Sitc Of Pump House Equipment At Bdk Hospital Jhunjhunu, Jhunjhunu-Rajasthan

Medical And Health Services -MAHS has published Sitc Of Pump House Equipment At Bdk Hospital Jhunjhunu. Submission Date for this Tender is 14-05-2020. Pump Supply Tenders in Jhunjhunu Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

24269570
Sitc Of Pump House Equipment At Bdk Hospital Jhunjhunu
Open Tender
Indian
Rajasthan
Jhunjhunu
14-05-2020

Tender Details

Sitc Of Pump House Equipment At Bdk Hospital Jhunjhunu

Key Value

Document Fees
INR 500 /-
EMD
INR 45400.0 /-
Tender Value
INR 22.70 Lakhs /-

BOQ Items

Name of Work : SITC of Pump House Equipment at BDK Hospital Jhunjhunu
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supplying, Installation, Testing & Commissioning of Local Fire authrity approved Electric Driven Main fire pump for Sprinkler / Hydrant applications suitable for automatic operation and consisting of following details given as A, B, C, D, E, F and G . 1
2 1.01 (A) Horizontal Single / Multi stage Centrifugal End suction, back pull type pump complete for delivery of below mentioned discharge , with necessary Butterfly valve on the suction side ( all items to be matching with the suction side dia of the pump) and pressure gauge ,Butterfly valve and non return valve on the delivery side side ( all items to be matching with the delivery side dia of the pump) and including bypass arrangement for Testing of pump 2
3 1.02 (B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal 3
4 1.03 (C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head 4
5 1.04 (D) Squirrel cage induction motor suitable for 3 phase, 415 V, 50 HZ, Ac supply 2900 / 1450 RPM T.E.F.C confirming to IP:55 , of required HP suitable for the above pump ,along with flexible coupling , coupling guard complete in all respect . 5
6 1.05 ( E) Common bed plate fabricated from mild steel channel for installation of pump and Motor 6
7 1.06 (F) Pump is to be inspected by third party like RITES / PDIL at manufacturer's premises and inspection report is to be submitted. 7
8 1.07 (G) Suitable cement concreat foundation duly plastered with anti vibration pads. 8
9 1.08 2280 LPM suitable for 70 Mtr Head, single stage, 2900 RPM 9 1 Each
10 2 SITC of Local fire authority approved Diesel Engine driven Pump suitable for automatic operation as per discharge defined beolw consisting of the following details given as A, B, C, D, E and F . 10
11 2.01 (A) Horizontal Single / Multi stage Centrifugal End suction, back pull type pump complete for delivery of below mentioned discharge complete with necessary flexible pipe, Butterfly valve on the suction side ( all items to be matching with the suction side dia of the pump) and pressure gauge ,Butterfly valve and non return valve on the delivery side side ( all items to be matching with the delivery side dia of the pump) and including bypass arrangement for Testing of pump 11
12 2.02 (B) Material of construction : Pump Casing - Cast Iron, Impellor - Bronze, Shaft - SS 410, Packing - Mechanical Seal 12
13 2.03 (C)Pump shall be capable of furnishing not less than 150 % of rated capacity at a head not less than 65 % of the rated head. The shut off head shall not exceed 120 % of rated head 13
14 2.04 (D) Radiator cooled Diesel Engine developing suitable BHP for the below mentioned discharge at 1500 / 1800 RPM, flexible coupling and coupling guard with the Pump, common bed plate for mounting of the Engine and Pump,Antivibration damping arrangement by cushy foot, Diesel Engine starting Panel for starting of the engine automatically if the Normal electrical supply fails with a unit of battery bank of 12/24v,180 Ah, Lead Acid Battery with Boost / Trickle charger as required for operation of Diesel engine, Exhaust Pipe of suitable diameter minimum 10 M length, with muffler, day oil tank of 300 1ts capacity with first charge and hand operated oil pumping set, 14
15 2.05 (E) Pump is to be inspected by third party like RITES / PDIL at manufacturer's premises and inspection report is to be submitted. 15
16 2.06 (F) Suitable cement concreat foundation duly plastered with anti vibration pads. 16
17 2.07 1620 LPM suitable for 56 Mtr Head, single stage, 1800 RPM 17 1 Each
18 3 SITC of Local fire authority approved Horizontal single stage Jockey pump with CI Body, Bronze impellor, SS shaft, mechanical seal coupled with Squirrel cage induction motor for automatic operation suitable for three phase, 415 V, 50 Hz AC supply with synchronous speed of 2900 RPM ,T.E.F.C type confirming to IP:55 with flexible coupling and coupling guard with the pump ,Common bed plate fabricated from mild steel channel , Suitable cement concreat foundation duly plastered with anti vibration pads. 18
19 3.01 180 LPM suitable for 56 Mtr 19 1 Each
20 4 SITC of floor mounted dust and vermin proof compartmentalised cubical type main fire pump house panel made out of CRCA sheet , required hardware ,duly treated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shade The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel ,hinged door with locking arrangement for equipment/switchgear . Thickness of sheet shall not be less than 1.6 mm up to 600 mm length / width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors and having accessories ( Group -I ) as below: 20
21 4.01 Incomer 21
22 4.02 320 Amp. TPN MCCB (adj.O/L) with Extended ROM, 35 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, Selector switches,CT, Indicating Lamps, 400 Amps Alum. Bus bar with with heat shrinkable sleeves. 22
23 4.03 Out going 23
24 4.04 (a) 200 Amp. TPN MCCB(adj.O/L) with Extended ROM, 35 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, Selector switches,CT, Indicating Lamps for 'ON', 'OFF', 'TRIP' 1 no. star Delta Starter of 75 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 2 Sets 24
25 4.05 (b) 63 Amp. TPN MCCB (adj.O/L) with Extended ROM, 25 kA, with Thermal magnetic release, Digital Ammeter, Voltmeter, Selector switches, CT, Indicating Lamps for 'ON', 'OFF', 'TRIP' 1 no. Star Delta / DOL Starter of 5 - 15 HP with thermal over load relay, timer, push buttons, Auto / Manual selector switch, Single phase preventor - 1 Set 25
26 4.06 © One no. Diesel Engine Auto Starting kit with Auto . Manual selector switch & 3 attempt starting device, timers, relays, Indicating lamp for High / Low Lub. Oil pressure, High water temperature and engine ON indication, Battery charger, suitable for 12 V / 24 V DC with trickle / boost selector switch, DC ammeter & voltmeter 26
27 4.07 (d) System controller to control Operation Main Electric pumps, Diesel pump, jockey pump in sequence as per specs. Consisting of relays, timers, sensors, annuciation window for fault indication. 27 1 Set
28 5 Providing & fixing 100mm dia bourden type, Stainless steel dial type pressure Gauge (0 - 16 Kg ) range, 3 / 8 " BSP bottom entry on Pump Delivery Line complete with Ball valve 28 6 Each
29 6 Providing, laying, testing & Commissioning of 'C' class heavy duty MS pipe conforming to IS 3589 and 1239 for hydrent and sprinkler underground rings including all accessories such as screwed/ welded flanges, tees, reducers etc. Conforming to IS : 1239/3589 complete including , welding, jointing with compressed asbestos gaskets, nuts, bolts etc. as required. with cleaning,wrapping and coating of the pipe with 4 mm thick tar based plymaric corrosion protection tape or equivalent including applying uniform coat of cold pipekot primer as per IS; 10221 for protection against corrsion suitable for all kind of soil at 1.0 M depth including excavation and making good the same as required at site . 29
30 6.01 b) 100 mm dia 30 24 Each
31 6.02 c) 150 mm dia 31 50 Each
32 7 Providing, laying, testing & Commissioning of 'C' class heavy duty MS pipe conforming to IS 3589 / 1239 for hydrent and sprinkler applications including fittings like elbows, tees, flanges, tapers, nuts bolts, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps and including painting of two coats of Red Oxide , painting with two or more coats of synthetic enamel paint of Post office red shade complete as required.The installation includes all civil openings ,breakages and making good the same. 32
33 7.01 a) 80 mm dia 33 12 Mtr.
34 7.02 b) 100 mm dia 34 10 Mtr.
35 7.03 c) 150 mm dia 35 50 Mtr.
36 7.04 d) 200 mm dia, 6.0 mm thick 36 3 Mtr.
37 8 Supplying and fixing air vessel of continuous welded construction fixed at riser top made of 250 mm dia, 8 mm thick MS sheet, 1200 mm in height with air release valve on top and flanged connection to riser, drain arrangement with 25 mm dia Gun Metal wheel valve, with required accessories, pressure gauge and painting with two coats of Red Oxide and two coat of post office red enamel paint as required. 37 1 Each
38 9 Providing, installation, testing and commissioning of stainless steel strainer of dia given below fabricated out of 1.6 mm. thick stainless steel sheet with 3 mm. dia holes with stainless steel flange of following sizes. 38
39 9.01 100 mm dia 39 1 Each
40 9.02 150 mm dia 40 2 Each
41 10 Supplying, fixing, testing commissioning of butterfly valve PN 1.6, with Bronze/ Gunmetal seat duly ISI marked complete with Nuts, Bolts, washers, gaskets, conforming to IS 13095, of following sizes as required. 41
42 10.01 100 mm dia 42 1 Each
43 10.02 150 mm dia 43 2 Each
44 11 Supplying and fixing Stainless steel IS:3444 Grade - 1 single headed Internal / external yard hydrant valve with 1 No. 63 mm dia instantaneous Stainless steel coupling and cast iron wheel, ISI marked, conforming to IS 5290 (type A) with blank Gunmetal cap and chain as required. 44 9 Each
45 12 Supplying and fixing 63 mm dia, 15 mtr. Long RRL hose pipe with 63 mm dia male and female Stainless steel couplings duly binded with GI wire, rivets etc. conforming to IS 636 (type-A) as required. 45 6 Each
46 13 Supplying & fixing 63 mm dia stainless steel IS : 3444 Gr. - 1 branch pipe with 20 mm (nominal internal diameter) size Gun metal nozzle confoming to IS 903, suitable for instantaneous connection to interconnect hose pipe coupling as required 46 9 Each
47 14 Supplying and fixing first -Aid hose reel wall mounted swinging type with MS construction spray painted in post office Red, conforming to IS 884 with upto date amendments, complete with the following as required. (A) 30 m long 20 mm (nominal internal) dia water hose Thermoplastic (Textile reinforced) Type -2 as per IS: 12585 (B)20 mm (nominal internal) dia gun metal globe valve & nozzle. (C)Drum and brackets for fixing the equipments on wall. (D)Connections from riser with 40 mm dia stop valve (gun metal) & M.S. pipe 47 6 Each
48 15 Supplying and fixing of Hose Cabinet of size 750 mm x 600 mm x 250 mm made of 1.6 mm thick MS sheet with 6 mm thick glazed glass doors including necessary locking arrangement suitable to accommodate external hydrant with butterfly valve, 2 Nos 15 Mtr. Long Hose pipe, 1 No. branch pipe, mounted on wall OR raised brick platform & duly painted with post office red externally and white internally with synthetic enamel paint complete in all respect, for external hydrant, as required. 48 9 Each
49 16 SITC Addressable analogue Optical type Smoke Detector with mounting base, two LED's etc. as required. 49 110 Each
50 17 SITC of Fault isolation module to electrically isolate different sections of detector loops. 50 3 Each
51 18 SITC of Addressable type manual fire alarm boxes (MCP/Pull Station ) shall, on command from the control panel, send data to the panel representing the state of the manual switch and the addressable communication module status. Manual fire alarm boxes shall be constructed of Lexan with clearly visible operating instructions provided on the cover. The word FIRE shall appear on the front of the stations in raised letters, 1.75 inches (44 mm) or larger. etc. as required. 51 4 Each
52 19 Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1 kV grade and approved make in existing surface or recessed conduit/casing capping including making connections etc. as required. 52
53 19.01 a) 2 x 1.5 sq.mm 53 1000 Mtr.
54 19.02 b) 4 x 1.5 sq.mm 54 200 Mtr.
55 20 S&F following sizes (dia.) of ISI marked ( IS:9537 P - II ) rigid steel conduit along with accessories in surface / recessed using saddles, clamps, fastener pvc bushes, check nuts, as required including cutting the wall and making good the same as required. 55
56 20.01 a) 20 mm 56 1100 R. mtr.
57 20.02 b) 25 mm 57 100 R. mtr.
58 21 Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 25 mm dia. G.I. 'B' class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. 58 2 Set
59 22 S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. 59
60 22.01 a) 8 SWG copper Wire 60 40 Mtr.
61 23 P/Laying P.V.C. / XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required of size. 61
62 23.01 a) 16.0 Sq.mm 4 core Ar 62 10 Mtr.
63 23.02 b) 35.0 Sq.mm 3.5 core Ar 63 10 Mtr.
64 23.03 c) 70.0 Sq mm 3.5 Core Ar 64 100 Mtr.
65 24 Supplying and making one end termination with heavy duty single compression brass gland SIBG type, heavy duty aluminium lugs duly crimped with crimping tool, PVC tape etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required of size. 65
66 24.01 a) 4 x 16.0 sq.mm 66 2 Set
67 24.02 b) 3 x 35.0 sq.mm 67 4 Set
68 24.03 c) 3 x 120.0 sq.mm 68 1 Set
69 25 Supply, Fabricating & installing following sizes of powder coated ladder type M.S. cable trays with rungs at span of 250mm including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling/wall with M.S. suspenders etc. as required. 69
70 25.01 150mm x 50mm x 1.6mm 70 20 Mtr.
71 26 SITC of Hooter suitable for addressable type fire alarm system with storb light with minimum 85 db audiable etc. as required. 71 4 each
72 27 P/Laying P.V.C. / XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with Copper conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required of size. 72
73 27.01 6 core 73 15 Mtr.