Special Repairs To Ht/Lt Lines Of Electricity Distribution Network, Overhead Tank And Tube Well No 2 Including Other Connecting Items At Site Iii (Baknaur) At Air Force Station Ambala Under Ge Air Force Ambala (2Nd Call Boq), GE AF AMBALA-Haryana

Military Engineer Services-MES has published Special Repairs To Ht/Lt Lines Of Electricity Distribution Network, Overhead Tank And Tube Well No 2 Including Other Connecting Items At Site Iii (Baknaur) At Air Force Station Ambala Under Ge Air Force Ambala (2Nd Call Boq). Submission Date for this Tender is 04-05-2020. Overhead Line Tenders in GE AF AMBALA Haryana. Bidders can get complete Tender details and download the document.




Tender Notice

24008814
Corrigendum : Special Repairs To Ht/Lt Lines Of Electricity Distribution Network, Overhead Tank And Tube Well No 2 Including Other Connecting Items At Site Iii (Baknaur) At Air Force Station Ambala Under Ge Air Force Ambala (2Nd Call Boq)
Open Tender
Indian
Haryana
GE AF AMBALA
04-05-2020

Tender Details

Special Repairs To Ht / Lt Lines Of Electricity Distribution Network, Overhead Tank And Tube Well No 2 Including Other Connecting Items At Site Iii ( Baknaur ) At Air Force Station Ambala Under Ge Air Force Ambala ( 2Nd Call Boq )

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 23-Mar-2020 Date Extended Date 02-04-2020
2 01-Apr-2020 CA NO. CWE/AF AMB/AMB-35/2019-20 CRITICAL DATES Date 20-04-2020
3 22-Apr-2020 CA NO. CWE/AF AMB/AMB-35/2019-20 BIDDING DATES Date 04-05-2020

Key Value

Document Fees
INR 1000 /-
EMD
INR 133000.0 /-
Tender Value
INR 72 Lakhs /-

BOQ Items

NAME OF WORK : SPECIAL REPAIRS TO HT/LT LINES OF ELETRICITY DISTRIBUTION NETWORK, OVERHEAD TANK AND TUBE WELL NO 2 INCLUDING OTHER CONNECTING ITEMS AT SITE III (BAKNAUR) AT AIR FORCE STATION AMBALA UNDER GE AIR FORCE AMBALA (2nd call BOQ)
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Dismantling of wrought iron or mild steel work of any description not otherwise specifically provided for and rubbish off the premises to a distance not exceeding 500 mtr complete all as specified and as directed Item1 30 QTL
2 2 Dewatering of existing water tank, cleaning the inside surfaces of the tank by scraping down walls & bottom surface using steel wire brushes to remove all disputation/ fungus, other micro- organisms etc using light hammer & wire brushes, taking out removing sediment loose dirt/ mud sludge, vegetation and other foreign material from the tank, disposal of all the waste/ spoil to out of MD land at a place by local bodies,washing repeatedly the inside surfaces of tank with water and applying antibacterial sterilisation spray to walls, floors and ceilings complete all as specified and as directed. Item2 219 SQM
3 3 Taking up or down steel water tubing and connections for refixing or removal from site for 15 mm to 25 mm bore pipe complete all as specified and directed. Item3 1510 RM
4 4 Taking up or down steel water tubing and connections for refixing or removal from site for 40 to 50 mm bore pipe complete all as specified and directed. Item4 787 RM
5 5 Taking up or down steel water tubing and connections for refixing or removal from site for 80 mm bore pipe complete all as specified and directed. Item5 250 RM
6 6 Excavation in trenches not exc 1.5m wide and not exc 1.5m in depth for foundation etc or for walls, shafts, manholes not exc 10 Sqm on plan or for laying pipe or cables or for errection of poles etc and getting out, in soft/loose soil complete all as directed Item6 686 CUM
7 7 Excavation in trenches not exc 1.5m wide and exc 1.5m but not exc 3.0 mtr in depth for foundation etc or for walls, shafts, manholes not exc 10 Sqm on plan or for laying pipe or cables or for errection of poles etc and getting out, in soft/loose soil complete all as directed Item7 5 CUM
8 8 Returning filling in including spreading leveling watering and well ramming in layers not exc 25 cm thick each complete all as specified and as directed. Item8 392 CUM
9 9 Removal of surplus soil to a distance not exc 500 mtrs & depositing where directed at a level not exc 1.5 mtrs above the starting point complete all as specified and as directed. Item9 264 CUM
10 10 Material and labour for Sand cushioning to cable with a layer of sand 8 cm deep before laying the cable and 15 cms deep after the cable (punned down to 18 cms depth after laying and stretching of cable ) complete all as specified and as directed. Item10 193 CUM
11 11 Supply and fixing GI pipe light grade 50 mm bore for cable protection laid in trenches/floor complete all as specified and as directed. Item11 50 RM
12 12 Material and labour for Drilling holes below road/hard standing with bocky upto 150mm dia for laying/ insertion of pipe complete all as specified and as directed. Item12 5 RM
13 13 M&L for PCC 1:3:6, type C-1 using 20 mm graded mechanically crushed stone aggregates as in foundation to poles/struts/stays etc complete all as specified and as directed. Item13 20 CUM
14 14 M&L for PCC 1:3:6, type C-1 using 20 mm graded mechanically crushed stone aggregates as in padestal to poles/ coping with & including necessary form work and fair finishing to exposed surfaces using extra cement complete all as specified and as directed. Item14 10 CUM
15 15 M&L for RCC 1:2:4, type B-1 using 20 mm graded mechanically crushed stone aggregates of any description and at any position as in columns, pillars, piers in staging of overhead reservoir complete all as specified and as directed.\n Item15 2.5 CUM
16 16 M&L for RCC 1:2:4, type B-1 using 20 mm graded mechanically crushed stone aggregates of any description and at any position as in beams, cantilevers, bressummers, lintels over 1.5m span in wall/ roof /shaft/dome of overhead reservoir complete all as specified and as directed.\n Item16 2.5 CUM
17 17 Formwork to sides and soffits of floor or roof beams, beam haunchings,\nbressummers including supports,overhangs, etc. also splays between floors and beams, etc with rough finished surfaces of concrete in wall/ roof /shaft/dome of overhead reservoir complete all as specified and as directed.\n Item17 25 SQM
18 18 Formwork to sides of pillars,posts, struts, piers, columns and stanchions with rough finished surfaces of concrete in staging of overhead reservoir complete all as specified and as directed.\n Item18 15 SQM
19 19 Supply and laying sub class 'B' bricks old sizes over the underground HT/LT cable, laid dry & flat abutting each other with width equal to length of bricks for protection of cable after taking down cable protection as existing at site complete all as specified and as directed. Item19 20.7 Per 1000 Nos
20 20 Removing laid stone aggregate from switch yard /electric installation , washing to remove grass, dust etc, and depositing/stacking in one place at switch yard for reuse complete all as specified and as directed. Item20 12 CUM
21 21 Supplying and laying Lime aggregate bleaching powder for laying properly in switch yard/ electric installations/ two pole/ four pole structure complete all as specified and as directed. Item21 100 KG
22 22 Supplying and laying 20 mm graded mechnically crushed stone aggregate for proper laying in switch yard/ electric installations/ two pole/ four pole structure complete all as specified and as directed. Item22 20 CUM
23 23 Supplying and applying Sika Rustoff 100 of SIKA or equivalent of Fosroc/Dr Fixit rust remover for rusted metal, iron based with brush for wetting of rusted metal surface and allow to react it for 16-24 hours and after 24 hours, a white layer will appear which will protect further corrosion of metal / steel for about 5-7 days including surface preparation, errection of steel props and before applying protective/passivating coating, the surface should be wire brushed,thoroughly cleaned for dust with dry cloth (covering/dosage shall not be less than 1kg per 3- 5 sqm in 2 coats depending on the diameter of the rods or 0.120 to 0.150 kg per sqm per coat depending on extent of rusting and nature of substrate) including surface preparation, errection of steel props complete all as specified and as directed.\n Item23 330 SQM
24 24 Supplying and applying Sika Armatec 108 of SIKA or equivalent of Fosroc/Dr Fixit , anti corrossion coating to the steel reinforcement consisting of two component,cement based polymer modified two component coating for corrosion protection, 2 coats of 1mm thick each, fully compatible with the reinstatement methods adopted,errection of steel props as required for the application including surface preparation complete all as specified and as directed (coverage area of mixed system shall not be less than 0.8Kg per Sqm for two coats).\n\n Item24 330 SQM
25 25 Supplying and applying two component solvent, free epoxy bonding agent Sika Sikadur 32LP of SIKA or equivalent of Fosroc/Dr Fixit , for bonding old to new concrete applied over old concrete using brush after cleaning of surface of all dust or latiance, two part in pre weighed , exhibits compressive strength 50 N/mm2 at 7 days, flexural strength 35 N/mm2 at 7 days , shear strength 10 N/mm2 at 7 days, tensile strength 20 N/mm2 and bond strength of 10 N/mm2, concrete be placed within the open time as per manufacturer to ensure maximum bonding and application shall be as per the manufacturer's instructions (coverage area shall not be less than 0.3 – 0.5 kg/m2 depending on substrate conditions) including surface preparation, errection of steel props complete all as specified and as directed.\n\n Item25 330 SQM
26 26 Supplying and applying Sikatop 122 F of SIKA or equivalent of Fosroc/Dr Fixit , ready to use cementitious, polymer modified, 2-component repair mortar in 20 mm thickness having white liquid and grey powder ratio 1: 6 (5kg of liquid + 30kg of powder) as per manufacturer's instructions so as to achieve \nCompressive Strength at 28 days 40-45 N/mm2 ,flexural strength at 28 days 12-15 N/mm2 and Adhesion > 2.0 N/mm2 (concrete failure) at 28 days including surface preparation, errection of steel props complete all as specified and as directed.\n\n Item26 330 SQM
27 27 Material and labour for making V groove,10mm wide and 30mm deep or upto the extend of crack present at site over crack line using electricity operated angle grinder with diamond concrete saw blade including cleaning the surfaces by air blower including surface preparation, errection of steel props complete all as specified and as directed.\nNote: The groove shall be cut on the concrete surface along the crack over beam or column .\n.\n\n Item27 400 RM
28 28 Material and labour for sealing exposed 'V' groove, 10mm wide and 30mm deep with moisture insensitive epoxy putty Sikagard 694 F(I) or equivalent of Dr. Fixit/Fosroc, solvent-free, moisture tolerant, thixotropic, two part structural adhesive in ratio 1:1 to achieve strength as per manufacturer instructions including surface preparation, errection of steel props complete all as specified and as directed.\nNote: The groove shall be cut on the concrete surface along the crack over beam or column .\n\n Item28 400 RM
29 29 Supplying, grouting and injecting low viscosity injection resin Sikadur 52 of SIKA or equivalent of Dr. Fixit/ Fosroc, high strength epoxy resin injection through the nozzles under pressure using grout pump to fill all possible pores and gaps not exc 5mm, left within the concrete mass consisting drilling holes in structural members at the intervals, clean the holes by air blower prior to fixing nozzles, insert 12 mm dia 50~75 mm long injection packers in cleaned holes with structural grade epoxy adhesive, supplying and applying a shrinkage free low viscous epoxy resin based injection grout, cut the packers by cut of wheel after completion of grouting without damaging structural elements all as per manufecturer's instructions including surface preparation, errection of steel props complete all as specified and as directed.\nNote : The quoted rates includes the cost of drilling holes, NRV nozzle or any other minor spares. Item29 550 Kg
30 30 Supplying and applying flexible protective and waterproofing Slurry Sika Topseal 107 of SIKA or equivalent of Dr. Fixit/Fosroc,made out of two components ready to use polymer modified cementatious coating certified for portable water in three coats with glass fiber mesh of =>45 GSM, compressive strength 30 - 40 N/mm2 at 20 degree celcius after 28 days, flexural Strength 10 - 12 N/mm2 at 20 degree celcius after 28 days, bond strength shall not be less than 2 - 3 N/mm2 after 28 days (Coverage area in first coat shall be 1-1.5 kg/m2 on damp surface and in second coat 0.8 - 1 kg/m2 and the thickness of coating shall not be less than 1.5 mm) including surface preparation, errection of steel props complete all as specified and as directed.\n Item30 330 SQM
31 31 Material and labour for three coats of two part water based protective epoxy coating Sikagard 67 of SIKA or equivalent of Fosroc using roller brush application all as per manufacturer's instructions including surface preparation, errection of steel props complete all as specified and as directed.\n Item31 330 SQM
32 32 Supplying and applying crack bridging & anti-carbonation protective coating Sikagard-550 W Elastic of SIKA or equivalent of Fosroc/Dr Fixit , one part plasto-elastic coating based on UV-curing acrylic dispersion with excellent crack-bridging properties, protective coating system to achieve DFT (dry film thickness) of 150 microns in two coats after application of one coat of Silane Siloxane modified Primer on concrete surface including surface preparation by high pressure water jet or manually,errection of steel props as per manufacturer's instructions in RAL Shades complete all as specified and as directed with the following characteristics:-.\n(i) Primer: Sikagard-551 S with consumption: 0.2 kg/m2.\n(ii) Coating: Sikagard-550 W Elastic with consumption: 0.2 kg/m2/coat in 2 coats. (iii) System requirements: diffusion coefficient CO2 (µCO2) >= 2.5 x 105; diffusion coefficient H2O (µH2O)> = 2.5 x 103 (iv) Crack-Bridging capacity as per Class IT according to ZTV SIB 90-TL/TP OS. \nNote:- The Product shall be in compliance with Standards Test according to ZTV SIBOS-D II from the Polymer Institute dd 16.10.01 Nr. P2438/P2436.\n\n Item32 330 SQM
33 33 Notes for Ser No 23 to 32: (i) The work shall be carried out by the authorised applicator of manufacturer .\n(ii) The quoted rates includes the cost of chipping of unsound concrete ,erection and installation.\n(iii) The contractor shall submit the written performance guarantee of treatment carried out to over head reservoir for any cracks, leakage and seepage for 05 years from the date of physical completion of work. \n(iv) 5% amount of the total amount of treatment shall be retained as a guarantee and shall be released after 05 years. However contractor may deposit the FDR of same amount in favour of GE. If contractor fail to rectify the defect pointed out during this period in writing, the defect shall be got rectified at contractor' risk and cost and the payment shall be made from the amount kept reserved or by encashing the FDR deposited by the contractor as guarantee. The contractor's quoted rates for this item shall deemed to be inclusive of this aspect. Item33
34 34 Material and labour for preparation of newly/old plastered surfaces of concrete of over head reservoir and applying two coats of exterior acrylic emulsion paint over a coat of primer for height n exc 3 meters from ground level complete all as specified and directed. Item34 100 SQM
35 35 Material and labour for preparation of newly/old plastered surfaces of concrete of over head reservoir and applying two coats of exterior acrylic emulsion paint over a coat of primer for height exc 3 mtr but n exc 6 meters complete all as specified and directed. Item35 100 SQM
36 36 Material and labour for preparation of newly/old plastered surfaces of concrete of over head reservoir and applying two coats of exterior acrylic emulsion paint over a coat of primer for height exc 6 mtr but n exc 9 meters complete all as specified and directed. Item36 100 SQM
37 37 Material and labour for preparation of newly/old plastered surfaces of concrete of over head reservoir and applying two coats of exterior acrylic emulsion paint over a coat of primer for height exc 9 mtr but n exc 12 meters complete all as specified and directed. Item37 100 SQM
38 38 Material and labour for preparation of newly/old plastered surfaces of concrete of over head reservoir and applying two coats of exterior acrylic emulsion paint over a coat of primer for height exc 12 mtr but n exc 15 meters complete all as specified and directed. Item38 100 SQM
39 39 Material and labour for preparation of newly/old plastered surfaces of concrete of over head reservoir and applying two coats of exterior acrylic emulsion paint over a coat of primer for height exc 15 mtr but n exc 18 meters complete all as specified and directed. Item39 250 SQM
40 40 Material and labour for preparation of newly/old plastered surfaces of concrete of over head reservoir and applying two coats of exterior acrylic emulsion paint over a coat of primer for height exc 18 mtr but n exc 21 meters complete all as specified and directed. Item40 250 SQM
41 41 Supply and fixing mild steel framed work as in door or gate of angle or other sections with gusset plates, rails, braces etc, using ornamental design as approved complete drilled for fixing of steel sheeting or other covering, doors etc to be prepared for hanging or sliding with and including either hooks and purpose made hinges or steel hanging door fittings (exclusive of steel sheeting or other covering, running rails and guides) and hanging, fastening and fixing complete conforming to Fe-290 Gde E-165 (machine butt hinges and flat iron hold fasts to be measured separately) complete all as specified and as directed Item41 3000 KG
42 42 Supply only mild steel deformed bars or TMT bars Fe 550, 10 mm dia and over, cut to length, bend to shape required, including cranking, bending spirally for hooping for columns, hooking ends and binding with mild steel wire (annealed) not less than 0.9 mm dia complete all as directed Item42 1500 KG
43 43 Material and labour for two coats of synthetic enamel paint on new or previously primed steel and iron surfaces, of any description including preparation of surface over 10cm width or girth over a coat of red oxide primer complete all as specified and as directed. Item43 100 SQM
44 44 Cutting existing water mains in position upto 150mm bore CI/DI for taking branch connections for CI special as required complete all as specified and as directed. \n Item44 12 EACH JOB
45 45 Supply and fixing in replacement of unserviceable trolley with new trolley structural modified, heavy duty, of size 1.5x3 Mtr or as required at site, made out of angle iron ,wheel base structure with easy carry handle, angle stand with fence on trolly for carry transformer of capacity up to 160 KVA from one side/site to another side/site with vehicle of MES including 04 Nos tubeless tyres/ tyres with tube, wheel drum duly connected with axle including arrangements for toeing the trolly alongwith shocker and applying two coats of synthetic enamel paint over a coat of red oxide primer on entire metal work complete all as specified and as directed. \nNote : Drawings mentioning all parts of trolly such as size of trolly ,thickness of sheet, shall be submitted by the contractor and shall be approved by GE before fabrication. Item45 1000 Kg
46 46 Supply and fixing in replacement of single phase timer switch with nature switch -02 EC infra rays sensor with pre drawn switching off timer , MCB power contractor, glass wool panel of maximum load capacity of 3 KWs/phase, 230 volts, 50 Hz, degree of protection conforms to IP-66 complete all as specified and as directed.\nMake :- Model swadeep -02 EC nature switch or equivalent of Schneider/ ABB \n Item46 2 EACH JOB
47 47 Supply and fixing in replacement of unserviceable battery bank comprising of 2Vx12 Nos,100 AH maintenace free batteries, battery bank and electronic battery charger with total harmonic distortion (THD) less than 3% suitable for 24V battery bank with normal charging capacity of 20A , with boost capacity 40A with the following specifications:-\n(i) Input voltage range 180V-280V\n(ii) Voltage regulation should be less than 3% of rated output from no\nload to full load at rated input\n(iii) Having input/output voltage and current display including normal andboost value through digital electronic meter including THD & frequency. Item47 1 EACH JOB
48 48 Supply and fixing in replacement of unserviceable inverter with new sinewave inverter 2 KVA, 24 volt with stand/frame made out of MS angle/ channel of suitable size with and including two maintenace free ILTT18048 TALL TUBULAR 150 Ah battery with and including wiring at power house /sub station for given supply to building complete all as specified and as directed.\nMake of Invertor :Microtek/ luminous/ Su Kam\nMake of Battery : Model No ILTT18048 TALL TUBULAR of Luminous or Model No IT500 (150AH) TALL TUBULAR BATTERY of EXIDE Item48 1 EACH JOB
49 49 Material and labour for ductile iron pipes with socketed and spigot ends suitable for tyton joints centrifugally cast (spun) class 'K-9' confirming to IS: 8329 in any length laid in trenches of 150 mm bore with cement mortar internal lining and external zinc coating with a bitumen finishing layer, including necassary joints/spares after taking down/out old pipe as existing at site complete all as specified and as directed. \nNote:- Excavation and earth work shall be measured and paid separately. Earth work shall be paid once if the new pipe is being laid in same trench from which old pipe is being taking out. Item49 75 RM
50 50 Supply and fixing ductile iron fittings or specials for spigot & socketed and flanged pipe conforming to IS-9523, ISI marked,tee ,equal or unequal, dead flanges/plug, connecting pieces, tapers, collars reducers for pipe of size upto 200mm bore complete all as specified and as directed. \nNote:- Excavation and earth work and rubber gasket joints shall be measured and paid separately. Item50 80 KG
51 51 Supply and fixing cast iron fittings or specials for spigot & socketed and flanged pipe conforming to IS-1538, ISI marked, tee ,equal or unequal, dead flanges/plug, connecting pieces, tapers, collars, reducers for pipe of size up to 200mm bore complete all as specified and as directed.\nNote:- Excavation and earth work and run lead joints shall be measured and paid separately. Item51 230 KG
52 52 Supplying, fixing and jointing Cast iron sluice valve, ISI marked, Class PN-1 with flanged and drilled ends, suitable for 150mm nominal bore pipe/fittings with iron wheel high tensile steel spindle with & including joints and jointing materials such as bolt, nuts, washers and rubber gasket etc including taking down of old valve complete all as specified & as directed. Item52 4 EACH
53 53 Supplying, fixing and jointing Cast iron sluice valve, ISI marked, Class PN-1 with flanged and drilled ends, suitable for 200mm nominal bore pipe/fittings with iron wheel high tensile steel spindle with & including joints and jointing materials such as bolt, nuts, washers and rubber gasket etc including taking down of old valve complete all as specified & as directed. Item53 2 EACH
54 54 Supplying, fixing and jointing Cast iron sluice valve, ISI marked, Class PN-1 with flanged and drilled ends, suitable for 250mm nominal bore pipe/fittings with iron wheel high tensile steel spindle with & including joints and jointing materials such as bolt, nuts, washers and rubber gasket etc including taking down of old valve complete all as specified & as directed. Item54 2 EACH
55 55 Refixing old steel tubing and connections retrieved from srl No. 04 here-in-before including cleaning at new or old location with & including providing new GI fittings, bore of tubing 15mm bore complete all as specified and as directed. Item55 100 RM
56 56 Refixing old steel tubing and connections retrieved from srl No. 04 here-in-before including cleaning at new or old location with & including providing new GI fittings, bore of tubing 20 mm bore complete all as specified and as directed. Item56 150 RM
57 57 Refixing old steel tubing and connections retrieved from srl No. 04 here-in-before including cleaning at new or old location with & including providing new GI fittings, bore of tubing 25 mm bore complete all as specified and as directed. Item57 210 RM
58 58 Refixing old steel tubing and connections retrieved from srl No. 05 here-in-before including cleaning at new or old location with & including providing new GI fittings, bore of tubing 40 mm bore complete all as specified and as directed. Item58 80 RM
59 59 Refixing old steel tubing and connections retrieved from srl No. 05 here-in-before including cleaning at new or old location with & including providing new GI fittings, bore of tubing 50 mm bore complete all as specified and as directed. Item59 107 RM
60 60 Refixing old steel tubing and connections retrieved from srl No. 06 here-in-before including cleaning at new or old location with & including providing new GI fittings, bore of tubing 80 mm bore complete all as specified and as directed. Item60 50 RM
61 61 Supply and fixing galvanised mild steel water tubes 15 mm bore, medium grade, galvanised with all fittings and fixed complete to wall and ceiling or laid in trench/floor with and including testing after laid complete all as specified and as directed. Item61 250 RM
62 62 Supply and fixing galvanised mild steel water tubes 20 mm bore, medium grade, galvanised with all fittings and fixed complete to wall and ceiling or laid in trench/floor with and including testing after laid complete all as specified and as directed. Item62 400 RM
63 63 Supply and fixing galvanised mild steel water tubes 25 mm bore, medium grade, galvanised with all fittings and fixed complete to wall and ceiling or laid in trench/floor with and including testing after laid complete all as specified and as directed. Item63 400 RM
64 64 Supply and fixing galvanised mild steel water tubes 40 mm bore, medium grade, galvanised with all fittings and fixed complete to wall and ceiling or laid in trench/floor with and including testing after laid complete all as specified and as directed. Item64 300 RM
65 65 Supply and fixing galvanised mild steel water tubes 50 mm bore, medium grade, galvanised with all fittings and fixed complete to wall and ceiling or laid in trench/floor with and including testing after laid complete all as specified and as directed. Item65 300 RM
66 66 Supply and fixing galvanised mild steel water tubes 80 mm bore, medium grade, galvanised with all fittings and fixed complete to wall and ceiling or laid in trench/floor with and including testing after laid complete all as specified and as directed.\nNote for Ser No 55 to 66:- Excavation and earth work shall be measured and paid separately. Earth work shall be paid once if the new pipe/refixing old pipe is being laid in same trench from which old pipe is being taking out under Ser No 04 to 06. Item66 200 RM
67 67 Material and labour for Non return valve of cast iron for 150mm bore pipe Class-I (ISI marked) with brass flap and seat without by pass engagement, flanged both ends, joints and jointing material such as nuts,bolts,washers, rubber gasket etc after taking down valve as existing at site complete all as specified and as directed.\n Item67 3 EACH
68 68 Supply and fixing gun metal globe or gate valve 20 mm bore,ISI marked,class-2 with spindle and iron wheel head, screwed both ends for iron pipe with & including fittings and fixtures after taking down/out valve as existing at site complete all as specified and as directed. Item68 15 EACH
69 69 Supply and fixing gun metal globe or gate valve 25 mm bore,ISI marked,class-2 with spindle and iron wheel head, screwed both ends for iron pipe with & including fittings and fixtures after taking down/out valve as existing at site complete all as specified and as directed. Item69 15 EACH
70 70 Supply and fixing gun metal globe or gate valve 40 mm bore,ISI marked,class-2 with spindle and iron wheel head, screwed both ends for iron pipe with & including fittings and fixtures after taking down/out valve as existing at site complete all as specified and as directed. Item70 15 EACH
71 71 Supply and fixing gun metal globe or gate valve 50 mm bore,ISI marked,class-2 with spindle and iron wheel head, screwed both ends for iron pipe with & including fittings and fixtures after taking down/out valve as existing at site complete all as specified and as directed. Item71 14 EACH
72 72 Supply and fixing gun metal globe or gate valve 80 mm bore,ISI marked,class-2 with spindle and iron wheel head, screwed both ends for iron pipe with & including fittings and fixtures after taking down/out valve as existing at site complete all as specified and as directed. Item72 9 EACH
73 73 Material and labour in replacement water pressure gauge, range 0-100 PSI, dial type, 100mm nominal dia, with and including control valve adopter etc and testing on pipe line complete all as specified and as directed Item73 1 EACH JOB
74 74 Material and labour for rubber gasket joints suitable for 150mm bore DI pipes fittings with and including rubber gasket complete all as specified and as directed. Item74 20 EACH
75 75 Material and labour for run lead joint with jointing material suitable for 150mm bore CI pipes/fittings complete all as specified and as directed\nNote :- Each joint shall be provided with 3.4 Kg lead and 0.20 Kg spun yarn. Item75 3 EACH
76 76 Material and labour for valve pit of internal size 1.5 x 1.5 mtr using PCC 1:4:8 at the base of valve pit 100mm thick, brick work and cement mortar1 :4, 10mm thick rendering internally with & including closing arrangement with 3.15 mm thick MS sheet of size 1.5x1.5 mtr with angle iron frame made out of 50 x50x6 mm thick along the brick work ,locking arrangement and applying two coat of blue synthetic enamel paint over a coat of red oxide primar on entire steel and iron surfaces, internally and externally, applying two coats of white wash internal valve pit surfaces after demolition of pit as existing at site complete all as specified and as shown on drawing. \nNote:- The valve pit shall be constructed as per drg No CE AF/STD-25/94 Sheet No 1/2 & 2/2 dt 01 Feb 94. These drgs may be taken/seen from GE (AF) Ambala office. Item76 7 EACH JOB
77 77 Supplying and errecting Prestressed concrete pole, 9.0 metres long. 102mm x 172mm at top and 102mm x 279mm at bottom, class 10 conforming to IS-1678, provision of precast holes in PCC poles for fixing 'D' iron, clamps and hooks for continuous G.I. earth wire etc. to the required size with bolts, nuts, washers etc with & including refixing light fittings with old retrieved GI brackets by providing new MS clamps with nuts , bolts & washers duly painted the entire steel and iron surfaces , testing & making necessary connections to make the security light fitting functional after demolition of pole as existing at site complete all as specified and as directed.\n Item77 6 EACH JOB
78 78 Supplying and errecting Prestressed concrete pole, 11.0 metres long. 152mm x 152mm at top and 152mm x 260mm at bottom, class 9 conforming to IS-1678, provision of precast holes in PCC poles for fixing 'D' iron, clamps and hooks for continuous G.I. earth wire etc. to the required size with bolts, nuts, washers etc with & including refixing light fittings with old retrieved GI brackets by providing new MS clamps with nuts , bolts & washers duly painted the entire steel and iron surfaces , testing & making necessary connections to make the security light fitting functional after demolition of pole as existing at site complete all as specified and as directed.\nNote for srl No. 77 & 78 :- Excavation, earth work and PCC shall be measured and paid separately. Item78 2 EACH JOB
79 79 Supply and fixing ACSR conductor,steel reinforced,Weasel, Beaver, Ferret,Mink including stretching on insulators on poles with minimum sag including binding wore , jointing sleeves, aluminium tap & PG clamps of suiatble size after taking down/out conductor as existing at site complete all as specified and as directed. \nNotes :- The rates quoted includes (i) Jumper on cutout point,2 pole/4 pole structure shall be provided with PVC sleeves .\n(ii) Cutting of branches of trees coming across the OH line. Item79 1.8 QTL
80 80 Supply and laying stay assembly complete with accessories comprising of stay wire 7/2.50 mm dia, 1800 mm long ,MS galvanised stay plate 6 mm thick of size 300x300 mm stay bow including loop type insulator porcelain viterous 90x140 mm clearance hole 25 mm as shown in electrical plate No. 1 after taking down/out assembly as existing at site complete all as specified and as directed. \nNote :- Stay clamps, excavation and earth work and concrete shall be measured and paid separately. Item80 9 PER SET
81 81 Supply and fixing cross arms, bracings, supports,clamps and back plates fabricated from structural steel sections including nuts, bolts,washers,\nwelding, bending cold or hot,drilling holes for bolts, in any shape or size as indicated or directed with and including applying two coats of synthetic enamel paint over a coat of red oxide primer, after taking down/out cross arms as existing at site complete all as specified and as directed. Item81 2 QTL
82 82 Supply and fixing in replacement swing out expulsion fuse assembly single pole,drop out fuse, for 11000 Volts of cap. 100 Amps with MS channel, post insulators etc complete all as specified and as directed. Item82 8 EACH
83 83 Supply and fixing separators with screw type on LT OH line for 4 wire LT system complete all as specified and as directed. Item83 100 EACH
84 84 Supply and fixing separators with screw type on LT OH line for 2 wire LT system complete all as specified and as directed. Item84 50 EACH
85 85 Supply and fixing in replacement indoor type potential transformer ratio 11000/110 V rated voltage, 11 KV, VA : 100/1 3 phase, 50 Hz, HSV 12 KV IL 35/75 KV with and including making connection testing etc. complete all as specified and as directed.\nNote:- The PT shall match and synchronised with existing VCB panel.\n\n Item85 2 EACH
86 86 Supply and fixing in replacement selecter switch for VCB panel board showing of RYB cureent suitable for 110 volts AC / 24 volt DC / 30 volts DC complete all as specified and as directed. Item86 12 EACH
87 87 Supply and fixing in replacement set of indication lamp,LED type, Red or Yellow or Green colour suitable for 110 volts AC / 110 volt DC / 30 volts DC complete all as specified and as directed.\n Item87 25 SET OF THREE
88 88 Supply and fixing under voltage coil assembly suitable for HT OCB/ VCB operated on 110/24 volt system and testing complete all as specified and directed. Item88 2 EACH
89 89 Supply and fixing closing coil operated on 110 / 24 volt system suitable for working of relay of HT OCB / VCB complete all as specified and as directed. Item89 2 EACH
90 90 Supply and fixing in replacement of defective connecting and testing spring charging motor,universal motor for VCB rating upto 800 Amp indoor/outdoor type HT VCB operated on 230 volts AC/ DC,with charging time less than 15 sec of approved rating complete all as specified and as directed. Item90 3 EACH
91 91 Repair of spring charging motor ,universal motor for VCB rating upto 800 Amp indoor/outdoor type HT VCB,operated on 230 volts AC/ DC,with charging time less than 15 sec of approved rating complete all as specified and as directed. Item91 3 EACH
92 92 Supply and fixing shunt trip coil assembly suitable for HT,OCB/ VCB, operating on 24/110 volt system and testing after taking down/out assembly as existing at site complete all as specified and directed. Item92 2 EACH
93 93 Supply and fixing FRP looping box with hinged, cover weather proof with locking arrangements, with aluminium bus bar of capacity 100 Amp, single phase 230V , 50 Hz , mounted on PVC insulation, fixed to pole with and including MS clamp made out of FI 40x3mm size, nuts, bolts and washers including cable connection with and including one MCB SP 06-32 Amp after taking down/out box as existing at site complete all as specified and as directed. Item93 20 EACH
94 94 Supply and fixing Glow sign display board acrylic type for indication of 11KV, HT line feeder with HT over headline and under ground cable in different colour with LED lights ,control wiring and switch controls as required in showing of line running and closed all feeder including additional/essential accessories complete all as specified and as directed.. \nNote: Size/design/drawing of glow sign board shall be got approved from GE before fabrication. Item94 25 SQM
95 95 Supply and fixing MCB TPN 63 amps rated busbar 415 volts 10 kA including making good the disturbed surfaces as per existing specifications after taking down/out MCB as existing at site complete all as specified and as directed.\n Item95 2 EACH
96 96 Supply and fixing sheet metal enclosures for SPN 4 way,DB's with 200 Amps rated busbar 240 volts AC, IP 53 protection, double door, concealed in walls/on surface including making good the disturbed surfaces as per existing specifications after taking down/out enclosure as existing at site complete all as specified and as directed. Item96 4 EACH
97 97 Supply and fixing sheet metal enclosures for SPN 8 way,DB's with 200 Amps rated busbar 240 volts AC, IP 53 protection, double door, concealed in walls/on surfaces including making good the disturbed surfaces as per existing specifications after taking down/out enclosure as existing at site complete all as specified and as directed. Item97 4 EACH
98 98 Supply and fixing in replacement SPN sheet metal enclosure with socket plug top and MCBs with a two pin and earth plug and socket with one single pole MCB 20 Amp complete all as specified and as directed.. Item98 4 EACH
99 99 Supply and fixing in replacement MCB 6 to 32 amps,SP,10 kA,240 volts with 'C' curve complete all as specified and as directed.\n Item99 72 EACH
100 100 Supply and fixing in replacement MCB 32-40 amps,SPN,10 kA,240 volts with 'C' curve complete all as specified and as directed.\n Item100 12 EACH
101 101 Supply & fixing MCB SPN, AC, 240 volts of 63 Amps, 2 modules, C curve, 10 kA, confirms to IS/IEC 60898 -1:2002 including making connections, after taking down/out enclosure as existing at site complete all as specified and as directed. Item101 10 EACH
102 102 Supply and fixing MCCB, 4 pole, 100 Amp, 25 kA, 415 volts, 50 Hz, frame DPX3 160 with adjustable thermal & magnetic release after taking down/out enclosure as existing at site complete all as specified and as directed.. Item102 2 EACH
103 103 Supply and fixing MCCB, 4 pole, 250 Amp, 25 kA, 415 volts, 50 Hz, frame DPX3 160 with adjustable thermal & magnetic release after taking down/out enclosure as existing at site complete all as specified and as directed.. Item103 1 EACH
104 104 Supply and fixing MCCB, 4 pole, 400 Amp, 25 kA, 415 volts, 50 Hz, frame DPX3 160 with adjustable thermal & magnetic release after taking down/out enclosure as existing at site complete all as specified and as directed.. Item104 1 EACH
105 105 Supplying, lowering, installation, testing and commissioning submersible pump set with 3 phase submersible electric motor coupled with the pump having 20000 GPH discharge at 100 mtr head suitable for a bore of 200mm dia including rope for removing and servicing pump motor complete all as specified and as directed. \nNote :- The capacity of motor pump shall be suitable to give a required discharge at the required head. Item105 1 EACH SET
106 106 Supply and fixing star induction motor capacity 1 HP with fitting of existing system at STP site complete all as specified and as directed.\n Item106 3 EACH
107 107 Supply and fixing submersible motor of capacity 2 HP including rope for removing and servicing for carry out complete with 80 mm pipe after taking down/out motor as existing at site complete all as specified and as directed.\n Item107 1 EACH
108 108 Supply and fixing cable jointing kit for 11 KV earthed grade cable for straight through heat shrinkable type joints with jointing material and accessories for 3 core XLPE armoured aluminium conductor cable of size 95 Sq mm including cutting after taking down/out kit as existing at site complete all as specified and as directed.\n Item108 2 EACH
109 109 Supply and fixing cable jointing kit for 11 KV earthed grade cable for outdoor termination heat shrinkable type joints with jointing material and accessories for 3 core XLPE armoured aluminium conductor cable of size 95 Sq mm including cutting after taking down/out kit as existing at site complete all as specified and as directed.\n Item109 6 EACH
110 110 Supplying & laying sub main wiring with two single core PVC insulated cable with 4 sqmm nominal cross sectional area stranded copper conductor and one single core green PVC insulated 2.5 sqmm stranded copper conductor earth continuity cable drawn through with and including non metallic rigid PVC conduit medium grade 20mm bore including accessories concealed in wall including cutting chases in wall and making good disturbed surface to match of wall/ceiling including taking down/out cable as existing at site complete all as specified and as directed.\nNote :- Two runs of 4 sqmm cable alongwith One run of 2.5 sqmm cable as earth wire with conduit shall be measured as one length.\n Item110 150 RM
111 111 Supplying, laying, jointing, testing and commissioning under ground XLPE LT electric cable 1100 Volts grade, heavy duty, PVC bedded galvanized steel strip or wire armoured electric power cable with stranded aluminium conductor, of cross sectional area 10 Sqmm 4 core conforming to IS- 7098 (Part I) 1988 as in trenches over brick and sand cushioning or along the wall/pole through pipe etc served with an inner sheathing of PVC tape and overall PVC sheathed armoured with galvanized steel wire or tape including taking down/out cable as existing at site complete all as specified and as directed.\n Item111 850 RM
112 112 Supplying, laying, jointing, testing and commissioning under ground XLPE LT electric cable 1100 Volts grade, heavy duty, PVC insulated and sheathed armoued electric power cable with stranded aluminium conductor, of cross sectional area 50 Sqmm 3.5 core conforming to IS- 7098 (Part I) 1988 as in trenches over brick and sand cushioning or along the wall/pole through pipe etc served with an inner sheathing of PVC tape and overall PVC sheathed armoured with galvanized steel wire or tape including taking down/out cable as existing at site complete all as specified and as directed.\n Item112 610 RM
113 113 Supplying, laying, jointing, testing and commissioning under ground XLPE LT electric cable 1100 Volts grade, heavy duty, PVC insulated and sheathed armoued electric power cable with stranded aluminium conductor, of cross sectional area 70 Sqmm 3.5/4 core conforming to IS- 7098 (Part I) 1988 as in trenches over brick and sand cushioning or along the wall/pole through pipe etc served with an inner sheathing of PVC tape and overall PVC sheathed armoured with galvanized steel wire or tape including taking down/out cable as existing at site complete all as specified and as directed.\n Item113 420 RM
114 114 Supplying, laying, jointing, testing and commissioning under ground XLPE LT electric cable 1100 Volts grade, heavy duty, PVC insulated and sheathed armoued electric power cable with stranded aluminium conductor, of cross sectional area 120 Sqmm 3.5 core conforming to IS- 7098 (Part I) 1988 as in trenches over brick and sand cushioning or along the wall/pole through pipe etc served with an inner sheathing of PVC tape and overall PVC sheathed armoured with galvanized steel wire or tape including taking down/out cable as existing at site complete all as specified and as directed.\nNote for srl No.111 to 114:- Excavation and earth work, GI pipe, brick and sand cushioning shall be measured and paid separately.\n\n Item114 550 RM
115 115 Supplying, laying, jointing, testing and commissioning of HT XLPE cable, 11000 volts (earthed), insulated, screened, sound compacted aluminium conductor, screening with extruded semi conducting layers, insulation screening with copper tape covers laid up with PVC (ST-2), extruded inner sheathed GI strip armoured PVC (ST-2) out sheathed, ISI marked with IS-7098 Part II with amendment, size 95 Sqmm, 3 core , laid in trenches /pipes /ducts /along poles/ walls/ equipment etc including taking down of existing cable complete all as specified and directed. \nNOTES : (i) Cable shall be of manufacturing date not earlier than Jun 2019. All the cable shall be embossed with year of manufacturing, meterage at every metre, in addition to its own standard markings as per IS i.e. Size, voltage etc. \n(ii) Cable shall be tested in the presence of GE after laying in the trench before returning filling in the trench.\n(iii) Excavation & earth work, sand cushioning, protection pipes, end termination joints & protection covers shall be measured and paid separately.\n(iv) No straight through joint shall be permitted in less than single drum length. \n(v) The contractor shall produce original purchase vouchers duly machine numbered alongwith excise duty gate pass of factory for verification and record. \n\n Item115 150 RM
116 116 Supply and fixing bracket for fixing street light fitting on pole/ building made out of 40 mm bore GI pipe, medium grade, 1.5 Mtrs long having 45 degree angle after 0.60 Mtr length and be fixed with 40x5mm thick flat iron clamps nuts, bolts and washers etc duly painted with two coats of synthetic enamel paint over a coat of primer on steel surfaces including 3 core 4 sqmm PVC cable aluminium conductor from gear/control box to fiting through PVC conduit after taking down/out bracket as existing at site complete all as specified and as directed.\n Item116 5 EACH
117 117 Supplying and Fixing Industrial batten luminaire for retrofit LED tube pre coated CRCA body heavy duty batten 1X18 Watt Lamp type LED T8 for retrofit LED Tube with and including 3 core copper wire as per requirement for connection including taking down/out fitting as existing at site complete all as specified and as directed.\n .\n Item117 80 EACH
118 118 Supplying and Fixing LED tube fitting with surface mounted on wall, self ballasted LED Retro fit LED tube lamp 18 Watt with thermoplastic body 270 degree wide distribution available CCT 4000 K & 6500 K including taking down/out fitting as existing at site complete all as specified and as directed.\n Item118 50 EACH
119 119 Supplying and fixing LED Bollard fitting 6 Watt, powder coated PDC aluminium body with opel diffiuser suitable for landscape lighting Avl CCT 3000K .IP-54,Lumanries and driver shall be of same make,Power factor should be greater than 0.9,CRI lumenance should be 70,Lumanries efficacy 90 lumen per watt,THD < 20% including taking down/out fitting as existing at site complete all as specified and as directed.\n\n \n\n Item119 6 EACH
120 120 Supplying and Fixing LED street light fitting, 45 Watts, 230 V, 50 HZ, suitable for operation over voltage range of 140 V to 270 V, duly housed in pressure die cast aluminium housing, compresing of LED with individual optical lens, electronic driver with THD <10%, efficiency >85% and PF more than 0.90, confirming to IP65, rendering color index of 75 with cool day light output. including taking down/out cable as existing at site complete all as specified and as directed.\n\n Item120 5 EACH
121 121 Cleaning & servicing of HT 11 KV vaccum circuit breaker (VCB) , 400/630 Amp, 3 phase, indoor/outdoor type by the rep of OEM, checking of each moving parts, spring charging system,triping system,indication system,metering system,remote operation closing & trip coil assembly, proper oiling, greasing and proper adjustment of trip bars, closing bar complete with the following testing :-\n(i) ON/OFF testing in local and remote position. (ii) Spring charge system testing (iii) Tripping test in over and earth fault position by external current injecting kit on primary & secondary side.(iv) Meggar testing between phase to phase and phase to earth in ON / OFF position both (v) Test report for VCB will be prepared from OEM and submitted to the GE. Item121 12 EACH JOB
122 122 Supplying, installation, testing and commissioning outdoor type, canopy type, double door feeder pillar box, factory made IP-65 protection, to accommodate MCCBs, bus bar, energy meter, indicating lamp , made out of 3.15mm thick CRCA sheet compartment type, three phase, 4 wire, 415 volts, 50Hz, well ventilted, weather resistance, dust and vermin proof with hinged door with locking arrangements mounted on angle iron frame of size 40 x 40 x 6mm, four legs with and including copper busbar chamber with bus bar 4 Nos of rating capacity 400 amps mounted on PVC insulated suitable cable glands, nuts, bolts and washerswith and including providing PCC platform made of 1:2:4 type B-1 using 20mm graded mechanically crushed stone agregates for grouting of pillar box and applying two coats of powder coated approved paint of any tint and making necassary connections to make it functional after taking down feeder pillar box as existing at site comprising of the following :-\n(A) (a) Digital Voltmeter with selector switch range 0 to 500 volts - 01 No\n(b) Digital Ammeter with selector switch range 0 to 100 Amp-01 No Item122 3 EACH JOB
123 122.01 (B) IN COMING\n(a) MCCB, 4 Pole, 415 Volts, 36 kA, 160 Amp rating micro-processor\nrelease type -01 No (b) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No (Model no: EM 6400 cat no : 30002021 of Schneider or equivalent of makes as specified) (c) RYB LED indicating lamp panel mounting type (Set of three) - 01 Set.\n(C) OUT GOING (a) MCCB, 4 Pole, 415 Volts, 16 kA, 100 Amp rating micro-processor release type -02 No \n\n Item123
124 123 Supplying, installation, testing and commissioning outdoor type, canopy type, double door feeder pillar box, factory made IP-65 protection, to accommodate MCCBs, bus bar, energy meter, indicating lamp , made out of 3.15mm thick CRCA sheet compartment type, three phase, 4 wire, 415 volts, 50Hz, well ventilted, weather resistance, dust and vermin proof with hinged door with locking arrangements mounted on angle iron frame of size 40 x 40 x 6mm, four legs with and including copper busbar chamber with bus bar 4 Nos of rating capacity 400 amps mounted on PVC insulated suitable cable glands, nuts, bolts and washerswith and including providing PCC platform made of 1:2:4 type B-1 using 20mm graded mechanically crushed stone agregates for grouting of pillar box and applying two coats of powder coated approved paint of any tint and making necassary connections to make it functional after taking down feeder pillar box as existing at site comprising of the following :-\n(A) (a) Digital Voltmeter with selector switch range 0 to 500 volts - 01 No\n(b) Digital Ammeter with selector switch range 0 to 100 Amp-01 No Item124 4 EACH JOB
125 123.01 (B) INCOMING:\n(a) MCCB, 4 pole, 415 volts, 36 kA, 250 Amp rating micro processor release type -01\n(b) Panel mounted multi function energy meter of accuracy CL-1.0 rating - 01 No (Model No EM 6400 Cat No 30002021 of Schneider) (c) RYB LED indicating lamp panel mounting type ( Set of three) -01 No\n(C) OUTGOING:\n(a) MCCB, 4 pole, 415 volts, 16 kA, 100 Amp rating micro processor release type -03 Nos\n (b) MCCB 'C' curve TPN, 415 volts, 16 kA, 63 Amp rating micro processor release type -01 No\n Item125
126 124 Supplying, installing, testing & commissioning LT Panel board, factory made, CPRI approved,outdoor type, IP-54 withstand short circuit current level , 35 kA rms symmetrical with over load, short circuit and earth fault protection, having fire barrier, fabrication of panel should be as per relavent IS mounted on angle iron stand/frame made out of angle size 40 X 40 X 6 mm grouted in PCC 1:3:6 type C-1 using 20 mm graded mechanically crushed stone aggregates, suitable for 415 volt, 3 PH, 4 wire, 50 HZ, AC supply system having bus bars chamber with anodised copper bus bars duly insulated by insulation of RYB colour,1000 Amps rating mounted on porcelain insulators, double door, made out of 3.15 mm thick CRCA steel sheet, totally enclosed, dust, vermin and rust proof front operated, front and rear opening provided with spring loaded hinges and door stopper for easy working, with front handle locking arrangement (godrej type) with lock duly embeded in and including PCC 1:3:6 platform of suitable size duly painted internally and externally with two coats of synthetic enamel paint over a coat of red oxide primer of any tint, with and including internal wiring with multistranded copper conductor cable (FRLS) of minimum 2.5 sqmm size including lugs and cable gland to incoming and outgoing cable and spreader & seperator for MCCBs including re-routing of LT cables within 10 Mtrs of distances etc with comprising of the following after taking down/out panel as existing at site:-\n Item126 2 EACH JOB
127 124.01 (A) INCOMING:\n (a) MCCB, 4 pole, 415 volts, 36 kA, 630 Amp rating microprocessor\n release type -01\n (b) Panel mounted multi fuction energy meter of accuracy CL-1.0 rating\n - 01 No (Model No EM 6400 Cat No 30002021 of Schneider)(c) RYB LED indicating lamp panel mounting type ( Set of three) -01 No\n(B) OUTGOING:\n (a) MCCB, 4 pole, 415 volts, 16 kA, 250 Amp rating microprocessor\n release type -02 Nos\n (b) MCCB 'C' curve TPN, 415 volts, 16 kA, 63 Amp rating microprocessor release type -03 Nos\n\n\n\n Item127
128 125 Supplying, installation, testing and commissioning outdoor type, canopy type, double door feeder pillar box, factory made IP-65 protection, to accommodate MCCBs, bus bar, energy meter, indicating lamp , made out of 3.15mm thick CRCA sheet compartment type, three phase, 4 wire, 415 volts, 50Hz, well ventilted, weather resistance, dust and vermin proof with hinged door with locking arrangements mounted on angle iron frame of size 40 x 40 x 6mm, four legs with and including copper busbar chamber with bus bar 4 Nos of rating capacity 800 amps mounted on PVC insulated suitable cable glands, nuts, bolts and washerswith and including providing PCC platform made of 1:2:4 type B-1 using 20mm graded mechanically crushed stone agregates for grouting of pillar box and applying two coats of powder coated approved paint of any tint and making necassary connections to make it functional after taking down feeder pillar box as existing at site comprising of the following :-\n(a) Voltmeter flush mounted, 0-500 V, 96mm Square digital type -01 No.\n(b) Ammeter, flush mounted 0-100A, CTs operated, 96mm Square digital\n type-03 Nos.\n(c) Phase indicating lamp set (RYB) industrial LED type-01 Set.\n(d) On load change over switch, 200 Amp, four pole, 415 V, 50 Hz open\n execution type-01 No\n Item128 1 EACH JOB
129 125.01 (e) MCCB AC 415 Volt conforming to IEC-947 IS-13947-I, breaking capacity\n 25 KA at 415 volt, 4 pole (WSN) frame size/type ASS with adjustable\n thermal and fixed magnetic setting of current rating 100 Amp for\n incoming-01 No\n(f) MCCB AC 415 Volt conforming to IEC-947 IS-13947-I, breaking capacity\n 25 KA at 415 Volt, 3 Pole of current rating 63 Amp for submersible pump\n set-02 Nos\n(g) Star Delta Starter, 3 phase, 415 V, 50 Hz having contactors, over load\n relay, electronic timer, phase sequence corrector, on off push button\n complete copper wiring suitable for submersible pump motor upto 50 HP\n including proper fixing arrangement copper cable thimble etc -02 Nos\n(h) Danger notice plate/stricker of suitable size on front panel board - 01 No\n(j) Single phase preventer suitable for 415 volt - 02 Nos.\nNotes for Ser No 122 to 125:- (i) The design of panel shall be got approved from Accepting officer before fabricated.\n(ii) All MCCB should be (ICU=ICS=100 %) Item129
130 126 Material and labour for earthing with galvanized steel earth plate 60 cm X 60 cm X 6 mm thick buried vertically in ground to depth not less than 2.25 metres below ground level, with top edge of earth plate not less than 1.5 m below ground level, connected to GI plate with 32x6 mm GI earth strip upto 7.5 mtrs long by means of bolts, nuts, check nuts and washers of galvanized iron and connection to earthing test point & earth dolly including watering pipe GI 20 mm bore, light grade, including protection pipe GI medium grade 15mm bore for earthing lead, wire mesh, funnel,lugs, salt, charcoal dust, excavation and refilling pit with PCC 1:2:4 type B1, precast RCC cover slab 50 mm thick 1:2:4 type B-1 using XPM reinforcement weighing not less 4kg/sqm in lieu of CI cover with CI frame all as shown in electrical plate No 3 of SSR part-I (2009), including testing on completion including taking down of existing earthing as exists on site complete all as specified and as directed. \nNote :-- (i) Any variation in length of earth lead and protection pipe of earth lead shall be adjusted through DO.\n(ii) On testing if the earth resistance is not obtained, earthing will be generated at NO extra cost ,till the desired earth resistance is obtained. Item130 14 Each Set
131 127 Deduct total amount of Credit from BOQ Rs 325410.00