Mukhathala Bp 2019-20 -Providing Ac Unit , Pa Systemand Electrification Of Newly Renovated Concil Hall Attache To Mukhathala Block Office
Tender Value
9.60 Lakhs
Estimated cost
Bid Submission
17 Feb 2020
0 days left
EMD
24000
Bank guarantee accepted
Document Fee
2150
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
Mukhathala → Kerala
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Mukhathala Bp 2019-20 -Providing Ac Unit , Pa Systemand Electrification Of Newly Renovated Concil Hall Attache To Mukhathala Block Office
BOQ
| Work Name:Providing AC Unit PA System and Electrification of Newly renovated Council Hall attached to Mukhathala Block Office | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1 | Supply and wiring points according to IS 732-1989 using rigid PVC ivory conduit of minimum size 20 mm conforming to IS 9537 part III 1983 and with suitable size specials conforming to IS 3419-1988, fixing the conduit using metal saddles spacing not exceeding 50 cm or concealed suitably and with 1.00 sq mm PVC insulated stranded single core FR copper conductor cable 650V grade,including providing switch board main ,and continuous earthing with 1.5sqmm green coloured FR wire , required qty of copper earth socket, brass bolt and nut crimping etc complete with suitable size modular type metal switch boxes, modular type front plates (white) etc. up to and including 6 A modular typeROHS compliant SP switches and making good the surface of wall, colour washing etc. complete. All the terminations in the switch boards and DB's shall be tinned and the wires shall be drawn and fixed along the periphery of the box using suitable ties, tie mounts etc as required. | BI01010001010000000000000515BI0100001113 | ||
| 2 | 1.1 | Single control light point with 6A, 3 plate ceiling rose | BI01010001010000000000000515BI0100001114 | 3 | Nos |
| 3 | 1.2 | Single control ceiling fan point with 6 A, 3 plate ceiling rose & with socket size stepped electronic regulator. | BI01010001010000000000000515BI0100001115 | 3 | Nos |
| 4 | 1.3 | 5 Light point controlled by one switch with out ceiling rose | BI01010001010000000000000515BI0100001116 | 2 | Nos |
| 5 | 1.4 | Combined plug point with 6 A, 5 pin plug socket controlled by 6 A switch in the same switch board as that of light points. | BI01010001010000000000000515BI0100001117 | 2 | Nos |
| 6 | 1.5 | Independent plug point with 6 A, 5 pin plug socket controlled by 6 A switch in seperate switch board as that of light points. | BI01010001010000000000000515BI0100001118 | 4 | Nos |
| 7 | 2 | Supply, conveyance installation testing and commissioning of 230 V, 50 hz, 1800 Lumen, 0.8 pf, 15% THD, 2.5 KV Lighting surge protection type 18 w 1200 mm LED pre-wired light fittings complete with all accessories . directly on wall or ceiling and giving connection with required length of 16/0.20mm 3 core copper conductor flex wire etc as required. | BI01010001010000000000000515BI0100001119 | 3 | Nos |
| 8 | 3 | Supply and installation of suitable size MS rod type fan clamp as per IS 732 as required. | BI01010001010000000000000515BI0100001120 | 3 | Nos |
| 9 | 4 | Supply and providing every additional length of down rod of suitable size heavy gauge GI / WI pipe with 16/0.20mm PVC insulated and PVC sheathed 3 core round copper conductor flex wire conforming in relevant ISS or with original wiring extended including painting as required. | 3 | mts | |
| 10 | 5 | Supply, Conveyance, installation, testing and commissioning of recess mounting 24 W LED down light fittings of all types directly in the existing opening on the false - ceiling including giving connections with required length of 16/0.20 mm 3 core round copper conductor flex wire conforming to relevant ISS or with the extended original wiring etc as required | 10 | Nos | |
| 11 | 6 | Supply and fixing the following sizes of PVC conduit conforming to IS 9537/1983 Part 3 along with all required accessories | BI01010001010000000000000515BI0100001121 | ||
| 12 | 6.1 | 20mm Dia medium gauge | 160 | Mts | |
| 13 | 6.2 | 25mm dia medium gauge | 48 | Mts | |
| 14 | 6.3 | 32 mm dia medium gauge(projector) | 12 | Mts | |
| 15 | 7 | Supply and drawing 650/1100 V grade PVC insulated stranded single core copper conductor cables conforming to IS 694 part I 1990 in the existing surface / recess conduit as required including giving necessary connections of the following sizes. | |||
| 16 | 7.1 | 1.00 sq mm 2 run (speeker) | 56 | Mts | |
| 17 | 7.2 | 2.50 sq mm 3 run | 68 | Mts | |
| 18 | 7.3 | 1.50 sq mm 3 run | 44 | Mts | |
| 19 | 7.4 | 4.00 sq mm 4 run + 2.5 sq.mm 1 run | 52 | Mts | |
| 20 | 7.5 | 6.00 sqmm 4run | 16 | Mts | |
| 21 | 8 | Supply & Fixing the following types/ sizes of boxes suitable for modular accessories in surface/ recess including making good the damages, colour washing etc as required | |||
| 22 | 8.1 | 3 module metal box in recess | 4 | Nos | |
| 23 | 8.2 | 9 module metal box in recess | 2 | Nos | |
| 24 | 8.3 | 3 module white/ off-white | 4 | Nos | |
| 25 | 8.4 | 9 module white/ off-white | 2 | Nos | |
| 26 | 8.5 | 6 A SP 1 way switch | 6 | Nos | |
| 27 | 8.6 | 16 A SP 1 way switch | 4 | Nos | |
| 28 | 8.7 | 6 A Universal socket | 6 | Nos | |
| 29 | 8.8 | 6/16 A socket | 4 | Nos | |
| 30 | 9 | Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required | |||
| 31 | 9.1 | 6 way (8+18) - three phase double cover (IP 42/43) | 1 | Nos | |
| 32 | 9.2 | 6 way (8+18) - double cover TPN vertical DB with provision for fixing MCCB as incomer and SP/ TP MCB as outgoing (IP 42/43) ( Main DB) | 1 | Nos | |
| 33 | 10 | Supply and installation of the following accessories suitable for 50 Hz , AC supply conforming to IS 8828-1995/ IEC 60898 of the following current ratings in the existing enclosure and giving connections as required | |||
| 34 | 10.1 | 40 A four pole mini break isolator | 1 | Nos | |
| 35 | 10.2 | 100 A, 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL | 1 | Nos | |
| 36 | 10.3 | 40 A, 4 pole, 30 mA RCCB | 1 | Nos | |
| 37 | 10.4 | 6 A to 32 A, 10 kA, SP MCB (ccurve) | 18 | Nos | |
| 38 | 10.5 | 40 A, 10 kA, TP MCB (C curve) | 6 | Nos | |
| 39 | 11 | Supply and drawing bare earthing conductors of the following sizes along with wiring/ cables and giving connection as required. | |||
| 40 | 11.1 | 2.00 mm copper conductor (14 SWG) | 78 | Mts | |
| 41 | 11.2 | 3.15 mm copper conductor (10 SWG) | 8 | Mts | |
| 42 | 12 | supply of superior quality copper earth socket for the following sizes of earth conductor including crimping etc. as required. | |||
| 43 | 12.1 | 2.00 mm (14 SWG) | 4 | nos | |
| 44 | 12.2 | 3.15 mm (10 SWG) | 24 | nos | |
| 45 | 13 | Supply and providing the following sizes of bolt and nut with washers on the existing MS box / earth bus etc. as required including drilling necessary holes as required | |||
| 46 | 13.1 | 25 x 3 mm brass bolt & nut | 4 | Nos | |
| 47 | 13.2 | 25 x 6 mm brass bolt & nut | 16 | Nos | |
| 48 | 14 | Fabrication, supply & installation of dust and vermin proof, wall mounting, Sintex make meter box of 600x600x 214 mm size suitable for fixing KSEB meter,fuse units, CT etc, hinged door construction for the front side with compartments if necessary, providing vision panel for the meter compartment, knock out for cable entry and exit. | 1 | No | |
| 49 | 14.1 | 32 A, 415 V, DIN type fuse base. | 3 | Nos | |
| 50 | 14.2 | 63 A, 415 V, 2 way neutral link mounted on DMC/ SMC base. | 1 | No | |
| 51 | 14.3 | 20A, 230 V, DIN type fuse | 6 | Nos | |
| 52 | 15 | Supply and installation of switch gear units in sheet steel enclosure complete with handle assembly, door interlock and pad locking arrangement of 32A, 4 pole ratings on existing angle iron frame work or directly to wall using necessary bolts & nuts, fixing the unit to wall, making good the damages, colour washing etc. including giving necessary connections as required. (excluding cost of HRC fuse links in case of SDF/ SDFCO) (AC) | 1 | No | |
| 53 | 16 | Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of 3.5 core 25 sq mm sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. | 8 | Mts | |
| 54 | 17 | 4 core 10 sq mm with factory made clamp | 42 | Mts | |
| 55 | 18 | 10sq mm | 2 | nos | |
| 56 | 19 | 25 sq mm comprasion Gland | 2 | Nos | |
| 57 | 20 | 35 sq mm with 12 mm wide x 1 mm thick clip | 4 | Nos | |
| 58 | 21 | 16 sq mm | 2 | Nos | |
| 59 | 22 | 10 sq mm | 4 | Nos | |
| 60 | 23 | Preparation of all drawing submitting and approvel from KSEB, obtaining power allocation, submitting of completion certificates and arranging inspection, getting sanction and energisation certificates from KSEB and obtaining power connection etc: for commissioning of the whole installation in the permises. | 1 | No | |
| 61 | 24 | Supplying and installation including all manner of supports/ suspenders, anchor bolts etc f made out of suitable size channel sections, slotted angles, flats, MS plates etc as required including painting with 2 coats of synthetic enamel paint over a coat of zinc chromate primer, making good the damages, colour washing etc as required. | 68 | Kg | |
| 62 | 25 | Supplu, Conveyance, testing and commissioning of 5.5 TR capacity ceiling suspended ductable type airconditioner with DX coil copper condenser complete with suitable capacity driven motor, air cooled condenser with all accessories, hermetically sealed scroll compressor electronic microprocessor pendant controller with digital display, first charge R 22 refrigerant gas, vibration isolator pads, ODU MS stand and saftey devices like thermal protector, pressure relief valve, over load relays single phase preventer, high-low pressure cut out, suitable for three phase 440 V supply.. | 1 | No | |
| 63 | 26 | Supply and installation of hard drawn 19 G copper piping including 9 mm thick nitrile rubber insulation | |||
| 64 | 26.1 | Suction Line 1/3/8 | 14 | Mts | |
| 65 | 26.2 | Liquid Line 7/8 | 14 | Mts | |
| 66 | 27 | Supply, installation, testing and commissioning of GSS ducting with angle , flanges and supports | |||
| 67 | 27.1 | 24 G ducts | 68 | m2 | |
| 68 | 27.2 | 22 G ducts | 12 | m2 | |
| 69 | 28 | Supply and installation of 9 mm thick Nitrile rebber insulation on ducts | 60 | m2 | |
| 70 | 29 | supply and insallation of 24 G density 12 mm thic glass wool rigid covered with 26 G aliminium perforated sheet along with Rp tissue | 11 | m2 | |
| 71 | 30 | Supply and providing aluminium returen air grill with adequate deflection. | 2.2 | m2 | |
| 72 | 31 | Supply and providing outdoor condensing unit frame made out of angle frame without catwalk. | 1 | No | |
| 73 | 32 | Supply and providing fresh air cowl | 1 | No | |
| 74 | 33 | Supply and providing Canvas connection in between indoor and duct | 1 | No | |
| 75 | 34 | Supply, installation, testing of leak with Dry N2, Vacumissing, gas charging with R22 gas and commissiong | 1 | No | |
| 76 | 35 | Central Distribution amplifier. | 1 | No | |
| 77 | 35.1 | Supply of central distribution amplifier of the following size | |||
| 78 | 35.2 | a) Digital recorder | |||
| 79 | 35.3 | b) Play bak prerecorder massages | |||
| 80 | 35.4 | c) 3 mic. Input and one aux input | |||
| 81 | 35.5 | d) Send/ return facility | |||
| 82 | 35.6 | e) Head phone out put provided | |||
| 83 | 35.7 | f) Automatic mic. Off switch provided | |||
| 84 | 36 | Chairman Control Unit | 1 | No | |
| 85 | 36.1 | a) Highly sensitive condenser microphone | |||
| 86 | 36.2 | b) 47 cm. goosneck + expansition | |||
| 87 | 36.3 | c) Ring led | |||
| 88 | 36.4 | d) Built - in speaker and volume control | |||
| 89 | 36.5 | e) Head phone out put provided | |||
| 90 | 36.6 | f) Priority mute delegate | |||
| 91 | 36.7 | g) Chime tone attention | |||
| 92 | 36.8 | h) Priority and talk switch | |||
| 93 | 37 | Delegate Unit | 25 | Nos | |
| 94 | 37.1 | a) Highly sensitive condenser microphone | |||
| 95 | 37.2 | b) 47 cm. goosneck + expansition | |||
| 96 | 37.3 | c) Ring led | |||
| 97 | 37.4 | d) Built - in speaker and volume control | |||
| 98 | 37.5 | e) Head phone out put provided | |||
| 99 | 37.6 | f) Indicate the out put signal level | |||
| 100 | 37.7 | g) Talk switch | |||
| 101 | 38 | Power boosting unit | 1 | No | |
| 102 | 39 | Confrence cable through conduit | 104 | Mts | |
| 103 | 40 | Extra speaker system for sound boosting | |||
| 104 | 40.1 | a) Amplifier 160 w | 1 | No | |
| 105 | 40.2 | b) 2way 30W Speaker | 3 | Nos | |
| 106 | 40.3 | c) Wireless microphone duit UHF | 1 | No | |
| 107 | 41 | Speaker Cabling through conduit | 65 | Mts | |
| 108 | 42 | Chagres for Conveyance, installation, testing and commissioning of whole unit | 1 | Job |
AI Tender Summary
Tender Timeline
Feb 10, 2020
11:30 IST
Tender Published
Tender notice published.
CompletedFeb 17, 2020
17:00 IST
Bid Submission Deadline
Online submission via eProcurement portal.
CompletedFeb 20, 2020
Bid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓
Disclaimer
We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender