Military Engineer Services-MES has published Repairs And Maintenance Of Electrical Installation Including Panels , Mccbs , Ug Cables , Street Light And Connected Works At Military Station Ajmer Repairs And Maintenance Of Electrical Installation Including Panels , Mccbs , Ug Cables , Street Lig. Submission Date for this Tender is 20-03-2020. Electrical Maintenance Tenders in NASIRABAD Rajasthan. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 19-Mar-2020 | Corrigendum no 02 | Date | 20-03-2020 |
Name of Work: REPAIRS & MAINTENANCE OF ELECTRICAL INSTALLATION INCLUDING PANELS, MCCBs, UG CABLES, STREET LIGHT & CONNECTED WORKS AT MILITARY STATION AJMER. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Dismantling old unserviceable bus bar & S & F new insulated aluminium bus bar, 50 x 10mm, 400 Amps capacity with colour coding including bus bar insulator of porcelain complete all as specified & directed. | BI01010001010000000000000515BI0100001119 | 5 | RM |
2 | 2 | Dismantling old unserviceable bus bar & S & F new insulated aluminium bus bar, 38 x 6mm, 200 Amps capacity with colour coding including bus bar insulator of porcelain complete all as specified & directed. | BI01010001010000000000000515BI0100001120 | 5 | RM |
3 | 3 | Taking out old unserviceable MCCB & S & F MCCB, 250 Amp, 4 Pole, 36 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting with thermal release range 160-200 Amp including spreader terminals and phase barriers complete all as specified and directed. \nMake L&T/Schneider/ Legrand as approved by GE. | BI01010001010000000000000515BI0100001121 | 1 | EACH |
4 | 4 | Taking out old unserviceable MCCB & S & F MCCB, 200 Amp, 4 Pole, 36 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting with thermal release range 100-200 Amp including spreader terminals and phase barriers complete all as specified and directed. \nMake L&T/Schneider/ Legrand as approved by GE. | BI01010001010000000000000515BI0100001122 | 1 | EACH |
5 | 5 | Taking out old unserviceable MCCB & S & F MCCB, 160 Amp, 4 Pole, 36 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting with thermal release range 100-160 Amp including spreader terminals and phase barriers including complete all as specified and directed. \nMake L&T / Schneider / Legrand as approved by GE | BI01010001010000000000000515BI0100001123 | 2 | EACH |
6 | 6 | Taking out old unserviceable MCCB & S & F MCCB, 100 Amp, 4 Pole, 36 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting with thermal release range 80-100 Amp including spreader terminals and phase barriers including complete all as specified and directed. \nMake L&T / Schneider / Legrand as approved by GE | BI01010001010000000000000515BI0100001124 | 2 | EACH |
7 | 7 | Taking out old unserviceable MCCB & S&F MCCB, 63 Amp, 4 Pole, 16 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting , with thermal release range 80-100 Amp including spreader terminals and phase barriers including complete all as specified and directed. \nMake L&T / Schneider / Legrand as approved by GE | BI01010001010000000000000515BI0100001125 | 2 | EACH |
8 | 8 | Taking out old unserviceable MCCB & S&F MCCB, 125 Amp, 3 Pole, 16 KA, 415 V, thermal magnetic release type, Ics=100 % Icu, with adjustable overload setting and adjustable short circuit setting , with thermal release range 80-100 Amp including spreader terminals and phase barriers including complete all as specified and directed. \nMake L&T / Schneider / Legrand as approved by GE | BI01010001010000000000000515BI0100001126 | 2 | EACH |
9 | 9 | Taking down old unserviceable power factor correction panel board & Supply, install, testing and commissioning of automatic power factor correction (APFC) panel board, outdoor type suitable for LT 415 volts, 3 phase, 4 wire system, 80 KVAR capacity, factory made cubical complete materialised dust and vermin proof (protection class IP 54), made out of 3.15mm thick MS sheet (CRCA) including factory made (CPRI approved) hinged type double door both side opening with locking arrangement with handle (godrej type) duly painted with seimens grey powder coated finish over a coat of zinc chrome primer including carry out internal connection with suitable aluminium bus bar including cable alloy for incoming and outgoing cable complete all as specified and directed by Engineer-In-Charge. The panel board shall be comprising of the following accessories:-\n(i) copper bus bar capacity 400 amp - 04 Nos.\n(ii) MCCB 125 Amps, 4 pole with thermal magnetic release, adjustable type, 25 KA, 415 Volts - 01 Nos (incoming).\n(iii) Digital volt meter 96mm x 96mm flush secure panel mounting type, 0-500 volts with selector switch - 01 Nos.\n(iv) Digital ammeter 96mm x 96mm flush secure panel mounting type, 0-100 amp with selector switch - 01 Nos.\nMake :- APL/ LET/ AE\n(v) RYB neon indicating LED lamp, set of three - 01 Set.\n(vi) Selector switch with LED indicator for each capacitor.\n(vii) Mixed die electric type capacitor\nMake of MCCB :- Legrand, schneider, siamens. | BI01010001010000000000000515BI0100001127 | 1 | EACH\nJOB |
10 | 10 | Taking down existing street light fitting any type and S&F Integral LED Street light luminaire of 72 W, comprising of pressure die cast housing with epoxy powder coated dark graphite grey colour finish, prismatic polycarbonate cover with individual LED lenses, LED street light luminaires with IP 65 protection and with all fixing arangement, nuts, bolts and washer connecting to electric system with 1.5 sqmm PVC aluminium stranded conductor 2 core of required length from light fitting to street light control box on pole, testing on completion complete all as specified and directed.\nMAKE: C&S Cat part No LTESS72WLED/LS 72W LED I or equivalent makes as specified in Appendix 'B'. | BI01010001010000000000000515BI0100001128 | 20 | EACH |
11 | 11 | Taking down old unserviceable street light bracket & S&F street light brackets made out of GI tubing, light grade, 32 mm bore 1200mm long, bent to shape at 120 degree, fixed on pole by providing MS clamp made up of flat iron 40 x 5 mm including bolts, nuts and washer of suitable size incuding painting the bracket & clamp with two coats of aluminium paint over a coat of primer complete all as specified and directed. | BI01010001010000000000000515BI0100001129 | 20 | EACH |
12 | 12 | Taking out old unserviceable main switch / timer switch / change over etc and supply, fixing and testing Street light automatic Nature switch of capacity 3 KW single phase complete with high and low voltage and overload protection, degree of protection confirm to IP-55 AC, SP complete with MCB and power contactor fixed on pole with 25 X 3mm MS strip clamp including provision of 10 sqmm 3 core copper cable for connection complete all as specified & directed.\nMake - Kakatiya Energy system Model SWADEEP-02 EC 3KW IP or equivalent as approved by GE. | BI01010001010000000000000515BI0100001130 | 5 | EACH |
13 | 13 | Taking out old unserviceable control box and S&F of control box for street light made of HDPE comprising of MCB 6 Amps double pole -01 No, bus bar of 63 Amps rating aluminium for phase and netural on porcelain based insulators with locking arrangement fixed to pole with MS clamp of size 20x3 mm, nuts bolts and washers complete all as specified.\nMake : Sintex/ Hensel/ SHI/BRITE | BI01010001010000000000000515BI0100001131 | 15 | EACH |
14 | 14 | Supply and fix in repair aviation obstruction LED light fitting, 3 watt, dia cast aluminium housing with red polycarbonate dome for better illumination, IP 65, 50 Hz fixing at the top of high mast light complete all as specified & directed.\nMake - Bajaj model - BGAV 302 LED or equivalent model of make C & S / HAVELLS / SURYA. | BI01010001010000000000000515BI0100001132 | 2 | EACH\n |
15 | 15 | Taking out old unserviceable garden /post top light any type and supply and fix 25 watt decorative LED post top Lantern luminaire, energy saving, designed with symmetricall light distribution, spun aluminium landscap luminaire with suitable screws/nuts complete all as specified and directed.\nMake : Havellls Cat Part No RUBYPT25WLED757PSYMTOPC or equivalent model of Crompton /Philips /Jaquar. | BI01010001010000000000000515BI0100001133 | 14 | EACH |
16 | 16 | Supply & Fix in repair LED driver suitable for 72 W LED, 240 volts. 50 Hz complete all as specified and directed. MAKE: Bajaj/Wipro/CG/Philips/Havells as approved by GE. | BI01010001010000000000000515BI0100001134 | 28 | EACH |
17 | 17 | Taking down defective 150/250/400 watt high mast consisting of SV/MH lamp type light fittings (Aprox 4 to 9 Nos in each fitting), any type, mounted on upto 16 mtr long high mast pole on brackets/round ring, disconnecting, replacement of defective components such as choke, ignitors, holders, capacitors, etc and providing suitable new PVC cable for internal wiring, including cleaning of cover, connection with supply and testing the street light fitting after fixing new components measured and paid separately in respective item of BOQ and then mounting to its original position and making the fitting functional including testing complete all as specified and directed. \nNote : \n(i) No T &P will be arranged by contractot \n(ii) Spares such as choke, ignitor, lamp holder, cable, lamps, etc shall be paid and measured separately.\n(iii) Rates also include repairing of defective street light timers, fault in street light feeders, etc \n(iv) During period of currency of CA any fitting will be not considered for more than once for payment purpose. | BI01010001010000000000000515BI0100001135 | 11 | EACH\nJOB |
18 | 18 | Supply only 400 watt HPSV/MH open construction electromagnetic ballast consisting of high quality silicon steel lamination, super enamelled copper wire, vacuum impriganated with white resin, terminal block with tapping for 220/240 volt, 50 Hz complete all as specified and directed.\nMAKE: Bajaj Cat Part No BJOS 400 SV / MH / C & S Cat part No LTAS 002 or equivalent in Bajaj/CG/Havells as approved by GE. | BI01010001010000000000000515BI0100001136 | 54 | EACH |
19 | 19 | Supply only 400 watt MH lamp SE/DE tubular suitable for integral / non integral street/flood light luminairs complete all as specified and directed. \nMAKE:BAJAJ CAT PART No 140037 or equivalent in Surya/ Bajaj/CG/Havells as approved by GE. | BI01010001010000000000000515BI0100001137 | 55 | EACH |
20 | 20 | Supply only electronic ignitors suitable for 150/250/400 watt SV/MH street light fitting 240V, 50HZ complete all as specified and directed.\nMAKE: Bajaj or equivalent in CG/Philips/Havells as approved by GE. | BI01010001010000000000000515BI0100001138 | 55 | EACH |
21 | 21 | Supply only LED driver suitable for 180/200/210 W LED, 240 volts. 50 Hz complete all as specified and directed. MAKE: Bajaj/Wipro/CG/Philips/Havells as approved by GE. | BI01010001010000000000000515BI0100001139 | 30 | EACH |
22 | 22 | Cleaning & upkeeping of sub station area, surrounding area of transformer/LT panel/Bus bar/Feeder pillar box and clearing away all grass vegetation, sapplings, shrus, bushed under growth roots and trees not exc 30 cm girth (Measured 1 mtr above the ground level) and removing of rubbish to a distance of 50 mtr out side periphary complete all as specified and directed compleate all as specified and directed. | BI01010001010000000000000515BI0100001140 | 300 | SQM |
23 | 23 | Disconnecting & taking down LT panel board & keeping aside for reuse and dismantling old rusted unserviceable legs & base of panel board & S & F new base of size 120 cm x 40 cm made out of 3.15mm thick MS sheet (CRCA) and four legs of 90 cm length (45 cm below and 45 cm above ground level grouted in PCC (1:3:6) type C-2 using 40mm graded stone aggregate) made of angle iron of size 40x40x6 mm, refixing the panel board with suitable size of nuts, bolts complete all as specified and directed. | BI01010001010000000000000515BI0100001141 | 2 | EACH\nJOB |
24 | 24 | Supply and fix in repairs PVC insulated & PVC sheathed copper conductor cable 1.5 Sqmm multi-standard 1100 volt grade three core complete all specified and directed.\nNote : One run of three core cable shall be measured as one length. | BI01010001010000000000000515BI0100001142 | 50 | RM |
25 | 25 | Supply and fix in repairs PVC insulated & PVC sheathed copper conductor cable 2.5 Sqmm multi-standard 1100 volt grade three core complete all specified and directed.\nNote : One run of three core cable shall be measured as one length. | BI01010001010000000000000515BI0100001143 | 50 | RM |
26 | 26 | Supply and fix in repairs PVC insulated & PVC sheathed copper conductor cable 6 Sqmm multi-standard 1100 volt grade five core complete all specified and directed.\nNote : One run of five core cable shall be measured as one length. | BI01010001010000000000000515BI0100001144 | 50 | RM |
27 | 27 | Material and labour for painting of feeder pillar box outside & inside with one coat of synthetic enamel gray paint including preparation of old steel surfaces complete all as specified & directed | BI01010001010000000000000515BI0100001145 | 10 | EACH\nJOB |
28 | 28 | Supply & lay rubber insulating mat of size 2 mtr x 1 mtr x 25 mm thick complete all as specified & directed | BI01010001010000000000000515BI0100001146 | 4 | EACH |
29 | 29 | M&L for earthing complete with galvanised steel earth plate electrode 60cm X 60cm X 6mm thick, burried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of plate not less than 1.5 mtr below the normal ground level connected to galvanized strip 32 X 6mm by means of bolts, nuts, check nuts and washers of galvanized iron or steel all as shown in electrical plate No 3 of SSR Part-I connected to OH conductor on pole/ Panel/ main switch board etc all as specified or indicated and testing on completion including provision galvanized strip protected by 40 mm bore GI, light grade pipe and watering pipe shall be 20 mm bore medium grade GI pipe including excavation & earth work, PCC pit with RCC cover, charcoal, salt, funnel, GI strip and protection pipe upto 7.5 mtr including taking down old one complete all as specified and directed\nNote : The unit rate shall also includes for excavation and earth work in soft/loose soil, PCC (1:3:6) type C-1 chamber, RCC 1:2:4 type B-1 cover 50mm thick reinforced with 8mm dia TMT bar @ 150mm c/c both ways, funel including wire mesh, charcol & salt. | BI01010001010000000000000515BI0100001147 | 7 | EACH\nSET |
30 | 30 | M&L for loose filling 20-40 mm graded coarse aggregate spread and levelled complete all as specified and directed. | BI01010001010000000000000515BI0100001148 | 10 | CUM |