Repair Maintenance Contract Electrical And Mechanical Services At Dr Bsa Hospital Rohini Delhi Sh Providing And Installation Of Microprocessor Based Control Panel Wireless Connectivity With Complete Scada Software For Automation Of Pump House

Tender Notice

24383822
Repair Maintenance Contract Electrical And Mechanical Services At Dr Bsa Hospital Rohini Delhi Sh Providing And Installation Of Microprocessor Based Control Panel Wireless Connectivity With Complete Scada Software For Automation Of Pump House
Indian
Delhi
29-05-2020
02-06-2020
02-06-2020

Tender Details

Repair Maintenance Contract Electrical And Mechanical Services At Dr Bsa Hospital Rohini Delhi Sh Providing And Installation Of Microprocessor Based Control Panel Wireless Connectivity With Complete Scada Software For Automation Of Pump House

Corrigendum Details

Sr No CorrigendumDate Description Submission Date
1 29-05-2020 Extended Date 02-06-2020

Key Value

Document Fees
Refer document
EMD
INR 88882.00 /-
Tender Value
INR 44.44 Lakhs /-

BOQ Items

Name of Work: RMO Electrical & Mechanical Services at Dr. BSA Hospital Rohini Delhi. (SH:-Providing & installation of microprocessor based control panel, wireless connectivity with complete Scada software for automation of pump house)
Sl. No. Item Description Item Code / Make Quantity Units
1 1 SH:-I (SITC of SCADA System) \nSupplying, installation, & commissioning of powder coated, floor mounted panel fabricated from 2mm thick CRCA sheet, suitable for 415V AC 50Hz, of size 1200mm x 1000mm with minimum 300mm thickness complete with control wiring, complete in all respect and fitted with i/c earthing etc.
2 1.01 Cooling fan 6'' (Make: Axair/Rexroth/Jigo/Eq) - 1 No
3 1.02 Single phase preventor (Make: Select/Minilec/L&T/Eq) - 1 No
4 1.03 Voltmeter, 0-500V AC (Make: AE/L&T/Schneider) - 1 No
5 1.04 Pushbuttons (Make: L&T/Schneider/Eq)
6 1.05 Relay card (Make: Phoenix/Omron/L&T) - 5 Nos
7 1.06 24V DC, 4.2A SMPS (Make: Phoenix/Omron/Delta/Eq) - 2 Nos
8 1.07 25A TP MCB (Make: Hager/Schneider/L&T/Eq) - 2 Nos
9 1.08 6A DP MCB (Make: Hager/Schneider/L&T/Eq) - 10 Nos
10 1.09 Indicating Lights (Make: L&T/AE/Eq) - 7 Nos
11 1.1 Panel Light (Make: Wipro/Bajaj/Philips/Eq) - 1 No
12 1.11 15A Switch Socket (Make: Anchor/Cona/Havells/Eq) - 2 No
13 1.12 32A, TP MCB (Make: Hager/L&T/Schneider) - 6 Nos.
14 1.13 25A SP MCB (Make: Hager/L&T/Schneider) - 3 Nos.
15 1.14 MNX9, TP Contactor (Make: Hager/L&T/Schneider) - 14 Nos.
16 1.15 MNX12, TP Contactor (Make: Hager/L&T/Schneider) - 2 Nos.
17 1.16 MN2, 9-15A O/L Relay (Make: Hager/L&T/Schneider) - 1 Nos.
18 1.17 MN2, 6-10A O/L Relay (Make: Hager/L&T/Schneider) - 4 Nos.
19 1.18 MN2, 2-3.3A O/L Relay (Make: Hager/L&T/Schneider) - 1 Nos.
20 1.19 MX0 (Make: Hager/L&T/Schneider) - 5 Nos.
21 1.2 Auxiliary Contact (Make: Hager/L&T/Schneider) - 16 Nos.
22 1.21 Start Delta Timer (Make: Hager/L&T/Schneider) - 5 Nos.
23 1.22 Selector switch NC block (Make:- L&T/AE/Schneider) - 1 No.
24 1.23 Selector switch NO+NC block (Make:- L&T/AE/Schneider/Eq)- 1 No. 1 P/Job
25 2 Supplying, installation Testing & commissioning of Micro Processor Unit with real time clock wireless Connectivity, 5 years data backup LCD display with Backlight operating keys 6 No Various functions high Speed mode with instant switches from one input to the Other & can be controlled In Slot for memory cartridge with connected to PC pc through software key + CGPS plug-in software. Software key should comprised of UDP/FTP/HTTP open standard Internal Expansion Socket Q26-family Wireless CPU®: with an ARM9 32 bit, 26-104MHz with integrated IDE & Internet connection with Uptime - Minimum 95%,Download Speed -1 Mbps Broadband Data Transfer Limit - Unlimited Wi-Fi Router/Access Point (Make::- Konfidance / Procom / IDEC) 1 Each
26 3 Providing & fixing of ultrsonic sensor to water level in each water storage tank of the system etc. as required. (Make::- Pepperl -Fuchs / Schneider / omron) 15 Each
27 4 Providing & installation of Butterfly Valve with Electrical actuated (50mm) a self contained control package with local controls, status indication relays, isolated control circuits with 24 VDC, 220 VAC, 1Ø, 50Hz. Position indication via local manual indicator and LED, temperature rating from - 5 ??C to +50 ??C operation and etc. as required with following facility. AIL SLIMSEAL is a Wafer type Butterfly Valve with an intergrally moulded elastomer body liner with working pressure rating upto 10NM.
28 4.01 Valve Design confirm to:-
29 4.02 BS 5155 - Specification for Butterfly valves, Wafer Short
30 4.03 API 609 - Lug and Wafer type Butterfly Valves, Category A
31 4.04 MSS SP 67- Butterfly valves, Narrow body
32 4.05 ISO 5752 - used in flanged pipe systems, Face to face and centre to face dimensions.
33 4.06 BS 6755 Part 1 Pressure testing
34 4.07 Black Nitrile/EPDM seat Test Pressure is at Body / Disc 24 & Seat 17.6.
35 4.08 Potentiometer unit is synchronous with output transmission shaft to provide a feedback singal. Local control unit is control with local/Remote selection switches.
36 4.09 Position Indicator can be either 0-100% or 4-20mA.
37 4.1 On-off duty with 60 start /hours.
38 4.11 Input signal (Potential free)open- close with 24 V DC supply from interal power supply or form External source.
39 4.12 Monitor relay for collecting fault signal such as torque switch tripped in mid travel, thermo switch tripped.
40 4.13 Local status annunciation LED (color Green) and fault annunciation LED (color Red)
41 4.14 Programmable Logic control.
42 4.15 Electrically & Mechanically Interlook
43 4.16 Run the actuator for a per defined travel in ON-OFF step.
44 4.17 Selector switch local-off - Remote (Lockable in all three positions) with potential free contacts for local-off / Localon.
45 4.18 24V DC, 150mA source. Limit and torque switches (2 No +2 Nc)
46 4.19 Enclosure IP 67.Epoxy paint with DA gray shade (Make: L& T/RC/Elger) 9 Each
47 5 Supply & Installation of Transponder & Reciever UBIQUITI- LITE Beam AC Gen-2 System required as:-
48 5.01 Dimension: 358 x 271.95 x 272.50 mm (minimum)
49 5.02 Networking Interface: (1)10/100/1000
50 5.03 Ethernet Port with Antenna gain: 23 dbi Max.
51 5.04 Power Output: 25 dbm Max.
52 5.05 Power Consumption: 7W
53 5.06 Input Power Supply: 24V, 0.3A
54 5.07 Operating Temperature: -40 to 70° C (-40 to 158° F)
55 5.08 Operating Humidity: 5 to 95%
56 5.09 Wind Servivability: 200km/h
57 5.1 Wind Loadiing: 275N@200km/h
58 5.11 Noncondensing ESD/EMD Protection: ± 24 kV
59 5.12 ( Make:: UBIQUITI / RAD /TPLINK ) 13 Each
60 6 Providing & Fixing of WiFi router for monitoring of pumps with the following specifications:-
61 6.01 External Power Supply: 9VDC/0.6A
62 6.02 Interface:-
63 6.03 4 10/100Mbps LAN Ports:
64 6.04 1 10/100 Mbps WAN Ports
65 6.05 Dimension: 7.6 x 5.3 x 1.3 in. (193 x 134 x 33mm)
66 6.06 Antenna: 2.5dBi Fixed Omni Directional Antenna
67 6.07 Wireless Function: Enable/Disable Wireless Radio, WDS Bridge, WMM
68 6.08 Wireless security:64/128/152-bit WEP/WPA/WPA2,WPA-PSK/WPA2-PSK
69 6.09 Freequency: 2.4-2.4835GHz
70 6.1 ( Make:: TP Link / D LINK / NETGEAR) 14 Each
71 7 Supply & installation of Scada software for on line Monitoring pump house for all the locations of site with following specification:- (Make: Konfidance / IDEC / procom)
72 7.01 Realtime Recipient should be added or delete manually according to the need as per the requirement. \nRealtime activity in pump house should be stored in a queue. \nOnline Monitoring application should be with in System for tracking. Online activity storage should be at central server for proper backup and support. \nGateway server will manage all the incoming and out going through real time. \nGateway client application can be installed at any number of mobile. \nFault or any breakdown reported immediately to concerned person through mobile messaging (persons can be any number). \nEach operations log stored in server & can be checked later on. \nSoftware can be breakup in to different level for checking whole pump house according to the client needs. \nReport can be checked according to the predefined level. \nEmployees data of different units can be stored in the software and messaging will be done according to the employees in the unit. \nOn network failure real time, Each operation should resend the data again. \nPower Consumption of each pumps should be come up on Mobile App & Server.
73 7.02 Data Sheet to be generated in excel form at the month ending to be summerized Power Consumption of each pumps.
74 7.03 Online Power Consumption on cloud based server with client login. 1 Each
75 8 Supplying and drawing following sizes of FR PVC insulated single core & multi core sheathed/unsheathed industrial multistrand cables flame retardant with bright annealed electrolytic bare copper conductor for voltage grade upto 1100v conforming to IS-694:1990. (Make:-KEI/POLICAB /HAVELLS)
76 8.01 (a) 0.75 sq. mm, 6 core 141 P/Mtr
77 8.02 (b) 1.0 sq. mm 4 core 136 P/Mtr
78 8.03 (c) 1.5 sq. mm, 3 core 145 P/Mtr
79 8.04 (d) 4 sq. mm, 4 core 46 P/Mtr
80 8.05 (e) CAT 6 Cable (2 run of cable) 114 P/Mtr
81 9 Micro Processor controlled panel having provision to be mounted with solar panel at 10 angle of 150 wp duly equipped with battery back up of 48 hours to be work in non sunny days also of size 500x250x200mm, 2mm thick, CRCA sheet powder coated suitable to operate on 220V, 50c/s single phase AC supply with single phase sequence protection, SMPS,10A DPMCB to control remote operation of Actuated Valve & ultrasonic sensor with internal memory 32Mb flash, Digital Combs: 1 UART, USB,cellular radio supporting squad band EDGE, Audio 1 analog differential & Radio cellular data as per the field requirement etc.(Make:- Konfidence / Procom / IDEC ) \n \n 9 Each
82 10 Supplying of Micro Processor controlled cubical feeder panel of size 500x250x200mm1mm thick, CRCAsheet powder coated suitable to operate on 220V, 50c/s single phaseAC supply with phase sequence protection & SMPS to control remote operation of submersible with internalmemory 32Mb flash,cellularData, Audio & Radiocellular interfaces as per the field requirement etc. (Make:- Konfidence / Procom / IDEC ) 3 Each
83 11 SH:-II (Comprehensive maintenance) \nAnnual comprehensive maintenance of the complete SCADA System including timely checking, repairing and replacement of faulty equipment of the system on as per the requirement of the site time to time as required.
84 11.01 (a) 1st year
85 11.02 (b) 2nd year 12 Month
86 11.03 (c) 3rd Year 12 Month
87 11.04 (d) 4th Year 12 Month
88 11.05 (e) 5th Year 12 Month