Sales : +91-777 804 8217
| Sr No | Corrigendum Date | Corrigendum | Type | New Submission Date |
|---|---|---|---|---|
| 1 | 20-05-2020 | Bid Auto Extn Corrigendum | Bid Auto Extn Corrigendum | 27-05-2020 |
| 2 | 09-05-2020 | Revised BOQ | BOQ | 20-05-2020 |
| Name of Work: MAINT AND SERVICING OF THE CENTRAL AC PLANTS OF VARIOUS CAPACITIES ALONGWITH THE COOLING TOWERS, AHUs HOT WATER GENERATORS ETC INCLUDING THEIR CONTROL PANELS AND REPLACEMENT TO MISCELLANEOUS ACCESSORIES UNDER GE (AF) IZATNAGAR BAREILLY. | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1 | Material and labour for complete periodical servicing of Central Air Conditioner Plants of Capacity 3 x 26 TR (Loc- Bumb Dump DB No; 1 &18 ),3 x 26 TR (Loc- 8 Sqn ) , 3 x 50 TR (Loc- Bumb Dump DB No; 7 & 8 ),4 x 10 TR ( Loc - Grooth complex), 3X39 TR (Loc- Reccy lab) ,3X 24 TR ( Loc-Simulator bldg),3x 37.5 TR (Loc- Base opps bldg) ,3 x 32 TR ( Loc- EW Lab) , 3 x 25 TR (Loc- Signal centre ) , 2 x 37.5 TR( Loc Arjan cinema hall) of Make Blue star and 3 x 85 TR ( Loc-SSC bldg ) of make voltas ( excluding AHUs and cooling tower ) and checking servicibility of the items like cards, sensors relays, switches etc compressor oil checking , checking of leakage of refrigerant piping etc and Descaling of complete chiller plant with suitable descaling chemical viscous compund which should be suitable for descaling of copper tube of chiller, condensers tubes of air conditioning plant .The arrangement should be included proper standard tools and plants and should be carried out through authorised vendor of the makes of plant i.e Bluestar/ voltas. The chemical should be non corrosive and non polluting and safe to handle. Part/ cat No of Descaling chemical compound is RXSOL-41-8865-25 Makes: Scalebreak/Vizagchemical/chemtex/west india chemical /.The qty of chemical is included in the job which is approx of 15 ltrs for each Job.It should be as directed by Engineer-in-Charge. The job includes all three units, condensers & Chiller cleaning measures as one job and .The complete job is to be carried out for two times in a period of contract for each plant .Reassly the complete plant after necessary job .Restarting and Maintaining of the required /desired Parametrs should be provided by the contractor. All the nuts, bolts of CI washers etc as required of suitable sizes are included in the complete job as specified and directed by Engr-in- Charge. | 11 | Each Job | |
| 2 | 1.01 | Note : Date wise rfecord of stage passing register maintained when servicing of each unit of each plant alongwith consumable used in each unit to be maintained dully signed by contractor, JE E/M & Eng-in-Charge. | |||
| 3 | 2 | Supply and replacement of Compressor oil of Cat Part No. 160/P.E.160S. Make:Klueber or equivalent of Castrol, Vidol, Servo, complete all as specified and directed. | 120 | Liters | |
| 4 | 3 | S & F for Gravity Propositioning angle valves 1/4\" x1/4\" of Cat Part No. MK 4 of Make Danfoss or equivalent of Parker or Sandhu complete all as specified and directed. | 10 | Each | |
| 5 | 4 | S & F for Crank case heater for Compressor model No -SM 185 S4 RC / SZ 185 S4 RC of Make-ACOCLIP or equivalent of Danfoss, Performer ,Sporlan complete all as specified and directed. | 8 | Each | |
| 6 | 5 | S & F for Liquid line Filter drier -DN/DCL 305 cat part No: 02370014 -46 bar of Make- Danfoss or equivalent of Performer complete all as specified and directed. | 10 | Each | |
| 7 | 6 | Supply and fix for Dry and wet bulb Psychrometer (PP Whirling Hygrometer) ISI marked complete in all respect along with accessories and covers of Make Unique or equivalent of Physilab or JRM complete all as specified and directed. | 15 | Each | |
| 8 | 7 | S & F for Thermostatic Expansion Valve TDEX-11 TR, 38.5 KW, with fixed orfice suitable for every type of plants i.e. Refrigerant type. Cat part No:MWP 667BE1414B of Make Danfoss or equivalent make of Parker and Sandhu complete all as specified and directed. | 10 | Each | |
| 9 | 8 | S & F for water pressure control unit Model No : FSW-8-251 of Make Nergy or as per sample as approved by GE complete all as specified and directed. | 8 | Each | |
| 10 | 9 | S & F for safety device control Valve Cat Part No. 022-01887,350 PSI Of Make :SAMLAN or equivalent of Danfoss, Parker,Sandhu complete all as specified and directed. | 8 | Each | |
| 11 | 10 | S & F for HRC fuse with holder, 20 Amps 415 V Make: L& T, CE or as per sample as approved by GE complete all as specified and directed. | 8 | Each | |
| 12 | 11 | S & F for Micro Computer Control (LCD type ) complete assembly including microcontroller card and internal PCB circuit board as required for complete control circuits of chiller plant .MODEL NO: XWGBS039AR2,Cat Part No:SE-1407 OF Make : Blue Star Complete all as Specefied and directed. | 4 | Each | |
| 13 | 12 | S & F for Danfoss commercial Compressor-scroll , Model No:SM 185-S4 RC 380 to 400 V 3 phase 50 HZ,Thermally protected ,Lubricant mineral oil-160P, Refigerant type R-22 of Cap-13.1 TR of Make- Danfoss or equivalent of Performer, Daikin or Carrier complete all as specified and directed.\nNote: \n(i)The compressor should be installed by the authorised companies refrigerant mechanic.\n(ii)After successful installation , the compressor should be vaccum by the nitrogen at desired pressure and leakage should be check.\n(iv)The rate of first charge of refrigerant gas in the compressor to be quoted in the rate of compressor by the contractor. | 1 | Each | |
| 14 | 13 | S & F for Danfoss commercial Compressor-scroll , Model No:SZ 185-S4 RC 380 to 400 V 3 Phase 50 HZ,Thermally protected ,Lubricant mineral oil-P.E.160 S, Refigerant type R-407 C of Cap-13.1 TR of Make- Danfoss or equivalent of Performer, Daikin or Carrier complete all as specified and directed.\nNote: \n(i)The compressor should be installed by the authorised companys refrigerant mechanic.\n(ii)After successful installation , the compressor should be vaccum by the nitrogen at desired pressure and leakage should be check.\n(iv)The rate of first charge of refrigerant gas in the compressor to be quoted in the rate of compressor by the contractor. | 3 | Each | |
| 15 | 14 | S & F of LWT/EWT ( leaving water temp and Entering water temp ) sensors with probe of best quality as per the plant capacity along with minimum 6 meter of suitable core of copper cable as per existing size complete all as specified and directed.\nNote: The sensor should be of original make and are capable of sensing the EWT and LWT.of Make Auber Instrumentsor equivalent to PAC systems and solutions / Nakshika Enterprise. | 30 | Each | |
| 16 | 15 | Material and labour for periodical servicing of AHUs by opening air filter, nut bolts, tray for AHU including cleaning of air filter panel, cleaning of cooling coil by coil cleaner solution and high pressure water and rectified refrigerant leakage in cooling coil complete with brazing and soldering, opening and disconnectning of AHU motor from blower room checking seviceability of shaft, fan puly fan belt and oiling /greasing complete , replacement unserviciable vibrating pads /spring in side of AHU for equal air flow from blower to defuser of any type /capacity blower complete all as specified and directed., | 14 | Each job | |
| 17 | 16 | Supply and replacement of pre fine Air filters panel of size 20 x 20 x 2 inch for dust filtration of particles up to 5 micros at 99% efficiency having air velocity through the filter Approx 350 to 400 FPM AHU of Make : Zenith filtersor equivalent to AFI/Spectraco/Asian filters complete all as specified and directed. | 60 | Each | |
| 18 | 17 | Material & labour for repair and servicing of cooling tower of cap 15 TR to 80 TR capacity AC Plant, Dismantling of cooling tower for removing of top cover and replacement of PVC Fill and unserviceable nozzle, replacement of rusted nuts, bolts with washers etc and cleaning bottom tank to remove mud and dust complete all as specified and directed by Engineer-in-charge.\nNote :- Spare parts ie flot valve,PVC Nozzels shall be measured and paid separately. | 10 | Each | |
| 19 | 18 | Material & labour for replacement of water hydra for cooling tower \nof cap 15TR to 85 TR capacity AC Plant by Dismantling of cooling tower electric motor and disconnecting all PVC Nozzles from hydra and replacement of as per existing size/model hydra for suitable water flow by pvc nozzles with replacement of rusted nuts, bolts with washers etc complete all as specified and directed by Engr-in-charge. | 2 | Each Job | |
| 20 | 19 | S & F for Galvanized wire mesh with wire of 1.40 mm dia, mesh size not less than 25 mm fixed on cooling tower by nut/bolts etc. complete all as specified and directed. | 4 | Each Job | |
| 21 | 20 | S&F for float valve assembly 25 mm complete all as specified and directed. | 10 | Each | |
| 22 | 21 | S&F for PVC Nozzles as per Sample complete all as specified and directed. | 40 | Each | |
| 23 | 22 | S&F for Honey Comb PVC Fills of Mechincal Draft FRP type cooling tower as per existing cooling tower makes, Size and type. Cap of cooling tower of AC plant upto 70 TR Round type. Standard of fills is 600MM X 300 MM X 150MM, Thickness 0.30 MM, No of PVC sheets per 150 MM width should be not less than 12 . Make Delta/JCT complete all as specified and directed. | 2 | Each | |
| 24 | 23 | Supply and refilling of Refrigerant Gas R- 407 C in sealed cylinders, complete all as specified and directed.\nNote :- Empty gas Cylinders shall be returned to contractor after use. Make: Floron , Mafron | 520 | Kg | |
| 25 | 24 | Supply and refilling of Refrigerant Gas R- 22 in sealed cylinders, complete all as specified and directed.\nNote :- Empty gas Cylinders shall be returned to contractor after use.\nMake: Floron , Mafron | 270 | Kg | |
| 26 | 25 | Supply and refilling of Refrigerant Gas R- 134 A in sealed cylinders, complete all as specified and directed.\nNote :- Empty gas Cylinders shall be returned to contractor after use.\nMake: Floron , Mafron | 270 | Kg | |
| 27 | 26 | Supply & refilling of Nitrogen gas in sealed cylinders of pressure rating of 90 psi of each cylinder for checking of leakage in all refrigerant piping and compressors (Empty Cylinders shall be returned to contractor after completion of contract) complete all as specified and as directed. | 10 | Each Cylinder | |
| 28 | 26.01 | Note :- All Consumable items used for servicing of plant (Chiller, condenser in item No. 01, Compressor oil in Item No. 02, consumable Gases used under item No. 23,24,25 & 26 will first be handed over to the Eng-in-Charge, who will take them in their charge and issue as and when required. Datewise record to that office will be measured duly signed by Contractor, JE E/M and Eng-in-Charge. The record to be enclosed with the RAR/ final bill for the verification. | |||
| 29 | 27 | M&L for rewinding of electric motor of Cap 60 HP three phase 415 volts by removing old u/s burnt copper winding wire, cleaning of slots and insertion of insulating paper in the slots in appropriate size and rewinding with super enameled copper wire ISI marked of suitable size along with insertion of superior quality of insulating material ,winding , varnishing and drying , including dismantling of electric motors connections and refixing back after rewinding including making necessary electric connection and testing complete all as specified and directed. \nMake of winding should be Hindustan/ Empire / RR Shramik /Seplco / Salzer. | 2 | Each Job | |
| 30 | 28 | All as per item No.27 but capacity of 25 HP. | 2 | Each Job | |
| 31 | 29 | All as per item No.27 but capacity of 15 HP. | 2 | Each Job | |
| 32 | 30 | All as per item No.27 but capacity of 7.5 HP. | 8 | Each Job | |
| 33 | 31 | All as per item No.27 but capacity of 3 -5 HP. | 8 | Each Job | |
| 34 | 32 | M&L for Repair /Overhauling of mono block pumping set 7.5 to 12.5 HP including replacement of GM bush, ball bearing, re-metaling, turning & polishing of pump shaft etc and testing commissioning and installation at site complete all as specified and directed.\nNote : - (i) Spare parts i.e.. GM bush, shaft sleeve and ball bearing shall measured and paid separately under relevent items.\n (ii) The complete job includes making good the existing pumps water leakage proof ,including gland/ packing etc.) | 6 | Each Job | |
| 35 | 33 | M&L for Repair /Overhauling of mono block pumping set 3 to 5 HP including replacement of GM bush, ball bearing , re-metaling, turning & polishing of pump shaft etc and testing commissioning and installation at site complete all as specified and directed.\nNote : - (i) Spare parts i.e.. GM bush, shaft sleeve and ball bearing shall measured and paid separately under relevent items.\n (ii) The complete job includes making good the existing pumps water leakage proof ,including gland/ packing etc.) | 6 | Each Job | |
| 36 | 34 | M & L for spray painting to Central AC Plant complete comprising of compressors, motors, condensor,cooling tower pump / monoblocks, MS / GI pipe lines of sizes etc after preparation of old painted surface as per colour code including and marking arrow, SM/ MES Nos, colour for 15 to 170 TR ACs plant as directed by the Engr-in- charge. | 10 | Each Job | |
| 37 | 35 | S & F in replacement of liquid valve (globe valve) Gun Metal, ISI marked including cutting / threading and welding of existing GI pipe of size 65 mm dia complete all as specified and directed.\nMake :- Zoloto/Kiran/Neta | 3 | Each | |
| 38 | 36 | S & F in replacement of GM gate valve ISI marked including cutting / threading and welding of existing GI pipe of size 65 mm dia complete all as specified and directed.\nMake :- Zoloto/Kiran/Neta | 3 | Each | |
| 39 | 37 | S & F in replacement of GM gate valve ISI marked including cutting / threading and welding of existing GI pipe of size 50 mm dia complete all as specified and directed.\nMake :- Zoloto/Kiran/Neta | 6 | Each | |
| 40 | 38 | S & F in replacement of GM gate valve ISI marked including cutting / threading and welding of existing GI pipe of size 40 mm dia complete all as specified and directed.\nMake :- Zoloto/Kiran/Neta | 4 | Each | |
| 41 | 39 | S & F in replacement of GM gate valve ISI marked including cutting / threading and welding of existing GI pipe of size 25 mm dia complete all as specified and directed.\nMake :- Zoloto/Kiran/Neta | 8 | Each | |
| 42 | 40 | S & F in replacement of GM gate valve ISI marked including cutting / threading and welding of existing GI pipe of size 20 mm dia complete all as specified and directed.\nMake :- Zoloto/Kiran/Neta | 8 | Each | |
| 43 | 41 | S&F in replacement of Discharge pressure gauges 100 mm dia 0 to 300 PSI of Make Feibig/HGURU/ SHUBH INSTRUMENTS complete all as specified and directed. | 8 | Each | |
| 44 | 42 | S&F in replacement of Suction/ Oil pressure gauges 100 mm dia 0 to 150 PSI of Make – Feibig/HGURU/SHUBH INSTRUMENTS complete all as specified and directed. | 8 | Each | |
| 45 | 43 | S & F for Wet and Dry thermometer for measuring temperature for air conditioner buildings in wooden body with arrangement of water etc Cat Part No Dimple wooden of body wall thermometer of Make : Sunshine Instruments or equivalent of Proxor group/Raj instrument as approved by the GE complete all as specified and directed. | 10 | Each | |
| 46 | 44 | S&F for Single phase preventer system of supply 415 Volt 50 Hz Model VSP2 of Make :- Minilec/ or equivalnet of L&T / ABB complete all as specified and directed. | 10 | Each | |
| 47 | 45 | S& F for Humidistat cum digital type thermometer with 99% efficiency and quick response time in AHU room, Make- Labortory deal / ADVANCE / MAXRADY LAB SOLUTIONS complete all as specified and directed. | 10 | Each | |
| 48 | 46 | S & F for V-Belt of size C– 107 of Make- Fenner complete all as specified and directed. | 8 | Each | |
| 49 | 47 | S & F for V-Belt of size A – 81 Make- Fenncomplete all as specified and directed.er | 6 | Each | |
| 50 | 48 | S & F for V-Belt of size B – 102 Make- Fenner complete all as specified and directed. | 5 | Each | |
| 51 | 49 | S & F for V-Belt of size A-50 Make- Fenner complete all as specified and directed. | 6 | Each | |
| 52 | 50 | S & F for V-Belt of size B-47/ B-56 Make- Fenner complete all as specified and directed. | 4 | Each | |
| 53 | 51 | S & F for V-Belt of size B – 88 / B – 90 Make- Fenner complete all as specified and directed. | 5 | Each | |
| 54 | 52 | S & F for V-Belt of size B – 82 Make- Fenner complete all as specified and directed. | 5 | Each | |
| 55 | 53 | S & F for V-Belt of size B – 78 / B – 80 Make- Fenner complete all as specified and directed. | 4 | Each | |
| 56 | 54 | S & F for V-Belt of size B-76 / B-56 Make- Fenner complete all as specified and directed. | 4 | Each | |
| 57 | 55 | S & F for V-Belt of size B-72 Make-Fenner complete all as specified and directed. | 5 | Each | |
| 58 | 56 | Supply and Fix in replacement of heating element 25 KW 220/380V Volts DN 40 water heater for hot warer generator complete all as specified and directed. Make-Daspass . Theta | 6 | Each | |
| 59 | 57 | Supply and fix in replacement of electric strip heaters 3 KW capacity ISI marked complete all as specified and directed. Make-Daspass,Theta. | 4 | Each | |
| 60 | 58 | M&L for Repairs to suction/discharge valve by replacement of Teflon sheet ‘O’ ring etc complete all as specified and directed. | 8 | Each Job | |
| 61 | 59 | M & L for providing thermal Insulation in replacement of old worm out insulation to supply air ducts /return air ducts with 32 mm thick , EPDM rubber with factory laminated glass cloth 7mil , 200 GSM sheet, Use adhesive fevicol SR 998, Joint should be sealed with tape of at least 2\" wide (Standard type ) and finished with Coating of Fevicol AC Duct king lag coating AF: 5590 and finally finish with UV resitance paint as per client choice complete all as specified and directed. Make of EDPM rubber is Aerflex and Make of Adhesive and lag coating is Fevicol. | 100 | Sqm | |
| 62 | 60 | M&L for repairs to the frame by cutting , jointing ,welding of existing frame from existing plate form including replacement of unserviceable MS angles as required as site and tightening / replacement of corroded nuts and bolts at existing site complete all as specified and directed by Engr-incharge. | 8 | Each Job | |
| 63 | 61 | Supply and replacement for Auxiliary contact MNX A-2 ,for 415 volt 10 Amps for contactor 25 Amp of Make:-L&T or Havells or Legrand or equivalent as approved by GE complete all as specified and directed. | 10 | Each | |
| 64 | 62 | Supply and replacement Contactor MNX-25, 220 Volt of Make-L&T or Havells or Legrand or equivalent as approved by GE complete all as specified and directed. | 8 | Each | |
| 65 | 63 | Supply and replacement Contactor MNX-70, 240 volt of Make- L&T or Havells or Legrand or equivalent as approved by GE complete all as specified and directed. | 2 | Each | |
| 66 | 64 | Supply and replacement Contactor MNX 18, 240 volt with auxiliary contract Make- L&T. or Havells or Legrand or equivalent as approved by GE complete all as specified and directed. | 20 | Each | |
| 67 | 65 | Supply and replacement Contactor MNX-50, 240 volt Make- L&T or Havells or Legrand or equivalent as approved complete all as specified and directed. | 10 | Each | |
| 68 | 66 | Supply and replacement of Spare coil for contactor type MNX-70 Cat Part No CS 94192 of make L&T or equivalent Cat Part of Havells or Legrand complete all as specified and directed. | 2 | Each | |
| 69 | 67 | Supply and replacement of Spare kit without coil for contactor type MNX-18 of Cat Part No CS 94125 of Make L&T or equivalent Cat Parf of Havells or Legrand complete all as specified and directed. | 8 | Each | |
| 70 | 68 | Supply and replacement Spare kit without coil for contactor type MNX-50 Cat Part No CS 94150 Make L&T or equivalent Cat Part of Havells or Legrand complete all as specified and directed. | 4 | Each | |
| 71 | 69 | Supply and replacement Spare coil for contactor type MNX-50 Cat Part No CS 94192 of Make L&T or equivalent Cat Part of Havells or Legrand complete all as specified and directed. | 4 | Each | |
| 72 | 70 | Supply and replacement Side mounting add-on block with Aux contact 1No+1Nc suitable for MNX- 9 to 40 contractor of Cat Part No CS 94220 of Make L&T or equivalent Cat Part of Havells or Legrand complete all as specified and directed. | 5 | Each | |
| 73 | 71 | Supply and replacement Side mounting add-on block with Aux contact 1No+1Nc suitable for MNX- 9 to 40 contractor of Cat Part No CS 94201 of Make L&T or equivalent Cat Part of Havells or Legrand complete all as specified and directed. | 5 | Each | |
| 74 | 72 | S & F for Electronic timers type ET-100,110/240 volt, 50 Hz Make : MICON Cat part No: 2ASD-CE or equivalent cat Part of L&T as approved by GE complete all as specified and directed. | 8 | Each | |
| 75 | 73 | S & F for Volt meter 0 – 500 V digital type, Make – AE /Crompton Greaves complete all as specified and directed. | 6 | Each | |
| 76 | 74 | S & F for Selector switch 4 way for volt meter. Make – Standard Gold complete all as specified and directed. | 6 | Each | |
| 77 | 75 | S & F for O/L relay 6 to 10 Amps 3 pole, directly operated. Make- L&T / BCH or equivalent as approved by GE complete all as specified and directed. | 5 | Each | |
| 78 | 76 | S & F for O/L relay 9 to 14 Amps 3 pole, directly operated. Make- L&T/BCH or equivalent as approved by GE complete all as specified and directed. | 6 | Each | |
| 79 | 77 | S & F for O/L relay 28 to 42 Amps 3 pole, directly operated. Make- L&T/BCH or equivalent as approved by GE complete all as specified and directed. | 5 | Each | |
| 80 | 78 | Supply and fix Timer GT – 200 complete with coil voltage 220. Make – BCH/L&T or equivalent as approved by GE complete all as specified and directed. | 6 | Each | |
| 81 | 79 | S & F for Amp meter 0–100 Amps digital type. Make - AE/Crompton Greaves or equivalent as approved by GE complete all as specified and directed. | 8 | Each | |
| 82 | 80 | S & F for Toggle switch SPST 10 Amps Make KAYCEEL / L&T or equivalent as approved by GE or equivalent as approved by GE complete all as specified and directed. | 6 | Each | |
| 83 | 81 | S & F for MCB, SP, of rating 63 Amps of Make-Schinider / L&T or equivalent as approved by GE complete all as specified and directed. | 8 | Each | |
| 84 | 82 | S & F for MCB, SP, of rating 6 to 40 Amps of Make-Schinider/ L&Tor equivalent as approved by GE complete all as specified and directed. | 8 | Each | |
| 85 | 83 | M&L for replacement of MCBs of capacity 40 Amps, four pole Make-Havells / L& T or equivalent make as approved by GE complete all as specified and directed. | 5 | Each | |
| 86 | 84 | M&L for attending job pertains to AC plant of any capacity as and when required with authorized dealer Ref-Mech / Electrician and helper, with necessary T&P for checking the equipment at existing location as and when required and find out the faults / defects and rectify the defects in situ and cleaning / normal maintenance to the equipments (including Lugs wire phase preventive, nuts bolts as required on site) complete to make the equipment functional in all respect complete all as specified and directed by the Engr- in-Charge. Note : (i) Spare parts shall be measured and paid separately\n (ii) The contractor has to provide services through OEM authorised dealers manpower only for mechanical as well electrical fault rectification.\n | 100 | Each Job | |
| 87 | 85 | S&F in replacement of MCCB, adjustable thermal and adjustable magnetic setting of capacity 400 Amps, 415V, four pole, 36 KA of Cat part no 830396 of Make Schnieder or equivalent Cat Part No. of ABB / Havells / L&T D-sine complete all as specified and directed | 2 | Each | |
| 88 | 86 | S&F in replacement of MCCB, adjustable thermal and adjustable magnetic setting of capacity 315 Amps, 415V, four pole , 36 KA of Cat Part No 830395 of Make Schnider or equivalent Cat Part of ABB / Havells / L&T D-sine complete all as specified and directed | 2 | Each | |
| 89 | 87 | S&F in replacement of MCCB, adjustable thermal and adjustable magnetic setting of capacity 250 Amps, 415V, four pole , 25 KA of Cat Part No 830297 of Make Havells or equivalent Cat Part No. Indo Asian / HPL /Havells schnider complete all as specified and directed | 2 | Each | |
| 90 | 88 | S&F in replacement of MCCB, adjustable thermal and adjustable magnetic setting of capacity 200 Amps, 415V, four pole, 25 KA of Cat Part No. 830296 of Make Schnieder or equivalent Cat Part No. ABB / Havells / L&T D-sine complete all as specified and directed. | 2 | Each | |
| 91 | 89 | S&F in replacement of MCCB, adjustable thermal and adjustable magnetic setting of capacity 160 Amps, 415V, four pole, 25 KA of Cat Part No 830295 of Make Schenieder or equivalent Cat Part No. Indo Asian / HPL / Havells complete all as specified and directed. | 3 | Each | |
| 92 | 90 | S&F in replacement of MCCB, adjustable thermal and adjustable magnetic setting of capacity,125 Amps, 415V, four pole , 25 KA of Cat Part No 830273 of Make Schnieder or equivalent Cat Part No. of ABB / Havells / L&T D-sine complete all as specified and directed. | 2 | Each | |
| 93 | 91 | S&F in replacement of MCCB, adjustable thermal and adjustable magnetic setting of capacity 63 Amps, 415V, four pole, 25 KA of Cat Part No. 830270 of Make Schneider or equivalent Cat Part No. of Indo Asian / HPL/ Havells complete all as specified and directed. | 2 | Each | |
| 94 | 92 | M & L for for 20 mm bore GI water tubing, medium grade, laid in trenches /wall / ducts with all required fitting complete all as specified and as directed | 25 | RM | |
| 95 | 93 | M & L for for 15 mm bore GI water tubing, medium grade, laid in trenches /wall / ducts with all required fitting complete all as specified and as directed | 25 | RM | |
| 96 | 94 | M & L for for 25 mm bore GI water tubing, medium grade, laid in trenches /wall / ducts with all required fitting complete all as specified and as directed | 25 | RM | |
| 97 | 95 | M & L for for 40 mm bore GI water tubing, medium grade, laid in trenches /wall / ducts with all required fitting complete all as specified and as directed | 25 | RM | |
| 98 | 96 | M & L for for 50 mm bore GI water tubing, medium grade, laid in trenches /wall / ducts with all required fitting complete all as specified and as directed | 25 | RM | |
| 99 | 97 | M & L for PVC insulated electric copper cable of size 16 sq mm 4 core including saddles & screws and laying in cable lay trunk perfectly complete all as specified and directed. Make:-Havells/polycab / Finolex | 60 | RM | |
| 100 | 98 | M & L for PVC insulated electric copper cable of size 16 sq mm 4 core including saddles & screws and laying in cable lay trunk perfectly complete all as specified and directed. Make:-Havells/polycab / Finolex | 50 | RM | |
| 101 | 99 | M&L for PVC insulated electric copper cable of size 35 sq mm 4 core including saddles,& screws and laying in cable lay trunk perfectly complete all as specified and directed. Make:-Havells/polycab / Finolex | 80 | RM | |
| 102 | 100 | M&L for PVC insulated electric copper cable of size 50 sq mm 4 core including saddles,& screws and laying in cable lay trunk perfectly complete all as specified and directed. Make:-Havells/polycab / Finolex | 60 | RM | |
| 103 | 101 | M&L for PVC insulated electric copper cable of size 4.0 sq mm 4 core including saddles & screws and laying in cable lay trunk perfectly complete all as specified and directed Make:-Havells/polycab / Finolex | 60 | RM | |
| 104 | 102 | M & L for 100 volts grade, heavy duty XLPE cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanized steel wire or tape and overall sheathed 50 Sqmm 3.5 core nominal cross section stranded conductor laying in cable lay trunk perfectly including saddles & screw complete all as specified and directed. Make:-Havells/polycab / Finolex | 60 | RM | |
| 105 | 103 | M & L for 1100 volts grade heavy duty XLPE cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanized steel wire or tape and overall sheathed 35 Sqmm 3.5 core nominal cross section stranded conductor laying in cable lay trunk perfectly including saddles & screw complete all as specified and directed Make:-Havells/polycab / Finolex | 100 | RM | |
| 106 | 104 | M&L for 1100 volts grade heavy duty XLPE cable with PVC insulated aluminium conductor served with an inner sheathing of PVC tape armoured with galvanized steel wire or tape and overall sheathed 25 Sqmm 3.5 core nominal cross section stranded conductor laying in cable lay trunk perfectly including saddles & screw complete all as specified and directed. Make:-Havells/polycab / Finolex | 100 | RM | |
| 107 | 105 | Repair to Microprocessor Electronic PCB Card of Chiller type Central AC plant of Make Blue star / Voltas including all devices like diodes, resistance, capacitor, IC, Thermostat, transformer, relay, switch, indicator, sensors etc. Complete all after disconnecting the PCB card from the Chiller unit and refixing the same after repair and testing complete all as specified and directed. | 10 | Each Job | |
| 108 | 106 | Supply only The Hygro Palm 2-series latest handheld measuring instrument for relative humidity, temperature and dew point. Based on AirChip3000 technology, with achieved degree of accuracy (100%). In combination with advances in sensor technology and integration, the HygroPalm2-series should provide superb precision and state-of-the-art functionality, taking humidity and temperature mesurement to a whole level of performance and reliability as (< 0.8 %rh / 0.1 K) should provide humidity and temperature data with all relative humidity and temperature measurements, dew Point and other psychrometric calculations. It should have Outstanding accuracy and repeatability with a 2,000 data point memory Auto-diagnostics and automatic correction Highest-possible measuring accuracy with elctronics operating range -10 to 60 degree celius, 0-100 % RH, 9 volts power battery supply and AC mains adaptor with IP-40 protection, should be made of ABS housing, Measurement range should be -10 to 60 degree celius 0 to 100 % RH and -50 to -200 Degree Celcius, Model : Hygropalm 2 series Make Rotronic complete in all respect with accessories and packing covers etc or equivalent of Stanley complete all as specified and directed. | 1 | Each | |
| 109 | 107 | Supply, installation, commissioning and testing of dehumidifier unit, in replacement of old unserviceable unit, main body made of metallic sheet duly powder coated, comprising built -in compressor of suitable capacity, special purpose fan motor high saving efficient system of minimum capacity of 140 liters per day, dehumidifying capacity of minimum 5.85 Kg per hrs, minimum Air flow of 1500 Cum per hrs, minimum humidity setting of RH -30% to 95% in working temp of 5 degree centigrade to 38 degree centigrade electric operated 220-240 volts 50 Hz having minimum power consumption of 2000 Watt rotary compressor based type with maximum controlling of noise level of 52 dB using CFC free refrigerant R-407c or R-410A, drain pipe arrangement towards outside internally fixture to remove the water outside the dehumidifying room, multiple functional wheels, automatic defuser system, delay timer for compressor complete in all respect as reqd at site and as directed by Engr-in-Charge complete all as specified and directed. MAKE Model No AMDH1400 of advance international or having same or superior specification in ADVANCE INTERNATIONAL / GMP DUEX INDUSTRIAL SYSTEM/HARRISONS PHARMA MACHINERY PVT LTD/ALISHAPNUEMATICS PVT LTD or as approved by GE in writing. | 1 | Each | |
| 110 | 108 | Supply and replacement triple layer rotational molded polyethylene water storage tanks ( cylindrical vertical with closed top) hoisted and fixed in position of Capacity 5000 liters complete all as specified and as directed Make : Syntax / Plasto /aashirwad. | 2 | Each | |
| 111 | 109 | Supply, fix and installation of shall and tube type evaporator for 25.1 TR water cooled chiller compaitable in scroll type compressor as per technical space. Actual capacity as per ambient condition : 25.1 TR chilled water inlet temp 1 degree centigrade, Chilled water outlet temp 7 degree centigrade, Chilled water flow rate : UGGPM, Fouling factor : 0.000088 Sqm K/W complete all as specified and as directed. Make : Blue star Model XWC2S-026AR2 | 1 | Each job | |
| 112 | 109.1 | Note: \n1. All the spares parts / equipments shall be procured from the authorized dealers of the equipment. All the tax invoices from the authorized dealer for the replaced item shall be produced to GE, before making payment.\n2. After De-scaling servicing and cleaning of compressor and condenser, the required Ambient temperature i.e. 22 degree Celsius should be maintained and confirmed to the Engineer-in-Charge.\n3. The complaint or Jobs for the maintenance works should be collected from the JE/Engineer-in- Charge on daily basis and the feedback / progress report for the same shall be provided to the JE /Eng-in-Charge on daily basis.\n4. The Refrigerant gas to the compressors shall be charged precisely and accurately by the professional refrigerant mechanic so that there would be no leakage of gas after charging. In case if there would be any leakage just after the charging then the contractor will be held responsible for the same and it will be not measured. \n5. The contractor shall stand guarantee for the trouble free functioning of equipment (where repaired carried out) for a period of one year from date of completion. |
Copyright © 2025 · All Rights Reserved. Terms of Usage | Privacy Policy