Internal Electrification In E Name Office Staff Quters Apf Pastiside Testing Lab And Ac Etc

BOQ

Name of Work:Internal Electrification in lighting system in farmar help booth, welcome room, canteen/dhaba, driver rest room, internal electrification, lighting system and S/I of split AC & its related works in E-NAM office etc NMY RobertsganjNote-(1) Above Rate are without GST. (2) GST will be paid extra maximum 12% on the above cost as per GST Rule.
Sl.No.Item DescriptionItem Code / MakeQuantityUnits
11Wiring point for light with 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in heavy guage rigid steel conduit pipe partly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, complete with 14 SWG copper earth continuity wire, piano type switch & ceiling rose/angle/batten holder on 3mm thick phenolic paminated backalite sheet etc complete in all respect as directed including matching colour wash. Add for light / fan points with modular type switch in place of piano type switch.138C+187A108Nos.
22Wiring point for Two way with 1.5 sq. mm.FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit pipe partly concealed in the wall and partly laid in slab alongwith the reinforcement before concreting, modular switch & ceiling rose/angle/batten holder on 1.5 sqmm FRLSHPVC insulated multistrandcopper conductor cable as earth wire drawn inside including matching color wash. Add for light / fan points with modular type switch in place of piano type switch.139C+187A3Nos.
33Wiring point for fan /fresh air fan (light duty exhaust fan) with 1 sq.mm. FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit pipe partly concealed in the wall, and partly laid in slab alongwith the reinforcement before concreting, complete with 1.5 sq.mm. FRLSH PVC insulated multistrand single core copper conductor cable as earthwire drawn inside the conduit, piano type switch & ceiling rose/angle batten holder on 3mm thick phenolic laminated backelite sheet etc. completion in all respects including matching colour wash. Add for light / fan points with modular type switch in place of piano type switch.140c+187C36Nos.
44Wiring point for Plug with 1 sq.mm. FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit pipe partly concealed in the wall, and partly laid in slab alongwith the reinforcement before concreting, complete with 1.5 sq.mm. FRLSH PVC insulated multistrand single core copper conductor cable as earthwire drawn inside the conduit, piano type switch & socket etc. completion in all respects including matching colour wash.. Add for plug point with modular switch & socket in place of piano type switch & socket.141c+187D36No.
55Wiring point for exhaust fan with 1.5 sq.mm. FRLSH PVC insulated multistrand single core copper conductor cable in PVC conduit pipe partly concealed in the wall, and partly laid in slab alongwith the reinforcement before concreting, complete with 1.5 sq.mm. FRLSH PVC insulated multistrand single core copper conductor cable as earthwire drawn inside the conduit, piano type modular switch & ceiling rose/angle batten holder on 3mm thick phenolic laminated backelite sheet etc. completion in all respects including matching colour wash.144c+187D7Nos.
66Wiring point for HPSV/SV Lamp with 2.5 sq.mm. FRLSH PVC insulated multi strand single core copper conductor cable in PVC conduit pipe partly concealed in the wall, and partly laid in slab along with the reinforcement before concreting, complete with 1.5 sq.mm. FRLSH PVC insulated multi strand single core copper conductor cable as earth wire drawn inside the conduit, piano type modular switch & ceiling rose/angle batten holder on 3mm thick phenolic laminated Bakelite sheet etc. completion in all respects including matching colour wash.143C+187D4Nos.
77Supply and wiring of sub main with two number 1.5 sqmm. FRLSH PVC insulated 1100 V grade single core multistrand single core copper conductor cable in 20mm dia heavy PVC conduit concealed in wall, and partly laid in slab alongwith the reinforcement before concreting, complete with 2.5 sq.mm. FRLSH PVC insulated multistrand single core copper conductor cable as earthwire drawn inside the conduit,including matching color wash etc. complete in all respects.1307495Mtr.
88S/F of 16 SWG MS drum with luvers duly painted including making hole in the wall for Exhaust Fan & finishing properly, complete in all respects.221 C1350Mtr.
99Supply and wiring of submain with two number 4 sq. mm. FRLSH PVC insulated 1100 V grade multistrand single core aluminium conductor cable in 25 mm dia heavy guage rigid steel conduit partly concealed in wall and partly laid in slab alongwith reinforcement before concreting, with one number 14 SWG copper earth continuity wire including matching colour wash etc. complete in all respect. 222C95Mtr.
1010Supply and wiring of 2 number 6 sq. mm. FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in 32 mm dia heavy guage rigid steel conduit partly concealed in wall and partly laid in slab alongwith reinforcement before concreting, with two number 10 SWG copper earth continuity wire including matching colour wash etc, complete in all respect.278C195Mtr.
1111Supply and wiring of 4 number 16 sq. mm. PVC insulated 1100 V grade single core Copper conductor cable in 40 mm dia PVC conduit partly concealed in wall and partly laid in slab alongwith reinforcement before concreting, with two number 10 sq mm single core Copper conductor cable as earth continuity wiredrawn in coudit including matching colour wash etc, complete in all respect.279C220Mtr.
1212S/F of recess/surface/Pendent mounting round 6 watt to 8 watt LED down lighter having powder coated die cost aluminium housing with extended heat sink, diffuser/reflector & driver set complete in all respect. CAT AAA 660-880 system lumens, 110lm/W, PF>0.95, THD<10% at full load CRI>80, with 5years warantee.140114Nos.
1313Supply and fixing of recess/ Surface/ Pendent mounting round 12 to 15 Watt LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set complete in all respect Cat AAA140220Nos.
1414Supply and fixing of LED Tube Light with batten suitable for up to 1 X 22 watt LED tube light complete including tube etc on surface complete in all respect. Cat AAA 14131413133Nos.
1515Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 110 to 130 Watt. Confirming to IP 65 and above Protection complete in all respect. 1424142471Nos.
1616S/F of decorative 40 watt to 45 watt 4000-4500 lumens LED Post top indirect light luminaire having pressure die cost aluminium body& clear glass with driver set Conforming to IP 65 & above protection having complete in all respect. 4400-4950 system lumens, 110lm/W, PF>0.95, THD<20% at full load CRI>80, with 5years warantee. CAT AAA14432Nos.
1717Supply and laying of aluminium conductor PVC insulated armoured served sheathed cables 1100 Volts grade at a depth of 750 mm below ground level over a cushion of 75 mm. thick sand all around and protected with burnt bricks on sides and on top. On surface the cable run shall be fixed on M.S. clamps etc. of suitable size or as directed by the Engineer-Incharge, complete in all respect. The armouring of the cable shall be properly connected with the earth conductor by clamps etc. 501(h) 10 sq. mm 4 core70Mtr.
1818501(k) 35 sq. mm 3.5 core130Mtr.
1919501(n) 95 sq. mm 3.5 core30Mtr.
2020Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. 503(g) 6 sq. mm 4 core6Nos.
2121503 (h) 10sq.mm 4 core10Nos.
2222503 (i) 16sqmm 4 core12Nos.
2323503 (k) 35sqmm 3.5 core5Nos.
2424503 (n) 95sqmm 3.5 core503 n1Nos.
2525Supply and fixing of one number 8 SWG G.I. wire in 15mm dia. G.I. pipe for earthing, laid in ground or in wall duly concealed including the cost of cement, sand, labour, T&P other material required for proper completion of the work as directed at site.72250Mtr.
2626Supply & Erracetion of factory fabricated & wired metal clad dust and vermin proof floor mounting, M.S. Channel Base with bottom and top cable entreis Electrical control panel with TPN MCCB's (Four Pole 36 KA with thermal magnatic release)Switches Complete and instrument chamber etc.complete in all respects. The instrument chamber shall be separate and shall comprise of flush type digital metering system for phase to phase voltage and single phase voltage, current and other parameters(KVA,P.F,KW etc) in each phase with touch type selector switches for different readings, instrument fuses, current transformer etc. The panel board shall have suitable capacity electrolytic alumininum busbars as per IS8623 or above istulated with heat shrink sleeving and mounted on non hygroscopic supports such as CMC/BMC support with deteachable side covers and shall be suitable for extension on the sides. The MCCB's shall be complete with suitable cable end boxes, compression glands and indicating lamp on incoming etc. The Job includes the grounting of the board as per directions of Engineer-in charge. All out goings of 100 Amp and above shall have an Ammeter. The panel board shall be fabricated with CRCA sheet with a minimum thickness of 1.6mm/2mm. Cubicle type switch board shall be of cat A & B Only. Incoming 200 Amp. MCCB-1 No Outgoing 100 Amp. MCCB-1 No & 63 Amp. MCCB-3 Nos. \n812C1No.
2727Supply and fixing of brass nickle plated compression gland for PVC insulated & armoured served sheathed, underground cable including rubber ring etc. complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of Engineer-Incharge. 504 (b) 6 sqmm504b44Nos.
2828504 (c) 10sqmm504 c64Nos.
2929504 (d) 16sqmm504 d85Nos.
3030504 (f) 35sqmm504 f3Nos.
3131504 (g) 50sqmm504 g1Nos.
3232504 (i) 95sqmm504 i3Nos.
3333Supply and burring of Safe Earthing Electrode T-39, ( Hot Dip Galvanized), Length up to 3000mm, outer door pipe 76mm inner Dia 38 mm, terminal Dia 12mm, outer GI pipe of 16 swg and inner GI pipe of 12 swg with Hot Dip Galvanization up to 100 micron filled with crystalline conductive mixture (CCM) having anti corrosive & conductive property with 50 kgs activated soil (BFC) capable of reducing the soil resistivity with good mixture of retaining capacity along with 30 cm square C.I. frame with hinged cover & masonry housing. (from apron to switch board, of 25mm x 3mm G.I. strip will be extra) make as App. in UP PWD & CPRI Certified 725 D725d4Nos.
3434S/L of 25mm x 3mm G.I. strip from earth electrode directly in the ground as required complete in all respects 71671650Mtr.
3535Supply and fixing of LED Tube Light with batten suitable for up to 1 X 22 watt LED tube light complete including tube etc on surface complete in all respect. CAT- AAA1024A2Nos.
3636S & F surface/Flush mounting 12 ways SPN distribution board with additional metal door without MCB complete in all respect, as Direct by Engineer in Charge. 1025A1025A16Nos.
3737S & F surface/Flush mounting 4ways TPN distribution board with additional metal door without MCB complete in all respect,as directed at site by Engineer in charge.1026A4Nos.
3838S&F surface/flush mounting 4 ways SPN distribution board with additional metal door without MCB complete in all respect, as directed at site by Engineer in charge. 1022A1022A1Nos.
3939S&F of 6 Amp to 32 Amp. MCB (10 KA) C Curve1002116Nos.
4040S&F of 6 Amp to 40 Amp. MCB (10 KA) C Curve100924Nos.
4141S&F of 6 Amp. to 40 Amp. 4 pole MCB (10 KA) C Curve1901A3Nos.
4242S&F of 40 Amp. 4 pole MCB (10 KA)1020A4Nos.
4343S&F of 63 Amp 4 pole MCCB (10 KA) 1021 A1021A5Nos.
4444S/O 1200 mm Ceiling Fan with fan Motor of AC Permanent insulation capacitor rating conforming BEE 5 Star raiting & IS 374/ 79 & also compite V, 50 Hz., I-ph AC the fan assemble should cnsists of down rod blades, Shackle canopies etc. & with double ball bearing system. 1501150159Nos.
4545Erection and testing of ceiling fan and regulator for room height upto 3.5 metres including supply of 3mm thick G.I.Pipe19mm dia. Duly painted, complete in all respect.111633Nos.
4646Erection and testing of exhaust fan on the existing hole with suitable size of rag bolts, nuts and washers etc., complete in all respect. 112011207Nos.
4747S/F of 16 SWG MS drum with luvers duly painted including making hole in the wall for Exhaust Fan & finishing properly, complete in all respects. 1122A1122A7Nos.
4848S/L of 1800mmX900mmX12mm thick chequered rubber mating of tested quality. 113611361Nos.
4949Supply and fixing of power plug with 20 Amp./250 volt flush type modular switch and 5 pin 20 A/250 volt flush type universal modular socket switch on concealed M.S box including supply of all material, labour T&P etc. required for proper completion of work. 1139A1139A30Nos.
5050Supply and fixing hexagonal fan box with hexagonal side of approx 80mm in length fabricated from 16 SWG MS sheet incorporating 10mm dia. M.S. round bar duly bent for supporting fan hanger duly painted with red oxide and screwing arrangement with wiring conduit laid in the R.C.C. roof before concreting alongwith supply of all material, labour, T&P etc. required for proper completion of the work.114933Nos.
5151Supply and fixing of electronic fan regulator( Modular) 120-280 V. ISI marked, on the existing switch board including making connections, required material, labour T&P etc. for proper completion of work to the satisfaction of Engineer in charge of work.1203C33Nos.
5252S/F of 15/16A Modular type Switch DSR 2018DSR28Nos.
5353S/F of 03 Pin 5/6A Modular type Socket DSR 2018DSR56Nos.
5454S/F of 6 Modules GI Box alongwith modular base&cover plate for modular switch in recess etc. as required DSR 2018DSR28Nos.
5555Wiring for circuit/ submain wiring 2X2.5sqmm+1X1.5sqmm earth wire of FRLSH PVC insulated copper conductor single core cable in surface/ recessed medium class PVC conduit as required. DSR 2018DSR390Mtr.
5656S/F of suitable size GI Box with modular plate & cover in front on surface or in recess including providing & fixing 25A modular socket outlet & 25A modular SP MCB C cure including connections, painting etc as required. power plug with 20A/250V flush type modular switch and 5 pin 20A/250V flush type universal modular socket switch on concealed MS box including S/o all material, labour, T&P etc. required for proper completion of the work. DSR 2018DSR31Nos.
5757S/I of 100mm widthX50mm depthX1.6mm thickness size of perforated painted with powder coating KS cable trays with perforating not more than 17.5% in convenient sections, joined with connectors, suspended from ceiling with MS suspenders including bolts,nuts, painting suspenders etc. as required. DSR 2018DSR20Mtr.
5858S/I of 200mm dia.(OD-200mm & ID-175MM nominal) size DWC HDPE Pipe ISI marked along with all accessories like socket, bend, couplers etc.conforming to IS 14930, PartII complete with fitting & cutting,jointingetc direct in ground(75 cm below ground level) including excavation & refiling the trench but excluding dand cushioning & protective covering etc. complete as required. DSR 2018DSR10Mtr.
5959S/I of Spilit Direct expansion Air- Conditioners Suitable for operation on A/C supply single phase 50 Hz 230 volts with hermetically sealed compressor with air cooled condensor, motor capacitor start and capacitor run, relay and overload protector internal unit, with one indoor and one outdoor unit. the condensor unit placed outside the room on the terrace, to avoide noice including standard length of suitable size copper tubing covered with insulation tube. (High wall Chorded/ Cordless) Suitable capacity 3 core sheathed/ PVC copper cable and a battery operated wireless remote unit. BEE Star Rated : 5 Star, 1.5 Tr. Inverter AC, EER ABOVE 4.00 Make: (O genral- ASGA18FTTC , Tosiba -RAS18BKCV/BACV, Mitsubishi- MSY/MUY-GN18VF AppdAPPD8Nos.
6060S/L Copper pipe for AC AppdAPPD120Feet
6161S/L Copper cable for AC Appd.APPD120Feet
6262S/F of 4KVA Steblizer AppdAPPD8Nos.
6363S/F of Drain pipe AppdAPPD80Feet
6464S/F of Stand for outdoor unit AppdAPPD8Nos.
6565Wiring point for light point with 1.5 sq.mm FRLSH PVC insulated multistrand single core copper conductor cable in heavy PVC conduit pipe partly concealed in the wall and partly laid in slab along with the reinforcement before concreting complete with 14 SWG copper earth continuity wire, modular switch, modular plate, suitable GI box etc. as required. 138 C138 C226Nos.
6666Wiring point for fan / fresh air fan(light duty exhaust fan) with 1 sq.mm FRLSH PVC insulated multistrand single core copper conductor cable in heavy PVC conduit pipe partly concealed in the wall and partly laid in slab along with the reinforcement before concreting complete with 14 SWG copper earth continuity wire, modular switch, modular plate, suitable GI box etc. as required. 140C140C36Nos.
6767Add for two way light points with modular type switch in place of piano type switch187A262Nos.
6868Wiring point for two way light with 1.5 sq.mm FRLSH PVC insulated multistrand single core copper conductor cable in heavy duty PVC conduit pipe partly concealed in the wall and partly laid in slab along with the reinforcement before concreting complete with 14 SWG copper earth continuity wire, GP box and two number two way piano type switches & ceiling rose / angle / batten holder on 3 mm thick phanolic laminated backelite sheet etc., complete in all respect, as directed, including matching colour wash. 139 C139 C4Nos.
6969Add for two way light points with modular type switch in place of piano type switch187B4Nos.
7070Wiring point for call bell with 1.5 sq.mm FRLSH PVC insulated multistrand single core copper conductor cable in heavy duty PVC conduit pipe partly concealed in the wall and partly laid in slab along with the reinforcement before concreting complete with 14 SWG copper earth continuity wire, GP box and piano type bell push or 2 pin socket etc. complete in all respect, as directed, including matching colour wash.142 C16Nos.
7171Add for call bell points with modular type switch in place of piano type switch187E16Nos.
7272Supply & Wiring of submain with two no. as per following sizes of FRLSH PVC insulated 1100 V grade multistrand single core copper conductor cable in heavy duty PVC conduit as required partly concealed in wall and partly laid in slab alongwith reinforcement before concreting, with one no. 14 SWG copper earth continuity wire including matching colour wash etc. complete in all respect.\n2 X 1.5 sq. mm + 1 X 1.5 sq. mm earth wire1311 C1012.3Mtr.
73732.5 sq. mm.1301 C1092Mtr.
74744sqmm221 C820Mtr.
7575Wiring point for plug with 1.5 sq.mm. FRLS PVC insulated multistrand single core coper conductor cable in heavy duty PVC conduit pipe partly concealed in wall and partly laid in slab alongwith the reinforcement befofre concreting, complet with 14 SWG copper earth continuity wire and piano type switch & socket etc., complete in all respect including matching colour wash141 C43Each
7676Add for plug point with modular type switch & socket in place of piano type switch & socket187 C43Each
7777S & F of power plug with 16A/ 250 volt flush type modular switch and 5 pin 16A/ 250 volt flush type universal modular socket on concealed M.S. box including supply of all material, labour T &P etc. required for proper completion of work.113931Each
7878S & F sheet steel enclosure surface / Flush mounting fitted with 20 Amp.. 2 Pin and earth matel clad scraping earth plug and socket complete in all respect as directed at site by engineer in charge. CAT A103110Each
7979As in item no. 281 but heavy duty (2 mm thick) PVC conduit of 20 mm281 A50Mtr.
8080As in item no. 282 but heavy duty (2 mm thick) PVC conduit of 25 mm282 A25Mtr.
8181Supply and fixing of call bell of approved make on polished MDFEG / Teak ply board including making connections etc. complete in allrespect.110116Each
8282Erection and testing of ceiling fan and regulator etc. excluding supply of down rod, complete in all respect111541Each
8383Supply and fixing of electronic fan regulator( Modular) 120-280 V. ISI marked, on the existing switch board including making connections, required material, labour T&P etc. for proper completion of work to the satisfaction of Engineer in charge of work1203 C40Each
8484Erection and testingof exhaustfan on the existinghole with suitable size of rag bolts, nuts and washers etc., complete in allrespect.112010Each
8585Supply and fixingof 16 gauge M.S. drum duly painted including making hole in the wall for exhaust fan and finishing properly\ncomplete in allrespect.112210Each
8686Supply and fixing of recess/ Surface/ Pendent mountinground 13 Watt to 15 watt LED Down Lighter havingPowder coated die cast aluminiumhousing with heat sink, diffuser/Reflector and driver set complete in all respect. (CAT-AAA)1403122Each
8787Supply and fixing of recess/ Surface/ Pendent mounting round 6 Watt 8 Watt LED Down Lighter having Powder coated die cast aluminium housing with heat sink, diffuser/ Reflector and driver set complete in all respect.140234Each
8888Supply and fixingof LED Tube Lightwith batten suitablefor upto 1 X 10 watt tube light as a Mirror Light complete includingtube etc on surface complete in all respect. (CAT-AAA)MR5Each
8989Supplying, erection, connecting, testing and commissioning of 305 mm sweep exhaust fan 1400 rpm including connection with 1.5 sq.mm. FRLS PVC insulated copper conductor cable.MR10Each
9090Supply and fixing of LED Street light Fitting having die cast aluminium body and diffuser with driver set suitable for 15 Watt. to 25 Watt. Confirming to IP 66 protection complete in all respect. CAT - AAA14194Each
9191Painting of the electric pole with 2 coats of aluminium paint over red oxide primer complete in all respect.63477Each
9292Supply & erection of overhead line with ACSR conductor on poles / service bracket including binding etc. complete in all respects.627120Kg
9393To tighting of ACSR condoctor LR627 LR997Kg
9494Supply & erection of overhead line with G.I. wire no. 8 to 4 SWG on poles/serivce bracket including binding etc. complete in all respect.62836Kg
9595Supply & erection of stay set at 3.5 Metres away from the pole complete with galvanised 19 mm dia x1.80 Metre long stay rod, 30 cm x 30 x 6.3 mm anchor plate, thimble stay clamps, stay insulator,19 mm 600 mm double screw tightener, 7/3.5 mm G.I. stay wire etc. in 1:3:6 cement concrete complete in all respect.63120Each
9696S/F of spacerAPPD210Each
9797S/F of 100 Amp. 415 V metal clad T.P.N. rewireable type switch fuse unit on angle iron bracket complete in all respect. Cat B3531Each
9898S & F surface/ flush mounting 8 way TPN distribution board with additional metal door with out MCB complete in all respect, as directed at site by Engineer in charge. (CAT A)1026C1Each
9999S & F of 40 amp. D.P. MCB (CAT A)10104Nos.
100100S&F and making connection of 25A 2 pole 30mA ELCB/ RCCB of Din Rail Mounting complete in all respect as per direction and satisfaction to the Engineer in charge3924Nos.
101101S&F and making connection of 40A 2 pole 30mA ELCB/RCCB of Din Rail Mounting complete in all respect as per direction and satisfaction to the Engineer in charge39310Nos.
102102S & F 6 amp. To 32 amp. SPMCB (10KA) C curve100286Nos.
103103Supply and burying of 600 mm X 600 mm X 6 mm GI Plate vertically for earthing with its top at least 3 meter below ground level complete with 20mm dia G.I pipe and funnel for watering and one earthing lead of one No. 8 to 10 SWG GI wire in 15 mm dia G.I pipe and GI wire will be extra ) 30 cm square C.I frame with hinged cover masonry housing alternate layers of charcoal/coke/ and salt at least 150 mm thick around etc. as per directions of Engineer-in-charge complete in all respect s as per Drawings7025Each
104104Supply and fixing of one number 8 SWG G.I. wire in 15mm dia. G.I. pipe for earthing, laid in ground or in wall duly concealed including the cost of cement, sand, labour,T&P other material required for proper completion of the work as directed at site721100Mtr.
105105Supply, laying of one number PVC insulated and PVC sheathed / XLPE Al. armoured power cables 1100 Volts grade of following size direct in hdpe pipe / cable tray / ground / duct /trench including excavation and refilling the trench etc. as required, but excluding sand cushioning and protective covering.\n16sqmm 2 core501 c300Mtr.
106106240sqmm 3.5 core501 r300Mtr.
107107Supplying and fixing of brass nickle plated compression gland for PVC insulated and armoured served sheathed ,underground cable including rubber ring etc.complete in all respect. The armouring of the cable shall be properly connected with the earth as per direction of the Engineer -Incharge.\n16sqmm 2 core503 c16Each
108108240sqmm 3.5 core503 r4Each
109109Supplying and fixing of plain or pin type copper tin plated cable socket (lug) to the cable leads , insulating with tape and making connection etc. complete in all respect as per direction of the Engineer -Incharge.\n16sqmm504 f12Each
110110120sqmm504 j8Each
111111240sqmm504 m12Each
112112Supply and erection of factory fabricated and wired metal clad dust and vermin proof floor mounting panel TPN switch board complete with the following HRC type heavy duty TPN fuse switches with fuses and instrument chamber etc. complete in all respects. The instrument chamber shall be separate and shall comprise of flush type ammeter, voltmerer, selector switches for ammeter and voltmeter, instrument fuses, current transormer etc. The board shall have suitable capacity electroytic alumininum busbars as per IS8623 istulate with heat shrink sleeving and mountend on non hygroscopic supports such as CMC/DMC support with deteachable side covers and shall be suitable for extension on the sides. The switches shall be complete with suitable cable end boxes, reverse entery boxes in case of pedestaal type, cable sockets, compression glands and indicating lamp on incoming etc. The job includes the grounting of the board as per direction of Engineer-in-Charge. All coutgoing switches of 100 Amp. and above will be provided with ampere metre current transformers and selector switches and instrument fuses etc. The switches board shall be fabricated with CRCA sheet with a minimum thickness of 1.6 mm/2 mm. Cubicle type switch board shall be of cat A B & B-II and pedestal type for Cat-B and C only. Incoming 630 Amp. TPN-1 No Outgoing 2 Nos. 200 amp. TPN Thermal Release MCCB 2 Nos. 63 amp. TPN Thermal Release MCCB8051Each

AI Tender Summary

OUR REF NO 24442880
AUTHORITY Government Departments
TENDER VALUE 48.56 Lakhs
LAST DATE 24-06-2020
Authority
Authority Name Rajya Krishi Utpadan Mandi Parishad
Work Description Internal Electrification In E Name Office Staff Quters Apf Pastiside Testing Lab And Ac Etc
Basic Detail
Tender No 64/2020/59 ROBERTSGANJ
Bidding Type Tender
Location
City ROBERTSGANJ
State Uttar Pradesh
Key Dates
Publish Date 30 May 2020
Submission Date 24 Jun 2020
Open Date 25 Jun 2020
Finance
Tender Value 48.56 Lakhs
Tender Fee 1180
EMD 4.86 Lakhs
Exemption Not Available
Document List
BOQ_713298.xls
Tendernotice_1.pdf
1AF07D34-904B-4E04-88BB-1C04C9CCEB39.html

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

May 30, 2020
11:30 IST

Tender Published

Tender notice published.

Completed
Jun 24, 2020
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Jun 25, 2020

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
xls

BOQ_713298.xls

pdf

Tendernotice_1.pdf

html

1AF07D34-904B-4E04-88BB-1C04C9CCEB39.html

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender

TenderDetail
Loading tenders