Augmentation Of Inner Break Water Jetty At Naval Dockyard Mumbai ( Mainly Electrical And Mechanical Portion ), MUMBAI-Maharashtra

Military Engineer Services-MES has published Augmentation Of Inner Break Water Jetty At Naval Dockyard Mumbai ( Mainly Electrical And Mechanical Portion ). Submission Date for this Tender is 07-08-2020. Jetty Tenders in MUMBAI Maharashtra. Bidders can get complete Tender details and download the document.




Tender Notice

23540745
Corrigendum : Augmentation Of Inner Break Water Jetty At Naval Dockyard Mumbai ( Mainly Electrical And Mechanical Portion )
Open Tender
Indian
Maharashtra
MUMBAI
07-08-2020

Tender Details

Augmentation Of Inner Break Water Jetty At Naval Dockyard Mumbai ( Mainly Electrical And Mechanical Portion )

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 26-Feb-2020 Amendment to critical dates - 26 Feb 2020 Date 17-03-2020
2 06-Mar-2020 Amendment to critical dates - 06 Mar Date 24-03-2020
3 13-Mar-2020 Amendment to critical dates - 13 Mar 2020 Date 31-03-2020
4 24-Mar-2020 Amendment to critical dates - 24 Mar 20 Date 15-04-2020
5 22-Apr-2020 Amendment to critical dates - 22 Apr 2020 Date 11-05-2020
6 11-May-2020 Amendment to critical dates - 11 May 2020 Date 09-06-2020
7 05-Jun-2020 Amendment to critical dates - 05 Jun 2020 Date 09-07-2020
8 08-Jul-2020 Amendment to critical dates - 07 Jul 2020 Date 07-08-2020

Key Value

Document Fees
INR 3000 /-
EMD
INR 1500000.0 /-
Tender Value
INR 34 Crore /-

BOQ Items

Nature of Work: AUGMENTATION OF INNER BREAK WATER JETTY AT NAVAL DOCKYARD MUMBAI (MAINLY E/M PORTION)
Sl. No. Item Description Item Code / Make Quantity Units
1 1 SCHEDULE 'A' PART-I (BUILDINGS/STRUCTURES)
2 1.01 Construction of TY TRANSFORMER SHED AND TOILET BLOCK complete all as shown on drawings and as specified.\nNOTE :-\nExcavated materials shall be removed from the site simultaneously & continuously while doing excavation work as space is not available for storing the excavated earth at site. Excavated materials shall be removed and deposited out side MD land at the tenderers cost. Unit rate quoted shall be deemed to be included for this work also.\n IBW_A1$C$14 1 Each\nJob
3 1.02 Total amount of Schedule 'A' Part I C/o to General Summary on Ser Page No.
4 2 SCHEDULE 'A' PART-II-B (EXCAVATION AND EARTHWORK FOR ITEMS UNDER SCHEDULE 'A' PART III TO PART X)
5 2.01 Removing excavated material (soil) to a place outside defence land including loading, unloading, transportation , levelling and any other charges complete all as specified. IBW_A1$C$17 204.61 Cubic Metre
6 2.02 Removing demolished building materials etc. (other than soil considered above and items under Schedule of Credit) to place outside defence land including loading, unloading, transportation , levelling and any other charges complete all as specified.\nNOTE :- Demolished concrete of 0.45 Cum shall be considered as one load. IBW_A1$C$18 157 Per\nLoad
7 2.03 Total amount of Schedule 'A' Part II-B C/o to General Summary on Ser Page No.
8 3 ABC
9 4 Schedule 'A' Part IV-B (INTERNAL ELECTRIFICATION)
10 4.01 Supply and fixing LED Industrial type light fitting 2 x 24 Watt, 4' aluminium, extruded channel, powder coated with diffuser for glare free light complete with all accessories connected with 3 core flexible copper cable PVC insulated of size 1.5 Sqmm suspended from ceiling with 2 nos of 19mm dia 16 gauge stove enameled steel conduit of required length (minimum 1.00 Mtr) with ball and socked at end for self aligning complete all as specified and as directed. IBW_A1$C$22 9 Each
11 4.02 Supply and fixing LED linear 2' surface/wall mounted 1 x 10 watt mirror light fitting aluminium extruded channel, powder coated with diffuser for glare free light complete with all accessories connected with 3 core flexible copper cable PVC insulated of size 1.5 Sqmm complete all as specified and as directed. IBW_A1$C$23 2 Each
12 4.03 Supply and fixing industrial type exhaust fan 240 volts, 50Hz, AC, 300mm sweep, 900 RPM single phase with louvers and shutters mounting MS rag and bolts etc. and provision with PVC insulated and PVC sheathed 3 core 1.5 sqmm flexible copper conductor cable FRLSH of suitable length from ceiling rose complete all as specifIed and as directed. IBW_A1$C$24 2 Each
13 4.04 Total amount of Schedule 'A' Part IV-B C/o to General Summary on Ser Page No.
14 5 Schedule 'A' Part V-B (EXTERNAL WATER SUPPLY)
15 5.01 Material and labour for ductile iron flanged pipe including specials, Class "K-7", of size 150 mm dia conforming to IS : 8329 including bend, tee, socket, elbow, reducers etc. including jointing and jointing materials complete all as specified and as directed. IBW_A1$C$27 240 Running Metre
16 5.02 Material and labour for ductile iron flanged pipe including specials, Class "K-7", of size 100 mm dia conforming to IS : 8329 including bend, tee, socket, elbow, reducers etc. including jointing and jointing materials complete all as specified and as directed. IBW_A1$C$28 30 Running Metre
17 5.03 Material and labour for making holes of 300 mm dia on RCC/stone floor/wall surface not exceeding 120 cm thick surface with boring machine for passing DI/CI/GI tubing complete all as specified and as directed. IBW_A1$C$29 4 Each
18 5.04 Total amount of Schedule 'A' Part V-B C/o to General Summary on Ser Page No.
19 6 SCHEDULE 'A' PART VI-B (EXTERNAL ELECTRIFICATION)
20 6.01 Disconnecting of HT panel and Bus Coupler (6.6/11 KV VCB) consisting of following and handing over to users complete all as specified and as directed:-\n(a) VCB 630A -02 Nos (Incoming)\n(b) VCB 630 Amps -04 Nos (Outgoing)\n(c) Bus coupler-1 No IBW_A1$C$32 1 Each Job
21 6.02 Supply, installation, testing and commissioning HT dual voltage 11/6.6 KV indoor type VCB panel board, consisting of 02 incomer, 07 Outgoing and 01 bus coupler, made out of 2.0 mm thick CRCA sheet, dust and vermin proof, locking arrangement, duly powder coated totally enclosed free standing floor mounting type, compartment based with truck mounted VCB spring operated electrically and manually charged operating mechanism suitable for horizontal isolation, horizontal draw out type VCB with copper busbars, back entry type complete VCB panel confirming to IS and IP 54 class of protection comprising necessary busbar extensions for connecting with existing HT switch gears and following protective and control devices including breakers complete all as specified and as directed :- IBW_A1$C$33 1 Each Set
22 6.0201 (a) Vacuum circuit breaker, 630 A rated current, 26.3 KA rated short time current for 3 sec, dual voltage (11/6.6 KV) three phase, AC, 50 Hz, quantity - 10 Nos. (02 incomer, 07 outgoing, 01 bus coupler)\n(b) Digital Voltmeter 0-15 KV with selector switch - 09 Nos (for 02 incomer and 07 outgoing)\n(c) Digital Ammeter 0-100A CT operated with selector switch - 09 Nos (for 02 incomer and 07 outgoing)\n(d) Flush mounting trivector energy meter with TOD, load survey data, 3 MDI and optical port class 1, trip and alarm -09 Nos (02 incomer and 07 outgoing)\n(e) Resin cast potential transformer with ratio 6.6/ 11KV/v3/ 110v/v3, 100VA accuracy class 1.0 with HT fuses and MCB SP protected on secondary side, mounted on withdrawal rack -02 Nos. (only for incomer) \n(f) Resin cast current transformer with ratio 150-75/ 5/5/1 and following characteristics: core 1-15VA class 1.0, core 2-15VA class 5 P 10, core 3 class PS, burden depending on knee voltage as per IS -2705 part IV-set of three -09 Sets (for all VCB panels except bus couplers). IBW_A1$C$34
23 6.0202 (g) Self powered microprocessor based numeric relay comprising of 3 O/C, 1 E/F protection relay with high set low set for phase and earth fault memory, universal auxiliary supply-09 Nos. (for all VCB panels except bus coupler).\n(h) Master trip relay -09 Nos (for all VCB panels except bus coupler). \n(j) Trip circuit supervision relay (VAX) - 09 Nos (for all VCB panels except bus coupler).\n(k) PT fuse failure relay (MVAPM-32) -02 Nos (only for incomer).\n(l) Anti pumping relay (VAA11) -10 Nos (for each VCB panels)\n(m) Air insulated rear end bottom entry cable box suitable for termination HT cable - 10 Nos (for each VCB panel)\n(n) Manual closing/tripping of CB with compartment door closed -10 Nos (for each VCB panel)\n(o) Trip and closing coil - 09 Nos (for all VCB panels except bus couplers).\n(p) Sufficient Nos of push button and standard colour coding of indication lamp LED type with back up fuses (for all VCB).\n IBW_A1$C$35
24 6.0203 (q) Motor operated spring charge stored energy trip for closing and opening of breaker (for all VCB panels except bus couplers). \n(r) Manual charging/operating arrangement. (for all VCB panels except bus couplers).\n(s) RS 485 port for communication. (for all VCB panels except bus couplers).\n(t) One No of space heater with thermostat. (for all VCB panels except bus couplers).\n(u) One No of inside lamp with switch. (for all VCB panels except bus couplers).\n(v) One No plug point with switch (5A, 230v). (for all VCB panels except bus couplers).\n(w) Copper busbar common for outgoing and bus coupler with PVC sleeve.\n(x) Foundation, PCC and any other civil work as per manufacturer instructions.\n(y) Control wiring with multi stranded copper conductor PVC insulated of suitable size and core as per manufacturer instructions all as required at site.\n(z) Transformer fault alarm/Trip Aux. relay-07 Nos (for outgoing VCB panels)\n(aa) Indication lamps for Transformer alarm and trip -07 Nos (for outgoing VCB panels) IBW_A1$C$36
25 6.0204 (ab) Transformer differential relay protection as per relevant standards - 07 Nos (for outgoing VCB panels)\n(ac) AC Power pack to operate entire control system and having sufficient power backup made up of battery bank with Maintenance free rechargeable dry type, (SMF) batteries with charger as per recommendation of manufacturer to operate spring charging motor at least 5 time in absence of main electric supply. \n(ad) The VCB/ Bus couplers shall be provided with all standard metering/accessories and compatible to SCADA/ PLC system.\nNOTES :-\n(i) The VCB shall be tested for High voltage test, primary injection test and secondary injection test individually at site after erection before commissioning and the cost for the same is deemed to be included in the quoted rate. \n(ii) Contractor shall submit type test certificate to the GE for approval before placing the order. \n(iii) Necessary internal wiring/connections shall be made accordingly without any extra cost. IBW_A1$C$37
26 6.0205 (iv) Necessary marking on VCBs for feeders, incomer, outgoing, bus coupler and CTs connected, percentage CT calibrated etc. shall be provided without any extra cost. \n(v) Necessary bus adaptor compartment for bus coupling shall be provided without any extra cost.\n(vi) The VCB Horizontal draw out shall be as per IS/IEC-62271-100.\n(vii) Type test of HT panel shall be conforming to IS/IEC-6227 1-200 \n(viii) Any other item required to complete the above job but not specified here shall be deemed to be included in the rate quoted by the contractor.\n(ix) Pre dispatch inspection shall be carried out by the authorised representative of Accepting Officer. In case of any deviation from approved drawing, the same shall be rejected and fresh panel shall be fabricated by the manufacturer. Testing shall be done at manufacturer's premises and all routine test like IR and continuity tests shall be performed/recorded in presence of authorised representative of Accepting Officer. IBW_A1$C$38
27 6.03 Supply, installation, testing and commissioning 6.6 KV/ 11 KV, 630Amps, Right extensible, Outdoor, 4 way RMU panel with two Isolators & 2 VCB, SF6 insulated, 11 KV Ring Main unit contained within Stainless steel tank suitable for outdoor use free standing complete all as specified and as directed and comprising of following :- \n(a) 630 Amp triple pole, manually operated vacuum circuit breaker encapsulated in SF6 Stainless steel tank with independent spring mechanism and fully rated earth switch with provision for earth of the cable - 2 Nos.\n(b) Air insulated cable boxes with split gland plate suitable for front side bottom entry 3 core cable up to 300 Sq mm -2 Nos.\n(c) 630 Amp triple pole, single break, 3-postion ('ON', 'OFF 'and "EARTH') ring main switches, each with independent manual charged spring mechanism and fully rated earth switch, with provision for earth and test of the cable - 2 Nos.\n(d) Air insulated cable boxes and glands suitable for front and bottom cable entry 3-core up to 300 Sq mm - 2 Nos. IBW_A1$C$39 1 Each
28 6.0301 NOTES :-\n(1) The Ring Main Unit shall comprise of the following accessories :-\n(i) 1 Mimic diagram on front panel complete with status indicators.\n(ii) Positive standard mechanical interlocks - 01 No \n(iii) Current transformers for metering and protective relays with suitable ratio class - 2 Set\n(iv) Self Powered Numerical relay with 3 o/c and 1 E/F.(self power release) -2 Nos. \n(v) Master trip relay with auxiliary relays for transformer fault indication - 2 Nos.\n(vi) Trip circuit supervision relay auxiliary relays for transformer fault indication - 2 Nos.\n(vii) 1 No. Power pack equipment with backup of 15 minutes for operation for relays.\n(viii) 4 Set of Neon indicator lamps for cable live indicator\n(ix) 2 Nos. PT's, 6.6 / 11 KV/ v3 with voltmeter & selector switch.\n(x) 1 No. digital Ammeter 100 A with selector switches.\n(xi) 1 No. digital Voltmeter with selector switch.\n(xii) 1 No. External stud for earthing connections.\n(xiii) 2 Nos. SF6 gas pressure indicator. IBW_A1$C$40
29 6.0302 (xiv) 4 Nos. local ' PULL TO TRIP' mechanism.\n(xv) 1 No. operating handles.\n(xvi) 1 Set Copper bus bars common for outgoing feeders\n(xvii) Manual charging for operation arrangement.\n(xviii) Fuses for metering and protection system.\n(xix) Front bottom entry of HT cables.\n(xx) All standard metering/accessories and compatible to SCADA/ PLC System.\n(2) Paint finish -All steel work shall be fmished painted in Dark grey shaded 632 as per IS.\n(3) RMU Panel should have following general characteristics :-\n(i) Enclosure degree of protection -IP54\n(ii) Type of Ventilation -Natural\n(iii) Rated Enclosure -K10\n(iv) Rated power frequency withstand -28/38 KV\nVoltage KV RMS/min\n(v) Rated lighting impulse withstand -75/95 KV Voltage KV, 1.2/ 50 micro sec\n(vi) Short time current rating KA, for sec -20kA/3sec\n(vii) Rated short ckt making current -50kA\n(viii) Reference standard -IEC 62271-202\n IBW_A1$C$41
30 6.0303 (4) Necessary drawing shall be got approved before placing order and PDl including testing shall be carried out by the representative of Accepting Officer. \n(5) The cost of PCC platform for mounting RMU Panel as per manufacturer's instruction shall be deemed to be included in the quoted rates IBW_A1$C$42
31 6.04 Disconnecting and removal of power transformer of 6.6/11 KV , 433 V, 3 Phase and Neutral AC 50Hz of 500 KVA capacity and handing over to user all as specified and as directed. IBW_A1$C$43 2 Each
32 6.05 Disconnecting and removal of power transformer of 6.6/11 KV , 433 V, 3 Phase and Neutral AC 50Hz of 750 KVA capacity and handing over to user all as specified and as directed. IBW_A1$C$44 1 Each
33 6.06 Disconnecting and removal of power transformer of 6.6/11 KV , 433 V, 3 Phase and Neutral AC 50Hz of 1000 KVA capacity and handing over to user all as specified and as directed. IBW_A1$C$45 1 Each
34 6.07 Designing, Supplying, handling, assembling, installation, testing and commissioning in correct assigned position, effecting proper connection Distribution Transformer step down, outdoor type SCADA compatible of capacity 1.60 MVA, dual ratio 11 KV-6.6 KV/0.440 KV , 3 phase, 50 cycles AC, Ester oil filled type with On Load Tap Changing arrangements with remote control panel operation (RTCC) on 11/6.6 KV/ sides to vary secondary voltage from (+)5% to (-) 15% in steps of 1.25% (16 steps), impedance not less than 6.50% at normal / common tap No.7 including suitable marshalling box and primary side terminals 3 Nos, outdoor bare bushings with arching horn and secondary side terminal extended copper bus bar with cable box on secondary side additional Neutral with one No. solid porcelain type out door bushings with sockets on the transformer lid for earthing purpose complete in all respects with standard accessories and fittings conforming to IS-1180, primary side delta and secondary side star connected, neutral grounded losses of the transformer as per IS :1180 Level-2 complete all as specified and as directed and having following features :- IBW_A1$C$46 4 Each
35 6.0701 (a) Transformer shall be Dyn -11 vector group ester oil immersed, naturally cooled, double wound copper winding core type, Radiator cooled MS tank complete with first fill of ester oil as per relevant IS with ONAN cooling system. The temperature of oil shall not rise 50oC to ambient temperature, of winding shall not rise 60oC. Transformer shall be painted with two coats of epoxy paint as per IS 632.\n(A) Standard Fittings :\n(i) Rating and diagram plate alongwith levels where ever necessary, non detachable\n(ii) Earthing terminals with lugs -2 Nos.\n(iii) Lifting lugs for main tank & top cover\n(iv) Thermometer pocket with cap along with thermometer.\n(v) Air release hole with plug.\n(vi) Oil conservator tank with oil filling hole, drain plugs Prismatic oil level and maximum oil level marking.\n(vii) Dehydrating breather charged with silica gel - 01 No. IBW_A1$C$47
36 6.0702 (viii) LV Bushing - 04 Nos.\n(ix) Sampling valves, top and bottom.\n(x) HV Bushing-03 Nos.\n(xi) Arching Horn on HT side - 03 Nos.\n(xii) Additional neutral separately brought out side, LV cable end box with bush insulator for neutral earthing.\n(xiii) First oil fill.\n(xiv) Drain cum bottom filter valve with plug.\n(xv) Top filter valve with plug.\n(xvi) Explosion vent with diaphragm and equalizer pipe\n(Pressure release valve).\n(xvii) Jacking lugs and hauling holes.\n(xviii) Inspection cover.\n(xix) Detachable radiators with shut off valves between radiators and tank.\n(xx) Radiator with air release hole and plug. Oil drain hole with plug and lifting eye all as per manufacturer's standards. IBW_A1$C$48
37 6.0703 (xxi) Base channel 100x50 mm, 460 mm long with hole to make them suitable for fixing on Platform or plinth.\n(xxii) 150mm dia oil temperature indicator stems type.\n(xxiii) Double float Bucholtz relay with two sets of contacts and isolating valves.\n(xxiv) 150mm dia winding temperature indicator with maximum indicating pointer and resetting device.\n(xxv) 100mm dia magnetic oil level gauge with low level alarm.\n(xxvi) Terminal connection on the HV bushing\n(xxvii) Unidirectional reversible roller -04 Nos (width distance should be as per Broad Gauge rails).\n(xxviii) Marshalling box.\n(xxix) Neutral Grounding Resister suitable for 1.60 MVA transformer in out door floor mounted enclosure suitable for 45 Degree centigrade ambient temperature and temperature rise 90 Degree centigrade all as approved by GE.\n(xxx) Indoor type Remote Tap Changer Centre Panel (RTCC) with Automatic Voltage regulator and necessary indications IBW_A1$C$49
38 6.0704 (B) On Load Tap Changer(OLTC), out door design weather proof, oil immersed, high speed, non inductive transition type employing, snap switches combining both selector and diverter duties housed in a self contained single compartment and mounting externally on transformer at suitable place. On load tap changer shall have following components :-\n(i) High torque electric motor suitable for 450V 3 phase 50 cycles AC supply including connected cabling.\n(ii) Motor drive and energy accumulator.\n(iii) Motor isolating device with over load protection.\n(iv) Raise, lower control for local operation.\n(v) Local / remote control selector switch.\n(vi) Raise / low limit switch.\n(vii) Retainer switch.\n(viii) Stepping Relay.\n(ix) Anti-condensation heater with switch.\n(x) Inter locking between manual and electric operation with and including handle for manual operation and Auxiliary Transformer\n(xi) Main isolating switch with set of fuses. IBW_A1$C$50
39 6.0705 (xii) Insulated terminal board (with connector) for transformer tap leads.\n(xiii) Mechanical tap position indicator with handle.\n(xiv) Tap changing operation counter.\n(xv) Rating plate.\n(xvi) Driving mechanism chamber locking arrangement.\n(xvii) Un-drilled gland plate for cable entry.\n(xviii) Terminal strips.\n(xix) Drain cum filter valves.\n(xx) Stoppers to prevent over travelling of mechanism.\n(xxi) Indoor floor mounted remote control cubicals (RTCC Panel, AVR relay) with rear accessories with wiring and followings :-\n(a) Remote tap position indicating meter digital type.\n(b) Tap change in progress signal lamps with belt\n(c) Raise / lower push buttons for remote operation\n(d) Inside illuminating lamp with door switch.\n(e) Supply on signals. IBW_A1$C$51
40 6.0706 NOTES :- \n(a) Single limb IMPULSE TEST AND HEAT RUN TEST shall be carried out at Manufacturers factory or approved laboratory and the rate for the same shall be deemed to be included in the quoted rate. \n(b) Transformer shall be inspected by inspecting officers nominated by Accepting Officer at manufacturers factory and all routine test pertaining to IS: 1180 shall be carried out.\n(c) Site testing: Insulation resistance, oil temperature alann trip, Winding temperature alarm and trip, Bucholtz relay alarm and trip, Low oil level alarm, testing of annunciation systems by auxiliary relay triping of transformer, Polarity marking and phase sequence, Ratio test, vector group, magnetizing current, dielectric strength and filtration if required shall be carried out.\n(d) Cost of armoured control copper cables of required length and core for OTI, WTI, deferential relay and Bucholtz relay etc. from Power Transformer to 11-6.6 KV C&R Control Panel and RTCC Panel shall be deemed to be included in the quoted rate. IBW_A1$C$52
41 6.0707 (e) Foundation and civil works as per manufacture's recommendation shall be provided at 'NO' extra cost to the dept. \n(f) Earthing shall be measured and paid separately.\n(g) The stud for neutrals shall be sufficiently long to fix 2 Nos strip earthing.\n(h) Routine test as per IS 1180 shall be conducted and test certificate shall be furnished.\n(j) The quoted price shall be deemed to be inclusive of connecting of trip contacts of bucholtz relay and temperature indicator of windings of oil to the trip coil in panel board.\n(k) Cost of initial oil filling with ester Oil having di electric strength not less than 70KV at 2.5mm gap shall be deemed to be included in the quoted rate.\n(l) All material and labour required for provision of differential Protection of transformer including wiring and testing at site shall be provided by the contractor without any extra cost. IBW_A1$C$53
42 6.0708 (m) RTCC and AV shall be suitable for automatic voltage regulation with master follower scheme with tap position indicator as per tap indication in the OLTC mechanism. RTCC shall also be provided with contol gear in respect of fan ON/OFF indication, auto and manual control switch AC supply on and tap changer in progress Indication lamp tap struck indication and alarm.\n(n) The erection of the transformer shall be done under the Supervision of manufacturer's authorized representative. Certificate in this regard shall be submitted by the contractor duly signed by authorized representative of manufacturer and Engineer-in-Charge/ GE. IBW_A1$C$54
43 6.08 Disconnecting the LT Panel from the incoming and out going cables and removal consisting of following comprising Items from the Sub station (IBW Jetty) complete all as specified and as directed :-\n(a) ACB 4P 1600A 50KA -1 No (Incoming)\n(b) ACB (B/C) 1600A -1 No\n(c) ACB 800A 4 Pole 50 KA - 4 Nos (Out going)\nNote : The complete dismantled items shall be handed over to user. IBW_A1$C$55 1 Each
44 6.09 Disconnecting and removing existing serviceable ACBs/MCCBs of various capacities from the existing LT panel board and handing over to user for reuse all as specified and as directed\n(a) ACB 4 Pole, 800A, 50KA - 03 Nos (Incomer - 01 No & Outgoing -2 Nos) \n(b) MCCB 4 Pole, 400 A, 50KA - 02 Nos (Outgoing)\nNote : The complete dismantled items shall be handed over to user. IBW_A1$C$56 1 Each
45 6.1 Disconnecting the LT Panel from the incoming and out going cables and removal consisting of following comprising Items from the Sub station( IBW Jetty)\n(a) ACB 4 P 800 A 50 KA -2 Nos (Incoming)\n(b) Bus coupler ACB 800 A, 50 KA -1 No\n(c) MCCB 4 Pole 400 A 50 KA -7 Nos (outgoing)\nNote : The complete dismantled items shall be handed over to user. IBW_A1$C$57 1 Each
46 6.11 Disconnecting and removing existing serviceable ACBs/MCCBs of various capacities from the existing LT panel board and handing over to user for reuse all as specified and as directed.\n(a) ACB 4 P 800 A 50 KA -3 Nos (Incoming & B/C)\n(b) MCCB 4 Pole 400 A, 50 KA -7 Nos (outgoing)\nNote : The complete dismantled items shall be handed over to user. IBW_A1$C$58 1 Each
47 6.12 Disconnecting the LT Panel from the incoming and out going cables and removal consisting of following comprising items from the Sub station (IBW Jetty)\n(a) ACB 4 P, 800 A, 50 KA -1 Nos (Incoming)\n(b) ACB 800 A, 50 KA -2 Nos \n(c) MCCB 4 P, 400 A, 50 KA -2 Nos \nNote : The complete dismantled items shall be handed over to user. IBW_A1$C$59 1 Each
48 6.13 Disconnecting and removing existing serviceable ACBs/MCCBs of various capacities from the existing LT panel board and handing over to user for reuse all as specified and as directed\n(a) ACB 4 P, 800 A, 50 KA - 03 Nos (Incomer - 01 No & Outgoing -2 Nos) \n(b) MCCB 4 Pole, 400 A, 50 KA - 02 Nos (Outgoing)\nNote : The complete dismantled items shall be handed over to user. IBW_A1$C$60 1 Each
49 6.14 Material and Labour for Design, Supply, Fabrication, Installation, Testing and Commissioning factory made, LT panel board, Indoor type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, made out of 2 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 with pre-treatment and powder coated of approved color including suitable frame work/ support made out of suitable size of angle iron/ flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sqmm ), required civil works/anchoring bolts for flxing, PCC foundation etc. complete all as specified and as directed with and including following :-\nBUSBAR CHAMBER : Electrically grade copper shrouded busbar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators and provision of extension. IBW_A1$C$61 1 Each
50 6.1401 INCOMER\n(a) Microprocessor based ACB, 2500 Amps, 4 pole, drawout type (EOD), breaking capacity Icu = Ics = Icw (I sec), 65 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories. -04 Nos \n (a) Ammeter 0 to 2500 Amps digital type with built in selector switch, CTs of suitable ratio(set of three) - 04 Nos\n(b) Voltmeter 0 to 500 volts digital type with built in selector switch - 04 Nos\n(c) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete - 04 Nos\n(d) Phase Indication lamps (RYB), LED type - 04 Nos (set of three).\n(e) MCB SP 2 Amps,"C" series for control protection RYB phases (set of 3 ) - 04 sets IBW_A1$C$62
51 6.1402 OUTGOING\n(i) Microprocessor based ACB, 1600 Amps, 4 pole, drawout type (EOD), breaking capacity Icu = Ics = lcw (1 sec), 65 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories. - 05 Nos\n(ii) Microprocessor based ACB, 1000 Amps, 4 pole, drawout type (EOD), breaking capacity Icu =Ics =Icw (1 sec), 65 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories - 06 Nos\n(iii) Microprocessor based ACB, 800 Amps, 4 pole, drawout type (EOD), breaking capacity Icu =Ics = Icw (1 sec), 65 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories -01 No\n IBW_A1$C$63
52 6.1403 (iv) Microprocessor based ACB, 630 Amps, 4 pole, drawout type (EOD), breaking capacity Icu = Ics = Icw (1 sec), 65 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories -09 Nos\n IBW_A1$C$64
53 6.15 Material and Labour for Design, Supply, Fabrication, Installation, Testing and Commissioning factory made, LT panel board, outdoor type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, made out of 3 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 with pre-treatment and powder coated of approved color including suitable frame work/ support made out of suitable size of angle iron/ flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm ), required civil works/anchoring bolts for flxing, PCC foundation etc. complete all as specified and as directed with and including following :-\nBUSBAR CHAMBER : Electrically grade copper shrouded busbar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, ftxed on DMC insulators and provision of extension. IBW_A1$C$65 1 Each
54 6.1501 INCOMER\n(a) Microprocessor based ACB 630 Amps, 4 pole, drawout type (EOD), breaking capacity Icu = Ics = Icw (1 sec), 65 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection , with lSI marked complete with all accessories -01 No\n(a) Ammeter 0 to 1000 Amps digital type with built in selector switch, CTs of suitable ratio(set of three) = 01 No\n(b) Voltmeter 0 to 500 volts digital type with built in selector switch - 01 No.\n(c) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOO temper detection and lodging power on/ off events, instantaneous parameter of rating 5 Amps, with display in absence of power complete - 01 No.\n IBW_A1$C$66
55 6.1502 (d) Phase Indication lamps (RYB), LED type - 01 No (set of three).\n(e) MCB SP 2 Amps,"C" series for control protection RYB phases (set of 3) - 01 set.\n OUTGOING\n(i) MCCB 320 Amps, 4 pole, 50 Hz, 35 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload, (ready, overload, pre alarm & Overload), in built instantaneous protection, Ics =100%=Icu (1 sec) complete all as specified and directed. - 02 Nos IBW_A1$C$67
56 6.1503 (ii) MCCB 200 Amps, 4 pole, 50 Hz, 35 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload, (ready, overload, pre alarm & Overload), in built instantaneous protection, Ics =100%= Icu(1 sec) complete all as specified and directed -02 Nos\n IBW_A1$C$68
57 6.16 Material and Labour for Design, Supply, Fabrication, Installation, Testing and Commissioning factory made, LT panel board, Outdoor type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, made out of 3 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 of 1962 with pre-treatment and powder coated of approved color including suitable frame work/ support made out of suitable size of angle iron/ flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm ), required civil works/anchoring bolts for flxing, PCC foundation etc. complete all as specified and as directed with and including following :-\nBUSBAR CHAMBER : Electrically grade copper shrouded busbar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators and provision of extension. IBW_A1$C$69 1 Each
58 6.1601 INCOMER\n(a) Microprocessor based ACB, 2000 Amps, 415 V, 4 pole, drawout type (EOD), breaking capacity Icu = Ics = Icw (1 sec), 65 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories -01 No\n(a) Ammeter 0 to 2000 Amps digital type with built in selector switch, CTs of suitable ratio(set of three) - 01 No\n(b) Voltmeter 0 to 500 volts digital type with built in selector switch - 01 No.\n(c) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD tamper detection and lodging power on/off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete -01 No.\n(d) Phase Indication lamps (RYB), LED type -01 No (set of three).\n(e) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3) -01 set\n IBW_A1$C$70
59 6.1602 OUTGOING\n(i) Microprocessor based ACB, 1250 Amps, 415 V, 4 pole, drawout type (EOD), breaking capacity Icu = Ics= Icw (1 sec), 65 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories-02 Nos\n(ii) MCCB 160 Amps, 4 pole, 50 HZ, 35 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload, (ready, overload, pre alarm & Overload), in built instantaneous protection, Ics =100%=Icu (1 sec) complete all as specified and directed -02 Nos IBW_A1$C$71
60 6.1603 Notes for 6.14 to 6.16:\n(a) Panel manufacturer should have in house powder coating plant with minimum 8 tanks pretreatment of MS sheet facilities, dust free spray paint booth. (8 tanks pretreatment process includes: degreasing / water rinsing / de-rusting / water rinsing / activation / phosphating / water rinsing / passivation).\n(b) Thickness of powder coating shall not be less than 80 microns and test certificate for powder coating shall be furnished along with LT panel.\n(c) Pre dispatch inspection shall be carried out by the authorized representative of Accepting Officer. In case of any deviation from approved drawing, the same shall be rejected and fresh LT panel shall be fabricated by the manufacturer. Testing shall be done at manufacturer's premises and all routine test like IR and continuity tests shall be performed/recorded in presence of authorized representative of Accepting Officer.\n(d) The panel manufacturer should have following certification: IBW_A1$C$72
61 6.1604 (i) CPRI certification Degree of protection IP-54 (should have IEC:61439-1-2 & IEC:60529 tests)\n(ii) CPRI certification short circuit with stand strength should be 50 KA RMS for 1 sec with initial peak of 105 KA.\n(iii) CPRI certification rated current for short circuit not less than 5000A\n(e) MCCB (Microprocessor based)/ ACBs provided should be capable for on line setting of the current.\n(f) ACBs provided should be capable for on line setting to the time delay.\n(g) All the electrical switch gear like MCCBs, MCBs and ACBs should be of same make.\n(h) All incomer ACBs and MCCBs should be compatable with SCADA through communication port.\n(j) Drawing of panel board should be got approved from GE before fabrication.\n(k) Panel board should be fully compartmentalized in accordance to form 4 b of lEC 61439-1-2. IBW_A1$C$73
62 6.17 Dismantling existing APFC panel 1 & 2 suitable for 1000KVA and 500 KVA transformer and handing over to user complete all as specified and as directed. IBW_A1$C$74 1 Each Job
63 6.18 Dismantling existing capacitor bank 26 KVAR for 750 KVA Transformer and handing over to user complete all as specified and as directed. IBW_A1$C$75 1 Each
64 6.19 Supply, installation, testing and commissioning electronic based APFC panel outdoor type having aggregate capacity 600 KVAR in 17 stage, microprocessor based along with factory made type panel weather proof, vermin proof, fully ventilated both side opening and fabricated out of CRCA sheet 3.00mm thick & frame angle of size 50mm x 50mm x 6mm having bus bar of aluminum 1250 Amps capacity, three phase and one neutral fixed on insulator and bus bar insulated by colored heat shrinkable sleeve & housed in specified compartment including powder coating internally externally the entire steel surfaces, all the cover having suitable locking arrangements, fully internally wired with suitable size of thimbles, incoming/outgoing internal connection with PVC insulated PVC sheathed multi stranded copper wire of suitable size all as specified and as directed and comprising of the following :- IBW_A1$C$76 4 Each
65 6.1901 (a) Power supply: 3 phase 4 wire line \n(b) Power rating: 600 KVAR \n(c) Rated system voltage: 440volts, 50Hz \n(d) Duty: continuous \n(e) Main incoming ACB 1250 Amp , 65 KA 4 pole, draw out type (EOD) - 01 No. \n(f) Power factor corrector relay 17 stages-01 No\n(g) Capacitor duty contactor for 100 KVAR -04 Nos\n(h) Capacitor duty contactor for 40 KVAR -04 Nos \n(j) Capacitor duty contactor for 10 KVAR -02 Nos\n(k) Power contactor 18 Amp for 5 KVAR -02 Nos\n(l) Power contactor 18 Amp for 2 KVAR -05 Nos\n(m) MCCB 360 A, 50 KA TP for 100 KVAR-04 Nos\n(n) MCB 100 A, 25KA TP for 40 KVAR-04 Nos \n(o) MCB 25 A, 10 KA TP for 10 KVAR-02 Nos\n(p) MCB 16 A, 10 KA TP for 5 & 2 KVAR-07 Nos IBW_A1$C$77
66 6.1902 (q) A/M selector switch-01 No\n(r) ON-OFF push button-17 sets \n(s) Aux contactor (4 NO + 4 NC) -04Nos\n(t) Indicating light ON-OFF-15 sets\n(u) Power capacitor 100 KVAR dry type having tolerance 0-10% with discharge device resistor, confirming to IS 13340 - 04 Nos\n(v) Power capacitor 40 KVAR dry type having tolerance 0-10% with discharge device resistor, confirming to IS 13340 - 04 No\n(w) Power capacitor 10 KVAR dry type having tolerance 0-10% with discharge device resistor, confirming to IS 13340 - 02 Nos\n(x) Power capacitor 5 KVAR dry type having tolerance 0-10% with discharge device resistor, confirming to IS 13340 - 02 Nos \n(y) Power capacitor 2 KVAR dry type having tolerance 0-10% with discharge device resistor, confirming to IS 13340 -05 Nos\n(z) Voltmeter 0-500 V digital type with built in selector switch -01 set \n(aa) Ammeter 0-1000 A digital type with built in selector switch, CTs of suitable ratio (set of three) -01 set IBW_A1$C$78
67 6.1903 (ab) Protection fuse 16 A with HRC -03 Nos\n(ac) Capacitor 5 KVAR fixed with busbar with MCB 20 A TP protection 1 set\nNOTES :-\n(a) Panel manufacturers should have in house powder coating plant with minimum 8 tanks pretreatment of MS sheet facilities, dust free spray paint booth. (8 tanks pretreatment process includes: degreasing / water rinsing / de-rusting / water rinsing / activation / phosphating / water rinsing /passivation). \n(b) Thickness of powder coating shall not be less than 80 microns and test certificate for powder coating shall be furnished along with LT panel.\n(c) Pre dispatch inspection shall be carried out by the authorized representative of Accepting Officer. In case of any deviation from approved drawing, the same shall be rejected and fresh LT panel shall be fabricated by the manufacturer. Testing shall be done at manufacturer's premises and all routine test like IR and continuity tests shall be performed/recorded in presence of authorized representative of Accepting Officer. IBW_A1$C$79
68 6.1904 (d) The panel manufacturer should have following certification: \n(i) CPRI certification Degree of protection IP-54 (shall have IEC:61439-1 -2 & IEC:60529 tests) \n(ii) CPRI certification short circuit with stand strength should be 50 KA RMS for 1 sec with initial peak of 105 KA.\n(iii) CPRl certification rated current for short circuit not less than 5000A\n(e) ACBs provided should be capable for on line setting to the time delay. \n(f) All the electrical switch gear like MCCBs, MCBs and ACBs should be of same make.\n(g) All incomer ACBs and MCCBs should have provision of capability with SCADA through communication port. \n(h) Drawing of panel board should be got approved from GE before fabrication. \n(j) Panel board should be fully compartmentalized in accordance to form 4 b of lEC 61439-1-2. IBW_A1$C$80
69 6.2 Dismantling and taking out MS angle iron / flat / channels / plate of any size and thickness and shape for cable supports/ pipe support / structure to feeder pillars/cope boxes/ ladder from existing trench/duct including cutting, bending, drilling, unscrewing & making good existing wall structure and handing over to user complete all as specified & as directed. IBW_A1$C$81 5000 Kilogram
70 6.21 Dismantling old unserviceable out door type switch gear panel / feeder pillar box (60 Hz) floor mounted, cubical type, of size of feeder pillar 2000mm (H), 1500 mm (W) and depth1500 mm(D) alongwith associated bus bar, metering , fuses , MCCBs (U/S) switches, indication lamps including disconnecting power cables all as specified and as directed.\nNote : The complete dismantled items shall be handed over to user. IBW_A1$C$82 4 Each
71 6.22 Dismantling old unserviceable out door type switch gear panel / feeder pillar box (60 Hz) floor mounted, cubical type, of size of feeder pillar 1350mm (H), 1000 mm (W) and depth 650 mm(D) alongwith associated bus bar, metering , fuses , MCCBs (U/S) switches, indication lamps including disconnecting power cables all as specified and as directed.\nNote : The complete dismantled items shall be handed over to user. IBW_A1$C$83 18 Each
72 6.23 Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, made out of 3.00 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 with pre-treatment and powder coated of approved colour including suitable frame work/ support made out of suitable size of angle iron/flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for operation and monitoring of I/ C and O/G feeders form the remote location, including the required civil works/ anchoring bolts for fixing, PCC foundation etc. with and including following complete all as specified and as directed\n IBW_A1$C$84 4 Each
73 6.2301 BUSBAR CHAMBER : Electrically grade copper shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators and provision of extension. \nINCOMER\n(a) Microprocessor based ACB, 1250 Amps, 415 Volts, 4 pole, drawout type (EOD), breaking capacity Icu = Ics = Icw (1 sec), 65 KA, 50 Hz over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories. -01 No \n(b) Ammeter 0 to 1500 Amps digital type with built in selector switch, CTs of suitable ratio(set of three) - 01 No\n(c) Voltmeter 0 to 500 volts digital type with built in selector switch - 02 Nos IBW_A1$C$85
74 6.2302 (d) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/ off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete -01 No. \n(e) Phase Indication lamps (RYB), LED type -01 No (set of three).\n(f) MCB SP 2 Amps, "C" series for control protection RYE phases (set of 3) -01 set\nOUTGOING \n(i) Microprocessor based ACB, 800 Amps, 415 Volts, 4 pole, drawout type (EOD), breaking capacity Icu = Ics = Icw (l sec), 50 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories - 02 Nos IBW_A1$C$86
75 6.24 Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 60 Hz, AC supply system, fully compartmentalized, both side openable, made out of 3.00 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 with pre-treatment and powder coated of approved colour including suitable frame work/support made out of suitable size of angle iron/flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for operation and monitoring of I/C and O/G feeders from the remote location, including the required civil works/ anchoring bolts for fixing, PCC foundation etc. with and including following all as specified and as directed :-\nBUSBAR CHAMBER : Electrically grade copper shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators and provision of extension. IBW_A1$C$87 5 Each
76 6.2401 INCOMER\n(a) Microprocessor based ACB, 1250 Amps, 415 Volts, 4 pole, drawout type (EOD), breaking capacity Icu=Ics=Icw (1 sec), 65 KA, 60 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with lSI marked complete with all accessories -01No\n(b) Ammeter 0 to 1500 Amps digital type with built in selector switch, CTs of suitable ratio (set of three) - 01 No\n(c) Voltmeter 0 to 500 volts digital type with built in selector switch - 01 No.\n(d) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 60 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD tamper detection and lodging power on/off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete -01 No. IBW_A1$C$88
77 6.2402 (e) Phase Indication lamps (RYB), LED type -01 No. (set of three).\n(f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3) - 01 set.\nOUTGOING\n(i) Microprocessor based ACB, 630 Amps, 415 Volts, 4 pole, drawout type (EOD), breaking capacity Icu= Ics= Icw (1 sec), 50KA, 60 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with ISI marked complete with all accessories -02 Nos \nNote: All accessories provided shall be suitable for operation on 60 Hz. IBW_A1$C$89
78 6.25 Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, made out of 3.00 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 with pre-treatment and powder coated of approved colour including suitable frame work/ support made out of suitable size of angle iron/ flat iron, front opening with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for operation and monitoring of I/C and O/G feeders from the remote location, including the required civil works/anchoring bolts for fixing, PCC foundation etc. with and including following all as specified and as directed :- IBW_A1$C$90 7 Each
79 6.2501 BUSBAR CHAMBER : Electrically grade copper shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators and provision of extension.\nINCOMER\n(a) Microprocessor based ACB, 800 Amps, 415 Volts, 4 pole, drawout type (EOD), breaking capacity Icu=Ics=Icw (1 sec), 50 KA, 50 Hz, over load, short circuit & instantaneous protection with adjustable current & time delay settings, inbuilt earth fault protection, with ISI marked complete with all accessories. -01 No\n(b) Ammeter 0 to 1000 Amps digital type with built in selector switch, CTs of suitable ratio (set of three) - 01 No\n(c) Voltmeter 0 to 500 volts digital type with built in selector switch - 01 No. IBW_A1$C$91
80 6.2502 (d) AC three phase LT/CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/ off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete -01 No.\n(e) Phase Indication lamps (RYB), LED type -01 No (set of three).\n(f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3 ) -01 set.\nOUTGOING\n(i) MCCB 400 Amps, 415Volts, 4 pole, 50 HZ, 50 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics=100%=Icu (1sec) complete all as specified and directed -02 Nos IBW_A1$C$92
81 6.26 Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, made out of 3.00 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 with pre-treatment and powder coated of approved colour including suitable frame work/ support made out of suitable size of angle iron/flat iron, front opening with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for operation and monitoring of I/ C and O/G feeders from the remote location, including the required civil works/anchoring bolts for fixing, PCC foundation etc. with and including following all as specified and as directed :- IBW_A1$C$93 3 Each
82 6.2601 BUS BAR CHAMBER : Electrically grade copper shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators and provision of extension.\nINCOMER\n(a) MCCB 630Amps, 415Volts, 4 pole, 50 Hz, 50 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics =100%= Icu (1 sec) complete all as specified and directed -01 No\n(b) Ammeter 0 to 1000 Amps digital type with built in selector switch, CTs of suitable ratio (set of three) - 01 No\n(c) Voltmeter 0 to 500 volts digital type with built in selector switch - 01 No. IBW_A1$C$94
83 6.2602 (d) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete -01 No.\n(e) Phase Indication lamps (RYB), LED type -01 No. (set of three).\n(f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3) -01 set.\nOUTGOING\n(i) MCCB 400 Amps, 415Volts, 4 pole, 50 HZ, 50 KA with micro processor base release, adjustable overload, adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics = 100%=Icu (1 sec) complete all as specified and directed -01 No.\n IBW_A1$C$95
84 6.27 Material and Labour for design, supply, fabrication, Installation, testing and commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, made out of 3.00 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS: 2147 with pre-treatment and powder coated of approved colour including suitable frame work/support made out of suitable size of angle iron/ flat iron, front opening type with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for operation and monitoring of I/C and O/G feeders from the remote location, including the required civil works/anchoring bolts for fixing, PCC foundation etc. with and including following all as specified and as directed :- IBW_A1$C$96 3 Each
85 6.2701 BUS BAR CHAMBER : Electrically grade copper shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators and provision of extension.\nINCOMER\n(a) MCCB 400 Amps, 415 Volts, 4 pole, 50 Hz, 50 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics =100%= Icu (1 sec) complete all as specified and directed - 01 No\n(b) Ammeter 0 to 1000 Amps digital type with built in selector switch, CTs of suitable ratio(set of three) - 01 No\n(c) Voltmeter 0 to 500 volts digital type with built in selector switch - 01 No. IBW_A1$C$97
86 6.2702 (d) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/off events instantaneous parameter of rating -5 Amps, with display in absence of power complete -01 No.\n(e) Phase Indication lamps (RYB), LED type -01 No.(set of three)\n(f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3 ) -01 set.\nOUTGOING\n(a) MCCB 63 Amps, 415 Volts, 4 pole, 50 Hz, 25 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics =100%=Icu(1sec) complete all as specified and directed - 05 Nos IBW_A1$C$98
87 6.2703 Notes for 6.23 to 6.27:\n(a) Panel manufacturers should have in house powder coating plant with minimum 8 tanks pretreatment of MS sheet facilities, dust free spray paint booth. (8 tanks pretreatment process includes: degreasing / water rinsing / de-rusting / water rinsing / activation / phosphating / water rinsing /passivation).\n(b) Thickness of powder coating shall not be less than 80 microns and test certificate for powder coating shall be furnished along with LT panel.\n(c) Pre dispatch inspection shall be carried out by the authorized representative of Accepting Officer. In case of any deviation from approved drawing, the same shall be rejected and fresh LT panel shall be fabricated by the manufacturer. Testing shall be done at manufacturer's premises and all routine test like IR and continuity tests shall be performed/recorded in presence of authorized representative of Accepting Officer.\n IBW_A1$C$99
88 6.2704 (d) The panel manufacturer should have following certification :-\n(i) CPRI certification Degree of protection IP-54 (shall have IEC:61439-1 -2 & IEC:60529 tests)\n(ii) CPRI certification short circuit withstand strength shall be 50KA RMS for 1sec with initial peak of 105KA.\n(iii) CPRI certification rated current for short circuit not less than 6000A\n(e) ACBs provided should be capable for on line setting to the time delay.\n(f) All the electrical switch gear like MCCBs, MCBs and ACBs should be of same make.\n(g) All incomer ACBs and MCCBs should be compatible with SCADA through communication port. \n(h) Drawing of panel board should be got approved from GE before fabrication.\n(j) Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2. IBW_A1$C$100
89 6.28 Disconnecting and removing LT 1100V grade cable, PVC insulated heavy duty, size 3.5 core not exceeding 400Sqmm aluminium/copper conductors and handing over to user all as specified and as directed.\n IBW_A1$C$101 4555 Running Metre
90 6.29 Disconnecting and removing LT 1100V grade cable, PVC insulated heavy duty, size 1 core 300Sqmm aluminium conductors and handing over to user all as specified and as directed.\n IBW_A1$C$102 150 Running Metre
91 6.3 Disconnecting and removing LT 1100V grade cable, PVC insulated heavy duty, size 1 core 630Sqmm aluminium conductors and handing over to user all as specified and as directed.\n IBW_A1$C$103 150 Running Metre
92 6.31 Disconnecting and removing HT 11000V grade cable, PVC insulated heavy duty, size from 3 core 185 Sqmm to 240 Sqmm with aluminium conductors and handing over to user all as specified and as directed.\n IBW_A1$C$104 2640 Running Metre
93 6.32 Dismantling and taking out MS angle iron / flat / channels / plate of any size and thickness and shape for cable supports/ pipe support / structure to feeder pillars/cope boxes/ ladder from existing trench/duct including cutting, bending, drilling, unscrewing & making good existing wall structure and handing over to user complete all as specified & as directed. IBW_A1$C$105 4500 Kilogram
94 6.33 Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, made out of 3.00 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS: 2147 with pre-treatment and powder coated of approved colour including suitable frame work/ support made out of suitable size of angle iron/flat iron, front opening with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for operation and monitoring of I/C and O/G feeders from the remote location, including the required civil works/anchoring bolts for fixing, PCC foundation etc. with and including following all as specified and as directed :- IBW_A1$C$106 1 Each
95 6.3301 BUSBAR CHAMBER : Electrically grade copper shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators and provision of extension.\nINCOMER \n(a) MCCB 400 Amps, 415 Volts, 4 pole, 50 Hz, 50 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics=100%=Icu (1 sec) complete all as specified and directed - 01 No\n(b) Ammeter 0 to 500 Amps digital type with built in selector switch, CTs of suitable ratio (set of three) - 01 No\n(c) Voltmeter 0 to 500 volts digital type with built in selector switch - 01 No. IBW_A1$C$107
96 6.3302 (d) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete - 01 No.\n(e) Phase Indication lamps (RYB), LED type -01 No. (set of three).\n(f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3) -01 set.\nOUTGOING\n(i) MCCB 150 Amps, 415 Volts, 4 pole, 50 Hz, 36 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics =100%=Icu (1 sec) complete all as specified and directed - 06Nos\n(ii) MCB 16/25 Amps, SP, 230 Volt, 10 KA, 50Hz with thermal magnetic release i.e. thermal setting 80 -100 % In and magnetic setting 3 -6 In, Ics= 100% = Icu -10 Nos IBW_A1$C$108
97 6.34 Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Outdoor type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 415 volts, 3 phase and neutral, 50 Hz, AC supply system, fully compartmentalized, both side openable, made out of 3.00mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS : 2147 with pre-treatment and powder coated of approved colour including suitable frame work/ support made out of suitable size of angle iron/flat iron, front opening with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm), panel compatible for SCADA system for operation and monitoring of I/C and O/G feeders from the remote location, including the required civil works/anchoring bolts for fixing, PCC foundation etc. with and including following all as specilled and as directed :- IBW_A1$C$109 1 Each
98 6.3401 BUSBAR CHAMBER : Electrically grade copper shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators and provision of extension.\nINCOMER\n(a) MCCB 100 Amps, 415 Volts, 4 pole, 50 Hz, 25KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics =100%=Icu (1 sec) complete all as specified and directed - 01 No\n(b) Ammeter 0 to 500 Amps digital type with built in selector switch, CTs of suitable ratio (set of three)- 01 No\n(c) Voltmeter 0 to 500 volts digital type with built in selector switch - 01No IBW_A1$C$110
99 6.3402 (d) AC three phase LT/ CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete -01 No\n(e) Phase Indication lamps (RYB), LED type -01 No (set of three).\n(f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3) - 01 set.\nOUTGOING\n(i) MCCB 40 Amps, 415 Volts, 4 pole, 50 Hz, 25 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics=100%=Icu(1 sec) complete all as specified and directed - 02 Nos IBW_A1$C$111
100 6.3403 (ii) MCB 40 Amps, 230 Volts, 2 pole, 50 Hz, 10 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics=100%=Icu(1 sec) complete all as specified and directed - 02 Nos\n\nNotes 6.33 and 6.34 :\n(a) Panel manufacturers should have in house powder coating plant with minimum 8 tanks pretreatment of MS sheet facilities, dust free spray paint booth. (8 tanks pretreatment process includes: degreasing / water rinsing / de-rusting / water rinsing / activation / phosphating / water rinsing /passivation).\n(b) Thickness of powder coating shall not be less than 80 microns and test certificate for powder coating shall be furnished along with LT panel. IBW_A1$C$112
101 6.3404 (c) Pre dispatch inspection shall be carried out by the authorized representative of Accepting Officer. In case of any deviation from approved drawing, the same shall be rejected and fresh LT panel shall be fabricated by the manufacturer. Testing shall be done at manufacturer's premises and all routine test like IR and continuity tests shall be performed/recorded in presence of authorized representative of Accepting Officer.\n(d) The panel manufacturer should have following certification :-\n(i) CPRI certification Degree of protection IP-54 (shall have IEC:61439-1 -2 & IEC:60529 tests)\n(ii) CPRI certification short circuit withstand strength shall be 50KA RMS for 1sec with initial peak of 105KA.\n(iii) CPRI certification rated current for short circuit not less than 6000A\n(e) ACBs provided should be capable for on line setting to the time delay.\n(f) All the electrical switch gear like MCCBs, MCBs and ACBs should be of same make. IBW_A1$C$113
102 6.3405 (g) All incomer ACBs and MCCBs should be compatable with SCADA through communication port. \n(h) Drawing of panel board should be got approved from GE before fabrication.\n(j) Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2. IBW_A1$C$114
103 6.35 Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, busbar chamber 2500 Amp, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, for 550 V DC Supply, 2 Pole, 50 Hz, fully compartmentalized, both side openable, made out of 3.00 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS: 2147 with pre-treatment and powder coated of approved colour including suitable frame work/ support made out of suitable size of angle iron/flat iron, front opening with provision for cable entry, with proper ferrule and cable glands including the required civil works/anchoring bolts for fixing, PCC foundation etc. all as specified and as directed.\nNote:- The bus bar link as required at site shall be provided. Minimum length of busbar shall be _____ metres. IBW_A1$C$115 2 Each
104 6.3501 Notes:\n(a) Bus bar chamber manufacturers shall have in house powder coating plant with minimum 8 tanks pretreatment of MS sheet facilities, dust free spray paint booth. (8 tanks pretreatment process includes: degreasing / water rinsing / de-rusting / water rinsing / activation / phosphating / water rinsing / passivation). \n(b) Thickness of powder coating shall not be less than 80 microns and test certificate for powder coating shall be furnished along with bus bar chamber. \n(c) The bus bar chamber manufacturer shall have following certification: \n(i) CPRI certification Degree of protection IP-54 (shall have IEC:61439-1 -2 & IEC:60529 tests) \n(ii) CPRI certification short circuit with stand strength shall be 50 KA RMS for 1 sec with initial peak of 105 KA. \n(iii) CPRI certification rated current for short circuit not less than 5000A. \n(d) Drawing of bus bar chamber shall be got approved from GE before fabrication. \n(e) Bus bar chamber shall be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2. IBW_A1$C$116
105 6.36 Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 400 Sqmm, 3.5 Core, confirming to IS-7098 (Part-I) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed\n IBW_A1$C$117 9385 Running Metre
106 6.37 Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 300 Sqmm, 3.5 Core, confirming to IS-7098 (Part-I) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed\n IBW_A1$C$118 10687 Running Metre
107 6.38 Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 240 Sqmm, 3.5 Core, confirming to IS-7098 (Part-I) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed\n \n IBW_A1$C$119 44 Running Metre
108 6.39 Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 120 Sqmm, 3.5 Core, confirming to IS-7098 (Part-I) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed\n IBW_A1$C$120 132 Running Metre
109 6.4 Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 400 Sqmm, 3 Core, confirming to IS-7098 (Part-II) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed\n IBW_A1$C$121 440 Running Metre
110 6.41 Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 400 Sqmm, 2 Core, confirming to IS-7098 (Part-II) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed\n IBW_A1$C$122 429 Running Metre
111 6.42 Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 300 Sqmm, 2 Core, confirming to IS-7098 (Part-II) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed\n IBW_A1$C$123 50 Running Metre
112 6.43 Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 4 Sqmm, 4 Core, confirming to IS-7098 (Part-I) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed\n IBW_A1$C$124 300 Running Metre
113 6.44 Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 1.5 Sqmm, 2 Core, confirming to IS-7098 (Part-I) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed\n IBW_A1$C$125 100 Running Metre
114 6.45 Supply, laying, connecting and testing XLPE Insulated Screened PVC bedded galvanized steel strip or wire armoured, electric power cable (heavy duty) 1100 Volts grade with stranded copper conductor of size 240 Sqmm, 1 Core, confirming to IS-7098 (Part-II) laid in cable trenches/ Duct/Wall/surfaces/ Pipe including termination with brass compression glands and copper lugs as required at site complete all as specified and as directed.\n\nNotes 6.36 to 6.45 :- \n(i) Predispatch inspection and testing shall be done by the officer detailed by the Accepting Officer. All testing shall be performed as per relevant IS. \n(ii) Testing for IR and continuity shall be recorded before and after laying of cable.\n(iii) Suitable glands and copper lugs for end termination of cables shall be provided by the contractor without any extra cost to the dept. \n(iv) No straight through joint shall be permitted.\n(v) Excavation, Earth work, sand cushioning, cable cover and GI pipe required shall be measured and paid separately.\n IBW_A1$C$126 1080 Running Metre
115 6.46 Laying and connecting retrieved LT cable of size 3.5/3 core 300 to 400 Sqmm with Aluminium/ Copper conductor complete all as specified and as directed. IBW_A1$C$127 200 Running Metre
116 6.47 Supply and fixing MCB distribution board suitable for following MCBs and fixed with 200 Amps rated copper neutral link and earth link complete all as specified and as directed:\n(a) MCB 4 Pole, 10A, 10KA -01 No\n(b) MCB SP, 6 to 32 A, 10KA -08 Nos IBW_A1$C$128 5 Each
117 6.48 Supply and fix LED flood light fitting 120Watt with cast alumumium housing including electronic driver, heat shrink reflector toughened glass cover with all accessories having High lumen output, driver PF >0.98, having over voltage protection upto 400volts, surge protection level 7-10 KV, thermal short circuit protection THD <10%, made up of long life LED chips(SMD) in modular with Ra >70 and LED lumen efficiency> 120 lumen per watt, pre-wired complete with all accessories and connecting with 3core flexible copper cable PVC insulated of size 1.5 Sqmm all as specified and as directed.\nNote : The firm shall give warranty for street light fitting including driver minimum for 3 years for any defects developed during the period. IBW_A1$C$129 12 Each
118 6.49 Fabricate, supply and fixing hot dip galvanized mild steel conforming to Fe-290, Gde-E-165 framed brackets made out of angle/Tee/Channel sections, including cutting to shape, bending, electric arc welding, drilling holes etc., GI bolts, nuts, washers etc., all as necessary for laying and fixing LT cables complete all as specified and as directed. IBW_A1$C$130 4000 Kilogram
119 6.5 Material and labour for horizontal core cutting of required size and length in the RCC trench, walls for passing of cables and pipe lines including dismantling of RCC and cutting of reinforcement bars if needed, without damaging the structure and its strength and making good the disturbed surface to match the existing surface complete all as specified and as directed. IBW_A1$C$131 0.5 Cubic Metre
120 6.51 Material and Labour for Design, Supply, Fabrication, Installation, testing and Commissioning factory made, LT panel board, Out door type, totally enclosed, dust and vermin proof, suitably ventilated, floor mounted, 110 Volts DC Supply, 2 Pole, 50 Hz, fully compartmentalized, both side openable, made out of 3.00 mm thick CRCA sheet steel, protection of enclosure IP-54 as per IS: 2147 with pre-treatment and powder coated of approved colour including suitable frame work/support made out of suitable size of angle iron/flat iron, front opening with provision for cable entry, with proper ferrule and cable glands, internal wiring with PVC insulated multi stranded Copper conductor FRLSH cable of adequate size (minimum 1.5 sq mm ), panel compatible for SCADA system for operation and monitoring of I/C and O/G feeders from the remote location, including the required civil works/ anchoring bolts for fixing, PCC foundation etc. with and including following all as specified and as directed :- IBW_A1$C$132 3 Each
121 6.5101 BUSBAR CHAMBER : Electrically grade copper shrouded bus bar of capacity equal to 1.5 times of rated incoming control switch gear including interconnection of all switch gears, fixed on DMC insulators and provision of extension. \nINCOMER \n(a) MCCB 250 Amps, 600 Volts, 2 pole, 50 Hz, 50 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics =100%=Icu(1 sec) complete all as specilied and directed - 01 No\n(b) Ammeter 0 to 500 Amps digital type with built in selector switch, CTs of suitable ratio (set of three) = 01 No\n(c) Voltmeter 0 to 600 volts digital type with built in selector switch - 01 No. IBW_A1$C$133
122 6.5102 (d) AC three phase LT/CT multifunctional energy meter of accuracy class-0.5, 3 x 240 volts 50 Hz, with optical and RS 232 port, backlit LCD display, measures and display, trivector energy and load survey, TOD temper detection and lodging power on/off events, instantaneous parameter of rating -5 Amps, with display in absence of power complete - 01 No. \n(e) Phase Indication lamps (RYB), LED type -01 No. (set of three). \n(f) MCB SP 2 Amps, "C" series for control protection RYB phases (set of 3) - 01 set. \nOUTGOING\n(i) MCCB 63 Amps, 600 volts, 2 pole,50 Hz, 50 KA with micro processor base release, adjustable overload, Adjustable short circuit, front LED indication of overload (ready, overload, pre alarm & Overload), inbuilt instantaneous protection, Ics =100%=Icu(1 sec) complete all as specified and directed - 03 Nos IBW_A1$C$134
123 6.5103 Notes:\n(a) Panel manufacturers should have in house powder coating plant with minimum 8 tanks pretreatment of MS sheet facilities, dust free spray paint booth. (8 tanks pretreatment process includes: degreasing / water rinsing / de-rusting / water rinsing / activation / phosphating / water rinsing /passivation).\n(b) Thickness of powder coating shall not be less than 80 microns and test certificate for powder coating shall be furnished along with LT panel.\n(c) Pre dispatch inspection shall be carried out by the authorized representative of Accepting Officer. In case of any deviation from approved drawing, the same shall be rejected and fresh LT panel shall be fabricated by the manufacturer. Testing shall be done at manufacturer's premises and all routine test like IR and continuity tests shall be performed/recorded in presence of authorized representative of Accepting Officer.\n(d) The panel manufacturer should have following certification :-\n IBW_A1$C$135
124 6.5104 (i) CPRI certification Degree of protection IP-54 (shall have IEC:61439-1 -2 & IEC:60529 tests)\n(ii) CPRI certification short circuit withstand strength should be 50KA RMS for 1 sec with initial peak of 105KA.\n(iii) CPRI certification rated current for short circuit not less than 5000A\n(e) ACBs provided should be capable for on line setting to the time delay.\n(f) All the electrical switch gear like MCCBs, MCBs and ACBs should be of same make.\n(g) All incomer ACBs and MCCBs should be compatable with SCADA through communication port. \n(h) Drawing of panel board should be got approved from GE before fabrication.\n(j) Panel board should be fully compartmentalized in accordance to form 4 b of IEC 61439-1-2. IBW_A1$C$136
125 6.52 Supply, installation, testing and commissioning Advance encapsulated compound based CPRI tested maintenance free, pipe-in-pipe technology upgraded (Zinc & Alloy Coated), ZINC COATED (80-100) microns with pure Zinc (99.9%) & ALLOY COATING (200-250) microns earthing system confirming to IS 3034, outer and inner pipe of 41.9mm, 26.4mm dia respectively, 2 metres length, Zinc coated with additional special Alloy coating 300mm on the topside for additional protection of the Terminal, annular space between the pipes filled up with COMPACT FILL(CF) (Crystalline Conductive Compound) (COMPACT FILL (CF) mixture which is machine pressed in the pipes shall not disintegrate or collapse when outer pipe corrodes), inner pipe extended with terminals for connectivity complete all as specified and as directed.\nMake "ASHWK"Model-ASEEL-1 9, 2m length (ZC & AC) IBW_A1$C$137 24 Each
126 6.5201 NOTES :- \n(i) The job includes digging the pits and refilling the same by Electrodite/Conductolite Back Fill compound (Ground Enhancer).\n(ii) The BFC should be eco friendly and it should not contain environmentally hazardous material/metal having ROHS Certification from NABL accredited lab. \n(iii) The earth pit shall be provided with a FRP earth pit cover for protection and safe guard of the terminals. \n(iv) In areas where soil condition is bad, good earth is to be arranged to fill the excavated pits by mixing the same with BFC 2 bags (as per soil condition) extra per pit/unit.\n(v) The material shall have good electrical conductivity & anti corrosion property in wide range of soil conditions.\n(vi) Complete work shall be executed all as per manufacturer's instruction. \n(vii) All the above given dimensions may vary ± 1 mm \n(viii) The quantity of BFC Electrodite shall be increased according to soil condition and to achive the earth value less than 1 O. IBW_A1$C$138
127 6.53 Material and labour for GI perforated cable tray of size 450mm x 50mm made out of not less than 2mm thick GI sheet including anchor fasteners, supporting whole thread rod, bolts, nuts, washers etc. complete all as specified and as directed. IBW_A1$C$139 1200 Running Metre
128 6.54 Material and labour for GI perforated cable tray of size 400mm x 50mm made out of not less than 2mm thick GI sheet including anchor fasteners, supporting whole thread rod, bolts, nuts, washers etc. complete all as specified and as directed. IBW_A1$C$140 600 Running Metre
129 6.55 Material and labour for GI perforated cable tray of size 350mm x 50mm made out of not less than 2mm thick GI sheet including anchor fasteners, supporting whole thread rod, bolts, nuts, washers etc. complete all as specified and as directed. IBW_A1$C$141 600 Running Metre
130 6.56 Total amount of Schedule 'A' Part VI-B C/o to General Summary on Ser Page No.
131 7 SCHEDULE 'A' PART VII-B (L P AIR PIPELINE)
132 7.01 Material and labour for providing air tapping point complete with 100 x 50 x 50 mm dia flanged Tee -01 No, 50 x 25 x 25 mm dia flanged Tee - 02 Nos, 25 mm dia gate valves-04 Nos including rubber gasket and complete with necessary nuts, bolts, washers etc. as required complete all as specified and as directed. IBW_A1$C$144 4 Each
133 7.02 Supply and fixing CI air moisture extractor for outlet of 100mm complete all as specified and as directed. IBW_A1$C$145 3 Each
134 7.03 Supply and fixing sluice valve Cast steel Class PN 1.6 complete with both ends flanged and drilled with ISI marked (IS- 14846) of size 150 mm dia including Stainless steel non rising spindle and hand wheel complete all as specified and as directed. IBW_A1$C$146 6 Each
135 7.04 Supply and fixing sluice valve Cast steel Class PN 1.6 complete with both ends flanged and drilled with ISI marked (IS- 14846) of size 100 mm dia including Stainless steel non rising spindle and hand wheel complete all as specified and as directed. IBW_A1$C$147 12 Each
136 7.05 Supply and fix pressure gauge bourdon with glycerin filled of range 0 to 21 kg/Sqcm, 4" dia and stainless steel body including accessories complete all as specified and as directed. IBW_A1$C$148 3 Each
137 7.06 Total amount of Schedule 'A' Part VII-B C/o to General Summary on Ser Page No.
138 8 SCHEDULE 'A' PART VIII-B (FIRE ALARM SYSTEM)
139 8.01 Supply and laying/fixing to wall/ceiling 2 core 1.5 Sqmm PVC insulated armoured multistranded copper conductor cable ISI marked all as specified and as directed. IBW_A1$C$151 1000 Running Metre
140 8.02 Supply & fixing Carbon-di-Oxide fire extinguisher ISI marked of capacity 4.5 Kilogram consisting of welded mild steel cylindrical body, squeeze lever discharge valve fitted with internal discharge tube, 300mm long high pressure discharge hose, discharge nozzle, suspension bracket, ISI marked with IS:15683, finishing externally with red enamel paint and fixed to wall with brackets with rawl plug/dash fasteners with internal charge, complete all as specified and as directed. IBW_A1$C$152 5 Each
141 8.03 Supply & fixing Carbon-di-Oxide fire extinguisher ISI marked of capacity 6.5 Kilogram consisting of welded mild steel cylindrical body, squeeze lever discharge valve fitted with internal discharge tube, 300mm long high pressure discharge hose, discharge nozzle, suspension bracket, ISI marked with IS:15683, finishing externally with red enamel paint and fixed to wall with brackets with rawl plug/dash fasteners with internal charge, complete all as specified and as directed. IBW_A1$C$153 5 Each
142 8.04 Supply & fixing 6 Kg DCP fire extinguisher ISI marked with stored pressure, handheld, floor mounted type suitable for class ABC fire ISI marked with IS:15683 complete with refill, full length back bracket, hose and clip complete all as specified and as directed. IBW_A1$C$154 5 Each
143 8.05 Supply & fixing 9 Kg DCP fire extinguisher ISI marked with stored pressure, handheld, floor mounted type suitable for class ABC fire ISI marked with IS:15683 marked complete with refill, full length back bracket, hose and clip complete all as specified and as directed.\nNote: All the work under this Schedule shall be got excecuted through approved consultant/ Agency after getting approval from Accepting officer. IBW_A1$C$155 5 Each
144 8.06 Total amount of Schedule 'A' Part VIII-B C/o to General Summary on Ser Page No.
145 9 ABC
146 10 ABC
147 11 GENERAL SUMMARY
148 11.01 Total Amount of Schedule ‘A’ Part I for “BUILDING AND STRUCTURE” brought forwarded from Serial Page No
149 11.02 Lump sum price worked out by the contractor for “EXCAVATION AND EARTH WORK” as listed in Schedule ‘A’ Part II-A 1 LUMP SUM
150 11.03 Total Amount of Schedule ‘A’ Part II-B for “EXCAVATION AND EARTH WORK” brought forwarded from Serial Page No
151 11.04 Lump sum price worked out by the contractor for “INTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part III 1 LUMP SUM
152 11.05 Lump sum price worked out by the contractor for “INTERNAL ELECTRIFICATION” as listed in Schedule ‘A’ Part IV-A 1 LUMP SUM
153 11.06 Total Amount of Schedule ‘A’ Part IV-B for “INTERNAL ELECTRIFICATION” brought forwarded from Serial Page No
154 11.07 Lump sum price worked out by the contractor for “EXTERNAL WATER SUPPLY” as listed in Schedule ‘A’ Part V-A 1 LUMP SUM
155 11.08 Total Amount of Schedule ‘A’ Part V-B for “EXTERNAL WATER SUPPLY” brought forwarded from Serial Page No
156 11.09 Lump sum price worked out by the contractor for “EXTERNAL ELECTRIFICATION” as listed in Schedule ‘A’ Part VI-A 1 LUMP SUM
157 11.1 Total Amount of Schedule ‘A’ Part VI-B for “EXTERNAL ELECTRIFICATION” brought forwarded from Serial Page No
158 11.11 Lump sum price worked out by the contractor for “LP AIR PIPELINE” as listed in Schedule ‘A’ Part VII-A 1 LUMP SUM
159 11.12 Total Amount of Schedule ‘A’ Part VII-B for “LP AIR PIPELINE” brought forwarded from Serial Page No
160 11.13 Lump sum price worked out by the contractor for “FIRE ALARM SYSTEM” as listed in Schedule ‘A’ Part VIII-A 1 LUMP SUM
161 11.14 Total Amount of Schedule ‘A’ Part VIII-B for “FIRE ALARM SYSTEM” brought forwarded from Serial Page No
162 11.15 Lump sum price worked out by the contractor for “REPAIRS TO RCC DUCT AND PROVISION OF NEW DUCT” as listed in Schedule ‘A’ Part IX 1 LUMP SUM
163 11.16 Lump sum price worked out by the contractor for "DEMOLITION/DISMANTLING" as listed in Schedule ‘A’ Part X 1 LUMP SUM