| Name of Work :- ELECTRIFICATION WORK IN CONSTRUCTION OF DEV NARAYAN RESIDENTIAL SCHOOL AT TEHLA RAJGARH DISTT ALWAR | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1 | Maintenance | |||
| 2 | 1.01 | Wiring of light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) of approved make in surface / recessed ISI marked medium duty PVC conduit & it's accessories, round tiles,Hot Dipped Galvanized Modular Box with earth terminal, 6 A Modular switch,Modular plate with grid plate, screws, making connections, testing etc. as required.Group-I | |||
| 3 | 1.02 | Short point (up to 3 mtr.) | 448 | P.Point | |
| 4 | 1.03 | Medium point (up to 6 mtr.) | 675 | P.Point | |
| 5 | 1.04 | Long point (up to 10 mtr..) | 1394 | P.Point | |
| 6 | 2 | Wiring of twin control light point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade (IS:694) of approved make in surface / recessed ISI marked medium duty PVC conduit & it's accessories, round tles, Hot Dipped Galvanized M.S Modular box of 20 SWG with earth terminal,6 A two way Modular switch, Modular plate with grid plate, screws, making connections, testing etc. as required.Group-I | |||
| 7 | 2.01 | Medium point (up to 6 mtr.) | 10 | P.Point | |
| 8 | 2.02 | Long point (up to 10 mtr..) | 10 | P.Point | |
| 9 | 3 | Wiring of 3 pin 5 amp. Light plug point with 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper conductor 1.1 kV grade and 1.5 sq. mm nominal size FR PVC insulated unsheathed flexible copper earth conductor 1.1 kV grade(IS:694) of approved make in surface / recessed ISI marked medium duty PVC conduit & it's accessories, Hot Dipped Galvanized M.S Modular box of 20 SWG with earth terminal, 6 A modular switch, 6 A modular socket, Modular plate with grid plate, screws, making connections, testing etc. as required.Group-I | |||
| 10 | 3.01 | On board | 1024 | P.Point | |
| 11 | 4 | Supplying and fixing of power plug point Modular accessories on hot dipped galvanized modular on surface or in recessed with suitable size of grid plate with cover plate including cost of modular 16 amp. Switch and socket outlet , making connection , testing , etc. as required. | |||
| 12 | 4.01 | Group-I | 447 | Each | |
| 13 | 5 | P & F following modular accessories made out of unbreakable and fire retardant poly carbonate with silver contacts including making connections testing etc. as required Group-I | |||
| 14 | 5.01 | RJ-11 telephone jack single two line | 75 | Each | |
| 15 | 5.02 | RJ-45 computer jack with shutter | 190 | Each | |
| 16 | 5.03 | 5 step fan regulator 2 Module | 424 | Each | |
| 17 | 5.04 | Blanking plate | 200 | Each | |
| 18 | 6 | P & F following size hot dip galvanized M.S. box of 20 SWG with earthing terminal in recess/ surface suitable for modular accessories as required.Group-I | |||
| 19 | 6.01 | 1-2 Module | 190 | Each | |
| 20 | 7 | P & F following size mounting grid plates with cover plates Group-I | |||
| 21 | 7.01 | 1/2 Module | 190 | Each | |
| 22 | 8 | S&F following sizes (dia.) of ISI marked medium duty PVC conduit along with accessories in surface / recessed using saddles, clamps, fastener as required including cutting the wall, covering conduit and making good the same as required.Group-I | |||
| 23 | 8.01 | 20 mm | 6400 | P.Mtr | |
| 24 | 8.02 | 25 mm | 6600 | P.Mtr | |
| 25 | 8.03 | 32 mm | 800 | P.Mtr | |
| 26 | 8.04 | 50 mm | 500 | P.Mtr | |
| 27 | 9 | Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1 kV grade and approved make in existing surface or recessed conduit/casing capping including making connections etc. as required.Group-I | |||
| 28 | 9.01 | 2 x 2.5 sq. mm. + 1x1.5sqmm | 7500 | P.Mtr | |
| 29 | 9.02 | 2 x 4.0 sq. mm. + 1 x 2.5 sq. mm. | 6400 | P.Mtr | |
| 30 | 9.03 | 2 x 6.0 sq. mm. + 1 x 2.5 sq. mm. | 1200 | P.Mtr | |
| 31 | 9.04 | 4 x 6.0 sq.mm | 800 | P.Mtr | |
| 32 | 9.05 | 1 x 2.5 sq.mm | 800 | P.Mtr | |
| 33 | 9.06 | 1 x 4.0 sq. mm. | 1200 | P.Mtr | |
| 34 | 9.07 | 4 x 10.0 sq.mm | 1200 | P.Mtr | |
| 35 | 10 | Supplying and drawing PVC/ Polythene insulated and PVC sheathed unarmoured/ armoured telephone cable with 0.5 mm dia. Tinned / annealed copper conductor taped &confirming to ITD specification S/WS -113C of approved make in existing surface or recessed conduit/casing capping.Group-I | |||
| 36 | 10.01 | Unarmoured Telephone cable in existing surface or recessed conduit/casing capping. | |||
| 37 | 10.02 | 2 pair | 2000 | P.Mtr | |
| 38 | 11 | P & F Krone module with base frame in the recess / surface made out of 16 SWG sheet steel box, front openable, having locking arrangements duly powder painted.,including dressing, ferruling and punching of telephone cable with krone tool etc. as required.Group-I | |||
| 39 | 11.01 | 10 Pairs | 5 | Each | |
| 40 | 11.02 | 20 Pairs | 4 | Each | |
| 41 | 12 | P & F IS:371 marked 6 amp surface type ceiling rose including making connection testing etc. as required. | |||
| 42 | 12.01 | Group-I | 900 | Each | |
| 43 | 13 | P & F ISI marked 6 amp bakelite batten/angle holder including making connection testing etc. as required.Group-I | |||
| 44 | 13.01 | Group-I | 490 | Each | |
| 45 | 14 | P & F of IP 20 LED tube light 20 watt with external batten made from CRCA sheet steel suitable to replace T-8/T-12 tube light, integral driver, 2000 luman + 5% tolerance system luman efficiacy of 100 Lm/ watt minimum expected life time of 25000 burning hours, CCT 5700 K, ANSI, CRI 80, driver efficiency >85%, Life expectancy of driver min 30000 hrs. PF 0.95 at full load/ 230 volt AC. | |||
| 46 | 14.01 | Group-I | 640 | Each | |
| 47 | 15 | P & F of 36 watt IP20 LED 2x2 fixture,recessed / surface type,having efficiency of not less than 100 luman/watt made out from CRCA housing and with high purity/transmisvity diffuser for uniform light distribution ,high efficiency driver electronics and in compliance to IEC standard ( integral with light fixture) life time of more than 50000 burning hours. CCT 6000°K. (minimum),CRI>80 driver maintaining PF>0.9 | |||
| 48 | 15.01 | Group-I | 31 | Each | |
| 49 | 16 | P & F of IP20 LED Recessed / Surface Mounted, Round / Sqaure Non-Dimmable Downlight with die-cast aluminum housing & Heat Sink for heat dissipation, high purity reflector with external BIS certified 2.5 KV surge protected driver having efficiency > 85% and in compliance to IEC standards. System Lumen efficacy of = 100 lm / watt and life time of minimum 35000 Burning Hours with 70% of intial Lumen maintaned, CCT 3000°K / 4000°K / 6000°K , maximum power consumption should not more than the specified rating and Fixture shall be of CE compliance. Group-I | |||
| 50 | 16.01 | Surface Mounting | |||
| 51 | 16.02 | LED Downlight 6 W | 173 | Each | |
| 52 | 16.03 | LED Downlight 12W | 234 | Each | |
| 53 | 16.04 | LED Downlight 18/20W | 234 | Each | |
| 54 | 17 | P & F 1200 mm sweep BEE Star rated double ball bearing capacitor start, aluminium body & blade ceiling fan complying to IS 374 : 1979,I/P 50 watt at max speed & 230volt,air delivery>210CMM,speed>330 RPM with down rod up to 30 cm with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. | |||
| 55 | 17.01 | Group-I | 421 | Each | |
| 56 | 18 | P & F 18 swg M.S. Recessed fan box, hexagonal/ round of size 130 mm dia, depth 75mm, 12 mm dia rod fan hook with 100 mm length extended on each side . | |||
| 57 | 18.01 | Group-I | 424 | Each | |
| 58 | 19 | P & F extra down rod of 15 mm dia . ERW (Electrical resistance welded ) of 1.6mm nominal thick medium duty steel pipe including cutting, threading, drilling, fixing quarter pin etc as reqd. | 290 | P.Mtr | |
| 59 | 20 | P & F of 4 star rated vertical storage water heater with outer casing made of M.S.sheet finished with anti-corrosive powder coating,inner tank made of pure electrolytic copper/stainless steel / SPHP, Tubular copper sheathed and Nickel plated heating element/ twin ceremic cartridge heating element, stem type thermostat and thermal cut out,Dual indicating lamps for power supply and thermostat,PUF insulation, Pressure relase valve,fusible plug etc. as required held in position with 4 no. rack bolts,duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top,including making inlet,outlet heavy gauge C.P./ Flexible alloy connection,testing etc. as required. Group-I | |||
| 60 | 20.01 | 15 Ltr. | 40 | Each | |
| 61 | 20.02 | 25 Ltr. | 2 | Each | |
| 62 | 21 | P & F ISI marked (IS:2082) Horizontal storage water heater with outer casing made of M.S.sheet finished with anti-corrosive powder coating,inner tank made of pure electrolytic copper/stainless steel , Tubular copper sheathed and Nickel plated heating element/ twin ceremic cartridge heating element, stem type thermostat and thermal cut out,Dual indicating lamps for power supply and thermostat,PUF insulation, Pressure relase valve,fusible plug etc. as required held in position with 4 no. rack bolts,duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top,including making inlet,outlet heavy gauge C.P. connection,testing etc. as required.Group-I | |||
| 63 | 21.01 | 35 Ltr. | 13 | Each | |
| 64 | 22 | P&F of Heavy duty capacitor start, Double ball bearing 900/1400 RPM single phase ISI marked Exhaust fan,IS:2312 marked in existing opening including making connections testing etc. as required.Group-I | |||
| 65 | 22.01 | 300 mm sweep(900/1400 RPM) | 32 | Each | |
| 66 | 23 | P&F of Double ball bearing, capacitor start single phase metallic blade fresh air fan, in existing opening including cost of hardware , flexible copper conductor ,making connections, testing etc. as required.Group-I | |||
| 67 | 23.01 | 300 mm sweep | 30 | Each | |
| 68 | 24 | P & F of Gravity Louver shutter of superior quality made out of PVC including cost of nuts, bolts, etc as reqd. | |||
| 69 | 24.01 | Up to 380 mm size | 62 | Each | |
| 70 | 25 | P/Laying P.V.C. / XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required of size.Group-I | |||
| 71 | 25.01 | 6 sq mm x 2.0 core armoured | 300 | P.Mtr | |
| 72 | 25.02 | 6 sq mm x 4.0 core armoured | 400 | P.Mtr | |
| 73 | 25.03 | 10 sq mm x 2.0 core armoured | 800 | P.Mtr | |
| 74 | 25.04 | 10 sq mm x 4.0 core armoured | 1200 | P.Mtr | |
| 75 | 25.05 | 16 sq mm x 4.0 core armoured | 150 | P.Mtr | |
| 76 | 25.06 | 35 sq mm x 3.5 core armoured | 600 | P.Mtr | |
| 77 | 25.07 | 50 Sqmm x3.5 core armoured | 400 | P.Mtr | |
| 78 | 25.08 | 120 Sqmm x3.5 core armoured | 200 | P.Mtr | |
| 79 | 25.09 | 150 Sqmm x3.5 core armoured | 400 | P.Mtr | |
| 80 | 25.1 | 300 Sqmm x3.5 core armoured | 300 | P.Mtr | |
| 81 | 26 | Supplying and making one end termination with heavy duty single compression brass gland SIBG type, heavy duty aluminium lugs duly crimped with crimping tool, PVC tape etc for following size of Armoured PVC insulated & PVC sheathed/ XLPE aluminium conductor cable of 1100 volt grade as required of size.Group-I | |||
| 82 | 26.01 | 2 x 6.0 sq.mm | 10 | Each | |
| 83 | 26.02 | 2 x 10.0 sq.mm | 8 | Each | |
| 84 | 26.03 | 4 x 6.0 sq.mm | 20 | Each | |
| 85 | 26.04 | 4 x 10.0 sq.mm | 40 | Each | |
| 86 | 26.05 | 4 x 16.0 sq.mm | 2 | Each | |
| 87 | 26.06 | 3.5 x 35.0 sq.mm | 10 | Each | |
| 88 | 26.07 | 3.5 x 50.0 sq.mm | 6 | Each | |
| 89 | 26.08 | 3.5 x 120.0 sq.mm | 8 | Each | |
| 90 | 26.09 | 3.5 x 150.0 sq.mm | 10 | Each | |
| 91 | 26.1 | 3.5 x 300.0 sq.mm | 4 | Each | |
| 92 | 27 | P/Laying P.V.C. / XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with Copper conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required of size.Group-I | |||
| 93 | 27.01 | 6.0 sqmmx 4.0 core armoured | 40 | P.Mtr | |
| 94 | 27.02 | 25.0 sqmmx 4.0 core armoured | 200 | P.Mtr | |
| 95 | 28 | P/Laying ISI marked P.V.C. insulated submersible cable confirming to IS:694 with flexible copper conductor including making connection etc. as required.Group-I | |||
| 96 | 28.01 | 2.5 Sq.mm 3 core flat / Round | 320 | P.Mtr | |
| 97 | 28.02 | 6.0 Sq.mm 3 core flat / Round | 500 | P.Mtr | |
| 98 | 29 | P&F 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C/ D tripping characteristic) ISI marked IS 8828(1996)]/ conforming to IEC 60898 in existing board/sheets including making connections, testing etc. as required.Group-I | |||
| 99 | 29.01 | Single pole MCB | |||
| 100 | 29.02 | 6 A to 32 A rating | 919 | Each | |
| 101 | 29.03 | Four pole MCB | |||
| 102 | 29.04 | 40 A 63 A rating | 65 | Each | |
| 103 | 29.05 | Triple pole MCB | |||
| 104 | 29.06 | 40 A to 63 A rating | 36 | Each | |
| 105 | 29.07 | Double pole MCB | |||
| 106 | 29.08 | 6 A to 32 A rating | 10 | Each | |
| 107 | 29.09 | 40 A 63 A rating | 10 | Each | |
| 108 | 30 | P&F of RCBO with overload, short-circuit and earth leakage protection ISI marked (IS12640)/ conforming to IEC 61009/1 complete in all respect including making connections, testing etc. as required.Group-I | |||
| 109 | 30.01 | Four pole 100/300 mA sensitivity | |||
| 110 | 30.02 | 40 A rating | 51 | Each | |
| 111 | 30.03 | Two pole 100/300mA sensitivity | |||
| 112 | 30.04 | 16 A rating | 13 | Each | |
| 113 | 31 | P&F Recessed/ Surface mounting heavy duty horizontal type sheet steel Distribution board phophatised/ powder painted complete with suitable rating insulated copper bus bar, shorting link , neutral link, earth link and din bar,masking sheet, conforming to IS13032 & IS8623 including making internal DB terminations with copper lugs , testing etc. as required.Group-I | |||
| 114 | 31.01 | Double door (Single phase) | |||
| 115 | 31.02 | 8 Way | 13 | Each | |
| 116 | 31.03 | 12 Way | 5 | Each | |
| 117 | 31.04 | Double door (Three phase) | |||
| 118 | 31.05 | 4 Way | 38 | Each | |
| 119 | 31.06 | 6 Way | 13 | Each | |
| 120 | 32 | P&F recessed/ surface mounting heavy duty Vertical type 16 SWG sheet steel Distribution board with provision of incomer suitable for MCCB and SP / TP MCB as outgoing , phophatised ,powder painted complete with insulated suitable rating copper bus bar , neutral link, earth link and din bar, masking sheet & conforming to IS13032 & IS8623 including making internal DB terminations with copper lugs , testing etc. as required.Group-I | |||
| 121 | 32.01 | Double door with Provision of Incomer MCCB 100 / 125 A Rating | |||
| 122 | 32.02 | 6 Way | 6 | Each | |
| 123 | 33 | Supply, installation, Testing and Commissioning of IP-65/ROHS/CE compliant Integrated Solar Street Light fixture having die cast Aluminium body encases with integrated monocrystaline solar PV panel with lithium(LiFePO4) ferro Phosphate battery and compliant to MNRE specifications / BIS approved .luminaire should be with secondary optic lenses for better distribution with delivered efficacy of > 100 Lumens per Watt ,with minimum 40000 hrs. rated Lamp life with LED's brand of Philips/Osram/Nichia/Cree/Seoul and driver efficiency should be >85% , CRI > 75, CCT 6000 to 6500°K, Microcontroller based high efficiency controller cum driver designed with automatic dimming function with PIR motion sensor ( full power lighting when a human move in the sensor range and only 30% lighting when a human move out ) , Dusk to Down operation, working temperature (-) 10°C to (+) 55°C, with adjustable clamp suitable for pole/wall mounting complete in all respect with protection like short circuit, overload, reverse polarity and battery protections. Light coverage must be 120 Degree or greater complete as required. As per MNRE Approved. | |||
| 124 | 33.01 | Compact Solar LED Street Light-30 Wp(mono)18V/12.8 V 12 AH/18 W | 36 | Each | |
| 125 | 34 | Supply, installation, Testing and Commissioning of mounting structure for solar street light comprising of tubular galvanised pole B class in three sections of Nominal Bore ( 80 mm -3.0 mtr + 65mm -1.50 mtr + 50 mm -1.5 mtr ) duly fabricated with welding or screwed with reducers having extended arm of 600 mm length of 32 mm G I medium class pipe ,having 200 mm X 200 mm Galvanised M S base plate of 8 mm thickness with 4 nos. holes of 16 mm for grounting, Installation of pole shall be done in either way directly to ground or with the help of 4 Nos. grouting bolts of 16 mm of 600 mm length with 2 Nos. rings including 30 cm x 30 cm muffing with 1:2:4 cement concrete up to a depth of 75 cm in ground and 25 cm above the ground duly plastered above ground level, installation will also cover welding work required at site such as clamp welding and grouting bolts rings welding whatever needed at site as per direction of Engineer Incharge. | |||
| 126 | 34.01 | Make:-G I Pipe-GST/TATA/JINDAL/PRAKASH/SURYA | 36 | Each | |
| 127 | 35 | Maintenance free Gel Earthing with Pipe in pipe / Pipe in strip technology filled with anti corrosive conductive compound ( CPRI Tested ) below the ground in 150 - 200 mm dia. earth pit & surrounding filled with required mineral filling compound ( MFC should have hygroscopic property to retain the moisture for long time to create low resistance zone ) and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size 300mm x 300mm complete testing of earth resistance as required. of following sizes.Group-I | |||
| 128 | 35.01 | With Pipe in Pipe Technology (Inner pipe dia. / Outer pipe dia. ) 80 - 100 micron GI Coating | |||
| 129 | 35.02 | GI pipe 2000 mm long, 50 / 25mm, Terminal 12 mm GI Strip | 30 | Set | |
| 130 | 35.03 | GI pipe 3000 mm long, 50 / 25mm, Terminal 14 mm GI Strip | 35 | Set | |
| 131 | 36 | S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required. | |||
| 132 | 36.01 | 8 SWG copper Wire | 1500 | P.Mtr | |
| 133 | 36.02 | 25mm x 5mm copper strip | 200 | P.Mtr | |
| 134 | 36.03 | 25mm x 6mm G.I. ( Hot Dipped ) Strip | 200 | P.Mtr | |
| 135 | 37 | P & F ISI marked flush/surface type buzzer including making connection testing etc. as required. | |||
| 136 | 37.01 | Group-I | 30 | Each | |
| 137 | 38 | P & F ISI marked ding dong/musical chime bell including making connection testing etc. as required. | |||
| 138 | 38.01 | Group-I | 10 | Each | |
| 139 | 39 | P&F metal clad industrial plug top & socket unit with pin and sleeve type contact on porcelain/ bakelite base in sheet steel enclosure (without MCB) including making connections, testing etc.as required Group-I | |||
| 140 | 39.01 | Single / Double Pole (Three pin) | |||
| 141 | 39.02 | 20 A | 106 | Each | |
| 142 | 40 | SITC of wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel made out of CRCA sheet , required hardware ,duly treated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shade The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel ,hinged door with locking arrangement for equipment/switchgear . Thickness of sheet shall not be less than 1.6 mm up to 600 mm length / width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors with / without detachable extension type structure. (only outer area on all sides shall be measured & panel to be fabricated from CPRI approved fabricator) | 80 | P.Sqm | |
| 143 | 41 | Supplying and fixing of Aluminium / Copper bus bar by means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. | |||
| 144 | 41.01 | Electrolytic grade Aluminium bus bar | 200 | P.Kg | |
| 145 | 42 | SF of 110/220 V, LED (22.5 mm dia ) Indicating lamp with integral circuit, terminal block, including connection etc. as required. | |||
| 146 | 42.01 | Red/yellow/Green colour Group-I | 48 | Each | |
| 147 | 43 | S & F of Electrical insulating rubber matts confirming to IS: 15652 / 2006 with one side anti skid abberation marks and pasting the mat with synthetic rubber adhesive as required. | |||
| 148 | 43.01 | 3.3 KV, 2 mm thick with proof voltage 10 KV / 3 min. and Break Down Voltage 30 KV | 22 | P.Sqm | |
| 149 | 44 | P & F in position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and enamel paint including cutting, welding, holes etc.of following sizes as required. | |||
| 150 | 44.01 | 50mm x 50mm x 6mm | 150 | P.Mtr | |
| 151 | 44.02 | 40mm x 40mm x 5mm | 30 | P.Mtr | |
| 152 | 45 | SF of (0-500) V range Volt meter on existing panel , making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.Group-I | |||
| 153 | 45.01 | Digital type | 12 | Each | |
| 154 | 46 | SF of CT operated direct reading type Ampere meter on existing panel , making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required.Group-I | |||
| 155 | 46.01 | Digital type | |||
| 156 | 46.02 | Below 500 A | 12 | Each | |
| 157 | 47 | SF of Current Transformer , with all necessary support in existing panel including connection etc. as required .Group-I | |||
| 158 | 47.01 | from 200 / 5 to 400/5 Ratio , 10 VA , class 1 accuracy | 9 | Each | |
| 159 | 47.02 | up to 150 / 5 Ratio , 5 VA , class 1 accuracy | 27 | Each | |
| 160 | 48 | SF of selector switch of 10 A for voltmeter (4 position ) including making connection etc. as required . | |||
| 161 | 48.01 | Group-I | 12 | Each | |
| 162 | 49 | SF of CT linked selector switch of 10 A for Ampere meter (4 position ) including making connection etc. as required . | |||
| 163 | 49.01 | Group-I | 12 | Each | |
| 164 | 50 | SITC of microprocessor based three phase sensing power factor correction relay having following sensing capacity secondary current , self analysing auto c/k setting according to targeted power factor setting, the relay shall have digit display unit for display of real power factor, targeted power factor, lag/lead capacitor switching status, alarm output for under current, over current, insufficient compensation, indication of switching on units, auto/manual status, and shall have over load protection, no volt release , having multi parameter like KW, KVA, KVAR, metering facility as required.Gr-I | |||
| 165 | 50.01 | 12 to 14 stage | |||
| 166 | 50.02 | sensitivity up to 50 milli Amp | 1 | Each | |
| 167 | 51 | P & F Cam operated rotary switches on existing panel with 2 way and off position Gr-I | |||
| 168 | 51.01 | Two pole | |||
| 169 | 51.02 | 16 A | 6 | Each | |
| 170 | 51.03 | 32 A | 6 | Each | |
| 171 | 52 | P & F of 440 Volt 3 pole capacitor (AC 6 B ) duty contactor with 3 no. early make and post break auxiliary contacts in series with quick discharge damping resistors/ reactors to limit the inrush current , conforming to IS:13947-4-1/IEC:947-4-1, Din rail mounting type including making connections, testing etc. as required. suitable for following capacity capacitor bank.Gr-I | |||
| 172 | 52.01 | up to 6 KVAR | 8 | Each | |
| 173 | 52.02 | 7 to 10 KVAR | 4 | Each | |
| 174 | 53 | SITC of self healing MPP/MP type shunt capacitor (banks) conforming to IS:13340-41 / IEC :831-1&2 in existing panel or parallel with load terminals , the capacitor shall be fitted with discharge resistors, pressure sensitive disconnector ( PSD ) and shall have dissipation factor less than 0.0025 at 50 Hz and total wattage loss less than 0.5 Watt per KVAR . including making connections with suitable capacity conductors/cables testing etc. as required.Gr-I | |||
| 175 | 53.01 | Heavy duty Three phase 440 V , 50 Hz capacitor (Bank) | 90 | kVAR | |
| 176 | 54 | SITC of quick make and quick break 4 POLE current limiting MCCB having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings and conforming to IS 60947-2 / IEC 60947-2 with front face and centralised adjustable, line load interchangeability, having positive isolation capability, provision for UVR , shunt trip ,earth fault trip, push ( test ) to trip , including making connections with lugs & spreaders, etc. as required.Group-I | |||
| 177 | 54.01 | With Thermal Magnetic release | |||
| 178 | 54.02 | up to 100 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu | 19 | Each | |
| 179 | 54.03 | up to 125 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu | 5 | Each | |
| 180 | 54.04 | 160 Amp, 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu | 23 | Each | |
| 181 | 54.05 | 200 Amp , 25/35kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu | 10 | Each | |
| 182 | 54.06 | 250 Amp , 35 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu | 4 | Each | |
| 183 | 54.07 | 400 Amp ,35 kA, adjustable O/L & adjustable S/C setting, Ics = 100 % Icu | 1 | Each | |
| 184 | 55 | Supply , Drawing and Testing of 4 pair, 24 AWG UTP Cat 6 Cable as per latest ammendments of TIA /EIA 568 B.2-1 Specifications in existing MS/PVC Conduits including making connections to Information outlets and Patch Panels with ferruling at both ends for identification with necessary tools for punching, stripping, crimping and testing required. | |||
| 185 | 55.01 | Group-I | 4800 | P.Mtr | |
| 186 | 56 | Supply , Installation, Testing and Comissioning of Rack mounted 19\", Cat 6 UTP,1.5-1.6 MM CRS chasis , powder coated Modular Patch Panels with collapsible shutters on jacks to support latest ammendments of TIA / EIA Cat 6 Specifications in Existing Communication Rack along with necessary connections of Cat 6 UTP Cables, With Rear Cable management trays and clamps.Group-I | |||
| 187 | 56.01 | 24 Ports | 8 | Each | |
| 188 | 56.02 | 12 Ports | 2 | Each | |
| 189 | 57 | Supply , Installation and Testing of 4 pair , 100 Ohm, 24 AWG , Cat 6 UTP, flexible , Double ended Patch Cords along with 2 No of RJ 45 connectors with strain relief transparent boots as per TIA /EIA 568 B.2-1 Specifications.Group-I | |||
| 190 | 57.01 | 1 Mtr/3 ft | 190 | Each | |
| 191 | 57.02 | 2 Mtr / 7 ft | 190 | Each | |
| 192 | 58 | Supply , Installation, Testing and Comissioning of Wall mounted Communication rack with glass doors, handles ,lock , Top and Bottom Cable entries, Supports for mounting rack on wall , Cable managers, one Fan, Equipment mounting hardware, power supply box for supplying power to switches, fans etc along with earth continuity kit, Mcb, indicator, moulded power supply cableGroup-I | |||
| 193 | 58.01 | 9 U(44 mm ) wall mounted | 2 | Each | |
| 194 | 58.02 | 12 U(44 mm ) wall mounted | 6 | Each | |
| 195 | 59 | SITC of ISI mark( IS:8472) self priming monoblock pump set of approved make, TEFC, permanent split capacitor type (PSC), fitted with thermal overload protection, mechanical seal, 1440/1500 RPM, single phase(180 to 240 V). Including cost of hardware etc on existing platform complete. Pump shall have following HP Rating, phase, Head, minimum Discharge respectively.Group-I | |||
| 196 | 59.01 | Self priming pumps | |||
| 197 | 59.02 | 1.0/ 1.1 HP, 1-Ø, (10-50)Mtr, (53-6.5)LPM | 2 | Each | |
| 198 | 60 | SITC of Managed Layer-2 Intelligent Ethernet Switch providing 24 x 10/100 Fast Ethernet ports and with min 2 SFP Giga Ports (provision for Fiber Giga connectivity) with related LAN Base Software | |||
| 199 | 60.01 | Group-I | 8 | Each | |
| 200 | 61 | SITC of 10/100 MBPS Unmanaged Switch | |||
| 201 | 61.01 | 8 Port | 1 | Each | |
| 202 | 62 | P / L of Double wall corrugated HDPE pipe confirming to IS : 14930 P - 1 & 2 with HDPE Coupler at 1 mtr. Depth below the ground for laying cable including making the trench and back filling , compaction of earth as required of Gemini or IS:14930 marked make. Outer Dia. / Inner dia. | |||
| 203 | 62.01 | 50/55 mm | 100 | P.Mtr | |
| 204 | 62.02 | 110 / 95 mm | 1600 | P.Mtr | |
| 205 | 62.03 | 180 / 152 mm | 1200 | P.Mtr | |
| 206 | 63 | SITC of Silent DG Set (As per latest CPCB emission norms) complete with 1500 RPM Diesel Engine of suitable BHP & AC Brush less SPDP Alternator mounted on a common base Frame & coupled through a flexible coupling or close coupled. Alternator shall be self regulated with standard Alternator Protection( Over voltage , over speed & under voltage, under speed warning & shutdown). Engine shall have residential silencer (isolated from main DG chamber), up to 3 M exhaust piping (with insulation & cladding), electronic / Mechanical governor, Manual & electric Start ,Batteries, Engine instruments panel, AVM and with Weatherproof, powder coated Accoustic enclosure for DG set for sound attenuation fabricated from 1.6 mmCRCA sheet steel (structure) with side wall fabricated from 1.6 mm CRCA sheet & filled with 100mm thick glass wool (96Kg/m3)/Foam. as per IS 8183 the doors of 100 mm thick and fabricated from 1.6mm CRCA sheet packed with accoustic material, All doors/ opening are sealed with neoprene/EPDN gaskets. | |||
| 207 | 63.01 | The enclosure has built in fuel tank, with protection and tripping of DG set against temperature of more than 50 degree centigrade. All controls for operation of DG set are from outside the enclosure with DG control panel having Microprocessor based Genset monitoring & control system, MCCB/ACB of suitable rating, Ammeter, Voltmeter, PF meter, frequency meter, KWH meter, Ind.lamps etc. mounted inside enclosure , visible and accessible from outside. The enclosure should be suitable for following capacity DG sets and alternator. Noise level shall be less than 75 dBA at a distance of 1 Mtrs. duly certified by authorised agency etc. complete in all respect of following capacity :Group-I | |||
| 208 | 63.02 | Radiator Cooled & Turbo Charged /AC | |||
| 209 | 63.03 | 125 KVA at 0.8 pf 415V 50Hz 3-? | 1 | Each | |
| 210 | 64 | SITC of Auto main failure (AMF) Panel fabricated from CRCA sheet steel 2 mmThick , Powder coated finish , Engine Start & Stop commands, control Relays , selector switches for Ammeter & Voltmeter, Ammeter & Voltmeter , Control & Power Contactors, Timers, Electronic Hooter ,Visual & Alarm indication for faults, UPS, operator interface panel complete in all respect suitable for following capacity DG sets:Group-I | |||
| 211 | 64.01 | PLC Based: | |||
| 212 | 64.02 | 80 to 160 KVA | 1 | Each | |
| 213 | 65 | P&F on load change over switch, front handle operated, four pole 415 V conforming to IS:13947 P-III including connections , testing etc. as required in the following rating:Group-I | |||
| 214 | 65.01 | Open execution type | |||
| 215 | 65.02 | 125 A | 2 | Each | |
| 216 | 65.03 | 200 A | 2 | Each | |
| 217 | 65.04 | 250 A | 3 | Each | |
| 218 | 66 | Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , Painting etc. as required. | 400 | P.Kg | |
| 219 | 67 | Rock /Glass wool with 22 g Aluminium cladding (Density- 96 kg/m3, Thickness-50 mm) | 15 | P.Mtr | |
| 220 | 68 | Supplying and fixing of chain link fencing with angle iron posts 50x50x6mm placed at every 3 Mtr. apart 30cm in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner and every tenth post to be strutted with (50 x 50 x 6cm) angle iron provided and fixed and fitted with posts including earth work in excavation etc. complete with chain link size. | |||
| 221 | 68.01 | 50mm x 50mm x 3.15mm | 200 | P.Sqm | |
| 222 | 69 | Providing, Fixing, Jointing, Testing & Commissioning of Medium duty MS B class pipes conforming to IS 3589 / 1239 part-I for DG Exhaust applications including cutting, welding etc & fittings like elbows,flanges, tapers, reducer, gaskets etc. fixing the pipe on the wall/ceiling with suitable clamps, hanger and nuts bolts . including the cost of thermal insulation with 50 mm thick layers of LRB rock wool (64 kg/m3 density) & 24 SWG aluminium sheet claddings etc complete as required.Group-I | |||
| 223 | 69.01 | 125 mm dia | 15 | P.Mtr | |
| 224 | 70 | SITC of MNRE approved & confirming to IS:12933 P-1,2,3&5 Evacuated tube Collector type solar hot water system with collector, insulated stainless steel storage tank with electrical back up , MS stand for Collector & Tank etc. as required. of following capacity.Gr-I Vide ACE amendment no 277 dated 15.07.14 | |||
| 225 | 70.01 | 250 litre/ day of Group-I | 1 | Each | |
| 226 | 70.02 | 400 litre/ day of Group-I | 16 | Each | |
| 227 | 71 | P & F PVC Storage Tank ISI Marked (IS : 12701 ) indicating the BIS license No of approved make with cover, 25mm dia 1M long G.I. over-flow pipe & 25 Cm. long wash out pipe with plug & socket, including making connection etc., complete of approved design:Group-I | |||
| 228 | 71.01 | 500 litres capacity. | 16 | Each | |
| 229 | 72 | Providing and Fixing chlorinated polyvinyl chloride (CPVC) Pipes Pipes having thermal stabillity for hot and cold water supply including all CPVC plain and brass threaded fittings including fixing the pipe with clamp at 1.0 m spacing.this includes jointings of pipe and fitting with one step of CPVC Solvant cement compelete as per direction of Engineer In charge ( External work) Gr-I | |||
| 230 | 72.01 | 20 mm nominal outer dia. pipe | 180 | P.Mtr | |
| 231 | 72.02 | 25 mm nominal outer dia. pipe | 200 | P.Mtr | |
| 232 | 73 | P & F Full-way Valve (IS:778 Mark) or wheel valve of approved make :Group-I | |||
| 233 | 73.01 | Gun metal 20mm nominal bore. | 30 | Each | |
| 234 | 73.02 | Gun metal 25mm nominal bore. | 22 | Each | |
| 235 | 74 | P & F Foot Valve of superior quality and appd make with fitting. | |||
| 236 | 74.01 | CI 80 mm | 16 | Each | |
| 237 | 75 | P/F Bib cock (IS:8931 mark) Superior Quality of Approved make Group-I | |||
| 238 | 75.01 | CP Brass Bib cock 15 mm nominal bore | 15 | Each | |
| 239 | 76 | P & Fixing M.S. sheet on existing angle iron frame by means of nuts and bolts and making required no. of holes for fixing accessories including two coat of red oxide paint and two coats of enamel paint etc. as required. | |||
| 240 | 76.01 | 6.4 mm thick | 2 | Sqm | |
| 241 | 77 | P & F of ac operated heavy duty 230 /440 Volt power contactor conforming to IS:13947-4-1/IEC:947-4-1 having provision of mechanical interlocking, auuxilary contacts, Din rail mounting type including making connections, testing etc. as required.Group-I | |||
| 242 | 77.01 | 4 pole Power contactors with following AC 1 Rating | |||
| 243 | 77.02 | 63 Amp | 2 | Each | |
| 244 | 78 | P&F of mechanical / digital time switch having following day / week programme and minimum 100 hours reserve and AC1 rating of 16-20 amperes including making connection, programming etc. as required .Group-I | |||
| 245 | 78.01 | One day & week reserve (mechanical type ) | 2 | Each | |
| 246 | 79 | P & F thermal over load relay with built in single phase protection and having at least 1NO & 1NC contacts, manual /auto reset facility including making connection testing etc. as required.Group-I | |||
| 247 | 79.01 | 15 to 20 Amp | 1 | Each | |
| 248 | 79.02 | 21 to 30 Amp | 1 | Each | |
| 249 | 80 | S & Laying following size' B ' class G.I. Pipe confirming to IS : 1239 P - 1 ( 1990 ) with accessories for laying earth conductor/strip / cable in ground/surface/recess as required | |||
| 250 | 80.01 | 80 mm dia. | 45 | Mtr | |
| 251 | 81 | Supply and erection of GI Octagonal / Conical pole of following length and dimension as per table E-10 with base plate on the cement concrete foundation of M-20 grade (1:1.5:3) with the help of anchor bolts of grade 6.8 (IS: 1367 P III ). The pole shall have a weatherproof flush door and locking arrangements. The complete work shall be supervised and certified by the manufacturers for satisfactory supply, erection, testing and commissioning. | |||
| 252 | 81.01 | Octagonal MS Poles made of S-355JO grade steel sheet , folded lengthwise to obtained Octagonal shape, having single longitudinal seam weld and hot dipped galvanised internally & externally in accordance with IS 2629. (See Table E - 10 for specs.) | |||
| 253 | 81.02 | 7 Mtr.Group-I | 35 | Each | |
| 254 | 82 | Supply, Erection and Fixing of hot dipped galvanised Overhang (48.3 X 3.25 mm) with cap (400 x 88.9 / 114.3 x 3.25 mm) over the existing poles | |||
| 255 | 82.01 | Single arm overhang | 25 | Mtr | |
| 256 | 82.02 | Double arm overhang | 10 | Mtr | |
| 257 | 83 | P&F of IP65 protected LED Street Light Luminaire on existing bracket. Fixture made of powder coated single piece pressure die cast aluminum with heat dissipation fins on housing with UV stabilized PC/Toughened Glass cover ( from 45W onwards ) and should be secondary lens on each LED . The System level Luminaire efficacy >=100 with High Power LEDs of CREE/NICHIA/OSRAM/PHILIPS/SEOUL make is to be used .The LED Driver shall be BIS certified and Input Voltage AC 110 to 270 V AC with Input Frequency 50Hz±3% Power Factor >0.95 Driver Efficiency >85% , THD(I) <10% Humidity 10% to 90% RH Working Temp -20C to 50C . Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% initial lumens maintained ,Rendering Index >75% .Surge protection shall be min = 5 KV internal and min 10 KV external. Manufactures Word Mark/Name Engraved/Embossed on die cast housing to allow traceability/authenticity till life of fixture. Fixtures shall be CE complianced.Group-I | |||
| 258 | 83.01 | LED Street Light fixture 80 Watt | 45 | Each | |
| 259 | 84 | Construction of Chamber in all type of soil with 300 mm thick masonry in CM 1:6m,10 cm thick C.C. 1:5:10 in foundation ,20 mm thick insider plaster in Cm 1:6 ,finished with floating neat cement ,50 mm thick M-15 grade C.C. Flooring ,earth work etc.compelete as per design including disposal of surplus earth with in a lead of 50 mtr. | |||
| 260 | 84.01 | Inside size 450mmx450mm depth up 0.50mtr cement cover with frame. | 20 | Each | |
| 261 | 85 | P & F of IP 55 protected light controlled switch based on infrared sensing and daylight with built in over load protection, timer to switch OFF at preselected time. Switch shall have 7 day power backup without hampering of preset time and over ride facility for maintenance purpose.Group-I | |||
| 262 | 85.01 | Suitable for 15 kw load (three phase) including contactor, MCB, cable glands, terminal block and locking arrangement | 1 | Each | |
| 263 | 86 | SITC of high mast lighting system (as per CP3-TR7/1996 of ILE, UK) consisting of totally hot dip galvanised by single dipped method high mast, lantern carriage suitable for up to 12 nos luminaries with welded arm, mast head frame assembly with full cover, aviation obstruction lights, double drum type self sustaining winch, integral power tool accesible from door with padlocking arrangement ( winch motor with control circuit) hot dipped galvanised heavy duty pipe lightening finial, suitable ropes (AISI 316, 7 / 19 costruction ), EPR insulated PCP sheathed trailing cable, outdoor type control panel for auto on / off, reverse / forward motor operation and CC foundation of M - 25 grade complete as required. The mast is constructed from mild steel plates (as per IS 5986 Gr. 510 ) cut and folded to form a polygonal section, telescopic jointed and welding as per BS 5135. The complete work shall be supervised and certified by the manufacturers for satisfactory supply, erection, testing and commissioning of high mast. ( See table E - 13 for specs.) group-I | |||
| 264 | 86.01 | 16.0 Mtr HM (in 2 section) | 1 | Each | |
| 265 | 87 | P & F of aviation obstruction light luminaire comprising of yellow painted die cast aluminium alloy housing, built in 75 VA step up transformer, heat resistant clear glass cover, neon spiral lamp / 2x100W GLS Lamp / LED Lamps complete in all respect Group-I | |||
| 266 | 87.01 | Aviation obstruction LED light luminaire | 2 | Each | |
| 267 | 88 | P & F of IP-65 protected high power LED flood light system with Pressure diecast aluminium housing , toughened glass diffuser with suitable lenses on LED to achieve various beam angles, 240 volt, 50Hz, of high power LED fixture supplied with pre wired cable of 1 mtr. Integrated driver shall be high efficiency having efficiency more than 85 % and in compliance to IEC standards/BIS certified. The System level Luminaire efficacy >=100 with High Power LEDs of CREE/NICHIA/OSRAM/PHILIPS/SEOUL make is to be used . LED Driver Input Voltage AC 110 to 270 V AC with Auto resetting Safety Cut-off. Input Frequency 50Hz±3% Power Factor >0.95 Driver Efficiency >85% ,Control Gear Integral Design, THD(I) <10% ,. Electrical Connector Must be provided Surge Protection Min >=5KV internal and 10KV external in 80W onwards,Humidity 10% to 90% RH Working Temp -20C to 50C . LED Luminaire Specifications: Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% lumen maintenance.Manufactures Word Mark/Name Engraved/Embossed on die cast housing to allow traceability/authenticity till life of fixture. Fixtures shall be CE complianced.Group-I | |||
| 268 | 88.01 | High Power LED Flood Light 150W | 16 | Each | |
| 269 | 88.02 | High Power LED Flood Light 100W | 18 | Each | |
| 270 | 88.03 | High Power LED Flood Light 80W | 12 | Each | |
| 271 | 89 | Supply and erection of hot dipped galvanised steel swaged tubular pole conforming to IS: 2713-1980 (part I to II) with galvanised base plate in position including excavation of the pit and filling the same with C.C. of M-20 grade (1:1.5:3) from base plate to 50cm above ground level, with the help of steel frame not less than 40 cm dia up to 114.3mm outer dia and 50 cm beyond 114.3mm outer dia around the pole. Duly finished with cement plaster, earthing terminals , cable entry, GI cable sleeve complete as required. The pole shall be galvanised using ISI mark seamless tube for structural purpose of following height & designation. ( See Table E - 09 for specs. ) | |||
| 272 | 89.01 | 7.5 Mtr. ( 410 SP - 5 ) | 6 | Each | |
| 273 | 90 | P&F of thermoplastic/ PVC cable junction boxes of following sizes including clamps for holding the box, cost of DIN rail for MCB mounting, connectors for cables terminals, threaded cable glands made of polyamide material etc. complete in all respect. | |||
| 274 | 90.01 | 300mm X 200mm X125mm | 6 | Each | |
| 275 | 91 | S & F of IP - 65 protected impact resistant polycarbonate / Polysterene enclosures of following sizes.Group-I | |||
| 276 | 91.01 | 180 x 180 x 91 mm | 4 | Each | |
| 277 | 92 | SITC of radial / mixed flow submersible motor pump sets ISI marked (IS:8034-1989) of approved make with required accessories including making connection suitable for T.W./ D.C.B./ Open well. The job includes lowering of riser pipe, G.I./ H.D.P.E. pipe with rope, cables, installation of complete fitting and accessories, jointing of electrical cables up to switch board. All labour for testing of submersible pumps set and supply of water to water mains, complete in all respect.Group-I | |||
| 278 | 92.01 | 100 mm diameter Submersible pump shall have following HP Rating, phase, Head, minimum Discharge respectively. | |||
| 279 | 92.02 | 5.0 HP, 1-Ø, (55-150)Mtr, (166-60)LPM | 1 | Each | |
| 280 | 93 | 150 mm diameter Submersible pump shall have following HP Rating, phase, Head, minimum Discharge respectively.Group-I | |||
| 281 | 93.01 | 5.0 HP, 3-Ø, (33-99)Mtr, (234-84)LPM | 1 | Each | |
| 282 | 94 | Supply & fixing of PVC threaded casing pipes for Tube well (IS 12818:1992) of 3mtr. Each for depth up to 1200 ft. Plain and strainer Casing CS for Depth upto 400ft. | |||
| 283 | 94.01 | more than 400 ft to 1200 ft. Depth | |||
| 284 | 94.02 | 40mm dia | 300 | P.Mtr | |
| 285 | 94.03 | 50 mm dia | 300 | P.Mtr | |
| 286 | 95 | Supply and fixing of Oil / Air break Starter panel made out of sheet steel powder coated enclosure comprising of over load protection relay, short circuit & single phasing protection, ON / OFF push buttons, ammeter, voltmeter, indicating lamps etc. complete in all respect suitable for following rating motors.Group-I | |||
| 287 | 95.01 | For single phase Submersible / Monoblock pump | |||
| 288 | 95.02 | 0.5 HP to 3.0 HP | 1 | Each | |
| 289 | 95.03 | For Three phase Submersible / Mono block pump | |||
| 290 | 95.04 | 3.0 HP to 10.0 HP ( Star / Delta ) | 1 | Each | |
| 291 | 96 | SITC of ISI marked Submersible mud pump set minimum 20 mm solid handling 2900 RPM , three phase, 415 V, 50 Hz, having following capacity.Group-I | |||
| 292 | 96.01 | 1 HP, ( 14 - 7.5 ) Mtr. (60 - 300) LPM | 1 | Each | |
| 293 | 97 | Providing and installation of chain pulley holded on CI round pulley duly supported on suitable MS channel/angle structure of 2x1500mm length and a 12mm MS bar. The structure be kept 1000mm above the ground level and remaining portion in cement concrete. | 1 | Each | |
| 294 | 98 | Providing of synthetic rope for submersible pump ISI marked (IS:5175) of following sizes. | |||
| 295 | 98.01 | 12mm (suitable up to 50 mm OD pipe) | 300 | Each | |
| 296 | 98.02 | 16mm (suitable above 50mm & up to 75mm OD pipe) | 300 | Each | |
| 297 | 99 | S & F of PVC trunking system for cable management including finishing accessories like corners, tee, adjustable angles, junction etc. as required . The trunking system shall have adaptable system for modular type RJ 45 data socket/ wiring accessories/ power sockets and shall be covered with peal off plastic cover.Group-I | |||
| 298 | 99.01 | 100/105mm x 50mm | 100 | P.Mtr | |
| 299 | 100 | Supply, Fabricating & installing following sizes of powder coated perforated M.S. cable trays including horizontal and vertical bends, reducers tees,cross members and other accessories as required and duly suspended from the ceiling with M.S. suspenders, fastners, supports etc. as required. | |||
| 300 | 100.01 | 150mm x 50mm x 1.6mm | 200 | P.Mtr | |
| 301 | 100.02 | 300mm x 50mm x 1.6mm | 50 | P.Mtr | |
| 302 | 101 | Supplying , installation , Testing and commissioning of grid connected SPV power plant in accordance with latest MNRE approved specifications/ BIS standards with free comprehensive maintenance for 5 years as per following details : | |||
| 303 | 101.01 | (a)SITC of MNRE specifications/Approved Polycrystalline standard IP-65 SPV modules of following capacity with minimum rating of each module 200 Wp with equal no. of module to be in each series circuit . PV module made out from min. 72 nos poly crystalline solar cells and frame made out from Anodized Allunimium alloy with hot dipped galvanized steel mounting structure , civil structure , lightning and over volage protection , earthing protection as per specification as required for making the solar system functional complete in all respect as required. | |||
| 304 | 101.02 | (b) SITC of IP-65 rating wall/floor mounted string inverter 3 phase , low maintenance , full sine wave , 50 Hz AC out put with grid tied features along with all protection , controlling arrangement and required accessories of following capacity .The inverter AC nominal power output rating must be equal or greater than the required KWp of the module at standard test condition(STC) and as per MNRE specification.The inverter unit shall be suitable for indoor and outdoor installations including all DC/Ac plugs and socket , D.B.'s and with all necessary electrical DC solar cables between modules and inverters and ac cables from inverter to AC panel ( Any length as required ) & lugs and terminations with solar metering and net Metering , conduits and cable trays and all other material and workmanship required to connect with main distribution panel as per the direction of engineer - in- charge . | |||
| 305 | 101.03 | 25.0 KW capacity | 1 | Job | |
| 306 | 102 | Supplying , installation , Testing and commissioning of off-grid SPV power plant in accordance with latest MNRE approved specifications/ BIS standards with free comprehensive maintenance for 5 years ( Excluding Batteries)as per following details : | |||
| 307 | 102.01 | (a)SITC of MNRE specifications/Approved Polycrystalline standard IP-65 SPV modules of following capacity with minimum rating of each module 200 Wp with equal no. of module to be in each series circuit . PV module made out from min. 72 nos poly crystalline solar cells and frame made out from Anodized Allunimium alloy with hot dipped galvanized steel mounting structure , civil structure , lightning and over volage protection , earthing protection as per specification as required for making the solar system functional complete in all respect as required. | |||
| 308 | 102.02 | (b) SITC of IP-65 rating wall/floor mounted MPPT inverter cum Charge controller 1/3 phase , low maintenance , full sine wave , 50 Hz AC out put along with all protection , controlling arrangement and required accessories of following capacity .The inverter AC nominal power output rating must be equal or greater than the required KWp of the module at standard test condition(STC) as per MNRE specification.The inverter unit shall be suitable for indoor and outdoor installations including all DC/Ac plugs and socket , D.B.'s and with all necessary electrical DC solar cables between modules and inverters/charge controller, battery bank of solar tubular batteries and ac cables from inverter to AC panel ( Any length as required ) & lugs and terminations with solar metering , conduits and cable trays and all other material and workmanship required to connect with main distribution panel as per the direction of engineer - in- charge . | |||
| 309 | 102.03 | 10.0 KW capacity , 3-Phase With 150 AH X 16 Nos Solar Tubular batteries | 1 | Job | |
| 310 | 103 | P&F flush/surface type enclosure for housing MCB/Isolator with Din rail including making connections with lugs, repairs etc. as required. Gr-1 | |||
| 311 | 103.01 | With sheet steel enclosure | |||
| 312 | 103.02 | Two way | 10 | Each |