Delhi Jal Board-DJB has published Nit . No . 15 ( 2019-20 ) /Ee ( Sdw ) Viii/ Item No . 2 Repair And Renovation Of Lt Panel Installed At Compressor Unit Of Pappankalan Phase-1 , Stp 20 Mgd Dwarka. Submission Date for this Tender is 06-04-2020. Electrical Panel Tenders in SEC. 16-D, PAPPANKALAN N. DELHI Delhi. Bidders can get complete Tender details and download the document.
Name of Work:-Repair and renovation of LT panel installed at compressor unit of Pappankalan Phase-1, STP 20 MGD Dwarka | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1.01 | Dismantling of components from LT panel from the panel. Removing of defective parts, & other parts i.e. indicating lights, ap. Meter etc dismantling of all incoming & outgoing connection | item1 | 1 | Job |
2 | 1.02 | Indicating lights R.Y.B. , Make: L&T/SG/FTC | item2 | 48 | Nos. |
3 | 1.03 | Push button Red with NO+NC elements Make: L&T/SG/FTC | item3 | 16 | Nos. |
4 | 1.04 | Push button Green with NO+NC elements ,Make: L&T/SG/FTC | item4 | 16 | Nos. |
5 | 1.05 | 16 mm Pin type copper lugs Make: Dowell/jainson | item5 | 150 | Nos. |
6 | 1.06 | 16mm ring type copper lugs Make: Dowell/jainson | item6 | 120 | Nos. |
7 | 1.07 | Terminal Block, make : Elemex/connectwell | item7 | 80 | Nos. |
8 | 1.08 | Auxiliary contractor 2NO+2NC,make:L&T/Siemens | item8 | 10 | Nos. |
9 | 1.09 | Star delta timer,make:L&T | item9 | 16 | Nos. |
10 | 1.1 | Amp. Meter digital size 96X96sqmm,,Make: L&T/AE | item10 | 16 | Nos. |
11 | 1.11 | Volt meter digital 0-500V size 96mmX96mm,,Make: L&T/AE | item11 | 2 | Nos. |
12 | 1.12 | MCB 4 pole 32 Amp. Make:legrand/L&T | item12 | 2 | Nos. |
13 | 1.13 | MCCB 250 Amp. TP 36 Ka with spreader terminal & handle Make:Siemens/L&T/C&S | item13 | 16 | Nos. |
14 | 1.14 | PVC insulated copper flexible wire 16 sqmm, Make:Kalinga/Havells/finolex | item14 | 150 | Mtr. |
15 | 1.15 | PVC insulated copper flexible wire 50 sqmm, Make: kalinga/Havells/finolex | item15 | 80 | Mtr. |
16 | 1.16 | Motor protection relay with thermal over load short circuit, phase loss, under current protection mode, make :L&T/Siemens | item16 | 16 | Job |
17 | 1.17 | cleaning of complete bus bar of panel insulation on bus bar by PVC sleeve or tape | item17 | 1 | Job |
18 | 1.18 | Replacement of tube light in panel & control MCB & making complete wiring | item18 | 2 | Job |
19 | 1.19 | Current transformer 250/5, Make: AE/Saviour/Advance | item19 | 16 | Nos. |
20 | 1.2 | Fixing of all above components in place of defective removed components as required complete with control wiring, fixing of amp.meter, indicating lights etc. complete with all incoming & outgoing cable connection with thimbling, | item20 | 1 | Job |
21 | 1.21 | Complete checking of LT panel wiring, minor accessories replacement i.e. panel door lock, gas cut, rubber bidding, setting of doors, cover any open door, hole for protection etc. complete in all respect. | item21 | 1 | Job |
22 | 1.22 | Enamel paint on complete LT panel 2 coating | item22 | 1 | job |
23 | 1.23 | Testing & commissioning of the panel as follow: -Meggaring of all equipments for phase to phase, neutral to body, neutral to earth and phase to earth.-All functional tests -Testing of the panel at site ON LOAD with engineer in chars as per relevant IS | item23 | 1 | Job |