Provn Of Capacitor Bank As Auto Power Factor Control ( Apfc ) Panels At Power House At Damana And Certain Sanctioned Em Works At Damana And Sunjuwan Under Ge Jammu, AoR of GE Jammu-Jammu And Kashmir

Military Engineer Services-MES has published Provn Of Capacitor Bank As Auto Power Factor Control ( Apfc ) Panels At Power House At Damana And Certain Sanctioned Em Works At Damana And Sunjuwan Under Ge Jammu. Submission Date for this Tender is 07-05-2020. Power Factor Panel Tenders in AoR of GE Jammu Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

24114314
Corrigendum : Provn Of Capacitor Bank As Auto Power Factor Control ( Apfc ) Panels At Power House At Damana And Certain Sanctioned Em Works At Damana And Sunjuwan Under Ge Jammu
Open Tender
Indian
Jammu And Kashmir
AoR of GE Jammu
07-05-2020

Tender Details

Provn Of Capacitor Bank As Auto Power Factor Control ( Apfc ) Panels At Power House At Damana And Certain Sanctioned Em Works At Damana And Sunjuwan Under Ge Jammu

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 07-Apr-2020 Corrigendum01 Date 18-04-2020
2 18-Apr-2020 Corrigendum02 Date 30-04-2020
3 30-Apr-2020 Bid Auto Extn Corrigendum Bid Auto Extn Corrigendum 07-05-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 72900.0 /-
Tender Value
INR 36.45 Lakhs /-

BOQ Items

Name of Work: PROVN OF CAPACITOR BANK AS AUTO POWER FACTOR CONTROL (APFC) PANELS AT POWER HOUSE AT DAMANA AND CERTAIN SANCTIONED E/M WORKS AT DAMANA AND SUNJUWAN UNDER GE JAMMU
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply and fixing of ceiling fans 1200mm sweep, high speed, single phase, 50 Hz, energy efficient, star rating, 230 Volts, confirming to ISI complete with and including fan down rod of suitable size, fan clamps, rubber bush and flexible three core branded copper of suitable size for necessary connection upto ceiling rose complete all as specified and as directed by Engr-in-Charge. 80 Each
2 2 Supply and fixing Voltage Stabilizer 500 KVA for automatic operation, three phase naturally oil cooled indoor type and designed for input variation between 320 V to 460 V with output voltage stabilized at 415 with accuracy + 2.5% and speed of correction 8 Volts per second and of capacity including 1st filling of transformer oil complete all as specified and as directed. 1 Each
3 3 Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 630 Sqmm 3.5 core laid in trenches/ on wall/ pole/ on air/ through pipe etc complete all as specified and as directed.\nNote:- Excavation and earth work, sand cushioning, covers and pipe etc shall be measured and paid separately. 87 RM
4 4 Excavation in trenches, n. exc 1.5m wide and n. exc. 1.5m in depth and getting out in hard/dense soil for foundation of pole, stay, laying of cable and pipe etc all as specified and as directed. 65.52 Cum
5 5 Returning and filling in, including spreading and well ramming in layers n. exc. 25 cm all as specified and as directed. 34.87 Cum
6 6 Removing excavated material to a distance n. exc. 50m and depositing complete where directed at a level n. exc. 1.50m above the starting point complete all as specified and as directed. 30.65 Cum
7 7 Material and Labour for dry sand cushioning to under ground cable in trenches laid 15cm below the cable and 8cm after laying the cable including spreading, levelling and hand punning complete all as specified and as directed. 23.77 Cum
8 8 Supply and laying common burnt clay sub class 'B' bricks old size, laid over sand cushioning laid at right angle along with cable all as specified and as directed. 2612 Each
9 9 Earthing complete with galvanised steel earth plate electrode 60cm X 60cm X 6mm thick buried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of plate of not less than 1.5 mtr below normal ground level, connecting to the GI strip 25 X 4mm using 40mm pipe for protection by means of bolts, nuts, check nuts and washer of GI and including provn of concrete pit in PCC (1:2:4) type B-1 using 20mm graded crushed stone aggregates with CI cover with suitable angle frame and handle, GI light grade 20mm bore pipe for watering, perforated at bottom, 1.75 mtr long placed on top edge of earth plate, charcoal and common salt filling, funnel, wire mesh, excavation and earth work in hard/dense soil, returning, filling in and removal of surplus soil to a distance not exceeding 50mtr, all as per electric plate No 5 of SSR Part-I and connecting to earth test point and including testing on completion complete all as specified and all as directed. 8 Each
10 10 Supply and fixing Voltage Stabilizer 200 KVA for automatic operation, three phase naturally oil cooled indoor type and designed for input variation between 320 V to 460 V with output voltage stabilized at 415 with accuracy + 2.5% and speed of correction 8 Volts per second and of capacity including 1st filling of transformer oil complete all as specified and as directed. 1 Each
11 11 Supply and lay cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 300 Sqmm 3.5 core laid in trenches/ on wall/ pole/ on air/ through pipe etc complete all as specified and as directed.\nNote:- Excavation and earth work, sand cushioning, covers and pipe etc shall be measured and paid separately. 49 RM
12 12 Dismantling and taking down carefully copper/aluminium point wiring (light, fan, socket or power) complete, including fittings such as switches, ceiling roses, pendeants, regulators, sockets, light fittings etc, to be measured separately and making good the disturbed surface complete all as specified and as directed. 62 Per Point
13 13 Taking down old and unserviceable Submain wiring any size of two core including earth wire complete including batten/ conduit and make good the disturbed surface to match the existing surface, all as specified and as directed by Engr-in-Charge. 30 RM
14 14 Taking out old and unservcieable distribution board/ main switch/ changeover switch of any type including fuses, MCBs etc after removing all connections and make good the disturbed surface all as specified and as directed by Engr-in-Charge. 3 Each
15 15 Material and Labour for point wiring complete with 1.5 Sqmm multistranded copper conductor FRLSH PVC insulated (unsheathed) heavy duty cable including continuous earth wire with cable of size 1.5 Sqmm copper conductor multistranded FRLSH PVC insulated (unsheathed) drawn into and including concealed PVC rigid conduit of size 20mm dia and 1.8mm wall thickness ISI marked terminated into existing CI/ pressed steel terminal boxes including 3.00mm thick hylam brand IS-2036 makred, laminated sheet cover for mounting switches, sockets, fan regulators etc including taking down existing point wiring all as specified and directed for the following:-\nNote:- (a) Wiring shall be done by using colour coding.\n(b) Earth wire shall be of green colour.
16 15.01 One light/ Fan point controlled by one switch 5 Amps one way using cable (1.5 Sqmm for phase and neutral and 1.5 Sqmm for earthing) complete all as specified and as directed. 46 Per Point
17 15.02 All as per Ser Item No 15.01 above but 5 Amp outlet on same board complete all as specified and as directed. 4 Per Point
18 15.03 All as per Ser Item No 15.01 above but 5 Amp socket outlet on independent board all as specified and as directed. 8 Per Point
19 15.04 All as per Ser Item No 15.00 above but for one socket outlet 5/15 Amps on independent board with cables of size 2.5 Sqmm complete all as specified and as directed. 4 Per Point
20 15.05 Note:- On RCC roof/ ceiling PVC conduit shall be provided on surface with proper fixing clips all as specified and as directed by Engr-in-Charge.
21 16 Distribution board sheet steel phosphatised powder coated for MCB/ DB with copper bus bar and neutral link earthing stud (confirming to IS-13032, IS-8623) SPN 8 way 240 Volts double door complete all as specified and as directed. 3 Each
22 17 Supply and fixing for MCB SP 6 to 32 Amps 240 Volts complete all as specified and as directed. 18 Each
23 18 Supply and fixing for MCB SPN 40 Amps 240 Volts complete all as specified and as directed. 41 Each
24 19 Supply and fixing for switch piano, flush type single pole one way 5 Amp, 240 Volts all as specified and as directed. 50 Each
25 20 Supply and fixing switch piano, flush type two way, 5 amps, 240 Volts for stair case all as specified and as directed. 2 Each
26 21 Supply and fixing socket outlet 5 amps/ 3 pin flush type for same board all as specified and as directed. 4 Each
27 22 Supply and fixing socket outlet combined 5 pin 5 Amp flush type, 240 Volts all as specified and as directed. 8 Each
28 23 Material and labour for Switch socket combination 2 in 1, 3 pin, 5/15 Amp flush type universal, 240 Volts for independent board complete all as specified and as directed. 6 Each
29 24 Supply and fixing Ceiling rose 3 terminal size 50 X 65 mm or 50mm dia round type surface type all as specified and as directed. 30 Each
30 25 Material and labour for decorative polycarbonate wall light fitting made up of polycarbonate, including 9 Watt LED retro fit Bulb, all as specified and as directed by Engr-in-Charge. 6 Each
31 26 Material and labour for Lamp holder, insulated body, with back plate suitable for batten fittings with and including LED Bulb 9 Watt complete all as specified and as directed. 10 Each
32 27 Energy efficient, endura linear LED wall mounted LED tubelight batten fittings, extruded aluminium heat sink provided for efficient heat dissipation and integrated electronic driver 18 watt LED 6K (4 ft) 230 Volts 50 Hz all as specified and as directed. 20 Each
33 28 Material and labour for LED street light of cap 1 X 11 watt Aluminium PDC housing, toughened glass cover with IP 65 protection in GI pipe bracket with suitable size medium grade complete all as specified and as directed by Engr-in-Charge. \n 4 Each
34 29 Stepped type electronic fan regulator flush type on the existing phenolic laminated sheet all as specified and as directed. 6 Each
35 30 Material and labour for Sub main wiring with proper colour coding, insulated, unsheathed, multistranded, copper conductor FRLSH, PVC cable of 2 run 6 Sqmm for phase and neutral and one run of 4.00 Sqmm for earth wire unsheathed, multistranded, copper conductor FRLSH, PVC cable, drawn through rigid PVC conduit fixed on wall/ ground/ ceiling etc and connected all as specified and as directed by Engr-in-Charge.\nNote:- (i) PVC conduit will be measured separately.\n(ii) Phase should be of Red/Yellow/Blue, neutral should be of black and earthing wire should be of green colour. Two runs of cable for phase/neutral and one run of cable for earth will be measured and paid as one unit length.\n(iii) Earthing wire shall be of green colour. 265 RM
36 31 Material and labour Earthing complete with galvanized steel earth plate electrode 600 X 600 X 6mm thick, buried directly in ground (earth pit not less than 2.25 metres deep below ground level) with top edge of the plate not less than 1.5 metres below normal ground level, connected to galvanised earth lead wire 4.0mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in Electrical plate No 3 connected to earthing test point including testing on completion complete all as specified and as directed. 2 Each
37 32 Distribution board sheet steel phosphatised powder painted for MCB TPN DB, 4 way, 415 Volts, with copper bus bar and neutral link earthing stud complete all as specified and as directed by Engr-in-Charge. 1 Each
38 33 Material and labour for plug and socket board SP&N enclosure with 2 Pole and earth metal plug and socket for incorporating 10A/20A SPN/DP MCB complete all as specified and as directed by Engr-in-Charge. 2 Each
39 34 Material and labour for taking down old UNSV Ceiling fans and fitting back after repair the burnt out ceiling fan from the ceiling by disconnecting the electrical connections, removing the burnt out winding from the starter of the ceiling fan any make and sweep and rewinding with matching gauge and turns of superenamelled copper wire leathenic paper, glass sleeves etc including varnishing the winding will be carry out at site or MES store yard and testing on completion complete all as specified and as directed.\nNote:- (a) Repair will be measured separately. 6 Each
40 34.01 Material and labour for rewinding of ceiling fan all as specified and as directed. 6 Each
41 34.02 Material and labour for replacement of ball bearing ceiling/ wall mounted fan (Set of Two) all as specified and as directed. 6 Each Set
42 34.03 Supply and replacement of capacitor 2.5/ 4 mfd 240 Volts of ceiling/ exhaust fan all as specified and as directed. 6 Each
43 34.04 Material and labour for replacement of MS tube 300mm long complete all as specified and as directed by Engr-in-Charge. 6 Each
44 34.05 Material and labour for replacement of clamps including rubber bush complete all as specified and as directed by Engr-in-Charge. 6 Each Set
45 34.06 Material and labour for preparation of existing painted surfaces of state ceiling fans any make and sweep and spray painting with two coat of super enamelled paint, marking linings etc to match the original colour and style including writing MES No complete all as specified and as directed. 6 Each
46 35 Supply and fixing of Exhaust fan, metal body, 230 Volts, single phase, 230mm sweep suitable for wall mounting and including making of hole in wall, making good the disturbed surface, Star rating, heavy duty all as specified and as directed. 2 Each
47 36 Supply and installed Water heater storage type (Geyser) star rating complete, capacity 35 Ltrs including grouting of bolt for fixing of geysers all as specified and as directed. 2 Each
48 37 Supplying and laying GI pipe medium grade in walls and ceiling or laid in floor including all fittings of size 15mm dia all as specified and as directed by Engr-in-Charge. 2 RM
49 38 Supply and fixing Stop valves, cast copper alloy, screwed down, high pressure, with crutch or butterfly handle, screwed both ends for iron pipe or for unions and fixed for 15mm dia of pipe all as specified and as directed. 2 Each
50 39 Supply and fixing PVC connection of size 15mm dia with PTMT nuts of length 450mm long (hot series and cold series) complete all as specified and as directed by Engr-in-Charge. 4 Each
51 40 Supply and fixing Bib tap cast copper alloy with crutch or butterfly handle screwed down, screwed for iron pipe for brass ferrule of size 15mm bore all as specified and as directed. 2 Each
52 41 Taking out/down unserviceable, defective any type/size cable including disconnecting/dismantling all the electrical connections all as required at site and all as directed. 130 RM
53 42 Material and labour for LT underground cable XLPE insulated, heavy duty armoured sheathed 1100 Volts grade 25 Sqmm, 3.5 Core, with aluminium conductor, ISI marked as per IS : 7098 (Part - I) complete all as specified and as directed including taking down old unserviceable cable. 130 RM
54 43 S&L and testing cable XLPE insulated screened PVC bedded galvanised steel strip or wire armoured, electric power cable (Heavy duty) with stranded aluminium conductor 1100 V grade cross sectional area 50 Sqmm, 3.5 core in and including taking out old one all as specified and as directed. 190 RM
55 44 Taking down old unserviceable GI pipe of size 50/40mm dia from on walls/ culverts all as specified and as directed. 5 RM
56 45 Material and labour for GI pipe light grade 40mm bore for cable protection as a guard pipe complete all as specified and as directed. 5 RM
57 46 Material and labour for GI tubing light grade incuding all accessories for mechanical protection laid under plinth/floors/path culverts of size 50mm dia complete all as specified and as directed. 40 RM
58 47 Supply and fixing sheet metal enclosure (factory made) double door for distribution board (when MCB's are to be used) triple pole and neutral 415 V, 4 ways connection with suitable size of thimbles complete all as specified and as directed. 6 Each
59 48 Supply and fixing side handle operated on load change over switch 125 Amp in CRCA body, 4 Pole 415 Volt all as specified and as directed. 1 Each
60 49 Material and labour for MCCB 4 Pole, current rating 125 Amp, thermal setting adjustable 70%-100% breaking capacity 25 KA at 415V, 50 Hz complete all as specified and as directed. 1 Each
61 50 Material and labour for MCCB 4 Pole, current rating 100 Amp, thermal setting adjustable 70%-100% breaking capacity 25 KA at 415V, 50 Hz complete all as specified and as directed. 5 Each
62 51 Supply and fixing temper proof three phase, 415 volt electronic energy meter with LCD display of 0-60 Amps rating confirming to ISI complete with temper proof cover all as specified and as directed. 5 Each
63 52 Supply, fixing, connecting and commissioning and testing of Company Make (automatic and manual operation) power factor improvement panel of capacity 250 KVAR for 500 KVA Transformer including interconnection with LT panel with appropriate size of electric cable for transformer Outdoor/Indoor) type panel factory made, weather proof, dust and vermin proof (IP 54/ IP 42) suitable for 1100 V / 440 V grade 3 phase 50 Hz AC supply floor mounted, fabricated out of 14 SWG MS sheet and having four Nos angle iron legs made out of 40 X 40 X 6mm, 60cm long angle iron below frame with front door and Side/ Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 Sqmm/ extension strips and connected with suitable size thimbles, lugs duly painted with L&T grey epoxy powder coating after suitable chemical treatment, legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles, all as specified and as directed by Engr-in-Charge. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (dvepl, tricolitre, L&T, Legrand) will be accepted and factory inspection will be done by GE/AGE at original manufacturer plant only and all other electric incoming and outgoing connections with PVC insulated multistranded flexible copper cable of suitable size and PVC flexible conduit medium quality as required and comprising of the following:- 1 Each
64 52.01 Incoming Feeder:-\nIncomer MCCB 630 Amps, Three Pole, Terminal based release with adjustable O/L, Adj S/C Setting Class II Front Face, 36KA rupturing capacity, lcs=100%lcu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barriers- 1 No all as specified and as directed.
65 52.02 Metering Section - Digital Ammeter (0-400) Amps, Digital Voltmeter (0-500) Volts, RYB Indicating Lamps, 1 Set Control Fuses, CTs. 3 all as specified and as directed.
66 52.03 Insulated Busbar of Aluminium of 630A Capacity for 3 phase, fixed on Insulators, Busbar should be PVC Sleeved with red, yellow, blue colour, Busbar support should be of smc/dmc - 1 set all as specified and as directed.
67 52.04 Multi 16 Step 440V, 5A (144 X 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display all as specified and as directed.
68 52.05 Outgoing Feeder:-\nAccessories for 1 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 1 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 6A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start/ Stop Push Button all as specified and as directed.
69 52.06 Accessories for 2 KVAR Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 2 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 16A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button all as specified and as directed.
70 52.07 Accessories for 7 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 7 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 20A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
71 52.08 Accessories for 10 KVAR Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 10 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 25A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
72 52.09 Accessories for 15 KVAR Capacitor Bank - 3 Nos :- Capacitor Duty Contactor 15 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 32A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button all as specified and as directed.
73 52.1 Accessories for 25 KVAR Capacitor Bank - 7 Nos :- Capacitor Duty Contactor 25 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 63A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
74 52.11 Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on / off of fans depending upon the temperature of the pane; 230 VAC 1500 rpm, 160 cu.m/h flying leads all as specified and as directed.
75 52.12 Automatic Power Factor controller steps Relay Micro processor based for switching ON and OFF of capacitors to Display of voltage, current, Active power, apparent Power display of COS Ø, THD voltage, THD current, alarm indication for defective step, low power factor and excess temperature. The relay having volt free c/o contact, automatic detention and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement. Switching program : LIFO\ncombi Filter, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 Volt, 45 to 65 Hz, current measuring 10MA-5A suitable for CT x/1A and x/5A commissioning without additional setting and programming. Three decimal power reading. Phasing out of fault capacitor bank automatically all as specified and as directed.
76 52.13 All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 14 swg thick MS sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer all as specified and as directed.\nNote:- APFC panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (Dvepl, Tricolite, L&T, Legrand) will be accepted and factory inspection will be done by GE/AGE at original manufacturer plant only.
77 53 Supply, fixing, connecting and commissioning and testing of Company Make (automatic and manual operation) power factor improvement panel of capacity 200 KVAR for 400 KVA Transformer including interconnection with LT panel with appropriate size of electric cable for transformer Outdoor/Indoor) type panel factory made, weather proof, dust and vermin proof (IP 54/ IP 42) suitable for 1100 V / 440 V grade 3 phase 50 Hz AC supply floor mounted, fabricated out of 14 SWG MS sheet and having four Nos angle iron legs made out of 40 X 40 X 6mm, 60cm long angle iron below frame with front door and Side/ Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 Sqmm/ extension strips and connected with suitable size thimbles, lugs duly painted with L&T grey epoxy powder coating after suitable chemical treatment, legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles, all as specified and as directed by Engr-in-Charge. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (dvepl, tricolitre, L&T, Legrand) will be accepted and factory inspection will be done by GE/AGE at original manufacturer plant only and all other electric incoming and outgoing connections with PVC insulated multistranded flexible copper cable of suitable size and PVC flexible conduit medium quality as required and comprising of the following:- 1 Nos
78 53.01 Incoming Feeder:-\nIncomer MCCB 400 Amps, Three Pole, Terminal based release with adjustable O/L, Adj S/C Setting Class II Front Face, 36KA rupturing capacity, lcs=100%lcu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barriers - 1 No all as specified and as directed.
79 53.02 Metering Section - Digital Ammeter (0-400) Amps, Digital Voltmeter (0-500) Volts, RYB Indicating Lamps, 1 Set Control Fuses, CTs. 3 all as specified and as directed.
80 53.03 Insulated Busbar of Aluminium of 400A Capacity for 3 phase, fixed on Insulators, Busbar should be PVC Sleeved with red, yellow, blue colour, Busbar support should be of smc/dmc - 1 set all as specified and as directed.
81 53.04 Multi 14 Step 440V, 5A (144 X 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display all as specified and as directed.
82 53.05 Outgoing Feeder:-\nAccessories for 1 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 1 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 6A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start/ Stop Push Button all as specified and as directed.
83 53.06 Accessories for 2 KVAR Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 2 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 16A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button all as specified and as directed.
84 53.07 Accessories for 7 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 7 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 20A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
85 53.08 Accessories for 10 KVAR Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 10 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 25A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
86 53.09 Accessories for 15 KVAR Capacitor Bank - 3 Nos :- Capacitor Duty Contactor 15 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 32A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button all as specified and as directed.
87 53.1 Accessories for 25 KVAR Capacitor Bank - 5 Nos :- Capacitor Duty Contactor 25 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 63A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
88 53.11 Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on / off of fans depending upon the temperature of the pane; 230 VAC 1500 rpm, 160 cu.m/h flying leads all as specified and as directed.
89 53.12 Automatic Power Factor controller steps Relay Micro processor based for switching ON and OFF of capacitors to Display of voltage, current, Active power, apparent Power display of COS Ø, THD voltage, THD current, alarm indication for defective step, low power factor and excess temperature. The relay having volt free c/o contact, automatic detention and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement. Switching program : LIFO\ncombi Filter, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 Volt, 45 to 65 Hz, current measuring 10MA-5A suitable for CT x/1A and x/5A commissioning without additional setting and programming. Three decimal power reading. Phasing out of fault capacitor bank automatically all as specified and as directed.
90 53.13 All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 14 swg thick MS sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer all as specified and as directed.\nNote:- APFC panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (Dvepl, Tricolite, L&T, Legrand) will be accepted and factory inspection will be done by GE/AGE at original manufacturer plant only.
91 54 Supply, fixing, connecting and commissioning and testing of Company Make (automatic and manual operation) power factor improvement panel of capacity 150 KVAR for 315 KVA Transformer including interconnection with LT panel with appropriate size of electric cable for transformer Outdoor/Indoor) type panel factory made, weather proof, dust and vermin proof (IP 54/ IP 42) suitable for 1100 V / 440 V grade 3 phase 50 Hz AC supply floor mounted, fabricated out of 14 SWG MS sheet and having four Nos angle iron legs made out of 40 X 40 X 6mm, 60cm long angle iron below frame with front door and Side/ Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 Sqmm/ extension strips and connected with suitable size thimbles, lugs duly painted with L&T grey epoxy powder coating after suitable chemical treatment, legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles, all as specified and as directed by Engr-in-Charge. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (dvepl, tricolitre, L&T, Legrand) will be accepted and factory inspection will be done by GE/AGE at original manufacturer plant only and all other electric incoming and outgoing connections with PVC insulated multistranded flexible copper cable of suitable size and PVC flexible conduit medium quality as required and comprising of the following:- 1 Nos
92 54.01 Incoming Feeder:-\nIncomer MCCB 250 Amps, Three Pole, Terminal based release with adjustable O/L, Adj S/C Setting Class II Front Face, 36KA rupturing capacity, lcs=100%lcu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barriers - 1 No all as specified and as directed.
93 54.02 Metering Section - Digital Ammeter (0-300) Amps, Digital Voltmeter (0-500) Volts, RYB Indicating Lamps, 1 Set Control Fuses, CTs. 3 all as specified and as directed.
94 54.03 Insulated Busbar of Aluminium of 300A Capacity for 3 phase, fixed on Insulators, Busbar should be PVC Sleeved with red, yellow, blue colour, Busbar support should be of smc/dmc - 1 set all as specified and as directed.
95 54.04 Multi 12 Step 440V, 5A (144 X 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display all as specified and as directed.
96 54.05 Outgoing Feeder:-\nAccessories for 1 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 1 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 6A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start/ Stop Push Button all as specified and as directed.
97 54.06 Accessories for 2 KVAR Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 2 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 16A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button all as specified and as directed.
98 54.07 Accessories for 7 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 7 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 20A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
99 54.08 Accessories for 10 KVAR Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 10 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 25A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
100 54.09 Accessories for 15 KVAR Capacitor Bank - 3 Nos :- Capacitor Duty Contactor 15 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 32A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button all as specified and as directed.
101 54.1 Accessories for 25 KVAR Capacitor Bank - 3 Nos :- Capacitor Duty Contactor 25 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 63A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
102 54.11 Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on / off of fans depending upon the temperature of the pane; 230 VAC 1500 rpm, 160 cu.m/h flying leads all as specified and as directed.
103 54.12 Automatic Power Factor controller steps Relay Micro processor based for switching ON and OFF of capacitors to Display of voltage, current, Active power, apparent Power display of COS Ø, THD voltage, THD current, alarm indication for defective step, low power factor and excess temperature. The relay having volt free c/o contact, automatic detention and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement. Switching program : LIFO\ncombi Filter, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 Volt, 45 to 65 Hz, current measuring 10MA-5A suitable for CT x/1A and x/5A commissioning without additional setting and programming. Three decimal power reading. Phasing out of fault capacitor bank automatically all as specified and as directed.
104 54.13 All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 14 swg thick MS sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer all as specified and as directed.\nNote:- APFC panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (Dvepl, Tricolite, L&T, Legrand) will be accepted and factory inspection will be done by GE/AGE at original manufacturer plant only.
105 55 Supply, fixing, connecting and commissioning and testing of Company Make (automatic and manual operation) power factor improvement panel of capacity 100 KVAR for 200 KVA Transformer including interconnection with LT panel with appropriate size of electric cable for transformer Outdoor/Indoor) type panel factory made, weather proof, dust and vermin proof (IP 54/ IP 42) suitable for 1100 V / 440 V grade 3 phase 50 Hz AC supply floor mounted, fabricated out of 14 SWG MS sheet and having four Nos angle iron legs made out of 40 X 40 X 6mm, 60cm long angle iron below frame with front door and Side/ Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 Sqmm/ extension strips and connected with suitable size thimbles, lugs duly painted with L&T grey epoxy powder coating after suitable chemical treatment, legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles, all as specified and as directed by Engr-in-Charge. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (dvepl, tricolitre, L&T, Legrand) will be accepted and factory inspection will be done by GE/AGE at original manufacturer plant only and all other electric incoming and outgoing connections with PVC insulated multistranded flexible copper cable of suitable size and PVC flexible conduit medium quality as required and comprising of the following:- 1 Nos
106 55.01 Incoming Feeder:-\nIncomer MCCB 160 Amps, Three Pole, Terminal based release with adjustable O/L, Adj S/C Setting Class II Front Face, 36KA rupturing capacity, lcs=100%lcu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barriers - 1 No all as specified and as directed.
107 55.02 Metering Section - Digital Ammeter (0-200) Amps, Digital Voltmeter (0-500) Volts, RYB Indicating Lamps, 1 Set Control Fuses, CTs. 3 all as specified and as directed.
108 55.03 Insulated Busbar of Aluminium of 200A Capacity for 3 phase, fixed on Insulators, Busbar should be PVC Sleeved with red, yellow, blue colour, Busbar support should be of smc/dmc - 1 set all as specified and as directed.
109 55.04 Multi 8 Step 440V, 5A (144 X 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display all as specified and as directed.
110 55.05 Outgoing Feeder:-\nAccessories for 1 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 1 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 6A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start/ Stop Push Button all as specified and as directed.
111 55.06 Accessories for 2 KVAR Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 2 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 16A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button all as specified and as directed.
112 55.07 Accessories for 7 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 7 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 20A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
113 55.08 Accessories for 10 KVAR Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 10 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 25A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
114 55.09 Accessories for 15 KVAR Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 15 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 32A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button all as specified and as directed.
115 55.1 Accessories for 20 KVAR Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 20 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 50A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
116 55.11 Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on / off of fans depending upon the temperature of the pane; 230 VAC 1500 rpm, 160 cu.m/h flying leads all as specified and as directed.
117 55.12 Automatic Power Factor controller steps Relay Micro processor based for switching ON and OFF of capacitors to Display of voltage, current, Active power, apparent Power display of COS Ø, THD voltage, THD current, alarm indication for defective step, low power factor and excess temperature. The relay having volt free c/o contact, automatic detention and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement. Switching program : LIFO\ncombi Filter, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 Volt, 45 to 65 Hz, current measuring 10MA-5A suitable for CT x/1A and x/5A commissioning without additional setting and programming. Three decimal power reading. Phasing out of fault capacitor bank automatically all as specified and as directed.
118 55.13 All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 14 swg thick MS sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer all as specified and as directed.\nNote:- APFC panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (Dvepl, Tricolite, L&T, Legrand) will be accepted and factory inspection will be done by GE/AGE at original manufacturer plant only.
119 56 Supply, fixing, connecting and commissioning and testing of Company Make (automatic and manual operation) power factor improvement panel of capacity 75 KVAR for 150/160 KVA Transformer including interconnection with LT panel with appropriate size of electric cable for transformer Outdoor/Indoor) type panel factory made, weather proof, dust and vermin proof (IP 54/ IP 42) suitable for 1100 V / 440 V grade 3 phase 50 Hz AC supply floor mounted, fabricated out of 14 SWG MS sheet and having four Nos angle iron legs made out of 40 X 40 X 6mm, 60cm long angle iron below frame with front door and Side/ Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 Sqmm/ extension strips and connected with suitable size thimbles, lugs duly painted with L&T grey epoxy powder coating after suitable chemical treatment, legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles, all as specified and as directed by Engr-in-Charge. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (dvepl, tricolitre, L&T, Legrand) will be accepted and factory inspection will be done by GE/AGE at original manufacturer plant only and all other electric incoming and outgoing connections with PVC insulated multistranded flexible copper cable of suitable size and PVC flexible conduit medium quality as required and comprising of the following:- 1 Nos
120 56.01 Incoming Feeder:-\nIncomer MCCB 125 Amps, Three Pole, Terminal based release with adjustable O/L, Adj S/C Setting Class II Front Face, 36KA rupturing capacity, lcs=100%lcu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barriers - 1 No all as specified and as directed.
121 56.02 Metering Section - Digital Ammeter (0-150) Amps, Digital Voltmeter (0-500) Volts, RYB Indicating Lamps, 1 Set Control Fuses, CTs. 3 all as specified and as directed.
122 56.03 Insulated Busbar of Aluminium of 150A Capacity for 3 phase, fixed on Insulators, Busbar should be PVC Sleeved with red, yellow, blue colour, Busbar support should be of smc/dmc - 1 set all as specified and as directed.
123 56.04 Multi 12 Step 440V, 5A (144 X 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display all as specified and as directed.
124 56.05 Outgoing Feeder:-\nAccessories for 1 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 1 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 6A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start/ Stop Push Button all as specified and as directed.
125 56.06 Accessories for 2 KVAR Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 2 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 16A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button all as specified and as directed.
126 56.07 Accessories for 4 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 4 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 20A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
127 56.08 Accessories for 8 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 8 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 16A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
128 56.09 Accessories for 10 KVAR Capacitor Bank - 3 Nos :- Capacitor Duty Contactor 10 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 25A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button all as specified and as directed.
129 56.1 Accessories for 15 KVAR Capacitor Bank - 3 Nos :- Capacitor Duty Contactor 15 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 32A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
130 56.11 Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on / off of fans depending upon the temperature of the pane; 230 VAC 1500 rpm, 160 cu.m/h flying leads all as specified and as directed.
131 56.12 Automatic Power Factor controller steps Relay Micro processor based for switching ON and OFF of capacitors to Display of voltage, current, Active power, apparent Power display of COS Ø, THD voltage, THD current, alarm indication for defective step, low power factor and excess temperature. The relay having volt free c/o contact, automatic detention and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement. Switching program : LIFO\ncombi Filter, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 Volt, 45 to 65 Hz, current measuring 10MA-5A suitable for CT x/1A and x/5A commissioning without additional setting and programming. Three decimal power reading. Phasing out of fault capacitor bank automatically all as specified and as directed.
132 56.13 All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 14 swg thick MS sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer all as specified and as directed.\nNote:- APFC panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (Dvepl, Tricolite, L&T, Legrand) will be accepted and factory inspection will be done by GE/AGE at original manufacturer plant only.
133 57 Supply, fixing, connecting and commissioning and testing of Company Make (automatic and manual operation) power factor improvement panel of capacity 50 KVAR for 75/100 KVA Transformer including interconnection with LT panel with appropriate size of electric cable for transformer Outdoor/Indoor) type panel factory made, weather proof, dust and vermin proof (IP 54/ IP 42) suitable for 1100 V / 440 V grade 3 phase 50 Hz AC supply floor mounted, fabricated out of 14 SWG MS sheet and having four Nos angle iron legs made out of 40 X 40 X 6mm, 60cm long angle iron below frame with front door and Side/ Back opening having locking arrangement prewired with copper conductor PVC insulated flexible wire size 1.5 Sqmm/ extension strips and connected with suitable size thimbles, lugs duly painted with L&T grey epoxy powder coating after suitable chemical treatment, legs duly embedded in ground in PCC 1:3:6 type C-1 (using 20mm graded crushed stone aggregate) of suitable size including locking arrangement suitable for mounting, with required sheet metal enclosures, thimbles, all as specified and as directed by Engr-in-Charge. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (dvepl, tricolitre, L&T, Legrand) will be accepted and factory inspection will be done by GE/AGE at original manufacturer plant only and all other electric incoming and outgoing connections with PVC insulated multistranded flexible copper cable of suitable size and PVC flexible conduit medium quality as required and comprising of the following:- 1 Nos
134 57.01 Incoming Feeder:-\nIncomer MCCB 100 Amps, Three Pole, Terminal based release with adjustable O/L, Adj S/C Setting Class II Front Face, 36KA rupturing capacity, lcs=100%lcu, Isolation with Positive Break Indication with Double Break Contacts, Standard Extended Rotary Handle, Spreaders, Phase Barriers - 1 No all as specified and as directed.
135 57.02 Metering Section - Digital Ammeter (0-100) Amps, Digital Voltmeter (0-500) Volts, RYB Indicating Lamps, 1 Set Control Fuses, CTs. 3 all as specified and as directed.
136 57.03 Insulated Busbar of Aluminium of 125A Capacity for 3 phase, fixed on Insulators, Busbar should be PVC Sleeved with red, yellow, blue colour, Busbar support should be of smc/dmc - 1 set all as specified and as directed.
137 57.04 Multi 8 Step 440V, 5A (144 X 144) microprocessor based power factor controller provided in the command module for target power factor setting, automatic adjustment of dead bank ratio, digital power factor display all as specified and as directed.
138 57.05 Outgoing Feeder:-\nAccessories for 1 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 1 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 6A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start/ Stop Push Button all as specified and as directed.
139 57.06 Accessories for 2 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 2 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 10A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button all as specified and as directed.
140 57.07 Accessories for 4 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 4 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 16A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
141 57.08 Accessories for 8 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 8 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 20A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
142 57.09 Accessories for 10 KVAR Capacitor Bank - 2 Nos :- Capacitor Duty Contactor 10 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 25A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button all as specified and as directed.
143 57.1 Accessories for 15 KVAR Capacitor Bank - 1 Nos :- Capacitor Duty Contactor 15 KVAR with Damping Resistors which limits inrush current 440 Volt, 3 phase, 50 Hz, coil - 220 VAC, MCB TP 32A having breaking capacity 10 KA with std. duty capacitor on / off indicators, Start / Stop Push button and selector switch all as specified and as directed.
144 57.11 Ventilating fans of required size to dissipate the heat liberated by capacitor unites complete with automatic switching on / off of fans depending upon the temperature of the pane; 230 VAC 1500 rpm, 160 cu.m/h flying leads all as specified and as directed.
145 57.12 Automatic Power Factor controller steps Relay Micro processor based for switching ON and OFF of capacitors to Display of voltage, current, Active power, apparent Power display of COS Ø, THD voltage, THD current, alarm indication for defective step, low power factor and excess temperature. The relay having volt free c/o contact, automatic detention and uses of optimum capacitor capable of 4 Quadrant operation and any phase offset requirement. Switching program : LIFO\ncombi Filter, manual mode built in under and over voltage release with auto reset large voltage input band of 90V to 440 Volt, 45 to 65 Hz, current measuring 10MA-5A suitable for CT x/1A and x/5A commissioning without additional setting and programming. Three decimal power reading. Phasing out of fault capacitor bank automatically all as specified and as directed.
146 57.13 All accessories prewired with suitable size copper Wire with stand high temperature, housed in cubical panel made out of 14 swg thick MS sheet factory made duly powder coated front and rear door open able with locking arrangement complete with foundation as required or recommended by manufacturer all as specified and as directed.\nNote:- APFC panel shall be manufactured by original manufacturer only. The firms specified cannot authorize any other vendors to manufacture APFC Panels on their behalf failing which panels so manufactured will not be accepted. The panels manufactured by original manufacturer only (Dvepl, Tricolite, L&T, Legrand) will be accepted and factory inspection will be done by GE/AGE at original manufacturer plant only.
147 58 XLPE insulated heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross sectional area 500 Sqmm, 3.5 core laid in trenches/ on wall/ pole/ on air/ through pipe etc complete all as specified and as directed.\nNote:- Excavation and earth work, sand cushioning, covers and pipe etc shall be measured and paid separately. 10 RM
148 59 XLPE insulated heavy duty electric cable with aluminium conductor, 1100 Volts grade, cross sectional area 240 Sqmm, 3.5 core laid in trenches/ on wall/ pole/ on air/ through pipe etc complete all as specified and as directed.\nNote:- Excavation and earth work, sand cushioning, covers and pipe etc shall be measured and paid separately. 8 RM