Kerala Tourism Development Corporation-KTDC has published Supply , Testing And Commissioning Of 62 Kva Or Nearest Higher Capacity Dg Set At Ktdctamarind Easy Hotel , Kannur Supply , Testing AndCommissioning Of 62Kva Or Nearest HigherCapacity Dg Set At KtdctamarindEasy Hotel , Kannur. Submission Date for this Tender is 15-02-2020. Diesel Generators Tenders in Kannur Kerala. Bidders can get complete Tender details and download the document.
Name of Work:Supply,Testing and Commissioning of 62 kVA OR Nearest higher capacity DG set at KTDC- Tamarind easy Hotel, kannur | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1.001 | Supply of 3 phase 62kVA or nearest higher capacity Diesel-Generator set with acoustic enclosure as per CPCB II norms suitable for placing in the outdoor with the following specifications. | BI01010001010000000000000515BI0100001114 | ||
2 | 1.002 | Engine | |||
3 | 1.003 | Suitable HP rated Water / liquid cooled,\nRadiator type, turbo charge aspirated 4 Stroke Electric Start engine with automatic speed regulation /digital engine governing system to develop mechanical output so as to satisfactorily generate full load electrical output in par with the alternator specifications as per given below with out sag in the line parameters at electrical side as recommended by the OEM | |||
4 | 1.004 | Alternator | |||
5 | 1.005 | 50 kW Brushless, Self excited, Self regulated alternator suitable for continous operation at 1500rpm with Automatic voltage regulation system to Generate 3 Phase, 4 Wire 415V +/- 1 % AC 50Hz at 0.8 lag pf Supply, insulation class F/H, 2/3 pitch, double layer lap wound stator winding, dynamically balanced rotor, low THD conforming to BS 5514 & ISO 3046 of make as recommended by the OEM | |||
6 | 1.006 | Accoustic Enclosure | BI01010001010000000000000515BI0100001115 | ||
7 | 1.007 | Canopy type Accoustic enclosure including air intake / exhaust baffles, sliding doors with suitable hinges, locks etc. for the DG sets using accoustically treated panels housed in 1.6 & 3mm / 0.5mm CRCA / LCMS / HRCA sheet steel section filled with special grade 100 mm Thick 96 kg/m3 Density Rock Wool, covered with R. P. Tissue Paper and Expended metal on wall specially designed for optimum sound attenuation with frameworks complete. with inspection lamps, inspection glass window,\nprovision for Cable Entry, control cables, etc. complying to IS 8183 | |||
8 | 1.008 | Generator Control Panel | |||
9 | 1.009 | Dust tight, vermin proof GCP falling to IP43 category fabricated out of 16 / 18 SWG CRCA Sheet Steel painted as per standards of the following specifications ( All switches shall confirm to conforming to IEC 60947-2 standards). | |||
10 | 1.01 | The Panel shall be provided with Engine Controller unit suitable for integration to AMF Relay system, suitable rating MCCB/MCB with O/C & S/C Protection as recommended by OEM, TPN best conductivity busbar with SMC supports, heat shrinkable sleeves etc. capable to handle generator full load current. | |||
11 | 1.02 | Suitable rating Class 1.0 Metering CTs per phase as recommended by OEM, multifunction / induvidual meters to read current in each phase, line to line and phase voltages, frequency, energy generated ( Wh) per phase and cummilative, hours of operation, powerfactor status, RYB Phase indicators ( LED Pilot type ) with suitable rating control MCB including all necessary control wiring etc. complete as per standards. ( Note : - The GCP shall meet all the statutory requirements complied with the Kerala State Electrical Inspectorate ) | |||
12 | 1.03 | Stantard accessories | |||
13 | 1.04 | Both Engine & Alternator shall be suitably coupled and mounted on common channel iron base frame with standard accessories such as anti vibration pad, required capacity battery, suitable battery-charger unit with charging arrangements from direct mains, As per OEM standards Capacity Diesel tank, residential type silencer, suitable cable termination box etc. complete as per Electrical Inspectorate standards, rules & regulations | |||
14 | 1.05 | The DG Control Panel shall be compatible for PLC based Auto mains failure system employed in the Main Panel. | |||
15 | 1.1 | 62 kVA or NEAREST HIGHER CAPACITY DG SET | 1 | Nos | |
16 | 2 | Charges for transportation to site, moving the generator to the foundation and testing and commissioning of the DG set | 1 | LS |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail