : Legrand cat No 4086 15 (5) MCB SP 20 Amps - 01 Nos, Make : Legrand cat No 4085 93 (6) Onload Changeover switch cubical type I-O-II for 400 Amps, 4 POLE, Cat - CO44000OOOO of Make -L&T or equiv in C&S/GE item20 1 EACH JOB
19 19 Supply, Install, design, testing and commissoning outdoor floor mounted pannel of size 1200mm x 800mm x 600mm cubical size near Bridge, SSB side. Panel made of 2.0 mm thick MS CRCA sheet and angle iron structure 40 x 40 x 6 mm, CPRI approved varmin proof compartmentalized, type of size as required including loking arrangement and two coat of powder coated paint over a coat of red oxide primer, fixed in floor with MS angle iron 40 x 40 x 6 mm frame structure and grouted with PCC M-15 (Nominal mix) using 20 mm graded stone aggregate with and including 2.5 sqmm single core copper FRLS/HRFR wired connection, brass cable gland for cable entry etc. having following accessories :- (a) Copper bus bar electrolytic grade rectangular 630 Amps full for phase and half for neutral mounted on epoxy insulators with colour coding PVC sleeves.-04 set (b) LED lamps 03 Nos (R, Y, B) - 7 Set (c) Digital Voltmeter 0-500 Volts - 01 No (d) Internal wiring of panel board, metering equipment with suitable size PVC insulated, unsheathed,industrial multistrand copper cable 1100 V grade cable , including provision of lugs/thimbles on either ends of cable. (e) Digital Ammeter - 01 No. (f) Inter connection of MCCBs with bus bar with suitable size copper strip/PVC insulated, unsheathed , multi stranded copper conductor cable, 1100 volts grade. (g) Selector Switch - 02 Nos. INCOMING :MCCB 200 Amps 4 Pole, 36 KA Braking Capacity- 01 Nos Make: Legrand Cat No. 4202 48 or equiv in Siemens/Schneide. OUTGOING : (1)MCCB 125 Amps 4 Pole, 36 KA Braking Capacity- 01 Nos Make: Legrand Cat No. 4200 96 or equiv in Siemens/Schneide (2) MCCB 100 Amps 4 Pole, 25 KA Braking Capacity- 02 Nos Make: Legrand Cat No. 4200 55 or equiv in Siemens/Schneide (3) MCCB 63 Amps 4 Pole, 25 KA Braking Capacity- 01 Nos Make: Legrand Cat No. 4200 53 or equiv in Siemens/Schneide (4) MCB TPN 32 Amps - 01 Nos, Make : Legrand cat No 4086 80 (5) MCB SPN 20 Amps - 02 Nos, Make : Legrand cat No 4086 15 (6) MCB SP 20 Amps - 01 Nos, Make : Legrand cat No 4085 93 or equiv in C&S/GE item21 1 EACH JOB
20 20 M&L Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6 mm burried directly in ground vertically to a depth not less than 2.25 mtr below ground level with top edge of earth plate at a depth not less than 1.5 mtr below ground level connected to galvanised iron or steel earth lead MS flat 32 x 6 mm by means of nuts, bolts, check nuts and washers of galvanised iron or steel, earth wire protected by galvanised iron pipe 50 mm dia (light grade) and connected to main switch board or main control panel as directed and as specified including concrete pit in PCC (1:3:6) type C1 pre-cast RCC cover slab 5 cm thick of size as shown reinforced with 8 mm dia TMT / deformed bars 100 mm c/c both ways including one handle made of 12 mm dia MS bars of length 500 mm, funnel, wiremesh 20 mm bore galvanised iron pipe medium grade for watering, charcoal and salt in alternate layers including necessary earth work complete all as shown in elect plate No. 3 of SSR Part I, all as directed . item23 6 EACH SET