| 1 | 1 | SCHEDULE 'A' SECTION I (B&R Portion) | | | |
|---|
| 2 | 2 | Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth, for foundations etc or manholes, cesspits, pipes and cables etc. not exc 10 Sqm on plan and getting out in soft / loose soil all as specified and directed by Engineer - in - Charge. | | 10 | Per Cum |
|---|
| 3 | 3 | Returning, filling in, including spreading, levelling, watering and well ramming in layers of soft / loose soil not exceeding 25cm thick all as specified and directed by Engineer - in - Charge. | | 4.55 | Per Cum |
|---|
| 4 | 4 | Removing excavated material exc. 250 m but n exc. 500 m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed by Engineer - in - Charge. | | 5.45 | Per Cum |
|---|
| 5 | 5 | M & L for broken bricks hard core of gauge not exceeding 63mm, deposited, spread levelled in layers n exc 15 cm thick, watered and rammed to a true surface all as specified and directed by Engineer - in - Charge. | | 3 | Per Cum |
|---|
| 6 | 6 | M&L Cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate as in foundation, filling and mass concrete all as specified and directed by Engineer - in - Charge | | 1.2 | Per Cum |
|---|
| 7 | 7 | M&L Brick work with old size burnt fly ash bricks, straight or curved on plan exceeding 6 mtr mean radius built in CM 1:6 all as specified and directed by Engineer - in - Charge . | | 10 | Per Cum |
|---|
| 8 | 8 | S & F mild steel work as in hand rails, half round or other steel section or core for wooden hand rail straight portion, drilled and countersunk for balusters running bars, for doors, balusters, nosing to steps including embeding in concrete and screwing etc. wind ties for roof including securing bolts; posts and struts in fencing including cutting tops to shape as directed, drilling holes, notching for wire, etc.; flat iron fillets (for securing wire mesh/ MS work etc.) including all necessary drilling, bolting or riveting, etc., and similar work conforming to Fe-290 Gde E-165 bent to shape all as specified and directed by Engineer - in - Charge. | | 30 | Per \nKg |
|---|
| 9 | 9 | S & F Mild steel bolts, purpose made, with hexagonal or square head one end and screwed the other, or screwed both ends; each scre-wed end to be fitted with washers and one hexagonal or square nut, exc 30cm long all as specified and directed by Engineer - in - Charge. | | 85 | Per \nKg |
|---|
| 10 | 10 | M&L rolled mild steel plates (Plain or chequered) Fe 410-W (Gde E- 250 ), quality-A, channels, square cut or notched (ordinary and counter sunk) forming holes without any attachment complete all as specified and as directed by Engineer-in-Charge. | | 8 | Per \nKg |
|---|
| 11 | 11 | S & F structural steel in roof trusses Fe 410-W (Gde E- 250 ), quality-A, (framed), trussed, purlins, rails and fastenings and heavy bracket framing including distance pieces, cleats etc all as specified and directed by Engineer - in - Charge. | | 200 | Per \nKg |
|---|
| 12 | 12 | S & F Pre- painted galvalume aluminum zinc coating GI based corrugated steel sheet 0.50mm thick of any colour having tensile strength of 550 Mpa as in roof covering/ cladding to wall, fixed with self tapping screws all as specified and directed by Engineer - in - Charge. | | 24 | Per Sqm |
|---|
| 13 | 13 | M & L for 75mm thick cement concrete type C-2 (1:3:6) using 40mm graded stone aggregate as in plinth protection etc all as specified and directed by Engineer - in - Charge. | | 12 | Per Sqm |
|---|
| 14 | 14 | M & L for 100mm thick cement concrete type D-2 (1:4:8) using 40mm graded stone aggregate as in sub floors, sub bases etc all as specified and directed by Engineer - in - Charge. | | 22 | Per Sqm |
|---|
| 15 | 15 | M & L 40 mm thick Cement Concrete 1:2:4 type B–1 using 20mm graded stone aggregates flooring finished even and smooth without using extra cement all as specified and directed by Engineer - in – Charge . | | 22 | Per Sqm |
|---|
| 16 | 16 | S & F glass dividing strips, 3mm thick, 38mm width and inserted in position to conform to design all as specified and directed by Engineer - in - Charge. | | 20 | Per\n RM |
|---|
| 17 | 17 | M & L 10mm thick rendering in Cement Mortar 1:3 on fair faces of brick work or concrete surfaces finished even and smooth without using extra cement complete all as specified and directed by Engineer - in - Charge . | | 30 | Per Sqm |
|---|
| 18 | 18 | M & L rendering 15mm thick on fair faces of brick work or concrete surfaces in CM 1:4 finished even & smooth without using extra cement all as specified and directed by Engineer - in - Charge .\nNote:- The rates do not include for the supply of integral water proofing compound, which shall be paid for in addition at “supplied only rates separately, as applicable. | | 35 | Per Sqm |
|---|
| 19 | 19 | M & L two coats of distemper oil emulsion over a coat of wall putty (Asian / JK / Birla), preparatory to distempering, on newly plastered surfaces of walls including preparation of surfaces all as specified and directed by Engineer - in - Charge. | | 30 | Per Sqm |
|---|
| 20 | 20 | M & L applying two coat of cement base paint on new plastered surfaces of walls including preparation of surfaces complete all as specified and directed by Engineer - in – Charge | | 35 | Per Sqm |
|---|
| 21 | 21 | SCHEDULE 'A' SECTION-II (E&M PORTION) | | | |
|---|
| 22 | 22 | Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth, for foundations or laying cables/ pipes etc and getting out in soft / loose soil all as specified and directed by Engineer - in - Charge. | | 48.6 | Per Cum |
|---|
| 23 | 23 | Returning, filling in, including spreading, levelling, watering and well ramming in layers of soft / loose soil not exceeding 25cm thick all as specified and directed by Engineer - in - Charge. | | 34 | Per Cum |
|---|
| 24 | 24 | Removal of excavated material to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed by Engineer - in - Charge. | | 14.6 | Per Cum |
|---|
| 25 | 25 | M & L sand cushioning for under ground cable, one layer of 8 cm thickness before laying the cable and other layer of 15 cm thickness after laying the cable, punned down to 18 cm thickness all as specified and directed by Engineer-in-Charge.\nNote:- Thickness after punned down shall be considered for payment. | | 14.58 | Per Cum |
|---|
| 26 | 26 | M & L brick protection using old size sub class ‘B’ bricks, laid flat, across the cable i.e. length perpendicular to the axis of cable all as specified and directed by Engineer-in-Charge. | | 13660 | Each\nBrick |
|---|
| 27 | 27 | Supplying, erecting and fixing in position Steel tubular swaged poles complete with cast iron base plate, finial taper plug, bolts, nuts & screws as specified type 410 SP-31 (9.0 metres long) complete all as specified and directed by Engineer - in - Charge (Earthwork and concrete work for embedding poles shall be measured and paid for separately) | | 6 | Each Job |
|---|
| 28 | 28 | M&L Cross arms, bracings, supports, clamps and back plates fabricated from mild steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for bolts, in any shape or size as indicated or directed and inclusive of one primer coat of red oxide, one under coat and one finishing coat of synthetic enamel paint complete all as specified and as directed by Engineer-in-charge. | | 2 | Per Quintal |
|---|
| 29 | 29 | S & F MCB distribution board of sheet metal single pole and neutral 8 way, double door, with 200 Amp rated bus bar 240 volt all as specified and directed by Engineer-in- Charge. | | 1 | Each |
|---|
| 30 | 30 | S & F MCB distribution board of sheet metal single pole and neutral 4 way, double door, with 200 Amp rated bus bar 240 volt all as specified and directed by Engineer-in- Charge. | | 2 | Each |
|---|
| 31 | 31 | S & F MCB single pole 6 to 32 Amp 240 volt with rupturing capacity not less than 10 KA all as specified and directed by Engineer – in – Charge . | | 4 | Each |
|---|
| 32 | 32 | S & F MCB single pole 40 Amp 240 volt with rupturing capacity not less than 10 KA all as specified and directed by Engineer – in – Charge . | | 3 | Each |
|---|
| 33 | 33 | S & F MCB, Single pole & neutral, 240 Volt, 63 Amps, braking capacity 10 KA all as specified and directed by Engineer - in - Charge. | | 3 | Each |
|---|
| 34 | 34 | S & F MCB single pole & neutral 40 Amp 240 volt with rupturing capacity not less than 10 KA all as specified and directed by Engineer – in – Charge. | | 1 | Each |
|---|
| 35 | 35 | Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick, burried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5mtr below normal ground level, connected to and including galvanized iron strip 32x6mm by means of GI bolts, nuts, check nuts and washers and connected other end to main board duly protected by GI pipe 40mm bore medium grade, earth plate surrounded by packed layer of coal dust and common salt 15cm thick all around bottom and top watering pipe 20mm bore of GI medium grade with funnel all as shown in electrical plate No. 3 of SSR Part – I and connecting to earthing test point, main switch board and testing on completion including CI cover, frame and PCC 1:3:6 type C-1 using 20mm graded stone aggregate as in earthing pit with CI cover and frame including necessary earth works etc, complete all as specified and directed by Engineer - in – Charge. Note:- 1. PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode of the earth pit and pipe for watering shall be provided in slanting manner. | | 2 | Each Set |
|---|
| 36 | 36 | Earthing complete with galvanized steel earth plate electrode 60cm x 60cm x 6mm thick, burried directly in ground (earth pit not less than 2.25mtr deep below normal ground level) with top edge of the plate not less than 1.5mtr below normal ground level, connected to and including galvanized iron strip 25x4mm by means of GI bolts, nuts, check nuts and washers and connected other end to main board duly protected by GI pipe 40mm bore medium grade, earth plate surrounded by packed layer of coal dust and common salt 15cm thick all around bottom and top watering pipe 20mm bore of GI medium grade with funnel all as shown in electrical plate No. 3 of SSR Part – I and connecting to earthing test point, main switch board and testing on completion including CI cover, frame and PCC 1:3:6 type C-1 using 20mm graded stone aggregate as in earthing pit with CI cover and frame including necessary earth works etc, complete all as specified and directed by Engineer - in – Charge. Note:- 1. PCC chamber shall be constructed at least 1.5 mtr away from the earth electrode of the earth pit and pipe for watering shall be provided in slanting manner. | | 12 | Each Set |
|---|
| 37 | 37 | S & F submain wiring with two single core cables PVC FRLS insulated unsheathed 6 Sqmm stranded copper conductor drawn in and including PVC conduit with and including PVC insulated 4.0 Sqmm stranded copper conductor cable as earth continuity conductor and connecting complete all as specified and directed by Engineer - in - Charge.\nNote : PVC cables two single core and one single core of sizes as mentioned will considered as one unit. | | 85 | Per \nRM |
|---|
| 38 | 38 | Excavating in trenches, not exceeding 1.5m wide and not exceeding 1.5m in depth, for foundations or laying cables/ pipes etc and getting out in soft / loose soil all as specified and directed by Engineer - in - Charge. | | 302 | Per Cum |
|---|
| 39 | 39 | Returning, filling in, including spreading, levelling, watering and well ramming in layers of soft / loose soil not exceeding 25cm thick all as specified and directed by Engineer - in - Charge. | | 90 | Per Cum |
|---|
| 40 | 40 | Removal of excavated material to a distance not exceeding 50m and depositing where directed at a level not exceeding 1.5m above the starting point all as specified and directed by Engineer - in - Charge. | | 112 | Per Cum |
|---|
| 41 | 41 | M & L sand cushioning for under ground cable 23 cm thick (one layer of 8 cm thickness before laying the cable and other layer of 15 cm thickness after laying the cable) all as specified and directed by Engineer-in-Charge. | | 109 | Per Cum |
|---|
| 42 | 42 | S & F 80mm bore light grade tube galvanised with all fittings laid in trenches or fixed to poles etc. all as specified and directed by Engineer - in – Charge. | | 30 | Per \nRM |
|---|
| 43 | 43 | S & F 50mm bore light grade tube galvanised with all fittings laid in trenches or fixed to poles etc. all as specified and directed by Engineer - in – Charge. | | 34 | Per \nRM |
|---|
| 44 | 44 | Supplying and laying XLPE cable, PVC insulated, armoured, heavy duty multi stranded aluminium conductor, electric cable LT, 1100V grade of size 6 Sqmm 2 core complete all as specified and as directed by Engineer-in-charge. | | 1000 | Per \nRM |
|---|
| 45 | 45 | Supplying and laying or fixing or passing through pipe, 1100 volts grade heavy duty cable XLPE aluminium conductor armoured PVC sheathed 16 Sqmm 2 core nominal cross section in service connections all as specified and directed by Engineer – in - Charge. | | 200 | Per \nRM |
|---|
| 46 | 46 | Supplying and laying XLPE cable, PVC insulated, armoured, heavy duty multi stranded aluminium conductor, electric cable LT, 1100V grade of size 25 Sqmm 2 core complete all as specified and as directed by Engineer-in-charge. | | 400 | Per \nRM |
|---|
| 47 | 47 | Supplying and laying XLPE cable, PVC insulated, armoured, heavy duty multi stranded aluminium conductor, electric cable LT, 1100V grade of size 50 Sqmm 4 core complete all as specified and as directed by Engineer-in-charge. | | 200 | Per \nRM |
|---|
| 48 | 48 | Supplying and laying XLPE cable, PVC insulated, armoured, heavy duty multi stranded aluminium conductor, electric cable LT, 1100V grade of size 120 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-charge. | | 440 | Per \nRM |
|---|
| 49 | 49 | Supplying and laying XLPE cable, PVC insulated, armoured, heavy duty multi stranded aluminium conductor, electric cable LT, 1100V grade of size 150 Sqmm 3.5 core complete all as specified and as directed by Engineer-in-charge. | | 90 | Per \nRM |
|---|
| 50 | 50 | M & L preparing old painted surface of 9 Mtr steel poles, painting the bottom 1.5mtr height above coping with one coat of synthetic enamel paint in alternate strips of black and white or yellow colour 30cm each and the remaining height including all fittings / accessories with one coat of aluminium paint and numbering the pole with synthetic enamel paint white in 80mm high letters over 150mm x 230mm yellow base complete all as specified and directed by Engineer - in - Charge. | | 100 | Each job |
|---|
| 51 | 51 | M & L preparing old painted surface of 11 Mtr steel poles, painting the bottom 1.5mtr height above coping with one coat of synthetic enamel paint in alternate strips of black and white or yellow colour 30cm each and the remaining height including all fittings / accessories with one coat of aluminium paint and numbering the pole with synthetic enamel paint white in 80mm high letters over 150mm x 230mm yellow base complete all as specified and directed by Engineer - in - Charge . | | 4 | Each job |
|---|
| 52 | 52 | Supply installation, testing and commissioning of inverter type air cooled split air conditioner electric driven single phase AC supply with R-410 refrigerant, 240 volts 50 Hz of capacity 2.0 TR comprising of all components e.g. out door condensing unit indoor blower unit, Cordless remote control, wall/roof mounting with suitable brackets as recommended by manufactures confirming to BEE rating not les than 5 Star rating, complete including copper piping of adequate size and of required length as recommended or directed duly insulated with suitable insulating material e.g. glass wool, plywood, moulded thermocoal etc initial charging or refrigerant eco friendly as specified and recommended by manufacturer all as specified and directed by Engineer-In-Charge. Make : VOLTAS/HITACHI/SAMSUNG | | 2 | Each |
|---|
| 53 | 53 | S& F voltage stabilizer automatic operation, three phase, natutally oil cooled (oil filled), indoor type of capacity 100 KVA and designed for input voltage for 300 volt to 480 volt and output voltage stabilized at 415 Volt (+ - 2.5%) and speed of correction 8 volts per second on 50 cycles AC supply complete with volt meter all as specified and directed by Engineer – in – Charge. Make : VINITEC ELECTRONIC / POWER TECH / INDIAN TRANSFORMERS & ELECTRICALS / ELECTRIFIED COMPANY | | 1 | Each |
|---|
| 54 | 54 | S&F FRP looping/junction box with fuse provision and suitable connection for three phase incomming cable 3 phase out going cable and single phase connection for light fiting incl controlled MCB SP-6 Amps - 01 Nos enclosed in thermo plastic in closed shock proof safe complete all as specified and as directed by Engineer-in-Charge. | | 2 | Each |
|---|
| 55 | 55 | S&F LED type street light fitting 60 watt pressure dia cast aluminium housing LED street light luminaries with IP-66 including GI chenel, clamps, nuts, bolts etc with all acessories complete all as specified and as directed by Engineer-in-Charge.\nMake :- Bajaj Cat No. BARFEG 160W LED or equivalent in Philips/CG/Havells | | 2 | Each |
|---|
| 56 | 56 | M & L for boring hole across the Road/plinth/hard standing by trench less technology method suitable for 100mm bore pipe for 0.4 mpa working pressure for cable passing without damaging Road / Plinth /Floor complete all as specified and directed. | | 24 | RM |
|---|
| 57 | 57 | Taking out old unserviceable underground LT Cable upto 300 Sqmm form trenches/floor/road/pipe/along poles including taking out old bricks complete all as specified and directed by Engineer-in-Charge. \nNote :Excavation, earth work required for item shall be measured and paid separately under respective items of BOQ. | | 1700 | RM |
|---|
| 58 | 58 | S&F in repair hot moulded FRP looping/junction box size 280mm x 200 mm for street light poles with locking arrangement and suitable connection for three phase incomming cable 3 phase out going cable and single phase connection or light fitting incl controlled MCB SP-10 Amps - 01 Nos enclosed in thermo plastic in closed shock proof safe IP-65, weather, vermin proof, dust and water proof complete with two Nos cables entry incl gland of standard size with suitable size mild steel clamps to fixed on pole complete all as specified and as directed by Engineer-in-Charge.\nMake :- Neptune/Hensel/Sintex | | 50 | Each |
|---|
| 59 | 59 | M&L for cement concrete in foundations, filling and mass concrete type D-2 1:4:8 with 40 mm graded stone aggrigate for foundation of pole etc complete all as specified and as directed by Engineer-in-Charge. | | 5 | CUM |
|---|
| 60 | 60 | Supply, installation , commissioning and testing of LT Panel duly powder coated outdoor cubical factory made out of CRCA sheet 3.15 mm thick machine pressed and angle iron frame in pedastal 50x50x6mm grouted in PCC 1:2:4 type B1 (20mm graded stone aggregate complete and suitable for 440 Volts AC3 phase 4 wire having insulated copper bus bar 800 Amps TPN with open avle shutter double door on both sides rear and front side with locking arrangement prewired with suitable size of copper conductor cable including incoming and outgoing aonnections with suitable size of copper strip from bus bars to MCCBs complete all as specified and as directed:-\nIncoming\n(a) MCCB 250 Amp 50 KA 4 pole 415 Volts - 01 No\n(b) Digital type Volt meter 0-400 volts with selector switch 01 with\n(c) Digital Amp meter 0-200 Amps with selector switch with suitable CTs\n(d) Indicator lamp LED type showing RYB-01 Set of three\n(e) Power capacitor 1x10 KVAR-01 No\nOutgoing\n(f) MCCB 100 Amp 25 KA TP 440 Volts - 03 Nos\n(g) MCCB 83 Amps TP 440 Volts - 02 Nos\nNote : Space shall be provided for MCCB-01 No as future expansion | | 2 | Each |
|---|
| 61 | 61 | S & F single pole and neutralenclosure with a two pin and earth plug and socket complete with one single pole MCB SPN of capacity 32 A | | 2 | Each |
|---|
| 62 | 62 | Supply, installation, commissioning and testing of LT panel outdoor cubical type, factory made, weather/vermin proof made out of CRAC sheet 3/15 mm thick CPRI approved, duly powder coated and angle iron frame of 50 mm X 50 mm X 6 mm (The base of angle iron frame should be 50 cms above the floor level and the legs 50 cms below the floor level and grouted in PCC (1:2:4) blocks of min size 60 cms X 60 cms X 30 cms -02 Nos type B-1 (20 mm graded stone aggregate) having insulated copper bus bar of 300 Amps rating and panel with openable shutter both side (rear and front size) with locking arrangement and including incomming and out going existing LT UG cables connection with suitable size of copper strip from bus bar to MCCB's complete all as specified and equipped with the following:- \nIncoming\n(i) MCCB, TPN, 350 Amps, 415 Volts, AC Supply, 36 KV rupturing capacity with adjustable thermal & adjustable magnetic seting (O/L. 8-1, S/C 5-10 in. Make - Indo Asian Cat No X2250S3T or equivalent in Havells. L&T - 1 No\nOutgoing\n(i) MCCB, TPN, 200 Amps, 415 Volts, AC Supply, 36 KV rupturing capacity with adjustable thermal & adjustable magnetic setting (O/L. 8-1, S/C 5-10 in. Make - Indo Asian Cat No X153T or equivalent in Havells. L&T - 3 No \n(ii) MCCB, TPN, 63 Amps, 415 Volts, AC Supply, 25 KV reputing capacity with adjustable thermal & adjustable magnetic setting (O/L. 8-1, S/C 5-10 in. Make - Indo Asian Cat No X153T or equivalent in Havells. L&T - 2 No\n(iii) Bus Bar chamber having copper bus bar - 400 Amps for phase 03 Nos and 200 Amps for neutral 01 Nos\n(iv) Digital tyoe voltemeter 0-500 Volts square type 96 mm X 96 mm with selector switch - 01 No.\n(v) Digital type voltementer 0-400 Volts square type 144 mm X 144 mm with CT's (CTR 60/5 Amps) and selector switch - 01 No\n(vi) Tapping of all bus bars with colour code and indiatro bulbs (RYB) with toggle switches 01 job\n(vii) Street light timer 3 phase 32 Amps complete with all accessories i/e MCB 32 Amps, digital time switch contracor fuse unit indicator lamp ratory switch and incomming and outgoing connector etc. | | 3 | Each |
|---|