Special Repair Of Electrical Installation & Fans & Replacement Of Main Panel, Dbs & Cables & Providing Acs,Dg Set At Office Of The Sub-Divisional Magistrate(Kalkaji),37-Institutional Area Tughlakabad,New Delhi-110062.(Sh:-Supply Installation Testi
Tender Overview
Project Description
Special Repair Of Electrical Installation & Fans & Replacement Of Main Panel, Dbs & Cables & Providing Acs, Dg Set At Office Of The Sub-Divisional Magistrate ( Kalkaji ) , 37-Institutional Area Tughlakabad, New Delhi-110062. ( Sh:-Supply Installation Testing And Commissioning Of 125 Kva Dg Set ) . , Sub Head - Dg Set Providing , Installing , Testing & Commissioning Of Silent Type Diesel Generating Set Having Prime Power Rating Of 125 Kva , 415 Volts At 1500 Rpm , 0 . 8 Lagging Power Factor At 415 V Suitable For 50 Hz , 3 Phase System & Consisting Of The Following: ( A ) Diesel Engine: Diesel Engine 4 Stroke Water Cooled , Electric Start , Of Suitable Bhp At 1500 Rpm Under Ntp Conditions Of Bs:5514 Capable Of Taking 10% Over Loading For One Hour After 12 Hours Of Continuous Operation . The Engine Will Be Fitted Complete With All The Required Accessories . ( B ) Engine Mounted Instrument Panel Fitted With Accessories & Indicators To Indicate Necessary Parameters And Having Digital Display As Per Standard Design Of The Manufacturer . I ) Start-Stop Switch Ii ) Water Temperature Indication Iii ) Lubrication Oil Pressure Indication Iv ) Battery Charging Indication V ) Rpm Indication Vi ) Over Speed Trip Indication Vii ) Low Lub . Oil Pressure Trip Indication Viii ) Engine Hours Indication Ix ) Kwh Meter ( To View The Record Of Total Unit Generated Upto Date ) . , ( C ) Alternator: Synchronous Alternator Rated At 125 Kva , 415 Volts At 1500 Rpm , 3 Phase , 50 Hz , Ac Supply With 0 . 8 Lagging Power Factor At 40 Degree C , 50% Rh At 1000 Mtr . Msl & At Ntp Conditions . The Alternator Shall Be Having Spdp Ip 23 Enclosure , Brushless , Continuous Duty , Self-Excited And Self-Regulated Through Avr Conforming To Bs:2613 . Suitable For Tropical Conditions And With Class-H Insulation . ( D ) Base Frame & Foundation: Both The Engine & Alternator Shall Be Mounted On Suitable Base Frame Made Of Ms Channel With Necessary Reinforcement Which Shall Be Installed On Suitable Cement Concrete Foundation & Vibration Isolation Arrangement As Per Recommendations Of Manufacturer . ( E ) Fuel Tank: Daily Service Fuel Tank Of 330 Liters Capacity Fabricated Out Of 3 Mm Thick M . S . Sheet Complete With All Standard Accessories & Fuel Piping Between Fuel Tank & Diesel Engine With Ms Class C Pipes Of Suitable Dia . Complete With Valves , Level Indications & Accessories As Required As Per Specifications . ( F ) Exhaust System: Dry Exhaust Mainfold With Hospital Silencer As Per Cpcb Norms . , ( G ) Starting-System: 12V / 24V Dc Starting System Comprising Of Starter Motors: Voltage Regulator And Arrangement For Initial Excitation Complete With Maintenance Free Batteries As Recommended By Manufacturer Of Dg Set & As Required As Per Specifications . ( H ) Acoustic & Weather Proof Enclosure With Arrangement For Fresh Air Intake For Cooling Of The Engine & Alternator , Extraction , Discharging Hot Air In To The Atmosphere As Per Specifications . , Fabricating , Installation , Testing & Commissioning Of Automatic Mains Failure Panel Fabricated In 2 Mm Thick Crca Sheet Steel With Suitable Size Ms Base Channel , Floor Mounted For Existing Dg Set Of 125 Kva , Including Manual Bypass For Both Main And Dg Set Supply Complete With Aluminium Bus Bars , Suitable For 125 Kva Silent Type Dg Set Complete With Relays , Timers , Set Of Cts For Metering & Protection & Energy Analyser To Indicate Current , Phase & Line Voltages , Frequency & Provision For Overload , Short Circuit , Restriction Earth Fault , Under Frequency , Connection With Existing Control Cabling Of Dg Set To Amf Panel , All Complete & Inter Locking Arrangement Including The Following . A ) 250 Amp 50 Ka 4 Pole Mccb - 2 Nos . B ) 250 Amp On Load 4 Pole Change Over Switch-2 Nos . C ) 250 Amp 4 Pole Power Contactor- 2 Nos . D ) Auto / Manual / Test / Off Selector Switch E ) 3 Nos . Of Current Transformer 250 / 5 Amps For Metering . F ) Energy Analyzer Unit To Indicate Current Voltage Frequency G ) Indicating Lamps For Load On Mains And Load On Dg Set . , H ) Sp Mcb For Instruments . I ) Control Unit With Three Impulse Automatic Engine Start / Stop And Failure To Start Lockout . J ) On / Off / Control Circuit With Indicator . K ) Audio / Video Annunciation For High Water Temperature Low Lubricating Oil Pressure Engine Over Speed Engine Fails To Start Amf Panel As Described Above , Providing And Laying In Position Cement Concrete 1:2:4 ( 1 Cement : 2 Coarse Sand : 4 Graded Stone Aggregate 20 Mm Nominal Size ) In Foundation Of Pump , Dg Set Etc . Including Form Work Etc . As Required . , Earthing With G . I . Earth Plate 600 Mm X 600 Mm X 6 Mm Thick Including Accessories , And Providing Masonry Enclosure With Cover Plate Having Locking Arrangement And Watering Pipe Of 2 . 7 Meter Long Etc . With Charcoal / Coke And Salt As Required . , Providing & Fixing 25 Mm X 5 Mm G . I . Strip On Surface Or In Recess For Connections Etc . As Required . , Providing & Fixing 25 Mm X 5 Mm G . I . Strip In 40 Mm Dia G . I . Pipe From Earth Electrode Including Connection With G . I . Nut , Bolt , Spring , Washer Excavation And Re-Filling Etc . As Required . , Fabrication Supplying Installation Testing & Commissioning Of Cubical Feeder Pillar Panel Board , Dust , Damp And Vermin Proof , Compartmentalized Made Out Of 2 . 0 Mm Thick ( Ns ) Crca Sheet Duly Powder Coated , 300 Mm Deep Complete With 4 Strips Alu . Bus Bar Of 300Amps . Capacity Complete With Connection , Interconnections , Internal Wiring With Copper Conductor Cable Of Suitable Sizes , Earthing Etc . As Reqd . , Providing & Fixing Following Rating & Breaking Capacity And Pole Mccb With Thermomagnetic Release & Terminal Spreaders In Existing Cubicle Panel Board Including Drilling Holes In Cubicle Panel , Making Connections , Etc . As Required . , 100 A , 16 Ka , Tpmccb , 125 A , 16 Ka , Tpmccb , 250 A , 36 Ka , Fpmccb , Credit Item , Less Credit For Unserviceable 62 . 5 Kva Dg Set .
BOQ
| Name of Work:-Special Repair of EI & Fans & Replacement of Main Panel, DB's & cables & Providing AC's,DG Set at Office of the Sub-Divisional Magistrate(Kalkaji),37-Institutional Area Tughlakabad,New Delhi-110062.(SH:-SITC of 125 KVA DG Set). | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1 | SUB HEAD - DG SET \nProviding, Installing, Testing & Commissioning of 'Silent type' Diesel Generating set having Prime Power Rating of 125 KVA, 415 volts at 1500 RPM, 0.8 lagging power factor at 415 V suitable for 50 Hz, 3 phase system & consisting of the following:\n(a)Diesel Engine:\nDiesel Engine 4 stroke water cooled, electric start, of suitable BHP at 1500 RPM under NTP conditions of BS:5514 capable of taking 10% over loading for one hour after 12 hours of continuous operation. The engine will be fitted complete with all the required accessories.\n(b)Engine mounted Instrument panel fitted with accessories & indicators to indicate necessary parameters and having digital display as per standard design of the manufacturer.\ni)Start-stop switch \nii)Water temperature indication\niii)Lubrication oil pressure indication\niv)Battery charging indication\nv)RPM indication\nvi)Over speed trip indication\nvii)Low lub. Oil pressure trip indication\nviii)Engine Hours indication\nix)KWH meter (to view the record of total unit generated upto date). | |||
| 2 | 1.01 | (c)Alternator:\nSynchronous alternator rated at 125 KVA,415 volts at 1500 RPM, 3 phase, 50 Hz, AC supply with 0.8 lagging power factor at 40 Degree C, 50% RH at 1000 Mtr. MSL & at NTP conditions. The alternator shall be having SPDP IP 23 enclosure, brushless, continuous duty, self-excited and self-regulated through AVR conforming to BS:2613. suitable for tropical conditions and with class-H insulation.\n(d)Base Frame & Foundation:\nBoth the engine & alternator shall be mounted on suitable base frame made of MS channel with necessary reinforcement which shall be installed on suitable cement concrete foundation & vibration isolation arrangement as per recommendations of manufacturer.\n(e)Fuel Tank:\nDaily service fuel tank of 330 liters capacity fabricated out of 3 mm thick M.S. Sheet complete with all standard accessories & fuel piping between fuel tank & diesel engine with MS class 'C' pipes of suitable dia. complete with valves, level indications & accessories as required as per specifications.\n(f)Exhaust System:\nDry exhaust mainfold with Hospital silencer as per CPCB norms. | |||
| 3 | 1.02 | (g)Starting-System:\n12V/24V DC starting system comprising of starter motors: voltage regulator and arrangement for initial excitation complete with maintenance free batteries as recommended by manufacturer of DG Set & as required as per specifications.\n(h)Acoustic & weather proof enclosure with arrangement for fresh air intake for cooling of the engine & alternator, extraction, discharging hot air in to the atmosphere as per specifications. | 1 | Set | |
| 4 | 2 | Fabricating, installation, testing & commissioning of automatic mains failure panel fabricated in 2 mm thick CRCA sheet steel with suitable size MS base channel, floor mounted for existing DG set of 125 KVA, including manual bypass for both Main and DG set supply complete with aluminium bus bars, suitable for 125 KVA silent type DG set complete with relays, timers, set of CTs for metering & protection & energy analyser to indicate current, phase & line voltages, frequency & provision for overload, short circuit, restriction earth fault, under frequency, connection with existing control cabling of DG set to AMF panel, all complete & inter locking arrangement including the following.\na)250 Amp 50 KA 4 pole MCCB - 2 Nos.\nb)250 Amp on load 4 pole change over switch-2 Nos.\nc) 250 Amp 4 pole power contactor- 2 Nos.\nd) Auto/ Manual/ Test/ Off selector switch\ne) 3 Nos. of current transformer 250/5 Amps for metering.\nf) Energy analyzer unit to indicate current voltage Frequency\ng) Indicating lamps for load on mains and load on DG Set. | |||
| 5 | 2.01 | h) SP MCB for instruments.\ni) Control unit with three impulse automatic engine start/stop and failure to start lockout.\nj) On/ off/ control circuit with indicator.\nk) Audio/ video annunciation for\nHigh water temperature\nLow lubricating oil pressure\nEngine over speed\nEngine fails to start\nAMF Panel as described above | 1 | No. | |
| 6 | 3 | Providing and laying in position cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) in foundation of pump, DG set etc. including form work etc. as required. | 3 | Cum | |
| 7 | 4 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. | 4 | Sets | |
| 8 | 5 | Providing & fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. | 12 | Mtrs. | |
| 9 | 6 | Providing & fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt,spring, washer excavation and re-filling etc. as required. | 15 | Mtrs. | |
| 10 | 7 | Fabrication Supplying installation testing & commissioning of cubical Feeder pillar panel board, dust, damp and vermin proof, compartmentalized made out of 2.0 mm thick (NS) CRCA Sheet duly powder coated, 300 mm deep complete with 4 strips alu. bus bar of 300amps. Capacity complete with connection, interconnections, internal wiring with copper conductor cable of suitable sizes, earthing etc. as reqd. | 1.4 | Sqmtrs. | |
| 11 | 8 | Providing & fixing following rating & breaking capacity and pole MCCB with thermomagnetic release & terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. | |||
| 12 | 8.01 | 100 A, 16 kA,TPMCCB | 3 | Nos. | |
| 13 | 8.02 | 125 A, 16 kA,TPMCCB | 2 | Nos. | |
| 14 | 8.03 | 250 A, 36 kA,FPMCCB | 1 | No. | |
| 15 | 9 | Credit Item | |||
| 16 | 9.01 | Less Credit for Unserviceable 62.5 KVA DG Set. | 1 | Nos. |
AI Tender Summary
Tender Timeline
Tender Published
Tender notice published.
CompletedBid Submission Deadline
Online submission via eProcurement portal.
CompletedBid Opening Date
Technical bids will be opened and evaluated.
CompletedTender Documents
Download All (ZIP) ↓We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender