Design And Construction Of Various Buildings , Cold Store ( Including Providing/Installation /Testing/Commissioning Of Machinery ) In Primary Processing Centre At Amritsar ( Punjab ) ( Supply , Errection , Testing And Commssioning Of 500Kva Compact , Amritsar-Punjab
TDR : 24278987
Tender Notice
BOQ
Expired
Amritsar
Punjab
Design And Construction Of Various Buildings , Cold Store ( Including Providing/Installation /Testing/Commissioning Of Machinery ) In Primary Processing Centre At Amritsar ( Punjab ) ( Supply , Errection , Testing And Commssioning Of 500Kva Compact
Name of Work:Design, Construction of Various buildings, Cold-Store (Including Providing/Installation, Testing/Commissioning of Machinery) in Primary processing Centre at Amritsar (Punjab) (Supply, erection, testing and commissioning of 500 KVA Compact Sub Station)
Sl.No.
Item Description
Item Code / Make
Quantity
Units
1
1
Supply, installation, testing and commissioning of 11 KV 500KA Compact Sub Station, 2 Way RMU 12KV Non-extensible, 21ka/3 Sec outdoor type SF6 Gas insulated RMU consisting of 1 No. 630 Circuit & 1No. 630 A load break switch with self powered IDMT relay for protection of 20/C+1E/F Complete in all respect as approved/desired by the Engineer-In-Charge of work at site. Make : Sudhir ABB,Schneider, SIEMENS,
BI01010001010000000000000515BI0100001112
2
1.01
Transformer Type: Oil Immersed\nStandard : IEC 60076/IS 1180 (Energery Eff. Level-2) \nVector Group : Dyn 11\nCooling System : ONAN\nWinding : Copper \nMegnectic Core: Made of grain oriented, cold rolled, sillicon steel strips.\nHigh Voltage : 11KVA\nLow Voltage : 433V\nInsulation Level: 12 KVA at the HV Side \nHV Power Frequency (KV peak) : 28KV \nHV Impulse Withstand voltage (KV Peak) \nLV Impulse withstand voltage (KV Peak) : 3KVA\nTrapping : Off Load tpa changer with +5% in steps of 2.5% on HT side\nTemperature \nAmbient Temperature: 50 Degree C \nWinding temperature rise : 45 Degree C \nOil : Mi Mineral oil meeting the IS 335 Standard Grade requirement for uninhabited oil.\nAccessories : \nOTI & WTI with Alarm & Trip : Yes \nPressure relief valve : Yes \nSkids: Yes \nearthing Terminal : Yes \nLifting Lugs: Yes \nRaiting Plate : Yes \n\n\n