Supply Installation Testing And Commissioning Of 11 K . V . Sub Station And Work Related To Booster Pump Set For 2 Nos Newly Constructed Hostel Building At Maharani College Campus , Jaipur, Maharani College Jaipur-Rajasthan

Public Works Department-PWD has published Supply Installation Testing And Commissioning Of 11 K . V . Sub Station And Work Related To Booster Pump Set For 2 Nos Newly Constructed Hostel Building At Maharani College Campus , Jaipur. Submission Date for this Tender is 02-03-2020. Submersible Pump Tenders in Maharani College Jaipur Rajasthan. Bidders can get complete Tender details and download the document.




Tender Notice

23711436
Supply Installation Testing And Commissioning Of 11 K . V . Sub Station And Work Related To Booster Pump Set For 2 Nos Newly Constructed Hostel Building At Maharani College Campus , Jaipur
Open Tender
Indian
Rajasthan
Maharani College Jaipur
02-03-2020

Tender Details

supply installation testing and commissioning Of 11 K . V . Sub Station And Work Related To Booster Pump Set For 2 Nos Newly Constructed Hostel Building At Maharani College Campus , Jaipur

Key Value

Document Fees
INR 500 /-
EMD
INR 53200.0 /-
Tender Value
INR 26.60 Lakhs /-

BOQ Items

Name of Work: SITC of 11 K.V. Sub station and work related to Booster Pump set for 2 Nos Newly Constructed Hostel Building at Maharani College Campus, Jaipur
Sl. No. Item Description Item Code / Make Quantity Units
1 1 S&F following sizes (dia.) of ISI marked medium duty PVC conduit along with accessories in surface / recessed using saddles, clamps, fastener as required including cutting the wall, covering conduit and making good the same as required. Gr-1
2 1.01 25 mm 45 R. mtr.
3 1.02 32 mm 45 R. mtr.
4 2 Supplying and drawing FR PVC insulated & unsheathed flexible copper conductor ISI marked (IS:694) of 1.1 kV grade and approved make in existing surface or recessed conduit/casing capping including making connections etc. as required. Gr-1
5 2.01 4 x 10.0 sq.mm 15 Mtr.
6 3 P/Laying ISI marked P.V.C. insulated submersible cable confirming to IS:694 with flexible copper conductor including making connection etc. as required. Gr-1
7 3.01 4.0 Sq.mm 3 core flat / Round 400 Mtr.
8 3.02 10.0 Sq.mm 3 core flat / Round 50 Mtr.
9 4 Supplying and fixing of power plug point Modular accessories on hot dipped galvanized modular on surface or in recessed with suitable size of grid plate with cover plate including cost of modular 16 amp. Switch and socket outlet , making connection , testing , etc. as required. Gr-1 16 Each
10 5 P & F in position frame made out of M.S. angle (riveted or welded) finished with two coats of red oxide and enamel paint including cutting, welding, holes etc.of following sizes as required.
11 5.01 50mm x 50mm x 6mm 30 Mtr.
12 6 P&F 240/415 V AC MCB with positive isolation of breaking capacity not less than 10 KA (B/ C/ D tripping characteristic) ISI marked IS 8828(1996)]/ conforming to IEC 60898 in existing board/sheets including making connections, testing etc. as required. Gr-1
13 6.01 Double pole MCB
14 6.02 6 A to 32 A rating 4 Each
15 6.03 Triple pole MCB
16 6.04 6 A to 32 A rating 4 Each
17 6.05 Four pole MCB
18 6.06 6 A to 32 A rating 4 Each
19 7 P&F 240/415 V Residual current circuit breaker conforming to IS:12640:1988/ IEC 61008 on existing board/sheet including making connections, testing etc. as required Gr-1
20 7.01 Two pole 30 mA sensitivity
21 7.02 25 A rating 16 Each
22 7.03 Four pole 30 mA sensitivity
23 7.04 40 A rating 15 Each
24 7.05 63 A rating 15 Each
25 8 P&F Recessed/ Surface mounting heavy duty horizontal type sheet steel Distribution board phophatised/ powder painted complete with suitable rating insulated copper bus bar, shorting link , neutral link, earth link and din bar,masking sheet, conforming to IS13032 & IS8623 including making internal DB terminations with copper lugs , testing etc. as required. Gr-1
26 8.01 Double door (Three phase)
27 8.02 4 Way 2 Each
28 9 P&F flush/surface type enclosure for housing MCB/Isolator with Din rail including making connections with lugs, repairs etc. as required. Gr-1
29 9.01 With sheet steel enclosure
30 9.02 Two way 16 Each
31 10 SITC of wall/ free standing floor mounted dust and vermin proof compartmentalised cubical panel made out of CRCA sheet , required hardware ,duly treated for derusting in 7 tank process with dephosphating and with powder coating on both side of panel in desired shade The panel having PU/ Neoprene rubber gasket of not less than 3mm thickness , separate detachable gland plate M.S. base channel ,hinged door with locking arrangement for equipment/switchgear . Thickness of sheet shall not be less than 1.6 mm up to 600 mm length / width of any compartment and be of 2.0 mm above 600 mm. Load bearing structure shall be of 2.0 mm thick sheet supported by base M.S. channel if required . Side walls and cable alley compartments having bolted type doors with / without detachable extension type structure. (only outer area on all sides shall be measured & panel to be fabricated from CPRI approved fabricator). Gr-1 37 SQ.Mtr.
32 11 Supplying and fixing of Aluminium / Copper bus bar by means of SMC / DMC type insulator, high tensile nuts and bolts spring washers in existing panel including bending , cutting in required shape and size and colour coding with heat shrinkable PVC sleeves. Gr-1
33 11.01 Electrolytic grade Aluminium bus bar 48 Kg.
34 12 SF of (0-500) V range Volt meter on existing panel , making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. Gr-1
35 12.01 Digital type 4 Each
36 13 SF of CT operated direct reading type Ampere meter on existing panel , making connection by PVC insulated copper conductor with PVC sleeves / channel etc. as required. Gr-1
37 13.01 Digital type
38 13.02 Below 500 A 4 Each
39 14 SF of Current Transformer , with all necessary support in existing panel including connection etc. as required . Gr-1
40 14.01 up to 150 / 5 Ratio , 5 VA , class 1 accuracy 3 Each
41 14.02 from 200 / 5 to 400/5 Ratio , 10 VA , class 1 accuracy 9 Each
42 15 SF of selector switch of 10 A for voltmeter (4 position ) including making connection etc. as required . Gr-1 4 Each
43 16 SF of CT linked selector switch of 10 A for Ampere meter (4 position ) including making connection etc. as required . Gr-1 4 Each
44 17 SF of 110/220 V, LED (22.5 mm dia ) Indicating lamp with integral circuit, terminal block, including connection etc. as required. Gr-1
45 17.01 Red/yellow/Green colour 16 Each
46 17.02 Blue colour 8 Each
47 18 SITC of Fixed / Draw out type 3 pole Air Circuit Breaker conforming to IS 60947 P - 2 in existing LT panel suitable for LT installation 440 V, 50 Hz and having adjustable over load short-circuit, earth fault and microprocessor based release with separate LED indication for each type of fault ,LCD display , Thermal memory at least 4NO & 4NC auxiliary contacts safety shutter and fault position acknowledgement mechanism . type ACB shall have separate indication for service, test, isolation, maintenance position, Breaking capacity Icu = Ics = Icw ( 1 sec ) , Uimp - 12 KV, including making connections etc. as required. Gr-1
48 18.01 Fixed Type
49 18.02 630 A Rating , 50kA 1 Each
50 19 SITC of quick make and quick break 4 POLE current limiting MCCB having following current rating, short circuit breaking capacity at 440/415 V, 50 Hz; O/L & S/C settings and conforming to IS 60947-2 / IEC 60947-2 with front face and centralised adjustable, line load interchangeability, having positive isolation capability, provision for UVR , shunt trip ,earth fault trip, push ( test ) to trip , including making connections with lugs & spreaders, etc. as required. Gr-1
51 19.01 With Thermal Magnetic release
52 19.02 up to 100 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu 3 Each
53 19.03 up to 125 Amp , 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu 2 Each
54 19.04 160 Amp, 25 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu 2 Each
55 19.05 250 Amp , 35 kA, adjustable O/L & fixed S/C setting, Ics = 100 % Icu 5 Each
56 20 P/Laying P.V.C. / XLPE insulated & P.V.C. sheathed cable of 1.1 KV grade with aluminium conductor of IS:1554 P-I / IS :7098 P - I of Group 1 of approved make in ground as per IS:1255 including excavation of 30cmx75cm size trench, 25 cm thick under layer of sand,IInd class bricks covering, refilling earth,compaction of earth, making necessary connection, testing etc. as required of size. Gr-1
57 20.01 16.0 Sq.mm Armoured
58 20.02 4 core 60 Mtr.
59 20.03 50.0 Sq.mm Armoured
60 20.04 3.5 core 70 Mtr.
61 20.05 185.0 Sq.mm Armoured
62 20.06 3.5 core 148 Mtr.
63 20.07 300.0 Sq.mm Armoured
64 20.08 3.5 core 240 Mtr.
65 21 P & Laying XLPE insulated IS:7098/II/85 of Group1 and approved make H.T.cable for working voltage 11 K.V.Earthed direct in ground including excavation of 30cmx100cm size trench, 25cm layer of river sand, IInd class bricks covering, refilling earth, compaction of earth, making necessary connection testing etc.as required of size. Gr-1
66 21.01 3 core 70.0 Sq.mm 90 Mtr.
67 22 Providing & making heat shrinkable type indoor/outdoor/straight through terminations/joint kit of Group1 and approved make suitable for XLPE insulated 11 KV / 33 KV cable, with required components, prepration of cable ends,testing etc. as required of following sizes . Gr-1
68 22.01 11 KV End Termination Kit Indoor type
69 22.02 3 core 70/95 Sq.mm 6 Set
70 23 Plate Earthing as per IS:3043 with G.I. Earth plate of size 600mm x 600mm x 6.0mm by embodying 3 to 4 mtr. below the ground level with 25 mm dia. G.I. 'B' class watering Pipe including all accessories like nut, bolts, reducer ,nipple, wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. 6 Set
71 24 Plate Earthing as per IS:3043 with copper Earth plate of size 600mm x 600mm x 3.0mm by embodying 3 to 4 mtr. below the ground level with 25 mm dia. G.I. 'B' class watering Pipe including all accessories like nut, bolts, reducer, nipple ,wire meshed funnel, and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size300mm x 300mm complete with alternate layers of salt and coke/charcoal, testing of earth resistance as required. 2 Set
72 25 Maintenance free Gel Earthing with Pipe in pipe / Pipe in strip technology filled with anti corrosive conductive compound ( CPRI Tested ) below the ground in 150 - 200 mm dia. earth pit & surrounding filled with required mineral filling compound ( MFC should have hygroscopic property to retain the moisture for long time to create low resistance zone ) and C.C. finished chamber covered with hinged type with locking arrangement C.I. Cover, C.I. Frame of size 300mm x 300mm complete testing of earth resistance as required. of following sizes.
73 25.01 With Pipe in Pipe Technology (Inner pipe dia. / Outer pipe dia. ) 80 - 100 micron GI Coating
74 25.02 GI pipe 2000 mm long, 50 / 25mm, Terminal 12 mm GI Strip 6 Set
75 26 S & Laying following size earth wire/strip in horizontal or vertical run in ground/surface/recess including riveting, soldering, saddles, making connection etc. as required.
76 26.01 8 SWG G.I. ( Hot Dipped ) Wire 100 Mtr.
77 26.02 32mm x 6mm copper strip 18 Mtr.
78 26.03 25mm x 3mm G.I. ( Hot Dipped ) Strip 40 Mtr.
79 26.04 32mm x6mm G.I. ( Hot Dipped ) Strip 45 Mtr.
80 27 S & Laying following size' B ' class G.I. Pipe confirming to IS : 1239 P - 1 ( 1990 ) with accessories for laying earth conductor/strip / cable in ground/surface/recess as required
81 27.01 80 mm dia. 10 Mtr.
82 28 P & F ISI marked (IS:2082) Horizontal storage water heater with outer casing made of M.S.sheet finished with anti-corrosive powder coating,inner tank made of pure electrolytic copper/stainless steel , Tubular copper sheathed and Nickel plated heating element/ twin ceremic cartridge heating element, stem type thermostat and thermal cut out,Dual indicating lamps for power supply and thermostat,PUF insulation, Pressure relase valve,fusible plug etc. as required held in position with 4 no. rack bolts,duly wired with 3 core 2.5/4.0 Sqmm PVC insulated & sheathed copper conductor and 16 A/25A three pin plug top,including making inlet,outlet heavy gauge C.P. connection,testing etc. as required. Gr-1
83 28.01 50 Ltr. 16 Each
84 29 P & F IP-65 protected Wall mounted Bulk Head light fixture suitable for 15/18 watt CFL lamp with integral control gear, housing made from cast aluminium with UV stablized diffuser comprising of copper ballast, copper conductor including making connection testing etc. as required (without lamp) Gr-1 10 Each
85 30 SITC of ISI mark( IS:8472) self priming monoblock pump set of approved make, TEFC, permanent split capacitor type (PSC), fitted with thermal overload protection, mechanical seal, 1440/1500 RPM, single phase(180 to 240 V). Including cost of hardware etc on existing platform complete. Pump shall have following HP Rating, phase, Head, minimum Discharge respectively. Gr-1
86 30.01 Non Self priming pumps
87 30.02 10 HP, 3-Ø, (6-28)Mtr, (45-7.5)LPM 3 Each
88 31 Supply and fixing of Oil / Air break Starter panel made out of sheet steel powder coated enclosure comprising of over load protection relay, short circuit & single phasing protection, ON / OFF push buttons, ammeter, voltmeter, indicating lamps etc. complete in all respect suitable for following rating motors. Gr-1
89 31.01 For Three phase Submersible / Mono block pump
90 31.02 3.0 HP to 10.0 HP ( Star / Delta ) 3 Each
91 32 SITC of 11 KV, 400/630 A, 20kA / 3 sec, Out door, Extensible type Ring main unit (RMU) in suitable RCC foundation with 2 no. Load break switch & 1 no. VCB / SF6 circuit breaker with over load, Earth fault, short circuit relay, copper bus bar, earthing switch, mechanical ON / OFF / Earth indication, Voltage presence indicator, Ring core protection CT 2.5 VA, 10P10 as per transformer rating, Shunt trip coil, Anti reflex operating handle, right angle boots etc. as required. Gr-1 1 Set
92 33 Supply & fabrication steel structure with MS channel / angle / joist / ISMB / sheet etc. including welding, rivetting, cutting, nut & bolt , Painting etc. as required. Gr-1 300 Kg
93 34 Earth work in excavation/ by mechanical means (Hydraulic Excavator)/ manual means over areas (exceeding 30 cm in depth, 1.5m in width as well as 10 sum on plan) including disposal of excavated earth, lead upto 50 m and lift upto 1.5 m, disposed earth to be levelled and neatly dressed: Gr-1 3 Cum
94 35 Random Rubble stone masonry for with hard stone in foundation and plinth in Cement Sand mortar above 30 CM thick wall in: Gr-1
95 35.01 Cement Mortar 1:6 ( 1-Cement : 6-Sand). 3 Cum.
96 36 Providing and laying in position cement concrete including curing, compaction etc. complete in specified grade excluding the cost of centering and shuttering - All work up to plinth level.
97 36.01 M10 grade Nominal Mix \n1: 3: 6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20mm nominal size). 2 Cum.
98 37 Plaster on new surface on wall in cement sand mortar 1:3 including racking of joints etc. complete fine finish :
99 37.01 20mm thick 8 Sqm
100 38 Supplying and fixing of chain link fencing with angle iron posts 50x50x6mm placed at every 3 Mtr. apart 30cm in ground embedded in cement concrete 1:3:6 (30x30x45cm) corner and every tenth post to be strutted with (50 x 50 x 6cm) angle iron provided and fixed and fitted with posts including earth work in excavation etc. complete with chain link size. Gr-1
101 38.01 50mm x 50mm x 3.15mm 30 Sqm.
102 39 Supply & Fixing ISI marked ( IS : 15683 ) Portable fire Extinguisher, Carbon-dioxide type flat base including valve, discharge hose of not less than 10 mm dia. min. 600 mm long & complete in all respects including initial fill with C02 gas confirming to IS:307-1966 filled to a filling ratio of not more than 0.667and wall suspension bracket. Capacity 4.5 Kg.Gr-1 1 Each
103 40 Supply & Fixing ISI marked ( IS : 15683 ) Portable Fire Exitnguisher, ABC type,finished externally with red enamel paint, complete in all respects including initial fill and wall suspension of following capacity. Gr-1
104 40.01 6 kg 1 Each
105 41 P & F energy efficient / energy saving 9 Watt IP 20 LED Bulb cool white, in existing holder / fixture as required, minimum 900 Lumen output, 25000 burning hours, CCT 5700K, ANSI, Lamp efficacy minimum 100 lumen/Watt, CRI>80, Driver efficiency >85%, PF 0.95 at full load/ 230 volt AC. Gr-1 10 Each
106 42 P&F of IP 20 LED tube light 20W with external batten made from CRCA sheet steel suitable to replace T-8/T-12 tubelights,integral driver, 2000 lumens +/- 5% tolerance, system lumens efficacy of 100 lm/watt minimum, expected life time of 25000 burning hours, CCT 5700K, ANSI, CRI 80, Driver efficiency >85%, Life expectancy of driver min. 30000 hrs. PF 0.95 at full load/ 230 volt AC. Gr-1 4 Each
107 43 P & F 1200 mm Sweep BEE 5 Star rated double ball bearing capacitor start, aluminium body & blade ceiling fan complying to IS374:1979, I/P 50 watt at max. speed & 230 volt, >210 CMM air delivery, speed >330 RPM with down rod up to 30 cm with 3 x 1.5 sq.mm pvc insulated flexible copper conductor making connection testing etc. as required. Gr-1 1 Each
108 44 P&F of IP65 protected LED Street Light Luminaire on existing bracket. Fixture made of powder coated single piece pressure die cast aluminum with heat dissipation fins on housing with UV stabilized PC/Toughened Glass cover ( from 45W onwards ) and should be secondary lens on each LED . The System level Luminaire efficacy >=100 with High Power LEDs of CREE/NICHIA/OSRAM/PHILIPS/SEOUL make is to be used .The LED Driver shall be BIS certified and Input Voltage AC 110 to 270 V AC with Input Frequency 50Hz±3% Power Factor >0.95 Driver Efficiency >85% , THD(I) <10% Humidity 10% to 90% RH Working Temp -20C to 50C . Life Expectancy Equal or more than 50000 burning hrs with Minimum 70% initial lumens maintained ,Rendering Index >75% .Surge protection shall be min = 5 KV internal and min 10 KV external. Manufactures Word Mark/Name Engraved/Embossed on die cast housing to allow traceability/authenticity till life of fixture. Fixtures shall be CE complianed. Gr-1
109 44.01 LED Street Light fixture 30 Watt 2 Each
110 45 S I T C of star rated Aluminium wound distribution Transformer of following rating 11/0.433KV Delta-Star Connected, Vector Group Dyn 11, as per BEE star level- 2 & BIS approved with losses as defined as per IS 1180 part I 2014. including standard accessories like conservator, silica gel breather, radiator, fins, HT cable box & LT cableboxes, Off -LTC (+5% to - 10% @ 2.5%) winding temperature rise of 50/55 degree C, ISI marked drain valve, Dial type Temperature gauge, first fill of oil, Epoxy based paint, including carrying of pre-commission Testing & Charging of Transformer. ( Transformer Should be CTL Tested , w/o any extra cost ) . Gr-1
111 45.01 315 KVA 1 Each