| 1 | 1 | Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5 in depth for taking out /laying of cable etc., and getting out in soft/loose soil.complete all as specified and directed by Engineer-in-Charge. | | 190 | CUBIC METRE |
|---|
| 2 | 2 | Excavating in trenches, not exceeding 1.5m wide and exceeding 1.5m and not exceeding 3m in depth for taking out /laying of cable etc., and getting out in hard/dense soil.complete all as specified and directed by Engineer-in-Charge. | | 1 | CUBIC METRE |
|---|
| 3 | 3 | Returning, filling in soil, including spreading leveling, watering and wall ramming in laying not exceeding 25 cm thick complete all as specified and directed by Engineer-in-Charge. | | 104 | CUBIC METRE |
|---|
| 4 | 4 | Removing excavated soil to a distance n.exe 50m and depositing where directed at alevel n.exe 1.5m above the starting point complete all as directed by Engineer - in -Charge. | | 87 | CUBIC METRE |
|---|
| 5 | 5 | Supply and spreading of dry sand in trenches for cable coushioning and punned down complete all as specified and directed by Engineer-in-Charge.\nNote:- Punned thickness only shall be measured for payment purpose. | | 56 | CUBIC METRE |
|---|
| 6 | 6 | M&L for common burnt bricks, sub class 'B', of size 250 x 125 x 75 mm laid in trenches for cable protection including taking out existing bricks complete all as specified and directed by Engineer-in-charge. | | 6.3 | ONE THOUSAND NUMBERS |
|---|
| 7 | 7 | Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 95 sqmm 3.5 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge. | | 320 | RUNNING METRE |
|---|
| 8 | 8 | Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 50 sqmm 3.5 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge. | | 130 | RUNNING METRE |
|---|
| 9 | 9 | Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 16 sqmm 2 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge. | | 150 | RUNNING METRE |
|---|
| 10 | 10 | Supply and laying in trenches, fixed to wall or drawn through pipe etc., XLPE Insulated screened PVC bedded, galvanized steel strip or wire armored, electric power cables (heavy duty) 1100 Volts grade with stranded aluminium conductor of size 10 sqmm 2 core and connecting with necessary lugs including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge.\nNote for Item No. 7 to 10:- Excavation, earth work, brick protection, protection pipe and sand coushioning shall be measured and paid separately. Make of cable shall be CCI / Gloster / ICC / Unistar / NICCO / Asian (RPG) / Havells / Polycab/PRG/Universal/Plaza/Crystal cables/Terracom/ Rallison/Mescab/Jeypore/KEI | | 300 | RUNNING METRE |
|---|
| 11 | 11 | Material and labour for 80 mm dia bore GI tubing Light grade, laid under roads/ floor, or fixed to wall or along the pole with suitable size M.S.flat iron clamps, nuts, bolts and washers for cable protection including taking down/out existing pipe complete all as specified and directed by Egineer-in-Charge. | | 40 | RUNNING METRE |
|---|
| 12 | 12 | Material and labour for 40 mm dia bore GI tubing Light grade, laid under roads/ floor, or fixed to wall or along the pole with suitable size M.S.flat iron clamps, nuts, bolts and washers for cable protection including taking down/out existing pipe complete all as specified and directed by Egineer-in-Charge. | | 10 | RUNNING METRE |
|---|
| 13 | 13 | Material and labour for 25 mm dia bore GI tubing Light grade, laid under roads/ floor, or fixed to wall or along the pole with suitable size M.S.flat iron clamps, nuts, bolts and washers for cable protection including taking down/out existing pipe complete all as specified and directed by Egineer-in-Charge.\nMake for iItem No. 11 to 13: TATA/ZENITH/JINDAL or equivalent as approved by GE. | | 30 | RUNNING METRE |
|---|
| 14 | 14 | S & F pin type insulator, porcelain, vitreous white/ brown or green including one galvanised mild steel spindle two GI washer and one GI nut 100mm height, 65mm dia for 1100 Volt grade including taking down existing insulator complete all as specified and directed by Engineer-in-Charge. | | 5 | EACH |
|---|
| 15 | 15 | S & F Schakle type insulator, porcelain, vitreous white/ brown or green including galvanised mild steel straps of size 31 x 5 mm, washers insulator bolt of 14 mm dia and nuts complete of size 100 mm hight and 115mm dia of working pressure 1100 volts grade including taking down existing insulator complete all as specified and directed by Engineer-in-Charge. \nMake for iItem No. 14 & 15: (i) Jaipuria (ii) Jayshree (iii) Maysore Electric Industries (iv) Oblum | | 10 | EACH |
|---|
| 16 | 16 | Cutting and trimming tree branches any girth and any size and any number, touching to over head line and clearing the distance 2.5 mtrs both side of LT/HT over head conductors of span not exceeding 60m between poles and removing cut branches to a distance not exceeding 50m complete all as specified and directed by Engineer-in-Charge.\nNote: | | 50 | PER SPAN |
|---|
| 17 | 17 | M&L for Plain cement concrete 1:3:6 mix type C2 (using 40 mm graded stone aggregate) in foundations, filling and mass-concrete etc., all as specified and directed by Engineer-in-Charge. | | 5 | CUBIC METRE |
|---|
| 18 | 18 | M & L Plain cement concrete 1:2:4 type B1 (using 20 mm graded stone aggregate) as in coping including necessary formwork, weathering, slightly rounded or chamfered andgles, finishing of exposed surfaces of concrete to even and smooth without using extra cement all as specified and directed by Engr-in-charge. | | 1.5 | CUBIC METRE |
|---|
| 19 | 19 | Supply and stringing of aluminium conductor steel reinforced (ACSR) of any size as in overhead lines including binding wires of suitable sizes and suitable conductors / parallel groove clamp Etc. other jointing materials for over head lines including taking down existing ACSR conductors complete all as specified and directed by Engineer-in-Charge. | | 1 | QUINTAL |
|---|
| 20 | 20 | Earhing complete with galvanized steel earth plate electrode 600X600X6.3mm buried directly in ground (earth pit not less than 2.25 m deep below ground level) with top edge of the plate not less than 1.5m below ground level, connected to GI earth strip of size 32x6mm, by means of galvanized iron or steel bolts, nuts, check nuts and washers, and conneced to equipments as directed, including funnel with GI med grade watering pipe 20 mm bore, wire mesh charcoal or coke and common salt in alternate layers, of 15 cm compacted thickness all around the earth electrode, with concrete pit in PCC 1:3:6 type C-1 , 50 mm thick pre cast RCC 1:2:4 type B1 cover slab reinforced with 8 mm dia reinforced bar 15 cm C/C and suitable handle of 10 mm dia round bar, 40 mm GI medium grade pipe for earth lead protection including necessary excavation earth work in soft/loose soil and disposal of spoil to a distance n.exc. 50 m and necessary testing complete all as shown on electrical plate No. 3 of MES SSR Part-I including taking out existing earth plate etc., complete all as specified and as directed by Engineer-in-Charge.\nNOTE: Rate quoted shall be deemed to include for earth lead and protection pipe upto 7.5m. | | 10 | EACH SET |
|---|
| 21 | 21 | Earthing complete with galvanized steel earth plate electrode 600 x 600 x 6.3 mm buried directly in ground ( earth pit not less than 2.25 m deep bellow ground level ) with top edge of the plate not less than 1.5 m below normal ground level, connected to GI earth lead wire 4 mm dia. by means of galvanized iron or steel bolts , nuts , check nuts and washers, and connected to equipments as directed , including funnel with GI medium grade watering pipe 20 mm bore , wire mesh , charcoal or coke and common salt in alternate layers of 15 cm compacted thickness all around the earth electrode , with concrete pit in PCC 1:3:6 type C-1 , 50 mm thick pre cast RCC 1 : 2 : 4 type B-1 cover slab reinforced with 8 mm dia deformed bar 15 cm C/C and suitable handle of 10 mm dia round bar, 15 mm GI medium grade pipe for earth lead protection including necessary excavation earth work in soft/loose soil and disposal of spoil to a distance n.exc. 50 m and necessary testing complete all as shown on electrical plate No. 3 of MES SSR Part-I including taking out existing earth plate etc., complete all as specified and as directed by Engineer-in-Charge.\nNOTE: Rate quoted shall be deemed to include for earth lead and protection pipe upto 7.5m. | | 4 | EACH SET |
|---|
| 22 | 22 | M&L for galvanised steel wire 3.15 or 4mm dia as earth continuity conductor including binding and connecting to earth test point etc., including taking down existing earth wire complete all as specified and directed by Engineer-in-Charge. | | 1 | QUINTAL |
|---|
| 23 | 23 | M&L for cross arms , bracings, supports, clamps and back plate fabricated from structural sections including nuts, bolts, and washer bending hot or cold , drilling holes for bolts of any size and painting with two coats of aluminum paint over one coat of red oxide primer including preparation of surfaces, including taking down existing cross arms etc., complete all as specified and directed by the Enginee-in-Charge. | | 2 | QUINTAL |
|---|
| 24 | 24 | M&L for Stay assembly with 20mm dia rod complete with accessories as shown in electrical plate No. 1 including taking out existing stay assembly, complete all as specified and directed by the Enginee-in-Charge.\nNote: Loop type insulator, stay clamps, stay wire, excavation and concrete shall be measured and paid separately. | | 5 | EACH SET |
|---|
| 25 | 25 | S & F loop type insulator, porcelain, vitreous white/ brown or green of size 90 x 140mm with clearence of hole 25.5 mm including taking down existing insulator complete all as specified and directed by Engineer-in-Charge. | | 5 | EACH |
|---|
| 26 | 26 | M&L for galvanised stay strand 7/4mm as stay wire including binding etc., including taking down existing stay wire complete all as specified and directed by Engineer-in-Charge. | | 0.5 | QUINTAL |
|---|
| 27 | 27 | M&L for applying one coat aluminium paint on 9 mtr long steel tubler pole in position after prepretion of surface of steel tubler pole including all fitted cross arms, clamps and nut, bolts etc., including painting of black and yellow paint strips of 05 Nos of 30 cm wide strips or as ordered by engineer-in-charge on poles up to 1.5 mtr high above coping level including numbering of size 70mmx40mm by using stencil to the pole with black synthetic enamel paint ( 1st grade ) 1.5 mtr above the ground level all as specified and as directed by Engineer-in-Charge. | | 120 | JOB |
|---|
| 28 | 28 | Restringing of existing LT overhead line for removing exessive sag including removing the existing binding wire and rebinding with new binding wire after tightning of overhead lines including disconnecting existing jumpher and connections and reconnecting after tightning of conductor incl replacement of all jumpers all as directed by Engr -incharge.\nNotes: - (a) Single wire run of conductor in LT lines shall be measured as one lenght for payment purpose.\n(b) ACSR conductor shall be measured and paid separately. | | 3000 | RUNNING METRE |
|---|
| 29 | 29 | S&F of MCCB of Four Pole, 415V, AC 50 Hz, 36KA breaking capacity 250 Amps with overload and thermal release range 70 to 100% and magnetic setting adjustable features including taking down old unserviceable MCCB complete all as specified and directed by Engineer-in-Charge. | | 1 | EACH |
|---|
| 30 | 30 | S&F of MCCB of Four Pole, 415V, AC 50 Hz, 36KA breaking capacity 200 Amps with overload and thermal release range 70 to 100% and magnetic setting adjustable features including taking down old unserviceable MCCB complete all as specified and directed by Engineer-in-Charge. | | 1 | EACH |
|---|
| 31 | 31 | S&F of MCCB of Four Pole, 415V, AC 50 Hz, 36KA breaking capacity 160 Amps with overload and thermal release range 70 to 100% and magnetic setting adjustable features including taking down old unserviceable MCCB complete all as specified and directed by Engineer-in-Charge. | | 3 | EACH |
|---|
| 32 | 32 | S&F of MCCB of Three Pole, 415V, AC 50 Hz, 16KA breaking capacity 63 to 100 Amps with overload and thermal tripping features including taking down old unserviceable MCCB complete all as specified and directed by Engineer-in-Charge. | | 3 | EACH |
|---|
| 33 | 33 | S&F of MCCB of Four Pole, 415V, AC 50 Hz, 16KA breaking capacity 100 Amps with overload and thermal tripping features including taking down old unserviceable MCCB complete all as specified and directed by Engineer-in-Charge.\nMake for Item No. 29 to 33: L&T/LEGRAND/SIEMENS/ABB | | 7 | EACH |
|---|
| 34 | 34 | S&F Busbar Chambers 4 way 100 Amps outdoor type (IP 65/66) pole mounted including provision of fixing on pole by means of suitable size of clamps with nut and bolts including necessary connection including taking down old unserviceable MCCB complete all as specified and directed by Engineer-in-Charge. \nMake: Havells cat part No. IHBC010004 or equivalent make of SMC/Hencel | | 4 | EACH |
|---|
| 35 | 35 | S&F Busbar Chambers 6 way 100 Amps outdoor type (IP 65/66) pole mounted including provision of fixing on pole by means of suitable size of clamps with nut and bolts including necessary connection including taking down old unserviceable MCCB complete all as specified and directed by Engineer-in-Charge. \nMake: Havells cat part No. IHBC010006 or equivalent make of SMC/Hencel | | 5 | EACH |
|---|
| 36 | 36 | M & L for DK Thermoplastic cable junction boxes IP 65 of size 185x165x60mm of metric knockouts for cable entry, weather proof for outdoor installation with and including glands and with 4 terminals for terminating one incoming and outgoing UG cable of size 10/16 sqmm 2/4 core and fixed to the PSC/Steel Poles by means of suitable size of clamps with nut and bolts incl provn of 01 No of single pole MCB 6-32 amps,10KA and MCB TPN 6-32 amps, 10 KA, ‘B’ series 01 No inside the box complete including taking down existing existing junction box all as specified and directed by Engineer-in-Charge.\nNOTE: Make of Junction box shall be Sintex or equivalent as approved by GE. | | 10 | EACH |
|---|
| 37 | 37 | Supply & fixing LED street light fitting 60Watt, System lumens output not less than 6500 lm, Colour Temp - 5700K, Effiicieny not less than 115 lm/W including bracket made out of 40 mm dia light grade GI pipe not less than 1.2 mtr long bend to shape duly fixed with MS clamps of 3mm thick, nut, bolts etc complete fixed to steel tabular poles including electrical connection complete with 3 core 1.5 Sqmm sheathed copper wire ISI marked stranded to LT terminal box to fitting complete including taking down existing fitting all as specified and as directed. \nMake: Model \"ENDURAPEARLPLUSSL60WLED757SASYTOPC\" of Havells or equivalent model of Crompton/Philips. | | 12 | EACH |
|---|
| 38 | 38 | Supplying & erecting of steel tubular swaged pole conforming to IS, specification complete with MS base plate, finial taper plug, bolts, nuts, type 410 SP-31, 9.00 mtr long and painted internally two coats of bituminous paint through out and externally upto planting depth and painting external exposed surfaces with two coats of alluminium paint over one coat of redoxide primer including provision of black and yellow paint strips of 05 Nos of 30 cm wide strips or as ordered by engineer-in-charge on poles up to 1.5 mtr high above coping level and numbering of poles with writing letters or figures ( Block ), height minimum 10 cm & letters or figures n'exc 10 Nos for electric LT/HT/SL including clamp including taking out existing pole of any size and type complete all as specified and directed by Engineer-in-Charge.\nNote:Earth work, excavation, PCC foundation, PCC coping shall be measured and paid seperately. | | 8 | EACH |
|---|
| 39 | 39 | Supply, installing, testing and commissioning factory made LT feeder pillar box (KIOSK) outdoor type platform mounted, CPRI approved suitable for 415 volts 3 phase 4 wire, 50 Hz AC supply system all as specified and directed having bus bar installed on DMC/Epoxy insulators. The panel shall be dust and vermin proof, IP-65 class protection and made of 3.15 mm CRCA steel sheet with double door shutter and locking arrangement, openable from front & back both including powder coated on both outer and inner surfaces for panel. The TPN copper bus bar of rating not less than the 1.5 times the rated capacity of the incommer MCCB including 50 x 50 x 6mm thick angle iron frame workupto height of 0.9mtr above ground level (duly painted with one coat red oxide and one coat of bitumen paint on exposed surfaces) with and including following spares and including dismantling of old unserviceable existing panel all as specified and as directed by Engr-in-Charge.\n(i) MCCB 4 pole 25 kA 100 Amp - 01 No (Incommer)\n(ii) MCCB 4 pole 16 kA 63 Amp - 02 Nos.\n(iii) Phase indiacting lamps (R-Y-B) - 01 set\n(iv) Internal wiring with PVC insulated, multi stranded copper conductor cable, 1100 V grade.\n(v) Multifunctioning meter with necessary CTs\n(vi) Spare compartment for MCCB for future expansion - 01 No | | 1 | JOB |
|---|
| 40 | 40 | Supply & fixing of LED 35watt New generation, post-top, energy saving, environmental friendly, long life aesthetically designed with symmetrical light distribution, spun aluminium landscape luminaire with high power LEDs as light source, conforming IP-65, alongwith 0.5 m long 80mm dia medium grade GI pipe and necessary connection by means of nut/bolts and PVC 3.0 core 0.5 sqmm conductor complete including taking down existing light fitting complete all as specified and directed by Engineer-in-Charge.\nMake: Model \"RUBYPT35WLED757PSYMTOPC\" of Havells or equivalent model of Crompton/Philips. | | 10 | EACH |
|---|
| 41 | 41 | Supplying & fixing 1100 volts grade heavy duty cable PVC insulated and FR PVC rounded sheathed, copper conductor (flexible) industrial cable, conforming IS: 694 of size 1.5 sqmm 3 core laid along pole from junction box to light fitting including taking out exising unserviceable cable complete all as specified and directed by Engineer-in-Charge. | | 100 | RUNNING METRE |
|---|
| 42 | 42 | Supply & fixing automatic street/security light switch of rating 8 KW in three phase using nature switch for automatic switching of street lights based on lux level on nature light. The sensor (Nature Switch) along with suitable power contactor, MCB and supprot terminals should be enclosed in pole/wall mountable enclosure made of rust proof, electric shock proof, termite proof and FR grade special moulding compound (Polycarbonate) conforming to IP 54 along with each contactor 25-32 Amps , Incoming-Outgoing MCBs (03 Nos each) rating : 32 Amps, circuit wiring min 10 sqmm including taking out exising unserviceable time switch complete all as specified and directed by Engineer-in-Charge.\nModel - SWADEEP - 02EC8KW3P MAKE- 1.Nature-Nature Switch : Kakatiya Energy systems Pvt. Ltd / HEALER / BAJAJ 2.Contactor : BCH / L& T / Schneider 3. MCB : Hager / Schneider /L&T/C&S \n4. Circuit wiring : Finolex / Polycab or equivalent | | 1 | EACH |
|---|
| 43 | 43 | Sub Total of Schedule 'A' | | | |
|---|
| 44 | 44 | Schedule of Credit (Minus) Rs. 81,730.00 B/F from Ser page No. 30 \nNOTE: Bidder shall insert credit amount as rate Rs. 81,730.00 in Green field under Col-M. If bidder does not insert the amount the same will be deducted from total amount of Schedule 'A' and accordingly total amount of tender will be considered in deciding the lowest tender. | | 1 | EACH |
|---|
| 45 | 45 | Sub Total of Schedule of Credit | | | |
|---|