| 1 | 1 | Excavation in trenches n.exc. 1.5 m wide and n.exc.1.5m in depth for laying of XLPE insulated Cable including getting out complete all as specified & directed by Engr-in-Charge. | | 6 | Cum |
|---|
| 2 | 2 | Returning filling in including spreading leveling watering and well ramming in layers not exceeding 25 cm complete all as specified & directed by Engr-in-Charge. | | 5 | Cum |
|---|
| 3 | 3 | Removing excavated material n.exc. 50m and depositing where directed at a level n.exc 1.5 m above starting point complete all as specified and directed. | | 1 | Cum |
|---|
| 4 | 4 | M&L for spreading & leveling dry clean Ganga sand in trenches for cushioning UG cable complete all as specified and directed. | | 3 | Cum |
|---|
| 5 | 5 | M&L for sub class old size of Brick in trenches for cable protection of LT Cables complete all as specified and directed. | | 240 | Each |
|---|
| 6 | 6 | S&F of 80 mm nominal bore light grade galvanised mild steel tubing with all fittings and fixed to poles / walls with mild steel clamps, bolts, nuts and washers complete all as specified and directed. | | 6 | RM |
|---|
| 7 | 7 | Supply and installation of 3 phase vertical tower AC 4.0 TR capacity, with cooling capacity of 48000 BTU/Hours along with dust filter anti-corrosive blue fin copper condenser, hydrophilic blue evaporator fins, powder coated outer body, auto/manual mode operation including memory function with heavy duty 3 phase scroll type compressor within the Eco friendly R22 refrigerant and which has low noise level, PVC copper wire of 4 core 2.5 sqmm to be used to indoor unit to outer door unit along with the foundation for outer unit and repairing the disturbed surface including distempering if required all as specified and directed. Make:- Blue star/Voltas/Carrier. | | 3 | Each |
|---|
| 8 | 8 | S&F copper pipe along with PVC cushion o size 3/4\" dia complete all as specified and directed. | | 25 | RM |
|---|
| 9 | 9 | All as per item No 8.00 but of size 1/2\" dia complete all as specified and directed. | | 25 | RM |
|---|
| 10 | 10 | M&L for sub main wiring with three runs of single core 6 Sqmm (nominal area) PVC insulated and unsheathed multi stranded copper conductor cable LT 1100 grade FRLS cable drawn and PVC casing N Capping with all necessary fittings and accessories and 02xrun of PVC insulated and unsheathed single core cable multi stranded with copper conductor of size 4 Sqmm as continuous neutral and earth wire (black and green in colour ) respectively, run through PVC casing N capping and connected to the terminal and common earth dolly all as specified and directed.\n(Note. Five run of cable and one run of PVC casing and capping and one run of earth continuity wire shall be measured as one run complete all as specified.) | | 80 | RM |
|---|
| 11 | 11 | S & F VTPN distribution board double door 4 ways with the provision of MCCB as incomer and wintrip MCB as outgoing with IP-43 protection, with suitable lugs for incomer, cable glands and bottom lugs for outgoing distribution system complete all as specified and directed. | | 1 | Each |
|---|
| 12 | 12 | S&F moulded case circuit breakers (MCCB's) 415 Volts, 63 Amps, 40 KA, 4 pole complete all as specified in existing DB'S in replacement and directed. | | 1 | Each |
|---|
| 13 | 13 | S&F in replacement MCB TP upto 40 Amp, 240 Volt complete all as specified and directed. | | 3 | Each |
|---|
| 14 | 14 | S & F triple pole and earth enclosure with a three pin and earth plug with socket complete with one triple pole MCB of capacity 32 Amp 'C' series all as specified and directed. | | 3 | Each |
|---|
| 15 | 15 | M& L for earthing complete with galvanized steel earth plate electrode 60cm x60 cm x6.0 mm thick buried directly in ground (earth pit not less than 2.25 Mtrs deep below ground level) with top edge of the plate not less than 1.50 Mtr below normal ground level connected to galvanized earth lead strip 32x6mm dia by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No.5 connected to earthing test point all as specified or indicated including testing on completion including PCC pit in (1:3:6) type C-2 cement concrete .RCC 1:2:4 Mix type B reinforced with 6mm dia MS bars @ 150mm RCC cover slab 40mm thick with two no’s fitting handle, GI pipe 20mm dia light grade with funnel & wire mesh for watering and 40mm dia light grade GI pipe for earth strip 32x6mm protection etc. complete all as specified and directed by Engr-in-Charge. | | 1 | Each Job |
|---|
| 16 | 16 | Supply and replacement of unserviceable XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric power cable heavy duty with aluminium conductor 1100 volts grade cross sectional 50 sq mm 3.5 core, laid in trenches/ducts /encased in GI pipe/fixed to pole including taking out of existing unserviceable cable/OH conductor all as specified and directed.\nMake : Polycab/Havells/Gloster | | 78 | RM |
|---|