| 1 | 1.01 | Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. (a) 25 mm | BI01010001010000000000000515BI0100001113 | 70 | MTR |
|---|
| 2 | 1.02 | 32 mm | BI01010001010000000000000515BI0100001114 | 25 | MTR |
|---|
| 3 | 1.03 | 50 mm | BI01010001010000000000000515BI0100001115 | 45 | MTR |
|---|
| 4 | 2.01 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required (a) 4 X 10 sq. mm + 2 X 6 sq. mm earth wire | BI01010001010000000000000515BI0100001119 | 40 | MTR |
|---|
| 5 | 2.02 | 2 X 10 sq. mm + 1 X 6 sq. mm earth wire | BI01010001010000000000000515BI0100001120 | 60 | MTR |
|---|
| 6 | 2.03 | 2 X 4 sq. mm + 1 X 4 sq. mm earth wire | BI01010001010000000000000515BI0100001120 | 90 | MTR |
|---|
| 7 | 3.01 | Supplying and drawing following sizes of FR LS PVC insulated copper conductor, single core cable in the existing surface/ recessed steel/ PVC conduit as required. (a ) 3 x 4 sq. mm | BI01010001010000000000000515BI0100001122 | 20 | MTR |
|---|
| 8 | 3.02 | 3 x 10 sq. mm | BI01010001010000000000000515BI0100001123 | 15 | MTR |
|---|
| 9 | 4 | Supplying and fixing following size/ modules, PVC/GI box alongwith modular base & cover plate for modular switches in recess etc as required. (a) 2 Module (75mmX75mm) | BI01010001010000000000000515BI0100001130 | 12 | NOS |
|---|
| 10 | 5 | Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required .(a) 6 pin 15/16 amp socket outlet | BI01010001010000000000000515BI0100001136 | 12 | NOS |
|---|
| 11 | 6 | Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) (a) 4 way (4 + 12), Double door | BI01010001010000000000000515BI0100001137 | 1 | NOS |
|---|
| 12 | 7.01 | Supplying and fixing 5-63AMP rating 240 volts,'C' series miniature circuit breaker suitable for lighting and other loads of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Make Havell's / Standard / HPL / C&S /ABB / L&T (a) Single pole 5-32 AMPS | BI01010001010000000000000515BI0100001138 | 5 | NOS |
|---|
| 13 | 7.02 | (b) Single pole 50/63 AMPS | BI01010001010000000000000515BI0100001139 | 7 | NOS |
|---|
| 14 | 8 | Supplying and fixing following rating, four pole, 415 volts, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required.(a) 100 amps | BI01010001010000000000000515BI0100001140 | 2 | NOS |
|---|
| 15 | 9 | Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required. | BI01010001010000000000000515BI0100001141 | 16 | NOS |
|---|
| 16 | 10 | Earthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. | BI01010001010000000000000515BI0100001142 | 4 | NOS |
|---|
| 17 | 11 | Providing and fixing 6 SWG dia G.I. wire on surface or in recess for loop earthing as required. | BI01010001010000000000000515BI0100001143 | 20 | MTR |
|---|
| 18 | 12 | SUPPLYING & Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation and refilling the trench etc as required, but excluding sand cushioning and protective covering. 3.5 X 120 SQ MM | BI01010001010000000000000515BI0100001145 | 165 | MTR |
|---|
| 19 | 13 | SUPPLYING AND Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1KV grade of following size in the existing RCC/ HUME/ METAL pipe as required 3.5 X120 SQ MM | BI01010001010000000000000515BI0100001146 | 8 | MTR |
|---|
| 20 | 14 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 3½ X 120 sq. mm (45mm) | BI01010001010000000000000515BI0100001147 | 4 | SET |
|---|