Repair/Maintenance Of Fire Fighting Systems, Fire Panels/ Equipment, Smoke Detctors With Allied Services At Hqtc,Bangalore, HQ TC BANGALORE-Karnataka

Military Engineer Services-MES has published Repair/Maintenance Of Fire Fighting Systems, Fire Panels/ Equipment, Smoke Detctors With Allied Services At Hqtc,Bangalore. Submission Date for this Tender is 02-03-2020. War Vehicle Tenders in HQ TC BANGALORE Karnataka. Bidders can get complete Tender details and download the document.




Tender Notice

23763039
Repair/Maintenance Of Fire Fighting Systems, Fire Panels/ Equipment, Smoke Detctors With Allied Services At Hqtc,Bangalore
Open Tender
Indian
Karnataka
HQ TC BANGALORE
02-03-2020

Tender Details

Repair / Maintenance Of Fire Fighting Systems, Fire Panels / Equipment, Smoke Detctors With Allied Services At Hqtc, Bangalore :-Periodical Maintenance And Servicing Of Fire Smoke Detectors Consisting Of Bentel Panel , Smoke Detectors 8 Nos Each In A System , Fm200 Cylinder With 57 Kg Fm200 Gas , Realease Switches , Control Switches Etc , Complete By Making Regular Servicing Of The System To Ensure Proper Functioning Including Replacement Of Spare Materials All As Directed . Location :- Af Net Site-I . , Maintenance And Servicing Of 10 Hp Pump Sets 09 Numbers Fixed In Map Pocket I&Ii Complete With Motor And Starter / Panel Board For Trouble Free Operation Including Checking The Insulation Resistance And Electrical Contacts And Setting Right The Loose Electrical Contacts / Connection , Lubricating The Pump Set , Replacement / Tightening Of Gland Packing , Arresting Leakages In Suction / Delivery Lines Etc . Including Provision Of Necessary Consumables Complete All As Specified And As Directed . Notes :- ( I ) The Spares Like Bearings , Bushes , Impellors , Couplings , Etc , Wherever Required For Replacement Shall Be Measured And Paid Separately Under Relevant Items Of This Schedule . ( Ii ) The Rate Quoted Deemed To Include For Replacement Of Minor Spare Parts Costing Upto Rs . 200 / - Each . ( Ii ) The Contractor Shall Be Responsible For Trouble Free Operation Of All The Pumpsets During The Currency Of The Contract And Shall Maintenance And Repairs Carried Out And Spares Replaced Shall Be Warranted During The Contract Period . , Servicing And Testing Of Ceasefire Smoke Detection Control Panel - 28 Wireless Zones , 2 Hardwired Zone , Tamper Alert , Passcode Protected , Rf Jamming Recognition , Diagnostic Feature For Rf Signal Strength Between Panel And Each Detector , Event Reporting Using Pstn Telephone Line , Dialing Upto 4 Telephone Numbers , Event Reporting As Per Users Choice , Remote Control Using Telephone Line , Lcd Screen Display , Intuitive Graphic And Audible User Interface , Two Way Voice Interaction , Battery Backup Stand By Time Upto 12 Hrs For 2 Nos And In Each All As Specified And As Directed . Location :- Armoury , Periodical Maintenance And Servicing Of Fire Smoke Detectors Consisting Of Bentel Panel , Smoke Detectors 8 Nos Each In A System , Fm200 Cylinder With 34 Kg Fm 200 Gas , Realease Switches , Control Switches Etc , Complete By Making Regular Servicing Of The System To Ensure Proper Functioning Including Replacement Of Spare Materials All As Directed By Engineer-In-Charge ( At Af Net Site-Ii ) , Periodical Servicing Of Zone Panel And Testing Of Smoke Detector - Fully Supervised Smoke Detector Wire Less Repeater , Long Life 9 Volt Alkaline Or Lithium Battery , Simple Ceiling Mount Installtion With Separate Installation Bracket For 9 Nos In Each All As Specified And As Directed . Location :- Command It Section . Note For Sl Item No . 1 To 5 :- Defect Shall Be Rectified Within 24 Hours Of Complaint Raised . In Any Case Rectification Beyond The Stipulated Time , Penalty Shall Be Levid Rs . 500 / - Per Day . , Supply And Fixing Of 12V , 7Ah Battery For Panels In Repalcement Of Old Unserviceable Batteries All As Specified And As Directed . Make: Exide , Supply And Fix Mcp ( Manual Call Point ) Glass In Replacement Of Old Broken / Damaged Glass All As Specified And As Directed . , Supply And Refilling In Cylinder / Replacing Gas With Fm200 Gas In Cylinder All As Specified And As Directed . , Supply And Fix Wire Less Smoke Detector Of Type 1Sd12 , Operated On 9 Volts Dc Battery Complete All As Directed . Make :- Cease Fire , Supply And Fix Heat Detector For Max Operating Temp Of 68 Degree Centigrade , In Repair , Complete All As Directed . , Supply And Fix Fire Alarm Panel Suitable For Fm 200 Gas Extinguishing System , Cross Zone Operated Complete Testing And Commissioning All As Directed And Specified . Make: 5S , Supply And Fix 1 . 5 Sqmm , 2 Core Flexible Armoured Copper Cable For Fire Detectors Comminication Compete All As Directed And Specified . , Supply And Fix Transformer 50 Va , Dry Type , Air Cooled , For 12 Zone Fire Alarm Conventional Panel Complete All As Directed And Specified . Make: Mini Max , Supply And Fix Alkaline Dry Battery 9 Volts , Pp3 Size , With Dura Lock Complete All As Directed . Make: Duracell Or Equivalent . , Supply And Fix Timer Unit For Automatic Fire Control Panel Opereated On Single Phase 230 Volts , Ac , 50Hz Complete Fixed In Repair All As Directed And Specified . Make: Selecktron Model-800S . , Supply And Fix Thermal Over Load Relay Of 10A With Max Fuse Rating At 32A Complies To Is:9224 Operated On Single Phase 230 Volts , Ac , 50Hz Complete In Repair All As Directed And Specified . , Supply And Fix Contactor , Continous Current Rating 40 A , 3 Phase , 440 Volts Complete In Repair All As Directed And Specified . Make: C&S . , Replacement Of Manual Call Point Duly Painted In Red Colour With Front Glass ( To Be Broken In Case Of Fire ) Complete With Test Key To Check He Response Without Breaking The Glass And Die Cast Aluminium Housing With Ifd Indicator All As Specified . , Replacement Of Zone Cards . , Spray Painting Of Fire Fighting Equipment By Applying One Coat Of Primer And Two Coats Of Synthetic Enamel Paint Of Red Colour ( Post Office Colour ) All As Specified & Directed . , Supply & Fix In Replacement Of First Aid Hose Fire Reel Wall Mounted Type Fitted With Of Dia 20 Mm And 30 Mtr Length , Hose With Isi Marked Ss Shut Of Nozzle And Connection Of 20Mm Gate Valve And Pipe Complete All As Specified And Directed . , Rewinding Of Motor Up To 10 Hp Capacity With Super Enameled Copper Winding Wire Of Suitable Gauge And Size , Providing Insulating Materials Such As Fibre Glass Tape , Varnishing , Heating Up Assembling In The Electric Motor , Testing And Commissioning Complete Including Replacement Of Bearings / Bushes By Using Hydraulic Press For Testing To Full Load All As Specified And As Directed Including Dismantling & Taking To Work Shop And Bring Back And Re Assembling All As Directed . , Supply And Fix Ball Bearing Both End Sealed Suitable To Fix With Electric Motor Of 10 Hp Capacity Fixed In Repairs All As Specified And As Directed . , Magnetic Sensor Suitable For Micro Processor Based Digital Water Level Indicator Fixed At Different Levels Inside Sump / Over Head Reservoir For Sensing Level Of Water Including Dismantling Old Unserviceable Sensor All As Directed , Pvc Insulated Copper Conductor Cable , 12 Core X 0 . 6Mm Gauge , Superior Quality Suitable For Carrying Signals From Sensor To Digital Water Level Indicator Of Approved Make Including Taking Down Existing Un-Serviceable Cable All As Specified And Directed . Make: Sunrich , Supply And Fix Fire Alarm Isi Marked Including Taking Down Old Unserviceable All As Directed . , Supply And Fix Single Phase Preventer Suitable For Any Capacity Upto 20 Hp Pump Sets Including Dismantling And Taking Up Old Unserviceable All As Specified And Directed . Make: L&T / Minilac , Supply And Instal Digital Water Level Indicator Fitted On 25000 Ltr Capacity Fire Tanks On Airmen Map Pocket -I &Ii Complete Including Necessary Accessories Connecting Cables , Digital Display Etc All As Specified And Directed . , Supply & Fix In Replacement Of Gun Metal Coupling Assembly With Lug ( Locking Pin ) For Hydrant Valve Complete E All As Specified And Directed . , Supply And Fix Water Pressure Guage 100Mm Dia Ranging 0-14 Kg / Sqcm Including Dismantling Unserviceable Exisitng Pressure Guage Complete All As Specified And Directed . Make: Accurate , Supply And Fix In Replacement Of Gun Metal One Way Fire Hydrant Landing Valve Of Size 63Mm Dia Isi Marked Complete With Instantaneous Coupling Complete All As Specified And

Key Value

Document Fees
INR 500 /-
EMD
INR 25000.0 /-
Tender Value
INR 12.50 Lakhs /-

BOQ Items

NAME OF WORK :- REPAIR/MAINTENANCE OF FIRE FIGHTING SYSTEMS, FIRE PANELS/ EQUIPMENT, SMOKE DETCTORS WITH ALLIED SERVICES AT HQTC,BANGALORE
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Periodical maintenance and servicing of Fire smoke detectors consisting of Bentel Panel, Smoke detectors 8 Nos each in a system, FM200 cylinder with 57 Kg FM200 gas, realease switches ,control switches etc, complete by making regular servicing of the system to ensure proper functioning including replacement of spare materials all as directed.\nLocation :- AF NET SITE-I. 9 Per Month
2 2 Maintenance and servicing of 10 HP pump sets 09 numbers fixed in MAP POCKET I&II complete with motor and starter/ panel board for trouble free operation including checking the insulation resistance and electrical contacts and setting right the loose electrical contacts/ connection, lubricating the pump set, replacement/ tightening of gland packing, arresting leakages in suction/ delivery lines etc. including provision of necessary consumables complete all as specified and as directed.\nNotes :-\n(i) The spares like bearings, bushes, impellors, Couplings, etc, wherever required for replacement shall be measured and paid separately under relevant items of this Schedule. \n(ii) The rate quoted deemed to include for replacement of minor spare parts costing upto Rs. 200/- Each. \n(ii) The Contractor shall be responsible for trouble free operation of all the pumpsets during the currency of the contract and shall maintenance and repairs carried out and spares replaced shall be warranted during the contract period. 9 Per Month
3 3 Servicing and testing of Ceasefire Smoke Detection Control Panel - 28 Wireless Zones, 2 Hardwired Zone, Tamper Alert, passcode protected, RF Jamming recognition, diagnostic feature for RF signal strength between panel and each detector, event reporting using PSTN Telephone line, dialing upto 4 telephone numbers, event reporting as per users choice, remote control using telephone line, LCD Screen Display, Intuitive graphic and audible user interface, Two Way voice interaction, Battery Backup stand by time upto 12 hrs for 2 Nos and in each all as specified and as directed. \nLocation :- Armoury 9 Per Month
4 4 Periodical maintenance and servicing of Fire smoke detectors consisting of Bentel Panel, Smoke detectors 8 Nos each in a system, FM200 cylinder with 34 Kg FM 200 gas, realease switches ,control switches etc, complete by making regular servicing of the system to ensure proper functioning including replacement of spare materials all as directed by Engineer-in-charge (At AF NET SITE-II) 9 Per Month
5 5 Periodical servicing of Zone panel and testing of Smoke Detector - Fully Supervised smoke Detector wire less repeater, Long life 9 volt alkaline or lithium battery, simple ceiling mount installtion with separate installation bracket for 9 Nos in each all as specified and as directed. Location :- Command IT section. \nNote for Sl item No.1 to 5 :- \nDefect shall be rectified within 24 hours of complaint raised. In any case rectification beyond the stipulated time, penalty shall be levid Rs.500/- per day. 9 Per Month
6 6 Supply and fixing of 12V, 7AH battery for panels in repalcement of old unserviceable batteries all as specified and as directed. \nMake: Exide 10 Each
7 7 Supply and fix MCP (manual call point) glass in replacement of old broken/ damaged glass all as specified and as directed. 4 Each
8 8 Supply and refilling in cylinder/ replacing gas with FM200 gas in cylinder all as specified and as directed. 90 Kgs
9 9 Supply and fix wire less smoke detector of Type 1SD12 , operated on 9 volts DC battery complete all as directed.\nMake :- Cease fire 3 Each
10 10 Supply and fix heat detector for max operating temp of 68 degree centigrade, in repair, complete all as directed. 2 Each
11 11 Supply and fix fire alarm panel suitable for FM 200 gas extinguishing system, cross zone operated complete testing and commissioning all as directed and specified. Make: 5S 2 Each
12 12 Supply and fix 1.5 sqmm, 2 core flexible armoured copper cable for fire detectors comminication compete all as directed and specified. 100 RM
13 13 Supply and fix transformer 50 VA , dry type, air cooled, for 12 zone fire alarm conventional panel complete all as directed and specified.\nMake: Mini max 2 Each
14 14 Supply and fix alkaline dry battery 9 volts, PP3 size, with dura lock complete all as directed.\nMake: Duracell or equivalent. 24 Each
15 15 Supply and fix timer unit for automatic fire control panel opereated on single phase 230 volts, AC,50Hz complete fixed in repair all as directed and specified.\nMake: selecktron model-800S. 2 Each
16 16 Supply and fix thermal over load relay of 10A with max fuse rating at 32A complies to IS:9224 operated on single phase 230 volts, AC,50Hz complete in repair all as directed and specified. 2 Each
17 17 Supply and fix contactor, continous current rating 40 A , 3 phase, 440 volts complete in repair all as directed and specified.\nMake: C&S. 3 Each
18 18 Replacement of manual call point duly painted in red colour with front glass (to be broken in case of fire) complete with test key to check he response without breaking the glass and die cast aluminium housing with IFD indicator all as specified. 10 Each
19 19 Replacement of Zone cards. \n 7 Each
20 20 Spray painting of fire fighting equipment by applying one coat of primer and two coats of synthetic enamel paint of red colour (post office colour) all as specified & directed. 20 sqm
21 21 Supply & fix in replacement of first aid hose fire reel wall mounted type fitted with of dia 20 mm and 30 mtr length, hose with ISI marked SS shut of nozzle and connection of 20mm gate valve and pipe complete all as specified and directed. 2 Each
22 22 Rewinding of motor up to 10 HP capacity with super enameled copper winding wire of suitable gauge and size, providing insulating materials such as fibre glass tape, varnishing, heating up assembling in the electric motor, testing and commissioning complete including replacement of bearings/ bushes by using hydraulic press for testing to full load all as specified and as directed including dismantling & taking to work shop and bring back and re assembling all as directed.\n 2 Each Job
23 23 Supply and fix ball bearing both end sealed suitable to fix with electric motor of 10 HP capacity fixed in repairs all as specified and as directed. 4 Each Job
24 24 Magnetic sensor suitable for micro processor based digital water level indicator fixed at different levels inside sump/ over head reservoir for sensing level of water including dismantling old unserviceable sensor all as directed 20 Each
25 25 PVC insulated copper conductor cable, 12 core x 0.6mm gauge, superior quality suitable for carrying signals from sensor to digital water level indicator of approved make including taking down existing un-serviceable cable all as specified and directed.\nMake: Sunrich 30 RM
26 26 Supply and fix fire alarm ISI marked including taking down old unserviceable all as directed. 4 Each
27 27 Supply and fix single phase preventer suitable for any capacity upto 20 Hp pump sets including dismantling and taking up old unserviceable all as specified and directed. Make: L&T / Minilac 2 Each
28 28 Supply and instal digital water level indicator fitted on 25000 ltr capacity Fire tanks on Airmen Map Pocket -I &II complete including necessary accessories connecting cables, digital display etc all as specified and directed. 2 Each
29 29 Supply & fix in replacement of Gun Metal Coupling Assembly with Lug (Locking Pin) for hydrant valve complete e all as specified and directed. 3 Each
30 30 Supply and fix water pressure guage 100mm dia ranging 0-14 kg/sqcm including dismantling unserviceable exisitng pressure guage complete all as specified and directed.\nMake: Accurate 3 Each
31 31 Supply and fix in replacement of Gun Metal one way fire hydrant landing valve of size 63mm dia ISI marked complete with instantaneous coupling complete all as specified and directed. 2 Each
32 32 Supply & fix in replacement of 63 mm dia, 15 mtr long rubberized fabric reinforced rubber lined canvas hose including gun metal male & female instantaneous coupling hose conforming to IS 636 type II and coupling conforming to IS 903-1975 all as specified and directed. 2 Each
33 33 Supply & fix standard short size F75 16mm nominal bore, outlet and standard instantaneous coupling 63mm dia complete as in repair all as specified and directed. 2 Each
34 34 Supply & fix in replacement of valve reflux cast iton (NRV) with by pass arrangement supplied installed complete of size 100mm dia including filling properly the gland packing kit complete all as specified and directed.\n(Make :- Kirloskar) 2 Each
35 35 Supply & fix butterfly valve of size 100mm dia complete as in repair all as specified and directed. 3 Each
36 36 Sluice valve, cast iron body with stainless steel spindle, class-1 ISI marked,100mm bore, PN-1, both end flanged and drilled and fixed with bolts and nuts and washers including providing rubber insertion of suitable thickness complete of following sizes including taking out existing unserviceable sluice valves all as specified and as directed 2 Each Job
37 37 Supply & Fix in repair MS pipe 100mm including removing old rusted one with special suit site condition replacing damaged existing CI distribution main pipe line by cutting and alligning true line, welding and jointing by providing high tensile steel fasteners for outsider and inside surfaces for specials, duly painted with anti corrosive tank mastic paint over a coat of red oxide primer. The work involves supply of materials incl necessary T&P to work site, incl necessary excavation, earthwork, linking pits , cutting of pipes using gas cutting/ griding machines , fixing of special bolts, nuts, washers all as required at site incl de-watering pump etc and completing the job within the stipulated time and testing complete all as specified and all as directed. 30 RM
38 38 M&L Fire brigade inlet connection 2way fixed in repair all as specified and directed.\n 2 Each
39 39 M&L for Yard hydrant Post / Stand Post 80/100 mm Dia GI / MS both flanged type 1.5m height fixed in repair all as specified and directed.\n 2 Each
Disclaimer :
We takes all possible care for accurate & authentic tender information, however Users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender.
Tell us about your Product / Services,
We will Find Tenders for you

Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy

For Tender Information Services Visit : TenderDetail