| 1 | 1.01 | Dismantling the existing damaged wiring & electrical fixtures including mending good the damages. | BI01010001010000000000000515BI0100001113 | 1 | Job |
|---|
| 2 | 2.01 | Supplying and fixing 415V,63A TPN SFU with sheet steel enclosure on angle iron frame on wall with nuts bolts etc incl. S & F 3 nos. DIN type HRC fuse as per rating. [L&T] \n[Make: L&T/ABB/Legrand/Schneider] | BI01010001010000000000000515BI0100001118 | 1 | Each |
|---|
| 3 | 3.01 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 25mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. [From Pannel To HTPN DB] \n 4 x 80/0.4 (10 sqmm) + 2 x 84/0.3 (6 sqmm) ECC.\n | BI01010001010000000000000515BI0100001119 | 60 | RM |
|---|
| 4 | 4.01 | Supplying and fixing double door Horizontal TPN MCB Distribution board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. \n6 Way with 1 No. FP 63A Isolator; 18 Nos. 16A SP MCB [Make: L&T/Legrand/Schneider] | BI01010001010000000000000515BI0100001121 | 1 | Set |
|---|
| 5 | 5.01 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 25mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required. [ HTPN DB To SPN DB] 2x84/0.3 (6 sqmm) + 1x56/0.3 (4 sqmm) as ECC. \n | BI01010001010000000000000515BI0100001123 | 20 | RM |
|---|
| 6 | 6.01 | Supplying and fixing double-door SPN MCB Distribution Board with IP-42/43 protection, concealed in wall after cutting the wall & mending good the damages to original finish incl. Inter connection with suitable size of copper wire and neutral link & provision for earthing attachment. \n 2+ 10 way with 1 No. DP Isolator (40 A) & 10 Nos. MCB(6-32A) [Make: L&T/Legrand/Schneider]\n | BI01010001010000000000000515BI0100001128 | 2 | Set |
|---|
| 7 | 7.01 | Distribution wiring in 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1x22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire for ECC, to light/fan/call bell points with Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall complete with 2 no. suitable size “Ph & N” copper bar incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. 175mmx100mmx65mm inspection box, making earthing attachment, painting the MS box and mending good the damages to original finish.\nAverage run 8 mtr | BI01010001010000000000000515BI0100001132 | 42 | Point |
|---|
| 8 | 8.01 | Distribution wiring in 1.1 KV grade 2 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make), with 1.1 KV grade 1 x 22/0.3 (1.5 sqmm) single core stranded 'FR' PVC insulated & unsheathed copper wire as ECC, to 5A 3 pin flush type plug socket & Piano Key type switch fixed on MS CRC sheet metal (16 SWG) switch board cum JB on wall incl. bakelite/Perspex (wall matching color) top cover 3 mm thick and incl. painting the MS box and mending good the damages to original finish.\nOn Board | BI01010001010000000000000515BI0100001135 | 6 | Point |
|---|
| 9 | 9.01 | Supply of indoor type mounting rail for single LED tube light [PHILLIPS-TMC 501 P IXT-LED P3241] complete with all accessories including supply of 1No. 4’, 18W LED Tube [PHILLIPS-Master LED tube 1200mm 18W865 T8 I]. Or equivelent make. | BI01010001010000000000000515BI0100001160 | 25 | Set |
|---|
| 10 | 10.01 | Fixing only single /twin fluorescent light fitting complete with all accessories directly on wall/ceiling/HW round block and suitable size of MS fastener. | BI01010001010000000000000515BI0100001162 | 25 | Each |
|---|
| 11 | 11.01 | Supplying & Fixing 240V, 9Watt B22 LED Lamps in existing holders. [Philips] | BI01010001010000000000000515BI0100001164 | 16 | Each |
|---|
| 12 | 12.01 | Supplying & Fixing 240 V AC Buzzer (Anchor) on HW board incl. S&F HW board. | BI01010001010000000000000515BI0100001167 | 1 | Each |
|---|
| 13 | 13.01 | Supply only of 230V, 50Hz, 32W AC Exhaust Fan of sweep 300mm. [Make: Havells Metallic Range Ventil Air – DB or as pre the choice of EIC] | BI01010001010000000000000515BI0100001169 | 2 | Each |
|---|
| 14 | 14.01 | Fixing only exhaust fan of 300mm diameter after making hole in wall and making good damages and smooth cement finish etc. as practicable as possible and providing necy. length of PVC insulated wire and making connection including S&F GI louver shutter on wall with necy. bolts & nuts (6 mmdia x 62 mm long). | BI01010001010000000000000515BI0100001170 | 2 | Each |
|---|
| 15 | 15.01 | Distribution wiring in 1.1 KV single core stranded 'FR' PVC insulated & unsheathed copper wire (Brand approved by EIC) in 20mm size PVC rigid conduit 'FR' (Precision make) incl. necy. fittings as required.\n2x36/0.3(2.5sqmm)+1x22/0.3(1.5sqmm) | BI01010001010000000000000515BI0100001171 | 340 | RM |
|---|
| 16 | 16.01 | Supply & Fixing 240 V, 20A, plug socket with separate 20 A Piano key type switch (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 150x100x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. | BI01010001010000000000000515BI0100001172 | 12 | Each |
|---|
| 17 | 17.01 | Supply & Fixing 240 V, 4 nos. 6A, plug socket with separate 4 nos. 6 A Piano key type switch, indicator & 16A switch type SP MCB (Brand approved by EIC) on sheet metal switch board embedded in wall incl. S & F 240x200x65mm MS (16SWG) switch board and bakelite/perspex top cover of 3mm thick by Brass screws after making housing for switch by cutting bakelite/perspex cover and making necessary connections as required. | BI01010001010000000000000515BI0100001173 | 12 | Each |
|---|
| 18 | 18.01 | Excavation of soil for installation of Earth Electrode and filling & ramming.\nFor Morrum Soil. \n\n | BI01010001010000000000000515BI0100001176 | 1 | Cu. Mtr |
|---|
| 19 | 19.01 | Earthing with 50 mm dia GI pipe 3.64 mm thick x 3.04 Mts. Long and 1 x 4 SWG GI (Hot Dip) wire (4 Mts. Long), 13 mm dia x 80 mm long GI bolts, double nuts, double washers incl. S & F 15 mm dia GI pipe protection (1 Mts. Long) to be filled with bitumen partly under the ground level and partly above ground level driven to an average depth of 3.65 Mts. Below the ground level as below:\na) By ISI-Medium GI pipe. \n\n\n | BI01010001010000000000000515BI0100001177 | 1 | Set |
|---|
| 20 | 20.01 | S/F earth busbar of galvanized (Hot Dip) MS flat 40 mm x 6 mm on wall having clearance of 6 mm from wall including providing drilled holes on the busbar complete with GI bolts, nuts, washers, spacing insulators etc. as reqd. | BI01010001010000000000000515BI0100001178 | 0.5 | Mtr |
|---|
| 21 | 21.01 | Connecting the main earth bus-bar to earth electrode including S/F GI (Hot Dip) strips 25 mm x 6 mm thick on wall/floor with staples buried inside wall/floor as required and making connection to equipments with bolts, nuts, washers, cable lugs etc. as required & mending good damages. \n | BI01010001010000000000000515BI0100001179 | 10 | Mtr |
|---|