| 1 | 1 | Maintenance and servicing of DG set 250 KVA, Make: Greaves Ltd including replacment of defective/wornout spares with new spares such as fule filter, lube oil fiter, gaskets, V belts,rubber hoses with clamps, nuts bolts and cleaning of alternator with vaccum cleaner and replacement of Engine oil, tappet setting ,servicing of radiator etc for the smooth operation DG set all as specified and directed. Note: 1) Minor spares such as fule filter and oil filter required for the service / Maintenance of the DG Sets deemed to be included in the above quoted rate. 2) Spares required for above will be measured and paid separately under relevent items of Sch. Location: Yerwada pump house. | | 1 | Each Job |
|---|
| 2 | 2 | All as item No.1 here in above but 110 KVA make kirloskar cummins installed at computer centre and indoor stadium at at BEG & Centre. | | 2 | Each Job |
|---|
| 3 | 3 | All as item No.1 here in above but 50 to 70 KVA make kirloskar installed at TB-II, ADG office, Rashmi and Sarvatra Vihar | | 4 | Each Job |
|---|
| 4 | 4 | All as item No.1 here in above but 30 to 40 KVA make kirloskar installed at shooting gallery in Telephone exchange, TB-II, Kekdi Line and Nirikshan Vihar. | | 5 | Each Job |
|---|
| 5 | 5 | All as item No.1 here in above but 15 to 20 KVA make kirloskar installed at TB-I Pump House,Depot Bn Pump House Baffle Range ,Depot Bn sub stn and Engine House Road. | | 5 | Each Job |
|---|
| 6 | 6 | Supply only Air filter inner and outer for 250 KVA DG set Greaves Ltd\n | | 1 | Set |
|---|
| 7 | 7 | Supply only Air filter inner and outer for 100 to110 KVA DG set Kirloskar cummins.\n | | 2 | Set |
|---|
| 8 | 8 | Supply only Air filter inner and outer for 50 to 70 KVA DG set Make:Kirloskar. | | 5 | Set |
|---|
| 9 | 9 | Supply only Air filter inner and outer for 30 and 40 KVA DG set, Make :Kirloskar | | 4 | Set |
|---|
| 10 | 10 | Supply only Air filter inner and outer for 15 to 20 KVA DG set Make: Kirloskar or equivalent | | 5 | Set |
|---|
| 11 | 11 | Supply only Fan belt for 250 KVA DG set,Make :JK/Dunlop | | 1 | Each |
|---|
| 12 | 12 | Supply only Fan belt for 110 to 110 KVA DG set, Make :JK/Dunlop | | 2 | Each |
|---|
| 13 | 13 | Supply only Fan belt for 50 to 70 KVA DG set,Make : JK/Dunlop | | 5 | Each |
|---|
| 14 | 14 | Supply only Fan belt for 30 to 40 KVA DG set,Make : JK/Dunlop | | 4 | Each |
|---|
| 15 | 15 | Supply only Fan belt for 15 to 20 KVA DG set, Make : JK/Dunlop | | 5 | Each |
|---|
| 16 | 16 | Supply only Fuel actuator with O Ring for 250 KVA DG set,Make : Greaves | | 1 | Each |
|---|
| 17 | 17 | Supply only Fuel actuator with O Ring for 100 to 110 KVA DG set,Make : Kirloskar | | 1 | Each |
|---|
| 18 | 18 | Supply only Fuel actuator with O Ring for 50 to 70 KVA DG set,Make : Kirloskar | | 1 | Each |
|---|
| 19 | 19 | Supply only ignition switch with Key for 110 KVA DG set,Make : Kirloskar | | 1 | Each |
|---|
| 20 | 20 | Supply only ignition switch with Key for 40 to70 KVA DG set,Make : Kirloskar | | 1 | Each |
|---|
| 21 | 21 | Supply only coolant temperature sensor with guage for 100 KVA to 250 KVA DG set. | | 2 | Each |
|---|
| 22 | 22 | Supply only coolant temperature sensor with guage for 15 KVA to 70 KVA DG set. | | 4 | Each |
|---|
| 23 | 23 | Supply only Lube oil pressure sensor ( Oil safety control ) for 100 to 250 KVA DG set. | | 1 | Each |
|---|
| 24 | 24 | Supply only Lube oil pressure sensor ( Oil safety control ) for 50 to 70 KVA DG set. | | 3 | Each |
|---|
| 25 | 25 | Supply only Lube oil pressure sensor ( Oil safety control ) for 30 to 40 KVA DG set. | | 2 | Each |
|---|
| 26 | 26 | Supply only Lube oil pressure sensor ( Oil safety control ) for 15 to 20 KVA DG set. | | 3 | Each |
|---|
| 27 | 27 | Supply only Hose set with clamps and screws suitable for DG set 250 KVA make: Greaves Ltd. | | 1 | Each |
|---|
| 28 | 28 | Supply only Hose set with clamps and screws suitable for DG set 100 KVA to 110 KVA make: Kirloskar. | | 2 | Each |
|---|
| 29 | 29 | Supply only Hose set with clamps and screws suitable for DG set 50 to 70 KVA make: Kirloskar. | | 3 | Each |
|---|
| 30 | 30 | Supply only Hose set with clamps and screws suitable for DG set 30 to 40 KVA make: Kirloskar. | | 3 | Each |
|---|
| 31 | 31 | Supply only Hose set with clamps and screws suitable for DG set 15 to 20 KVA make: Kirloskar. | | 4 | Each |
|---|
| 32 | 32 | Supply and replacement of self starter 12 volt dc including testing and commissioning as all specified and directed. Make :- Lucas/Mico | | 2 | Each |
|---|
| 33 | 33 | Supply and replacement of self starter 24 volt dc including testing and commissioning as all specified and directed. Make :- Lucas/Mico | | 1 | Each |
|---|
| 34 | 34 | Supply and Replacement of battery box made out to shape with angle iron 40x40x 5 mm, size 40cm x40cm x 20cm (Internal ) to arrange existing batteries all as directed. | | 3 | Each |
|---|
| 35 | 35 | Supply and Replacement of heavy duty battery terminals Brass with copper lead Pvc insulated multi stranded 25 sq mm duly soldered for +ve and -ve,05 mtr to 1.2 mtr long for 12/ 24 volt batteries. | | 8 | Each |
|---|
| 36 | 36 | Supply and fixing heating proof asbestos rope 12 mm dia on engine exhaust pipe including dismantling of burn out asbestors rope and arresting all leakages by welding / tightening the exhaust line including aluminium cladding and making complete fire proof, flame proof all as specified and directed. | | 40 | Kg |
|---|
| 37 | 37 | Preparation of old painted surface of the DG Set installed in acuastic enclosure including Base frame, radiator ,Fuel tank etc of the following capacities complete degreasing and spray painting the same with two coats of approved synthetic enamel paint including writing SM/MES nos,Desriptions,Location,Capacity etc on DG set size of letter shall be 5 CMx5CM of capacity 15 KVA to 70 KVA all as directed by Engr in Charge . | | 2 | Each Job |
|---|
| 38 | 38 | Preparation of old painted surface of the DG Set including Base frame, radiator, Fuel tank etc of the following capacities complete degreasing and spray painting the same with two coats of approved synthetic enamel paint including writing SM/MES nos,Description,Location,Capacity etc on DG set size of letter shall be 5 CMx5CM of capacity 100 KVA to 250 KVA all as directed by Engr in Charge . | | 2 | Each Job |
|---|
| 39 | 39 | Supply and replacement of Anti vibration pad as per existing size and make all as directed by Engr-in-charge. | | 6 | Each |
|---|
| 40 | 40 | Descaling,Cleaning and pressure testing of radiator assembly as required including Brazing etc complete to make leak proof of capacity 15 KVA to 70 KVA all as directed by the Engr-in-charge. | | 14 | Each |
|---|
| 41 | 41 | Descaling,Cleaning and pressure testing of radiator assembly as required including Brazing etc complete to make leak proof of capacity 100 KVA to 250 KVA all as directed by the Engr-in-charge. | | 3 | Each |
|---|
| 42 | 42 | Supply&Fix solonoid switch 12 Volts all as specified and and directed | | 4 | Each |
|---|
| 43 | 43 | Supply&Fix solonoid switch 24 Volts as specified and and directed | | 1 | Each |
|---|
| 44 | 44 | Supply&Fix in replacement/ Topping up of Coolent for radiators as approved by the Engr-In-Charge. Make Bosch | | 150 | Ltrs |
|---|
| 45 | 45 | Supply& Fix Oil pressure gauge for 100 KVA to 250 KVA all as specified and and directed | | 2 | Each |
|---|
| 46 | 46 | Supply & Fix Oil pressure gauge for 15 KVA to 70 KVA all as specified and and directed. | | 6 | Each |
|---|
| 47 | 47 | Supply and Replacement of hour run meter with hour counter | | 2 | Each |
|---|
| 48 | 48 | Supply and filling / Topping up engine oil multi grade as per manufacturers Recommendations in engine all as specified and directed. (Make ELF Oil/ Castrol /HP) including draining out old and burned engine oil. | | 250 | Ltrs |
|---|
| 49 | 49 | Overhauling of FIP (Fuel Injection Pump) at work shop including replacement of small spares required,complete setting and pressure testing at work shop to make the FIP and injectors functional for DG set 100 KVA to 250 KVA all as specified and directed. | | 2 | Each Job |
|---|
| 50 | 50 | Overhauling of FIP ( fuel injection pump ) at work shop including replacement of small spares required,complete setting and pressure testing at work shop to make the FIP and injectors functional for DG set 15 KVA to 70 KVA all as specified and directed. | | 4 | Each Job |
|---|
| 51 | 51 | Supply and Replacement of locks and keys for aquastic enclosures as per samples. | | 6 | Each |
|---|
| 52 | 52 | Supply and Replacement of control pannel complete suitable for 15 KVA to 70 KVA DG Set. | | 2 | Each |
|---|
| 53 | 53 | Supply and Replacement of AVR (automatic voltage regulator ) suitable for DG set 100 KVA to 250 KVA. | | 1 | Each |
|---|
| 54 | 54 | Supply and Replacement of AVR (automatic voltage regulator ) suitable for DG set 50 KVA to 70 KVA. | | 2 | Each |
|---|
| 55 | 55 | Supply and Replacement of AVR (automatic voltage regulator ) suitable for DG set 15 KVA to 40 KVA. | | 2 | Each |
|---|
| 56 | 56 | M& L for winding,varnishing & hardening of AC alternator stator including transportation from site to wksp and back. | | 250 | Per KVA |
|---|
| 57 | 57 | M& L fro winding, Varnishing and insulation of rotor including trasportation from site to wksp and back. | | 250 | Per KVA |
|---|
| 58 | 58 | S& F DG set controller, Model No ACG 543 all as specified and and directed. | | 1 | Each |
|---|
| 59 | 59 | S&F fuel hose for any capacity DG set 1 mtr to 5 mtr for fuel tank to DG set all as specified and and directed. | | 15 | RM |
|---|
| 60 | 60 | M & labour for calibration of fuel feed pump for any capacity of DG set | | 5 | Each |
|---|
| 61 | 61 | S&F 4 pole power contactor, 415Volts, 60 amps, , incl dismentling taking down unsv one, Make-L&T, Type-ML-3, Cat No-SS90721 or equivelent model of ABB/Schneider | | 4 | Each |
|---|
| 62 | 62 | S&F 4 pole power contactor, 415Volts, 100 to 160 amps, , incl dismentling taking down unsv one, Make-L&T, Type-ML-3, Cat No-SS90721 or equivelent model of ABB/Schneider | | 3 | Each |
|---|
| 63 | 63 | S& F SMPS 12 vots 10 amp for 15 to 70 KVA DG set | | 2 | Each |
|---|
| 64 | 64 | S& F SMPS 24 volts 10 amp 100 to 250 KVA DG set | | 2 | Each |
|---|
| 65 | 65 | S&F rectifier diode assembly 15 to 70 KVA DG set | | 4 | Each |
|---|
| 66 | 66 | S&F rectifier diode assembly 100 to 250 KVA DG set | | 3 | Each |
|---|
| 67 | 67 | Repair of turbocharging with repair Kit 100 to 250 KVA DG set | | 2 | Each |
|---|
| 68 | 68 | Repair of turbocharging with repair Kit 15 to 70 KVA DG set | | 2 | Each |
|---|
| 69 | 69 | Removing old unserviceable alternator from DG Set of 50 to 70 KVA of any make & supply & fixing new alternaotr 12 volt of the same type with all necessary modifications including all fittings such as pully , belt , cables hardwares etc including fixing testing & commissioning complete all as specified & directed | | 1 | Each Job |
|---|
| 70 | 70 | M & L for Earthing complete with galvanised steel pipe electrode, 40mm bore, medium grade, 3 mtr long buried directly and vertically in ground with top edge at ground level after making bore hole of size not less than 300 mm dia and 3.0 Mtr long using suitable mechanical drilling rig (for drilling near the specified location), connected with galvanised steel earthing strip of 25x4 mm all as shown in Plate No-2, connected to the earthing test point, concrete pit in PCC 1:3:6 type C-2with pit cover, funnel, wiremesh, 32 mm dia light grade GI tubing for protection of GI strip 25x4mm, charcoal and salt in alternate 150mm thick layers around GI earth pipe, including necessary returning filling in & removal all as specified or indicated in SSR Part-I, including testing to achieve earth resistance value as per IS specification on completion. | | 10 | Each Set |
|---|
| 71 | 71 | PCC (1:3:6) type C-2 using 40mm graded aggregate as in foundation for filling in, mass concrete for foundation of DG set, Panel board, stay, post top lantern, repairs to road cutting, drain, path etc complete all as specified and directed. | | 10 | Cum |
|---|
| 72 | 72 | PCC (1:2:4) type B-1 using 20mm graded aggregate a of reconstruction old damaged copings of DG set/ panel etc, including necessary form work complete all as specified and directed | | 10 | Cum |
|---|
| 73 | 73 | Materisl and labour for fixing or passing through pipe, laid in trenches or fixed to pole/wall or fixed to LT panel board, 1100 volts grade heavy duty cable with PVC insulated stranded aluminium conductor served with inner sheathing of PVC tape, armoured with galvanised steel wire or tape and overall PVC sheathed 16 sqmm 4 core with required aluminium cable lugs, | | 140 | RM |
|---|
| 74 | 74 | All as per item No. 10 here-in-before but 25sqmm 3,5 core complete all as specified | | 130 | RM |
|---|
| 75 | 75 | All as per item No. 10 here-in-before but 50sqmm 3.5 core complete all as specified | | 120 | RM |
|---|