Repair/Maintenance Of Air Conditioner Plants Under Ge ( Af ) Tughlakabad, GE (AF) Tughlakabad-Delhi

Military Engineer Services-MES has published Repair/Maintenance Of Air Conditioner Plants Under Ge ( Af ) Tughlakabad. Submission Date for this Tender is 18-04-2020. Air Conditioner Tenders in GE (AF) Tughlakabad Delhi. Bidders can get complete Tender details and download the document.




Tender Notice

23799504
Corrigendum : Repair/Maintenance Of Air Conditioner Plants Under Ge ( Af ) Tughlakabad
Open Tender
Indian
Delhi
GE (AF) Tughlakabad
18-04-2020

Tender Details

Repair / Maintenance Of Air Conditioner Plants Under Ge ( Af ) Tughlakabad

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 17-Mar-2020 Corrigendum_2 Date 19-03-2020
2 27-Mar-2020 Corrigendum5 Date 18-04-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 53600.0 /-
Tender Value
INR 26.80 Lakhs /-

BOQ Items

Name of Work : REPAIR/MAINT OF AC PLANTS UNDER GE (AF) TUGHLAKABAD
Sl. No. Item Description Item Code / Make Quantity Units
1 1 M&L for checking the leakage in both low and high side of the system by feeding dry nitrogen to maintain adequate pressure in the system, plugging the leaks including S&F in replacement of Teflon sealing of all refrigerant line valves like liquid lines valves/suction/ discharge valves of compressors, gland packages of all angle valves, flaring of all connections framing welding etc complete all as specified and as directed for the following AC plants:- \nNote:- Entire work shall be carried out by OEM i.e Bluestar for following plants.
2 1.01 Central AC plant of capacity 3 x 37.5 TR-Plant for RSBN. OEM- Bluestar 1 Each Job
3 1.02 Central AC plant of capacity 3x15TR-Plant for Signal Section.OEM- Bluestar 1 Each Job
4 1.03 Central AC plant of capacity 2 x 30 TR-Plant for ESCT. OEM-Bluestar 1 Each Job
5 1.04 Central AC plant of Capacity 3x7.5 TR plant for PW-VI room. OEM-Bluestar 1 Each Job
6 1.05 Central AC plant of Cap 2x5.5TR-Plant for New signal centre.OEM-Bluestar 1 Each Job
7 1.06 Central AC plant of Capacity 3 x 26 TR plant for Spyder. OEM-Bluestar 1 Each Job
8 2 Opening the upper sheet and side sheet of AHU’s of the following central AC plants for access to cooling coil, including M&L for washing/cleaning of cooling coil externally with mild acid (or caustic soda hot water solution) followed by water jet including cleaning/washing of air filters and descaling of cooling coil of AHU, re-fixing and changing of V Belt both set with necessary fitting and T&P for mounting. \nNote:- Entire work is to be carried out by OEM i.e Bluestar for following plants.
9 2.01 Central AC plant of capacity 3x37.5 TR-Plant for RSBN . Make-Bluestar 2 Each Job
10 2.02 Central AC plant of capacity 3x15 TR-Plant for Signal Sec. Make-Bluestar 2 Each Job
11 2.03 Central AC plant of capacity 2x30 TR-Plant for ESCT. Make-Bluestar 2 Each Job
12 2.04 Central AC plant of capacity 3x26 TR-Plant for spyder. Make-Bluestar 2 Each Job
13 3 M&L for repair of AHU motor suitable for AC plants with following capacity by dismounting it from weather making unit of AHU replacement of Bush, bearing by opening nuts bolts and removing electrical connections of the motor, replacement of V type Belt with new belt, replacement of stator and rotor assembly rewinding of motor, replacement and alignment of shaft. complete all as specified and as directed.
14 3.01 Central AC plant of capacity 3x37.5 TR-Plant for RSBN . Make-Bluestar 2 Each Job
15 3.02 Central AC plant of capacity 3x15 TR-Plant for Signal Sec. Make-Bluestar 1 Each Job
16 3.03 Central AC plant of capacity 2x30 TR-Plant for ESCT. Make-Bluestar 1 Each Job
17 3.04 Central AC plant of capacity 3x26 TR-Plant for spyder. Make-Bluestar 2 Each Job
18 4 M&L for fixing of Cast Iron butterfly valve (wafer Type) of the following size without lugs, lever operated, SS 304 Disc, Nitrile /EPDM rubber lining test pressure PN-1.0/PN-1.6 by replacing the existing one, complete all as specified and as directed. Make Zoloto Art No 1078/Leader
19 4.01 50 mm dia 25 Each
20 4.02 65 mm dia 15 Each
21 4.03 80 mm dia 15 Each
22 5 M&L for fixing of gun metal gate valve butterfly type of 15 mm dia. complete all as specified and directed. Make Zoloto/Leader 5 Each
23 5.01 All as per item No-5 but of 20 mm dia 10 Each
24 5.02 All as per item No-5 but of 25 mm dia 10 Each
25 6 M&L for replacement of cast iron Y type strainer flanged type as per existing of the following size \nMake: Zoloto/Leader
26 6.01 50 mm dia. 2 Each
27 6.02 65 mm dia. 2 Each
28 6.03 80 mm dia. 2 Each
29 7 M&L for opening the outer sheets of package unit to access cooling coil, washing/cleaning of cooling coil externally with mild acid (or caustic soda hot water solution) followed by water jet including cleaning / washing of air filter and re-fixing the same of the following complete all as specified and directed. \nNote:- Entire work is to be carried out by OEM only i.e Bluestar/Voltas/Fedders Lloyd
30 7.01 Central AC Plant of capacity 1 x 7.5 TR Plant for PW-III. OEM-Fedders Lloyed 1 Each Job
31 7.02 Central AC Plant of capacity 3 x 7.5 TR Plant for PW-VI. OEM-Voltas 1 Each Job
32 7.03 Central AC Plant of capacity 2 x 5.5 TR Plant for signal Sec. OEM- Bluestar 1 Each Job
33 8 M&L for removing the existing choked fins of existing cooling towers cap and supply and fixing new fins of cooling tower for following AC Plant complete all as specified and directed.
34 8.01 Central AC plant of capacity 3x37.5 TR-Plant for RSBN . Make-Bluestar 1 Each Job
35 8.02 Central AC plant of capacity 3x15 TR-Plant for Signal Sec. Make-Bluestar 1 Each Job
36 8.03 Central AC plant of capacity 2x30 TR-Plant for ESCT. Make-Bluestar 1 Each Job
37 8.04 Central AC plant of capacity 3x26 TR-Plant for spyder. Make-Bluestar 1 Each Job
38 9 M&L for evacuation of gas from the system into the emplty cylinder provided by department/pumping down to the system, descaling condenser unit of the following capacity plants after bypassing the cooling tower, pumps & supply and circulation of the descalling solution (ANTI SCALENE SCALE FOEE-100) with pump brushing the tubes and where required drilling the stubbon scalling without damaging the tube, replacement of deshed end gasket and unserviceable nuts and bolts assembling back complete testing and commissioning including removing air lock, recharging the gas taken out of the system complete all as specified and directed.\nNotes:-(i) Descaling pumps, nylon brush, acid including storage containers, drill and drill bits to be arranged by contractor and cost of the same deemed to be included in the rate quoted for the following:- (ii) Entire work shall be carried out by OEM i.e Bluestar for the following plants.
39 9.01 Central AC plant of capacity 3x37.5 TR-Plant for RSBN. Number of compressors are 9(OEM- Bluestar) 3 Each Job
40 9.02 Central AC plant of capacity 3x15 TR-Plant for Signal Sec (OEM- Bluestar). Number of compressors are 3 3 Each Job
41 9.03 Central AC plant of capacity 2x30 TR-Plant for ESCT (OEM-Bluestar). Number of compressors are 4 3 Each Job
42 9.04 Central AC plant of capacity 3x26 TR-Plant for spyder (OEM- Bluestar. Number of compressors are 6 3 Each Job
43 10 M&L for Vacuum the system and after maintaining vacuum for 24 hours supply and charge refrigerant gas HCFC 22 complete all as specified and directed.\nMake:-Mafron/Refron 150 KG
44 11 M&L for Vacuum the system and after maintaining vacuum for 24 hours supply and charge refrigerant gas 407 C complete all as specified and directed, \nMake:-Mafron/Refron 150 KG
45 12 M&L for replacement for EWT/LWT sensor suitable for tripping for AC plant of spyder 2x26 TR, RSBN 2x37.5, 2x15 Signal, 2x30 TR ESCT AC plant as required and specified by OEM i.e Bluestar. Complete all as specified and as directed. 8 Each
46 13 M&L for replacement for digital temperature humidity display assembly as per existing for AC plant of spyder 2x26 TR, RSBN 2x37.5, 2x15 Signal, 2x30 TR ESCT AC plant as required complete all as specified and as directed. 5 Each
47 14 M&L for replacement for temperature gauge placed on pipe line as per existing for AC plant of spyder 2x26 TR, RSBN 2x37.5, 2x15 Signal, 2x30 TR ESCT AC plant as required complete all as specified and as directed. 12 Each
48 15 M&L for replacement for pressure gauge (low/high) as per existing for AC plant of spyder 2x26 TR, RSBN 2x37.5, 2x15 Signal, 2x30 TR ESCT AC plant as required complete all as specified and as directed. 12 Each
49 16 Taking down defective /unserviceable AC compressor of capacity 5.5/7.5 TR package type AC, and repair of the same compressor at company authorized outlet including replacement of EWT/LWT sensors, card including timer and contactor MNX 32-02 Nos. and electrical wiring by super enamelled copper conductor 6 sqmm, pressure testing & establishing vacuum for dehydration complete all as specified and directed by Engr-in-Charge. NOTE- Compressor maintenance cost for next 6 months is deemed to be included in qouted rates. 2 Each Job
50 17 M&L for dismantling existing water softener and replacement with raw water in to online electrostatic non chemical water treatment system electrically operated control panel to be fixed on sub header/tapping suitable for , the outer casing shall be of 304 grade stainless steel with both ends flanged and capable of preventing scale formation. Signal AC Plant 3x15 TR, Spyder AC Plant 3x26 TR flanged ends including necessary mechanical jointing operation like welding work, nut, bolts and rubber packing with starter panel electronically operated of existing length. Complete all as specified and directed by Engr-in-Charge. Make: scale off model no 3021 mfg by Weldon Engineers/ Ion Exchange NOTE- Water softner maintenance cost for next 6 months is deemed to be included in qouted rates. 2 Each Job
51 18 M&L Sub main wiring complete with non-metallic rigid PVC insulated fire retardant grade unsheathed 1100V grade multistranded copper conductor cable 2 run of 6 Sqmm single core confirming to IS-694 with copper conductor drawn through and including PVC casing capping/conduit heavy duty and accessories in walls, roof and floors along with 1 run of 6 Sqmm PVC insulated unsheathed cable with multistranded copper conductor as earth continuity conductor complete including chase cutting by cutter to concealed PVC conduit complete all as specified and as directed. Make of cable:- Plaza/Havells/Finolex 50 RM
52 19 Supply and fixing in replacement 1100 volts grade heavy duty cable insulated aluminium conductor derved with inner sheathing of PVC tape and over all PVC sheathed in service connected suspended by insulated hangers not more than 1 mtr apart incl 4 mm suspension wire one twin core 16 sqmm solid conductor complete all as specified and directed 50 RM
53 20 Supply and fixing in replacement 1100 volts grade heavy duty cable insulated aluminium conductor derved with inner sheathing of PVC tape and over all PVC sheathed in service connected suspended by insulated hangers not more than 1 mtr apart incl 4 mm suspension wire one twin core 25 sqmm solid conductor complete all as specified and directed 50 RM
54 21 M&L for painting of AC Plant as per existing colour including Compressor, condenser, motor, chiller pump, AHU, cooling tower including base and all pipe lines & connected valve etc complete all as specified and directed for the following plants:- (Make of Paint-Asian/Indigo)
55 21.01 Central AC plant of capacity 3x37.5 TR-Plant for RSBN 1 Each Job
56 21.02 Central AC plant of capacity 3x15 TR-Plant for Signal Sec 1 Each Job
57 21.03 Central AC plant of capacity 2x30 TR-Plant for ESCT 1 Each Job
58 21.04 Central AC plant of capacity 2x26 TR-Plant for Syder 1 Each Job
59 22 M&L for repair of indoor type LT panel board and replacement of unserviceable switch/control gears and meters, selector switches, indicator lamps etc including rewiring and extension of incoming and outgoing cables by opening of loops and provisioning of cable lugs /thimbles as required and replacement of rusted sheet metal with existing size MS sheets by necessary arc/gas welding(Approx sheet 1 Sqmtrs ) including two coats of synthetic enamel spray painting over a coat of red oxide primer both inside and outside surfaces of Panel Board including rewriting of identification for controls complete all as specified and directed.\nNote:- MCCB, contactors, relay, single phase preventer, timer, Change over, Indicator lamp, Selector switch, Ammeter, Voltmeter etc given below will be measured and paid seperately under respective items of this schedule. 4 Each Job
60 23 M&L in replacement Single phase preventer with Auto switch . Type- Cat No 2.BSP-2. \nMake- Bentex / Minilec 10 Each
61 24 M&L in replacement MCCB (AC 415 V) with adjustable thermal & adjustable magnetic setting 04 pole 400 Amp 36 KA. \nMake : GE/Havells/Legrand 1 Each
62 25 M&L in replacement MCCB of capacity , 250 Amps ,04 pole , 415 V, 36 KA Breaking capacity with fixed thermal magnetic release.\nMake- Legrand/ L&T/Havells. 1 Each
63 26 M&L in replacement MCCB 200 A, 4 Pole, 415 V, 36 KA Breaking capacity, with fixed thermal magnetic release.\nMake- Legrand/L&T/Havells. 2 Each
64 27 M&L in replacement MCCB 100 A, 3 Pole, 415 V, 35 KA Breaking capacity, with fixed thermal magnetic release.\nMake- Legrand/ L&T/Havells 3 Each
65 28 M&L in replacement Moulded Case Circuit Breaker (MCCB) (AC 415 V) with adjustable thermal & adjustable magnetic setting three pole 63 Amp 35 KA Cat Part No - IHLANT0063 of havells or equivalent L&T/Legrand. 4 Each
66 29 M&L in replacement Motor protection circuit breaker thermal overload relays suitable for ML contactors relay range 9-14 A\nMake-Havells/L&T/Legrand 10 Each
67 30 M&L in replacement Electronic overload relay (Manual reset) relay frame size 4 inch relay range 16-44 Amp suitable for contactor frame size CH 1 to CH 2 Type MPR200Nx . \nMake-Havells/L&T/Legrand 6 Each
68 31 S&F for flare nuts for connecting copper pipe for indoor & outdoor unit complete all as specified and as directed. 12 Set of Two
69 32 M & L welding/brazing rod copper for fixing to AC plant equipments complete all as specified and directed. 10 Each
70 33 Supply only LPG cylinder for brazing complete all as specified and directed. 4 Each
71 34 S&F in replacement Power contactor 3 pole Type MNX 18 AC 3 rating 18 A with auxiliary contact 1 NO + 1 NC complete all as specified and directed.\nMake- L&T/Legrand 6 Each
72 35 M&L in replacement Power contactor 3 pole Type MNX 70 AC 3 rating 70 A with auxiliary contact 2 NO + 2 NC , cat No - ST19002 of Make- L&T/Legrand 1 Each
73 36 M&L in replacement Power contactor 3 pole Type MNX 50 AC 3 rating 50 A with auxiliary contact 2 NO + 2 NC , cat No - ST19002 of Make- L&T/Legrand 1 Each
74 37 S&F in replacement Power contactor 3 pole Type 3 ML AC 3 rating 40 A with auxiliary contact 2NO + 2NC, cat No - SS90721 of Make- L&T/Legrand 1 Each
75 38 S&F in replacement Power contactor 3 pole Type MNX 25 A AC 3 rating 25 A with auxilary contact 2NO + 2NC, cat No - SS90921 of Make- L&T/Legrand 8 Each
76 39 S&F in replacement Power contactor 3 pole Type 1.5 ML AC 3 rating 25 A with auxilary contact 2 NO + 2 NC, Cat No - SS91851of Make- L&T/Legrand 4 Each
77 40 M&L in replacement Power contactor 3 pole Type MNX 32 AC 3 rating 32 A with auxilary contact 2NO + 2NC, Cat No - CS94136 of Make- L&T/Legrand 14 Each
78 41 M&L for thermal insulation for ducts with 13mm thick nitrile rubber insulation, complete all as specified and directed 50 Sqm
79 42 Supply and installation of aluminium powder coated grills / diffusers for supply air/return air with MS volume control dampers complete all as specified and directed. 4 Each
80 43 M&L for supply/return air ducting fabricated out of GI Sheet of thickness as under in diffirent size and shape complete all as specified and directed.
81 43.01 Made out of 22 Gauge 9 Sqm
82 43.02 Made out of 24 Gauge 9 Sqm
83 44 S&F Plastic trunking without cover 80mmx50mm. complete all specified and directed. Make- Legrand 30 RM
84 45 S&F Flexible cover 65mm width complete all specified and directed.\nMake- Legrand 30 RM
85 46 S&F high pressure cutout for R-22. complete all specified and directed.\nMake Danfoss 4 Each
86 47 S&F Low pressure cutout for R-22. complete all specified and directed.Make Danfoss 4 Each
87 48 S&F Oil pressure cutout for R-22. complete all specified and directed.\nMake Danfoss 4 Each
88 49 S&F Solonoid Valve for AC plant of Cap upto 80 TR of existing make complete all specified and directed. 4 Each
89 50 M&L in replacement of PUF insulation 36 mm of density 36 kg/cum and 26 gauge GI cladding complete with necessary mounting arrangement like clamps , nut bolt etc suitable for existing AC Plant cap upto 100 TR complete all as specified and as directed. 60 RM
90 51 M&L in replacement of PCB with display unit complete with necessary mounting suitable for existing AC Plant cap upto 100 TR,complete all as specified and as directed. 12 Each
91 52 M&L in replacement Duct filter with ss material filter media capacity shall capable 5 microns as per existing, suitable for AC plant of capacity upto 75 TR, package units as per site requirement complete all as specified and directed.\n 6 Each
92 53 M&L in replacement Strip heaters of cap 3KW (3000 W). \nMake- Dass pass 10 Each
93 54 M&L in replacement compressor Strip heaters of cap 1.5KW. Make- Dass pass 6 Each
94 55 M&L in replacement Aluminium sprinkler 3'x63mm with necessary mounting complete suitable for existing cooling towers,complete all as specified and as directed by Engr-in-Charge 4 Each
95 56 M&L in replacement PVC elemator for distribution of water over fills with necessary mounting complete suitable for existing cooling towers cap upto 100 TR complete all as specified and as directed. 2 Each
96 57 Taking out the unserviceable motor and rewinding of motor capacity 7.5 HP with same gauge with super enameled copper wire including removing burnt winding cleaning of slots separation of rotor and starter making insulation to all joint and replacement of the following items complete all as specified and directed.\n(a) Replacement of ball bearing. Make: SKF-02 Nos (b) Replacement of bush \n(c) Replacement of cooling fan - 01 Nos. 10 Each Job
97 58 All as per srl item no.57 here-in-before but motor capacity 5 HP 3 Each Job
98 59 All as per srl item no.57 here-in-before but motor capacity 3 HP 4 Each Job
99 60 All as per srl item no.57 here-in-before but motor capacity 2 HP 2 Each Job
100 61 M&L for opening of pump 7.5 HP centrifugal for repair and replacement of following unserviceable parts including re-fixing of all the same and testing and commissioning complete all as specified and as directed.\n(a) Replacement of gun metal impeller. -01 Nos \n(b)Replacement of gun metal bush -02 Nos \n(c) Replacement of ball bearing. Make: SKF - 01 Nos. \n(d) Replacement of oil seal -01 Nos. \n(e) Replacement of gland -01 Job 10 Each Job
101 62 All as per srl item No 61 here-in-before but 5 HP 3 Each Job
102 63 All as per srl item No- 61 here-in-before but 3 HP 4 Each Job
103 64 M&L for fasteners made of aluminium with suitable size for fixing of cooling tower fan blades including nut, bolts etc complete all as specified and as directed. 4 Set of Four
104 65 M&L for cleaning of Y type strainer by opening of all nut, bolts and removing filter under strainer cleaning the accumulated mud, cooling tower of any capacity, choked nozzles, valves etc complete all as specified and directed. 6 Each Job
105 66 M&L for PVC pipe of size 50/63 mm dia (Cooling tower) with drill holes for sprinkling water including cap front/back including all fittings etc. for plant of capacity 75 TR, 30 TR, 52TR, 40 TR. complete all as specified and directed. 4 Each Job
106 67 Taking down the unserviceable MCB and replace same MCB TPN 40 Amp 10 kA complete all as specified and directed.Make-Havells, Legrand 6 Each
107 68 M&L for Rotational moulded polyethylene water storage capacity 500 litre tank (cylindrical vertical with closed top) hoisted and fixed in position complete all as specified and as directed. Make- Syntex/ Reno/ Polycon 1 Each
108 69 M&L for Rotational moulded polyethylene water storage capacity 1000 litre tank (cylindrical vertical with closed top) hoisted and fixed in position complete all as specified and as directed.Make- Syntex/ Reno/ Polycon 1 Each
109 70 M&L for Rotational moulded polyethylene water storage capacity 2000 litre tank (cylindrical vertical with closed top) hoisted and fixed in position complete all as specified and as directed.Make- Syntex/ Reno/ Polycon 1 Each
110 71 M&L for fixing cooling tower FRP Type forced draft suitable for AC plant capacity 80 TR along with high speed fan motor and mounting and connection frame along with nut bolt, washer, sprinkler complete all as specified and as directed. Note: Work includes welding work to GI pipe and PCC/brick work required for raising platform height on which cooling tower is to be fixed.Make- FRP Polo / Ascent Engineering NOTE- Cooling tower maintenance cost for next 6 months from the installationshall deemed to be included in qouted rates. 1 Each
111 72 M&L for fire extinguisher contains specified mono ammonium phosphate (MAP-90) ABC dry powder type of 2 Kg capacity complete with all fitments and accessories complete all as specified and as directed. Make-Ceasefire/Newage 3 Each
112 73 M&L for fire extinguisher carbon dioxide (Co2) based of 4.5 kg capacity complete with all fitments and accessories complete all as specified and as directed. Make-Ceasefire/Newage 3 Each
113 74 Taking down the unserviceable MCB SP and replace the same MCB SP 6-32 Amp 10 kA complete all as specified and as directed. Make-Havells/Legrand/Schneider 10 Each
114 75 M&L for commissioning, testing of new commercial scroll sealed compressor Model No SM185S4RC suitable for 15 TR central type air conditioning plant, max operating 35 Ampere LR 175A, suction pressure varying from 25 bar to 27.8 bar suction temperature maximum varying from 630C to 680C refrigeration water chiller type, refrigerant R 22, lubricant oil type mineral oil, 160 P. complete all including necessary brazing complete all as specified and as directed.. \nMake-Danfoss or as approved by GE \nNOTE:- Compressor maintenance cost for next 6 months from the installation shalldeemed to be included in qouted rates. 3 Each
115 76 M&L for filter dryer strainer suitable for central AC plant of various capacities for installation in suction/chiller/liquid line.Make- Danfoss 6 Each
116 77 M&L for fabrication of MS steel work with thickness not less than 7 mm framed brackets of angles or tees with web and flanges cut to shape, drilled and countersunk for screw, including bending and welding angles, as necessary, gusset plates, riveting, etc. n exc 10 kg each brackets, conforming to Fe.290.Gde-E-165 (Brackets over 10 kg each to be measured under 'Structural Steel') FOR BASE FRAME WORK OF PUMPS & MOTORS Complete all as specified and directed and Engr-in-Charge 350 Kg
117 78 M & L for Pre - insulated MS pipe dia 65 mm , Class 'C' having thickness of PUF insulation 36 mm of density 36 Kg/Cum and 26 gauge GI cladding complete suitable for above ground with all mounting arrangements like clamps with nut bolt , brazing etc. complete all as specified and as directed. Make-Jindal/TATA/Prakash 12 RM
118 79 M & L for Pre - insulated MS pipe dia 80 mm , Class 'C' having thickness of PUF insulation 36 mm of density 36 Kg/Cum and 26 gauge GI cladding complete suitable for above ground with all mounting arrangements like clamps with nut bolt , brazing etc. complete all as specified and as directed. Make-Jindal/TATA/Prakash 6 RM
119 80 M & L for Pre - insulated MS pipe dia 50 mm , Class 'C' having thickness of PUF insulation 36 mm of density 36 Kg/Cum and 26 gauge GI claddingcomplete suitable for above ground with all mounting arrangements like clamps with nut bolt ,brazing etc. complete all as specified and as directed. Make-Jindal/TATA/Prakash 12 RM
120 81 M&L for replacement of chiller with inner copper tubing and outer shell of mild steel as specified in IS with flange on both the sides of capacity 37.5 TR as per site complete including necessary brazing, welding work complete all as specified and directed. \nNote:-Dismantling of existing pipeline and miscellineous work required at site and refixing of all water lines and sensors shall deemed to be included in qouted rate by Contractor Make-Bluestar 1 Each Job
121 82 M& L for in replacement of complete control pannel of existing make along with PCB display unit including neccessary wiring & U/S timer circuit for 7.5 TR package type AC plant at PW-VI complete all specified & directed. 2 Each
122 83 M& L for in replacement of display unit of existing make including neccessary wiring & U/S timer circuit for package/central type AC plant cap upto 100 TR complete all specified&directed. 7 Each
123 84 Supply and fixing the following unserviceable accessories of complete central/package type AC plant of capacity upto 100 TR including connecting testing complete all as specified and as directed:-
124 84.01 Out door unit condencing/AHU motor's fan blade 2 Each
125 84.02 Fan motor belt as per existing 3 Each
126 84.03 Canvas cloth for linkage as per existing 3 Each Job
127 84.04 Phase sequence corrector 2 Each
128 84.05 Expansion valve as per existing 5 Each
129 84.06 Notes:- \n1. Contractor has to deploy mimimum one refrigeration mechanic with one helper daily for day to day complaints pertaining to central/Package AC plants of any size/capacity for 24 hrs and the rate for the same shall deemed to be included in quoted rates by the contractor for the said work, failling which the recovery shall be made from the contractor's dues at double the rate prevailing for one skilled and semi skilledby Delhi Govt.or central Govt whichever is higher \n2. Contractor has to submit copy of MOU with OEM of respective plant and machinery within 20 days of work order No-01 isuued on contractor failing which recovery shall be made on this account @ rate of Rs.2000 per day from the contractor's dues.
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail