| 1 | 1 | M & L for general routine and maintenance including replacement of unserviceable components of package type AC of capacity 10TR/11TR consisting 2x5.5 Scroll compressor Mode No : DPA 1322RI Make : Blue Star/Voltas by opening front grill and the bottom side and taking out the cover of outdoor unit and carry out following Job/Repair complete all as specified and directed:-\n(Note: Spare parts will be measured and paid separately as supply only). | | 3 | Each Job |
|---|
| 2 | 1.01 | Sliding the filter out and washing it with water and hot and drying in the shade, reinstalling the same. | | | |
|---|
| 3 | 1.02 | Checking the compressor for oil leak and inspection of vibrations insulation rubber for wear and tightening the mounting lugs. | | | |
|---|
| 4 | 1.03 | Removing the cover from the bottom and filter from side of indoor unit and testing for gas leaks around the coil. | | | |
|---|
| 5 | 1.04 | Removing the front grill and the cover on the front bottom side to access the coil and testing for leaks using halide detector. | | | |
|---|
| 6 | 1.05 | Condenser coil and out door unit cleaning the coil using air blower or vacuum pump to clean MCHX coil and washing the coil using water jet. | | | |
|---|
| 7 | 1.06 | Electrical circuit and terminals :-checking all wires, cables and connecting terminals and ensure its tighteness. | | | |
|---|
| 8 | 1.07 | Cleaning and painting of outdoor unit and MS support stand . | | | |
|---|
| 9 | 2 | Supply only in replacement of the following spares of package AC Model No : DPA 1322RI complete all as specified and directed:- | | | |
|---|
| 10 | 2.01 | Condenser fan blade suitable for Model No DPA 1322RI package AC as per sample. | | 2 | Each |
|---|
| 11 | 2.02 | Scroll hermetically sealed compressor 5.5 TR 3 Phase suitable for Model No DPA 1322RI package AC Make Copeland or equivalent as approved by GE. | | 2 | Each |
|---|
| 12 | 2.03 | Belt suitable for Model No DPA 1322RI package AC Make- Fenner/Dunlop or equivalent as approved by GE. | | 4 | Each |
|---|
| 13 | 2.04 | Filter drier Cat No. EK-083 suitable for Model No DPA 1322RI package AC 11 TR of Make Blue Star Make- Emersion/Catch oil/Danfoss | | 4 | Each |
|---|
| 14 | 2.05 | Air filter suitable for Model No DPA 1322RI package AC 11TR of Blue Star Make Cecon/Thermodyne or equivalent as approved by GE. | | 4 | Each |
|---|
| 15 | 2.06 | Over load thermal relay 2.5 to 4.0 Amp suitable for Model No DPA 1322RI package AC 11 TR of Blue star Make - Siemens or equivalent as approved by GE. | | 6 | Each |
|---|
| 16 | 2.07 | Evaporative blower fan blade suitable for Model No DPA 1322RI package AC of Blue star | | 3 | Each |
|---|
| 17 | 2.08 | Pressure control HP/LP cut out suitable for Model No. DPA 1322RI package AC Make - Danfoss/Indfos or equivalent as approved by GE. | | 3 | Each |
|---|
| 18 | 2.09 | Blower ball bearing suitable for package AC blower of Make- SKF/NTN or equivalent as approved by GE. | | 4 | Each |
|---|
| 19 | 2.1 | Blower Shaft as per sample suitable for package AC 11 TR make of Blue Star. | | 2 | Each |
|---|
| 20 | 2.11 | Service Valve suction/discharge of size 1/4\" as per sample suitable for package AC 11 TR. | | 3 | Each |
|---|
| 21 | 2.12 | Condenser fan motor 1/3 HP, 920RPM suitable for package AC 11 TR Make Blue Star/Voltas or equivalent as approved by GE | | 2 | Each |
|---|
| 22 | 2.13 | Sensor (as per sample) suitable for package AC 11 TR, Make of Blue Star/Voltas or Equivalent approved by GE. | | 5 | Each |
|---|
| 23 | 2.14 | Micro processor lead (as per sample) suitable for package AC 11TR, Make of Blue Star/Voltas or equivalent approved by GE. | | 3 | Each |
|---|
| 24 | 2.15 | Wiring kit (as per sample) suitable for package AC 11 TR, Make of Blue Star/Voltas or equivalent approved by GE. | | 3 | Each |
|---|
| 25 | 2.16 | Power transformer for a (as per sample) suitable for package AC 11 TR, Make of Blue Star. | | 3 | Each |
|---|
| 26 | 3 | Replacement microprocessor controller suitable for model No DPA 1322RI Package AC having following features Make Blue Star or equivalent as approved by GE. | | 2 | Each |
|---|
| 27 | 3.01 | Run time equalization. | | | |
|---|
| 28 | 3.02 | Auto start after power failure. | | | |
|---|
| 29 | 3.03 | Memory back up. | | | |
|---|
| 30 | 3.04 | Built in time delay. | | | |
|---|
| 31 | 3.05 | Single phasing and reverse phase protection. | | | |
|---|
| 32 | 3.06 | Fuzzy logic | | | |
|---|
| 33 | 3.07 | Self fault diagnostics. | | | |
|---|
| 34 | 3.08 | Easy look up with fire alarm system. | | | |
|---|
| 35 | 4 | Taking out burnt/defective evaporative motor/condenser fan motor and rewinding with super enameled copper wire, re-fixing in existing unit of package AC testing and commissioning all as directed. Make of copper wire- Devidayal or equivalent as approved by GE. | | 2 | Each job |
|---|
| 36 | 5 | Supply of refrigerant gas mafran (R-22) monochlorodifloro methane confirming to IS-5160 duly filled in company sealed cylinder of capacity 61 Kgs complete all as specified and directed.\n(Note:- Empty Gas cylinder will be issued by Deptt) | | 122 | Kg |
|---|
| 37 | 6 | Filling only refrigerant gas for compressor 11 Ton capacity with R-22 gas and compressor oil upto specified quantity including flushing out old gas and oil including testing on full load & checking for leakage by nitrogen gas in the plant for 24 hr complete all as specified and directed.\n(Note:- Gas will be issued under relevant Item No 05 here-in-above) | | 3 | Each |
|---|
| 38 | 7 | M&L for Servicing of vertical type AC from various location and any height, like first floor, for maintenance, opening, cleaning with Magna/Hibird solution , giving water/air pressure, oiling including taking out old unserviceable parts and fixing new parts complete incl re-fixing at existing place after repairing and, servicing and testing for smooth functioning complete all as specified and directed. | | | |
|---|
| 39 | 7.01 | 2.5 TR cap vertical type AC | | 5 | Each |
|---|
| 40 | 7.02 | 3.5 TR cap vertical type AC | | 3 | Each |
|---|
| 41 | 7.03 | 5.5 TR cap vertical type AC | | 15 | Each |
|---|
| 42 | 8 | M&L for checking and rectification of un-serviceability of Vertical type AC of 2.5/3.5/5.5 TR by thorough checking and rectification of electrical faults of any type, including replacement of un-serviceable parts and cleaning of filters etc and testing of plant for smooth functioning complete all as specified and directed.\n(Note:- Spare parts will be measured and paid for separately). | | 18 | Each |
|---|
| 43 | 9 | Supply only following items for vertical type AC's compete all as specified and directed:- | | | |
|---|
| 44 | 9.01 | Single phase preventer relay for 2.5/3.5 TR cap vertical type AC (as per sample) Make : Sriram/Renutral/L&T | | 4 | Each |
|---|
| 45 | 9.02 | Sensor for as per sample suitable for Vertical type AC of 2.5/3.5/5.5 TR, Make of Blue Star, | | 5 | Each |
|---|
| 46 | 9.03 | Running capacitor 50 MFD, Make : EPCOS/Unistar/L&T | | 10 | Each |
|---|
| 47 | 9.04 | PCB for 2.5/3.5 TR cap vertical type AC (as per sample) | | 2 | Each |
|---|
| 48 | 9.05 | PCB for 5.5 TR cap vertical type AC (as per sample) with remote. | | 2 | Each |
|---|
| 49 | 9.06 | Contactor for 2.5/3.5 TR cap vertical type AC (as per sample), Make:- L&T/Seimens/ABB | | 4 | Each |
|---|
| 50 | 9.07 | Contactor for 5.5 TR cap vertical type AC (as per sample), Make:- L&T/Seimens/ABB | | 6 | Each |
|---|
| 51 | 9.08 | Connection box locally fabricated for connecting cables complete with lugs as per sample. | | 4 | Each |
|---|
| 52 | 10 | S&F in Replacement of U/S sealed unit with new hermetically company sealed compressor unit of following capacity three phase 415 volt incl welding/brazing of gas pipe line, vacuum pressure leakage, testing etc supply and fixing including charging refrigerant gas as required complete all as specified and directed . | | | |
|---|
| 53 | 10.01 | Three phase Sealed unit compressor 2.5 TR capacity Make : LG/Tecumsah/Kirloskar/Hitachi | | 4 | Each |
|---|
| 54 | 10.02 | Three phase Sealed unit compressor 3.5 TR capacity Make : Tecumsah/Kirloskar/Hitachi | | 3 | Each |
|---|
| 55 | 10.03 | Three phase Sealed unit compressor 5.5 TR capacity, Make-LG/Tecumsah/Kirloskar/Hitachi | | 6 | Each |
|---|
| 56 | 10.04 | Note for item No 10: - Old compressor unit will be the property of contractor for as per Sch of credit. | | | |
|---|
| 57 | 11 | S&F for rewiring of FHP motor with superior quality single core PVC insulated cable of suitable size/rating for 2.5 TR vertical type AC complete all as specified and directed. Make : Gulmarg/ National / AUE or equivalent as approved by GE. | | 3 | Each |
|---|
| 58 | 12 | All as per item No. 11.00 here in before but for 3.5 TR vertical type AC. | | 2 | Each |
|---|
| 59 | 13 | All as per item No. 11.00 here in before but for 5.5 TR vertical type AC. | | 5 | Each |
|---|
| 60 | 14 | M&L for charging only of refrigerant gas (R-22/407) in vertical type AC after detecting the leakage of refrigerant gas in the system and testing complete all as specified and directed. | | | |
|---|
| 61 | 14.01 | 2.5 TR cap vertical type AC | | 5 | Each |
|---|
| 62 | 14.02 | 3.5 TR cap vertical type AC | | 3 | Each |
|---|
| 63 | 14.03 | 5.5 TR cap vertical type AC | | 12 | Each |
|---|
| 64 | 15 | Supply only refrigerant gas M/F/R-407 duly filled in company sealed cylinder of capacity 10 Kgs complete for vertical /package type AC’s complete all as specified and directed by Engr-in-charge.\n\n( Note: cylinder should be provided by the contractor without any extra cost and the same will be returned after usage of gas. ) | | 10 | Kgs |
|---|
| 65 | 16 | M & L for cleaning of air duct through authorized company to remove dust, bacteria, mould spores and other foreign body by using HEPA filter vacuum unit and high pressure steam as required. Robotic video camera must be used for inspection, cleaning and sanitizing purpose. Access panels shall be fitted if required to gain access to clean the damper etc and shall be refitted with screws and sealant, after thorough cleaning, the system should be properly sanitized by using an EPA resister bacteria stat. Also submit a proof of cleaning of duct by using robotic camera and the video film copied on ac CD in duplicate before and cleaning. One copy of CD will be kept on record of Engineer-in-charge and other copy shall be submitted during payment of RAR as well as final bill. No payment shall be made in absence of video proof. Make : Blue star/Voltas/ Carrier. | | 615 | Sqm |
|---|
| 66 | 17 | Supply, assembly and erection of GI sheet with C & SS rectangular/square duct made out of 'L' shaped hollow profile, duly factory boxed, incl all accessories such as corner, Cleat. Carriage bolt, Gasket and appropriate sealant on longitudinal joints etc complete of size 20 Gauge complete all as specified and directed by Engr-in-charge. | | 80 | Sqm |
|---|
| 67 | 17.01 | Note : Duct shall be fabricated from galvanised sheet steel zinc coated having zinc coating 120 gm/sqm total on both sides conforming to IS-277-2003.\n\n | | | |
|---|
| 68 | 18 | S&F of crosslink XLPE foam nitrile rubber insulated on duct surface of size 8 to 9 mm thick on top, bottom and sides with adhesive and blank taping complete all as specification and directed. | | 75 | Sqm |
|---|
| 69 | 19 | M&L for hessian cloth lining of approved quality all around the duct with suitable size screws complete all as specified and directed. | | 45 | Sqm |
|---|
| 70 | 20 | M & L for replacement of MCCB, 3 pole adjustable type 36 KA, 125 Amps. Make : Havells / BCH/ Legrand/L&T. | | 2 | Each |
|---|
| 71 | 21 | S&F copper pipe along with PVC cushion o size 5/8\" dia all as specified and directed. | | 38 | RM |
|---|
| 72 | 22 | All as per item No 21.00 but of size 1\" dia | | 38 | RM |
|---|
| 73 | 23 | M&L for sub main wiring with three runs of single core 6 Sqmm (nominal area) PVC insulated and unsheathed multi stranded copper conductor cable LT 1100 grade FRLS cable drawn and PVC casing N Capping with all necessary fittings and accessories and 02xrun of PVC insulated and unsheathed single core cable multi stranded with copper conductor of size 4 Sqmm as continuous neutral and earth wire (black and green in colour ) respectively, run through PVC casing N capping and connected to the terminal and common earth dolly all as specified and directed.\n(Note. Five run of cable and one run of PVC casing and capping and one run of earth continuity wire shall be measured as one run complete all as specified.) | | 224 | RM |
|---|
| 74 | 24 | S & F triple pole and earth enclosure with a three pin and earth plug with socket complete with one triple pole MCB of capacity 32 Amps 'C' series all as specified and directed. Make : Havells / Legrand/Indo Asian | | 8 | Each |
|---|