Supply , Installation , Testing And Commissioning Of Vrv/ Vrf Air Conditioning System ( Equipment ) At Govt . Hospital , Kot Balwal , Jammu, JAMMU-Jammu And Kashmir

Public Works Department-PWD has published Supply , Installation , Testing And Commissioning Of Vrv/ Vrf Air Conditioning System ( Equipment ) At Govt . Hospital , Kot Balwal , Jammu. Submission Date for this Tender is 28-02-2020. Air Compressor Tenders in JAMMU Jammu And Kashmir. Bidders can get complete Tender details and download the document.




Tender Notice

23652639
Corrigendum : Supply , Installation , Testing And Commissioning Of Vrv/ Vrf Air Conditioning System ( Equipment ) At Govt . Hospital , Kot Balwal , Jammu
Open Tender
Indian
Jammu And Kashmir
JAMMU
28-02-2020

Tender Details

Supply , Installation , Testing And Commissioning Of Vrv/ Vrf Air Conditioning System ( Equipment ) At Govt . Hospital , Kot Balwal , Jammu

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 27-Feb-2020 EXTENSION NOTICE Date 28-02-2020

Key Value

Document Fees
INR 1000 /-
EMD
INR 150000.0 /-
Tender Value
INR 75 Lakhs /-

BOQ Items

Name of Work: Supply, Installation , testing & Commissioning of VRV/VRF Air Conditioning system ( Equipment) at Govt Hospital, Kot Balwal, Jammu.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply, installation,testing & Commissioning of Variable Refregerant volume modular type Air conditioning system suitable for heating and cooling by using invertor driven /digital scroll compressors complete with indoor and outdoor units with indidual controller and with fittings etc as per quantity given below including full charging of R410A refregerant gas complete and COP >5.5 as per specifications and directions of Engineer -in -Charge at site . Air Cooled VRV/VRF Units with Scroll Compressor with invertor technology shall be capable of modulating capacity , works on (R410A) with heating cooling both mode.The units shall be factory charged.The outdoor units shall be a factory assembled unit housed in a strudy weather proof casing constructed from rustproofed mild steel panels coated with powder coated finish.The out door units shall have multiple scroll compressors and be able to operate even in case of breakdown of one compressor.\n\nSITC of Outdoor Units-Heat Pump (R410A)\n\nODU 60hp 1 Job
2 2 ODU 36hp 1 Job
3 3 ODU 20hp 1 Job
4 4 Supply, installtion,testing & commissioning of Split Indoor Units(Nominal Capacity)\n\nHi-wall Type Unit - 1.5 TR(Minimum) 2 Nos.
5 5 Hi-wall Type Unit - 1.2 TR(Minimum) 4 Nos.
6 6 Hi-wall Type Unit - 1.0 TR(Minimum) 2 Nos.
7 7 Hi-wall Type Unit - 0.80 TR(Minimum) 3 Nos.
8 8 Supply, installtion,testing & commissioning of Round Flow Type cassette units with builtin drain pump with decorative panel(Nominal Capacity)\n\nRound Flow Cassette Type Unit - 4.0 TR 3 Nos.
9 9 Round Flow Cassette Type Unit -2.0TR 2 Nos.
10 10 Supply, installtion,testing & commissioning of Split Ducted units with builtin drain pump with decorative panel(Nominal Capacity)\n\nDuct Type Unit - 2.0TR 11 Nos.
11 11 Duct Type Unit - 4.0TR 1 Nos.
12 12 Duct Type Unit - 3.0TR 8 Nos.
13 13 Duct Type Unit - 2.5TR 7 Nos.
14 14 SITC of ceiling mounted Ductable units for OT's. complete with filteration as specified with micro V filter and HEPA filter complete suitable with outdoor units. 2 Nos.
15 15 Remote Controller \nInstallation , testing and commissioning of corded remote controller suitable for Indoor units and suitable to work on single phase 230 volt (+)(-) 10% 50 Hz AC supply. 43 Nos.
16 16 Refrigerant Joints/ Headers \nInstallation , testing and commissioning of imported Y-joints fittings and header to all indoor units at all floors including alignments of joints complete as required. 40 Nos.
17 17 Refrigerant Joints/ Headers \nSupply Installation , testing and commissioning of imported (AHU Kits)fittings and header to all indoor units at all floors including alignments of joints complete as required. 2 Nos.
18 18 Refrigerant Piping \nInterconnecting refrigerant pipe work with (19mm/13 mm thick) closed cell elastomeric nitrile rubber tubular insulation between each set of indoor & outdoor units as per specifications, all piping inside the room shall be properly supported /fixed with suitable size of clamps /M.S hanger and all exterinal /exposed to sun piping shall run in M.S.painted cable tray with cover at site. \n\n41.9 mm O.D (Insulation: 19mm) 90 Rm
19 19 38.1 mm O.D (Insulation: 19mm) 90 Rm
20 20 34.9 mm O.D. (insulation : 19 mm) 100 Rm
21 21 28.6 mm O.D. (insulation : 19 mm) 100 Rm
22 22 25.4 mm O.D (Insulation : 19mm) 70 Rm
23 23 22.2 mm O.D. (insulation : 19 mm) 130 Rm
24 24 19.1 mm O.D. (insulation : 13 mm) 300 Rm
25 25 15.9 mm O.D. (insulation : 13 mm) 500 Rm
26 26 12.7 mm O.D. (insulation :19 mm) 200 Rm
27 27 9.5 mm O.D. (insulation : 13 mm) 400 Rm
28 28 6.4 mm O.D. (insulation : 13 mm) 70 Rm
29 29 31.7 mm O.D. (insulation : 19 mm) 125 Rm
30 30 Supplying and installing following size of perforated painted\nwith powder coating M.S. cable trays with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with M.S. suspenders including bolts & nuts, painting suspenders etc as required.\n\nSize:300 mm width X 50 mm depth X 1.6 mm thickness 150 Rm
31 31 Drain Piping \nProviding and fixing rigid CPVC piping complete with fittings, supports as per specifications and duly insulated with 6 mm thick closed cell nitrile rubber insulation. \n\n25 mm dia 150 Rm
32 32 32 mm dia 200 Rm
33 33 Ducting Providing, fixing, testing and commissioning of sheet metal ducting complete with support, dampers etc\n\n0.50mm (26 Gauge) 80 Sq Mt
34 34 0.63mm (24Gauge) 40 Sq Mt
35 35 Insulation Providing, fixing & Commissioning closed cell nitrile rubber/ chemically crossed linked XLPE insulation on duct.\n\n09mm 80 Sq Mt
36 36 13mm 40 Sq Mt
37 37 Duct Acoustic Lining \nProviding & fixing of duct acoustic lining with fiber glass insulation of density 30kg/m3 covered with 26GI perforated sheet with nuts & bolts\n\n 13mm thick 40 Sq Mt
38 38 25mm thick 60 Sq Mt
39 39 Grilles Providing and fixing of duct accoustic lining as per specifications and drawings.\n\nAl Extruded Supply air Grills with damper 8 Sq Mt
40 40 Al Extruded Return air Grills with out damper 10 Sq Mt
41 41 Control & Transmission Wiring \nProviding & fixing control wiring of 2 core x 1.5 sqmm copper in PVC conduit pipe of 25mm dia including providing & fixing support @1.5mt distance C/C where it is not recessed between indoor units and their wired remote. 950 Rmt
42 42 Control & Transmission Wiring \nProviding & fixing control wiring of 3 core x 1.0 sqmm copper in PVC conduit pipe of 25mm dia including providing & fixing support @1.5mt distance C/C where it is not recessed between indoor units and their wired remote. 700 Rmt
43 43 Main Electrical Panel \nFabrication, supplying, installation testing and commissioning of following pannel CPRI approved made out of 2mm thick M.S. sheet, floor/wall mounted, vermin and dust proof, indoor type with suitable size of angle iron legs for grouting in the ground, with lockable type hinged doors, duly p0wder coated with provision for fixing of 1 no incomer MCCB, outgoing MCB's, , required number of sets of Aluminium Bus Bar, providing & fixing . strips for housing MCB's and other allied accessories etc. as required. (Make as per annexure). Main Panel = 25Cft.(APPROX) MCCB's of 100 amp and ELCB's MCCB FP 400 Amp. 36 KA Microprocessor type (main incomer) complete with spreader links. All MCCB's shall have rotary handle and ICU=ICS =100%. MCCB FP 40 Amp. 25 KA Aluminium Bus Bar suitable for 500 Amp. 4 Strips of suitable lengthCT Set of suitable rating 200/5 A 1.15 VA burden Indicating Lamp(Led Type) Selector SwitchVoltmeter (0-500) Volts Digital type Ammeter (0-500) Amps. Digital typeMCB Strip for 12 Nos. MCB's 1 Lot
44 44 Sub Main Panel \nProviding and fixing of following protection equipments and other allied accessories including connections, inter connections, with suitable size of PVC insulated copper conductor cable including earthing etc. as required.\nwith suitable rating Incomer of 125amp\nAluminium Bus Bar suitable for 300 Amp. 4 Strips of suitable length\nIndicating Lamp(Led Type)\nSelector Switch\nVoltmeter (0-500) Volts Digital type \nAmmeter (0-500) Amps. Digital type\n2 pole MCB Strip for 20 Nos. MCB's 3 Lot
45 45 EARTHING \nSupply, installation, testing & commissioning of CPRI Approved maintenance free copper earthing system with 3 mtrs. Electrode 40 mm dia with minium 2mm thick and does not require manual additional of water. The electrode shall be pre-filled with hygroscopic powder and provided with suitable breathing and leaching ports at the ends. the electrode shall be surrounded by suitable powdered form of BEE MOIST so as to provide maximum contact between the electrode and the compund. The compound should be eco-friendly and providing and laying of 2 Nos. 25 x 3 mm copper strip from copper rod upto the main panel. The earthing pit should be covered with PVC cover. 1 Lot
46 46 CABLING \n\nPower wiring in PVC conduit of 4C x 25MM sq for each ODU from main panel 150 Rmt
47 47 Power wiring in PVC conduit of 3C x 2.5MM sq for each IDU from main panel to IDU 250 Rmt
48 48 SERVO STABLIZER \nSupply, Installation, Testing and commissioning of 150kVA Automatic Servo Voltage Stabilizer oil cooled, outdoor type, suitable for operation on 3 phase 50Hz, 415V system with input voltage correction range of 160V to 460V, output 415V +/-1%, unbalanced input , unbalanced load, first filling of oil, overvoltage, undervoltage, overcurrent, short ciruit, protections and complete with by pass system. The servo shall be CPRI TESTED and certificate of test report shall be submitte to the department. 1 Lot
49 49 SITC of 150mm, 3.5 core aluminium armoured cable 150 Rmt
50 50 Operation & Maintenance of the HVAC System for 2 Years after expire of warranty period. This should include minimum of 2 No’s O&M staff of qualified and experienced persons for One shift of 8 hours Basis at site. 1 Lot