Repair Replacement Of Gods Lightening Arrestors Ht Lt Bushing Filteration Of Transformer Oil Us Lt Panel Ug Cable Mccbs Lt Acbs And Led Solar Light Painting To Panels Including Earthing System Bus Bar Chamber And Other Connected Works At 24 Ed Under, Manauri, Allahabad-Uttar Pradesh

Military Engineer Services-MES has published Repair Replacement Of Gods Lightening Arrestors Ht Lt Bushing Filteration Of Transformer Oil Us Lt Panel Ug Cable Mccbs Lt Acbs And Led Solar Light Painting To Panels Including Earthing System Bus Bar Chamber And Other Connected Works At 24 Ed Under. Submission Date for this Tender is 27-02-2020. Bushings Tenders in Manauri, Allahabad Uttar Pradesh. Bidders can get complete Tender details and download the document.




Tender Notice

23365747
Corrigendum : Repair Replacement Of Gods Lightening Arrestors Ht Lt Bushing Filteration Of Transformer Oil Us Lt Panel Ug Cable Mccbs Lt Acbs And Led Solar Light Painting To Panels Including Earthing System Bus Bar Chamber And Other Connected Works At 24 Ed Under
Open Tender
Indian
Uttar Pradesh
Manauri, Allahabad
27-02-2020

Tender Details

Repair Replacement Of Gods Lightening Arrestors Ht Lt Bushing Filteration Of Transformer Oil Us Lt Panel Ug Cable Mccbs Lt Acbs And Led Solar Light Painting To Panels Including Earthing System Bus Bar Chamber And Other Connected Works At 24 Ed Under

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 07-Feb-2020 Corrigendum No 01 Date 27-02-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 50000.0 /-
Tender Value
Refer document

BOQ Items

Name of Work: NAME OF WORK: REPAIR / REPLACEMENT OF GOD’s LIGHTENING ARRESTORS, HT/LT BUSHING, FILTERATION OF TRANSFORMER OIL, U/S LT PANEL, UG CABLE, MCCBs, LT ACB's AND LED SOLAR LIGHT PAINTING TO PANELS INCLUDING EARTHING BUS BAR CHAMBER AND OTHER CONNECTED WORKS AT 24 ED UNDER AGE (I) MANAURI
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Excavation in trenches not exc 1.5 M wide and not exc 1.5 M in depth for pipe line, etc getting out in soft/ loose soil and levelling of bottom surface to required level complete all as specified and as directed. (96+157) 253 Cum
2 2 Returning filling in, including spreading, levelling, watering and well ramming in layers not exceeding 25cm complete all as specified and as directed. (45+82) 127 Cum
3 3 Removing excavated material (soil) out side MD land at contractor's own arrangement complete all as specified & directed. (46+75)\n\n 121 Cum
4 4 Supply, laying and spreading of dry (Ganga) sand, free from organic impurities for cushioning as in trenches 8cm depth below cable and 15cm above cable and punned to 10cm depth complete all as specified & directed. (115+63)\n(Note :- Punned thickness shall be considered for measurement purpose) .\n\n 178 Cum
5 5 Labour for dismantling/taking out/cutting etc to XLPE insulated cable upto 33 KV graded in any specification from trench/tray/pole/GOD etc at site to replacing the defective piece/portion or jointing by straight through joint kit etc incl removing brick/cable cover safely for re-using as same existing complete all as specified and directed.\n(Note:- (a) Earth work shall be measured and paid against respecteive item.\n(b) Required T&P and safety equipments shall be arrange by contractor at his own arrangement). 250 RM
6 6 Labour for fault detacting location by using vehicle mounting fault locator machine to move along route layout of XLPE insulated HT 11/33 KV under ground cable at varrious location at AOR by gradually step by step testing of tracing the correct fault location incl making all testing after re-laying of reparied cable as per existing complete all as specified and directed.\n(Note:- Quoted rate shall bedeemed included cost of payment of fees for providing fault locator machine from state electricity authority and its transportion including desel & driver charges complete). 4 Each Job
7 7 Labour for re-laying, connecting, jointing, thimbling using in suitable size and cramping etc to serviceable XLPE insulate cable upto 33 KV grade (Earthed)in all specification incl brick and sand etc all as per existing complete with other site required works complete all as specified and directed. 250 RM
8 8 Supply, laying in trench /fixed with surface of wall/roof etc jointing, thimbling and glanding in suitable size testing of cable XLPE insulated, screened, PVC bedded galvanised steel strip or wire, armoured, electric power cable (heavy duty) with alumunium conductor 11KV, grade cross sectional area 120Sqmm x 3 Core (Earthed) complete all as specified and directed. \n(Make- KEI/Finolex/Nicco/Havells/Paragon/Fort Gloster or equivalent in makes given in Appx 'B' duly approved by AGE (I)) 120 RM
9 9 Supply,laying and testing of reinforced precast concrete cable cover class HVP type 2 with peak size of 450mm x 180mm x 40mm thick complete all as specified and directed. \n(Make: Mehtab tiles, Indore or equivalent in makes given in Appx 'B' duly approved by AGE (I)) 1200 Each
10 10 Labour only for cutting/boring to plinth protection/hard standing/road etc in suitable depth but not less than 45cm, and corssing of GI pipe of size 80mm bore so that XLPE under ground cable can be passed and giving mechanical protection to cable complete all as specified and directed.\nNote:- Quoted rate shall be included the cost of required material for repairing to disturbed surface of plinth protection/hard standing complete all as per existing specification. GI pipe shall be measured and paid seperately under respective itmes of BOQ). (10+20) 30 RM
11 11 Taking up of existing GI tubing in any specification with accessories complete all as specified and directed. 25 RM
12 12 Supply and laying of GI tubing light grade 80mm bore with all fittings laid in trenches across the road or fixed with pole/surface of wall etc as per site conditions with required fixing accessories complete all as specified and directed.\n(Make- Tata/Jindal/Swastic or equivalent in makes given in Appx 'B' duly approved by AGE (I)) 15 RM
13 13 All as per item No 12 above but 50 mm bore. 10 RM
14 14 Supply, fixing, connecting, jointing, thimbling to end of cable testing etc to cable jointing kit for 11 KV (Earthed) grade cable for out door end temination heat shrink type joint complete with jointing material and accessoreis suitable for 120sqmm, 3 core XLPE armoured aluminium conductor cable complete all as specified and directed. \n(Make: Denson/M-seal/Rayhchem or equivalent` makes given in Appx 'B' duly approved by AGE (I)) 4 EACH
15 15 All as per item No 14 but here -in-before but of size 3 core x 95 Sqmm indoor type end termination complete all as specified and directed. 2 EACH
16 16 All as per item No 14 above but out door straight through heat shrik type joint suitable for 11 KV grade 3 core XLPE insulated armoured aluminium conductor cable of size 120 to 185 Sqmm complete all as specified and directed. 1 EACH
17 17 Supply, fixing, connecting, jointing, thimbling to end of cable and commissioning and testing heat shrinkable cable jointing kit suitable for 33 KV grade (Earthed) cable for outdoor type end termination complete with jointing material and accessories suitable for 3 core XLPE insulated armoured aluminium conductor cable of size 300 Sqmm 3 core including taking down existing complete all as specified and directed.\n(Note:- Earth work shall be measured and paid seperately against respective item of BOQ).\n(Make- Denson/M-seal/Rayhchem or equivalent in makes given in Appx 'B' duly approved by AGE (I)) 4 EACH
18 18 All as per item No 17 above but of size 300sqmm 3 core Indoor type end termination joint 1 EACH
19 19 All as per item No 17above but of outdor type straight through heat shrink type joint suitable for 33 KV grade, 300 sqmm 3 core XLPE armoured cable 1 EACH
20 20 Labour only for removing /scrapping rubbing down, cleaning to old fadded paint from surface of steel structure/girder/angle frame etc as per site condition of any size & specification using remmer paper etc and prepairing for re-painting of existing steel surfaces any width or girth complete all as specified and directed 500 SQM
21 21 M&L painting to steel prepared surfaces of any width or girth not otherwise described by using synthetic enamel paint in two coats (one as finishing coat) over one coat of red oxide zinc chrome primer on surface of steel structure/girder/angle frame etc in any description at E/M installation using paint spray gun on specified working pressure including sign making/marking with using different colour in given size of letter etc complete all as specified and directed.\n(Note- Paint colour & shade including writing marking of letters etc shall be deemed included in quoted unit rate and the same shall be approved by Engr-in-charge)\n(Make- Assian/Berger/Dulex or equivalent makes given in Appx 'B' duly by AGE (I)) 70 SQM
22 22 M&L painting using heat resisting paint in two coats (one as finishing) over one coat of red oxide zinc chrome primer on external surface of transformer in any rating/capacity using Ist quality paint and applying thorugh spray gun machine on specified working pressure incl writing of MES/SM No using different colour including writting letter in given size etc after removing/scrapping/rubbing to old fedded paint and filler filling etc complete all as specified and directed.\n(Note- Quoted unit rate shall be deemed included cost of writting letters & filling depresion by using putty, complete Colour & shade shall be approved by Engr-in-charge)\n(Make- Assian/Berger/Dulex or equivalent makes given in Appx 'B' duly by AGE (I)) 16 Each Job
23 23 Supply and fixing in replacement to danger notice plate/caution sign board made out by 1.6mm thick mild steel sheet vitreous enamelled white with letter figures and conventional skull and bones in signal red colour and fixed with MS clamps, bolts and nuts of approved size for HT network in size 25x20 CM complete all as specified and directed. \n(Note- Given caution shall be written in two language i.e Hindi and English and quoted rate shall be deemed included cost of letter writting & conventional skull & bones figure). 10 EACH
24 24 M&L cement concrete 1:4:8 type D-2 using 40mm graded stone aggregate as in foundation, filling & mass concrete complete as specified & directed. (8+2) 10 Cum
25 25 M&L in replacement cross arms bracing, supports, clamps and back plate fabricated from structural steel section including nut & bolts, washers, welding, bending, cold or hot, drilling hole for bolts in any shape or size as indicated over and including of two coat of synthetic enamel paint over a coat of primer red oxide complete all as specified and as directed. 2 Per Qtl
26 26 Dismantling of Air break gang operated switches vertical / horizontal mounted including insulators and operating mechanism for repair / replacement of broken / worn out components and insulators etc complete all as specified and directed. 2 Each Job
27 27 Supply , installation, testing and commissioning of switch air break gang operated HT 11 KV grade triple pole with 12 Nos insulators 200 Amps rating with drop out fuse assembly with fuse carrier, fuse element mounted on insulator and fitted on steel frame, mechanically operated machanism from ground level consisting of operating rod 25mm bore 'light grade' GI pipe of suitable length complete all as specified and as directed. \n(Make: Jaipuria or BHEL or oblum or equivalent makes given in Appx 'B' duly approved by AGE (I)) 2 Each Job
28 28 Supply and fixing ,insatallation, commissioning and testing of lightening arrestor non-linear resistance type single pole made out of porcelain brown glazed, heavy duty station class, gapless, zinc oxide type ( non - linear ) fitted with pressure relief device, arc diverting ports, grading / corona rings, discharge counter with ammeter, mounting insulator type conforming of Fe410W (Gde E-250) including dismantling of old unserviceable lightening arrester complete with comprising following parameters :- \n(i) Nominal system voltage : 33 KV normal discharge current rating 10 KA & high dishcarge with 65 KA assembly. \n(Make: Jaipuria or BHEL or oblum or equivalent makes given in Appx 'B' duly approved by AGE (I)) 1 SET OF THREE
29 29 All as per item No 28 above but suitable for 11 KV working pressure. 2 SET OF THREE
30 30 M&L for in replacement Anti climbing device spikes type fabricated out of MS bar (round, Square and flat) including nuts, bolts, washer and welding in two holes made to shape to suit the cross section of the pole complete all as specified and directed 0.5 Per Qtl
31 31 Supply testing and commissioning of battery cell 2 volts DC dry type suitable for battery bank 30 Volt DC dry type chargeable stationery battery set, 90 hours capacity maintenance free batteries operating to DC control panel to 33 KV & 11 KV VCB in sheet metal cabinet floor mounted type suitable for input 230 volt single phase 50Hzs and making control wiring for connecting the DC triping set of above VCB control panel complete all as specified and directed.\n(Make: Excide or Luminious or equivalent makes given in Appx 'B' duly approved by AGE (I)) 6 Each Job
32 32 Supply only aerial fuses porcelain type suitable for line wire with brass contact bolt and nuts maximum current rating 30 Amps in 3 mm dia of wire complete all as specified and directed. 100 EACH
33 33 Supply only aerial fuses porcelain type suitable for line wire with brass contact bolt and nuts maximum current rating 15 Amps in 3 mm dia of wire complete all as specified and directed. 50 EACH
34 34 Supply only aluminium thimble/lugs suitable for thembling to XLPE insulated cable in size 300 Sqmm x 3 core, 33 KV grade complete all as specified and directed. 5 SET OF THREE
35 35 M & L Painting to existing two/three steel pole structure of 11 mtr height including mild steel work like cross arms, clamps, pipe channel, bracing etc after cleaning and prepration of surfaces painting externally above planting depth with one coat of aluminum paint over a coat of aluminum primer including preparation of existing surfaces and marking pole numbers in 15 cm dia with approved colour in circular and making 03 Numbers & 02 Numbers of bands & strips with 30 cm wide fluorescent paint from bottom of pole to 1.5 mtr height of pole complete all as specified and as directed.\n(NOTE: Cutting of bushes & tree branches upto 3m height of pole shall be deemed included in quoted unit rate.) 8 Each Job
36 36 Supply and fixing in replacement to PG clamp suitable for ACSR for making inter connection on 33 KV network complete all as specified and directed 12 Each
37 37 Supply , straining and stringing in replacement of aluminium conductor steel reinforced (ASCR) in any specification making interconnection of newtwork fixing on existing structure/pole complete all as specified and directed.\n(Note: Sagging length of ACSR conductor shall be deemed included in the quoted unit rates). 1 Per Qtl
38 38 M&L for Caliberation, servicing, testing commissioning re-setting (Earth fault protection, over loading current & short cercuit current) controlling relay of 33/11KV step down transformer rating/capacity 1500 KVA controlling by SF-6 in rating 630 KVA -01 No and as same controlling to 33/0.433 11KV-06 Nos connecting with out going feeder (network) and interconnecting bus cuppler located at 33 KVA MRS ( Main recieing station) by Engineer of government authorised agency with connecting & protecting of equipment complete all as specified and directed.\nNote (i) Quoted rate shall be included to required minor spares for making serviceable \n(ii) Duplicate copy of time setting test report of network shall be deposited by contractor in sub divn for office record. 1 Each Job
39 39 M&L checking (all connection and mechanism) cleaning overhauling servicing of 3 phase 11 KV ring main unit (RMU) 8 Nos extensible type 630 Amps rating including replacement to minor spare such as spring copper finger/contact set male and female locking arrangment , operating handle, plencer assembly rocking gear, auxillary switch, relay time re-setting, right mechanism etc to all for making serviceable by Engineer of Govt approved agency reassembling testing and commissioning etc as site complete all as specified and directed.\n(Note:- Quoted rate shall be included cost of rquired other spares to made fully functional & serviceable of RMU). 1 Each Job
40 40 Dismantling of insulator any type and any size complete all as specified and as directed. 12 EACH
41 41 S & F pin type insulator of size 150 mm height, 150 mm dia, 11000 volt grade, porcelain, vitreous, white, brown or green including 01 No galvanised mild steel spindle, two galvanised iron washers and one galvanised iron nuts complete all as specified and as directed.\n(Make: Jaipuria or BHEL or oblum or equivalent makes given in Appx 'B' duly approved by AGE (I)) 12 EACH
42 42 Demolition of cement concrete in ground floors and paving n exc 15 cm thickness (below or above ground level) complete all as specified & directed. 8 Cum
43 43 M&L brick work with sub class 'B' bricks using old size bricks straight or curved on plan exc 6m mean radius built in cement mortar CM (1:6) for plinth foundation & cable trenches required in E/M installation complete as specified & directed. 14 Cum
44 44 Demolition of brick work or stone/boulder masonary built in cement mortar including all quions arches, pillar etc complete all as specified & directed. 14 Cum
45 45 Supply and filling broken/crushed stone boulder filling dry handpacked tightly laying in layers on ground surface in size 40 to 50mm after excavation, removing, dressing, leveling, compact work etc all as per site rquirement on existing ground surface of E/M installations complete all as specified and directed.\nNote:- Quoted unit rate shall be deemed included cost required for earth work to prepare the surface for laying boulder in layers with compact work. 50 Cum
46 46 M&L cement plaster 15mm thick in CM (1:4) on fair faces of brick work or concrete surface finished even and smooth without using extra cement complete all as specified and directed . 140 SQM
47 47 M & L for earthing complete with galvanized steel earth plate electrode of size 60 cm x 60 cm x 6 mm thick buried directly in ground (earth pit not less than 2.25 metre deep below the ground level) with top edge of earth plate not less than 1.50 metre below normal ground level connected to galvanized earth lead strip 32 x 6 mm size by means of nut, bolts & check nuts and washers of galvanized iron or steel connected to Earthing test point complete all as specified or indicated , including earthing pit with PCC 1 : 3 : 6 type C 1 using 20mm graded stone aggregate & RCC cover slab 40 mm thick as in RCC 1:2:4 type B-1 using 20mm graded stone aggregate, reinforced with 8mm dia TMT bars @ 150 mm centre to centre both way with two Nos lifting handle, GI pipe 20 mm dia 'light grade' with funnel and wire mesh for watering and 40 mm dia 'light grade' GI pipe for GI earth strip 32 x 6mm protection etc complete all as shown in electrical plate No. 3 of SSR Part - I (2009) including testing on completion complete all as specified and directed. 6 Each Set
48 48 M&L earth continuity conductor or main earthing lead fixed to wall on batten or recess or chacess or burried in ground or drawn in conduit / pipes or fixed to pole or any other indicated situation for loop earthing etc for galvanised earth strip 32 x 6mm including taking down existing strip complete all as specified and directed. 100 RM
49 49 Taking out stone/chequered tile by excavation the surface with required T&P, cleaning the area by removing the vegetation /grass, stacking the crushed stone/chequred tile or other cleaning for refixing in old/new position after filling & compacting of approved soil in complete area not less than 100mm thick, spraying the anti grass treatment in complete area and proper levelling of area around the 33 KV switch yard, complete and refixing/regilling by relaying the stone aggregate and relaying the chequred tile in CM (1:4) complete all as specified and directed.\n(Note: Approved soil shall be measured and paid seperately under respective items of BOQ) 700 SQM
50 50 Supply only for filling purpose of apporved fine soil obtained from outside MOD land and to laid in the 33 KV switch yard duly well rammed, compacted and levelled complete all as specified and directed.\n(Note: Approved soil shall be measured at filling area after dedcution of 10% for obtaning on standard prproctor density to optimum moisture condition) 105 Cum
51 51 M&L Servicing of 33 KV switch yard outdoor equipment including isolators- 15 Nos, CTs-4 Set, PTs-4 Set, lightenning arrestor and all the other outdoor equipment by opening their connection and cleaning contacts with sand papper, greasing the equipment whose required reconnecting all the connections and all the works required at site complete\n(Note: The rates quoted shall be deemed included cost of T&P and other items required at site ) 1 Each Job
52 52 De-hydration/ filtration of transformer oil by hiring on line filtration plant to achieve di-electric strength not less than minimum 45 KV including following work services:-\n(a) Removal of all suspended particles such as dust, rust, scales, collided carbon oxidation sludge etc upto < 1 micron.\n(b) De-hydration of transformer oil under vaccum\n(c) Circulation of heated oil and filling of treated oil in transformer tank. \n(NOTE: (i) Contractor shall use the vehicle mounted filtration plant with new suitable size heavy duty hose pipe.\n(ii) The transformer oil required for replacing/ top up shall be measured and paid seperately as " Supply only". \n(iii) conducting field testing of di-electric strength of the transformer oil before and after filteration.\n(iv) Checking the megger/ earth resistance values with battery operated megger of 5 KV. 5000 Ltr
53 53 Supply and filling new Transformer oil having die electric strength not less than 45 KV in sealed container complete including centrifuging of oil (if required ) up to getting dielectric strength not less than 45 KV complete all as specified and directed. \n(NOTE: Transformer oil will be supplied by the contractor in sealed container of approved make alongwith necessary manufacturer test cetificate and purchase vouchers).\nMake: Power oil or Savita or equivalent make given in Appx 'B' duly approved by AGE (I) 600 Ltrs
54 54 Rectifying and arresting the oil leakage of transformer of any capacity, disconnection of cable termination of HV& LV ends , opening the top cover by using tripod, chain and pulley after removing all fitments, replacing the components of the transformer such as gaskets, "O" rings etc. Rectify the leaks in a variety of areas such as radiator fins, flanges, circuit breakers, valves, fastener assemblies, Oil leakage through pin hole / crack joint , drain valve / radiator valve , Oil leakages through gasket joints. Applying putty/M-Seal Monoplast where ever necessary. Refixing the top cover and all fitments, refixing cable termination of the HV& LV ends, \n(Note : Testing and Cost of all type of rubber gasket, "O" rings, putty/M-Seal Monoplast, lugs, nuts, bolts, double washers etc shall deemed to be included in the quoted unit rate). 1 Each Job
55 55 Supply only brass terminal studs with nuts, oil seal and washer for LV side of transformer capacity range 160 KVA to 250 KVA including replacement of gasket etc to make transfromer leak proog complet all as specified and directed 6 EACH
56 56 Supply only brass terminal studs with nuts, oil seal and washer for LV side of transfomer capacity rage 300 KVA to 500 KVA including replacement of gasket etc to make transfromer leak proog complete all as specified and directed 4 EACH
57 57 Supply only brass terminal studs with nuts, oil seal and washer for LV side of transfomer capacity rage 160 KVA to 400 KVA including replacement of gasket etc to make transfromer leak proog complet all as specified and directed 6 EACH
58 58 Disconnecting/ removing of HT/LT cable and earth connections of copper wound, 11KV/ 433 Volts capacity 160 KVA to 500 KVA outdoor/indoor type transformer of Make Indian transformer and Electrical Pvt Ltd at sub station , by draining out of the transformer oil in empty barrels provided by the department, transporting the unserviceable transformer to a approved agncy workshop of OEM only (T&P and vehicle to be arranged by contractor under quoted unit rate) and transporting oil filled barrels in store provided by the department at a distance not exceeding 2 KM, servicing of transformer comprising of followig works services:-\n(a) Opening of top cover by removing nuts, bolts and all mounting accessories and conservator tanks for visual inspection. (b) Checking of HV/LV insulators including internal inspection. (c) Replacement of corroded nuts/ bolts with double washers, burned lugs, etc by new one. (d) Servicing of tap changing gears by cleaning and polishing tapping contact points. (e) Removing, cleaning, polishing of bushings and studs of both HV/LV side by using soft cotton cloth including checking for cracking and refixing the same. (f) Refixing all cable terminals HV/LV sides and transformer top cover, conservator tank and other fitments in position. (g) Cleaning and heating of silica gel in breather. (h) Connecting HV/LV side with existing incomming and outgoing cables including re-connection of earth strip/ lead. (j) HV side cable connection shall be made with new HV tape & M seal monoplast as required at site. (k) All marshalling boxes to be cleaned from inside. (l) All the terminal connection of control and relay wiring to be checked and tighten. (m) Examine the rollers carefully includes greasing them properly. (n) Checking of earthig connection and tightening nuts & bolts with ensuring the earthing system working properly complete all specified & directed.\n(NOTE:- (i) Records shall be maintained for each transformer of each capacity duly signed by contractor and Engineer-in-Charge.\n(ii) Any serious faults/ defect to be carried out under this item and paid separately under respective item of BOQ.\n(iii) Inventory of parts to be rplaced during overhauling of transformer at workshop will be maintained & signed by Engr-in-Charge and OEM agencies certification of transformer overhauling & thier liability/gurantee/warntee will be prodcued by contractor before payment of this item in RAR. 1 Each \nJob
59 59 Taking out of the following old defective part from existing transformer of capacity 160KVA to 500 KVA of any make ( for the transformer mentioned under item No. 58 here-in-before) and in lieu providing new part in the above transformer complete all as specified and directed by theEngineer-in-Charge:-\n(a) Replacement of HV/LV leg coil in copper winding with insulation varnishing and baking coil assembly and rewinding with super enamelled double paper covered copper wire/ strip for HV/LV (11/0.433 KV) winding having existing size and proper insulation and demoisturising before assembling the winding core and including primary testing, ration testing no load testing, core insulation testing as directed by EIC. \n(NOTE: Rewinding and testing on load transformer will be carried through approved firm of OEM only). 120 KG
60 60 Disconnecting removing of LT cable and earth connections of copper wound, 1100 volt grade from treches /duct /pipe including bricks setting aside for reuse or made to schedule of cerdit as per site required complete all as specified and directed.\n(Note:- Earth work shall be measured and paid under respecitive items of BOQ) 200 RM
61 61 M&L brick, sub class 'B' bricks laid dry, flat, length equal to width of brick over sand cusioning in trenches for cable protection complete all as specified and directed 6216 Each
62 62 Labour only for laying existing cable of any specification in trench/air/drawn thorugh in GI pipe under across the road/path etc all as per site requirement complete all as specified and directed. 200 RM
63 63 Supply, laid in trench /fixed with surface of wall/roof etc jointing, thimbling and glanding in suitable size testing to cable XLPE insulated, screened, PVC bedded galvanised steel strip or wire armoured electric LT cable with alumunium conductor 1100 volts, grade cross section area 4 core x 25 Sqmm complete all as specified and directed. \n(Make- Havells/Finolex/RPG/Polycab/Paragon/Fort Gloster or equivalent make in Appx 'B' duly approved by AGE (I)) 150 RM
64 64 All as per item No 63 above but size of cable 3.5 core x 50 Sqmm 150 RM
65 65 All as per item No 63 above but size of cable 3.5 core x 70 Sqmm 250 RM
66 66 All as per item No 63 above but size of cable 3.5 core x 95 Sqmm 100 RM
67 67 All as per item No 63 abvoe but size of cable 3.5 core x 120 Sqmm 260 RM
68 68 Supply & fixing in replacement 40mm dia GI tubing 'light grade' with fixing acessories laid in trenches or on wall or pole with clamp complete all as specified & directed.\n\n(make: Tata/Jindal/Swastic or equivalent make in Appx 'B' duly approved by AGE (I))\n\n\n 12 RM
69 69 All as per item No 68 above of but size of 50mm dia 12 RM
70 70 All as per item No 68 above but of size of 80mm dia 12 RM
71 71 S&F in replacement MCCB, 3 pole, TP 63 Amp rating having breaking capacity of 16 KA at 415V adjustable thermal process based magnetic setting type Ics=75% Icu complete all as specified aid directed\n\n(Make: Legrand Cat part No 420003 or equivalent make in Appx 'B' duly approved by AGE (I))\n 2 Each
72 72 All as per item No 71 above but 3 pole 125 Amps capacity.\n\n(Make: Legrand Cat part No 420006 or equivalent make in Appx 'B' duly approved by AGE (I)) 5 Each
73 73 S&F in replacement MCCB, 4 pole, 320 Amp rating having breaking capacity of 36 KA at 415V adjustable thermal process based magnetic setting type Ics=75% Icu complete all as specified aid directed.\n(Make: Legrand Cat part No 422006 or equivalent make in Appx 'B' duly approved by AGE (I)) 2 Each
74 74 Labour only for fixing in replacement MCCB in any specification make, model etc and supply and fixing extended poles with nuts, bolts and washers to be fixing incl making complete all internal connection using suitable size of copper cable /strip complete all as specified and directed\n(Note MCCB of any size & capacity shall be issued by Deptt under Sch 'B Stores free for fixing only). 50 Each Job
75 75 M&L repair/replacement of LT panel lock with key in rear/front hinges in any specification/make/model with required cutting, welding , jointing, reveting etc work using angle iron in existing specification on requirement and painting in two coat of synthetic enamel paint over one coat of red oxide primer and matching with existing surface complete all as specified and directed. 3 Each Job
76 76 S&F in replacement of Voltmeter in size as required with accuracy class 1.5 and rated burden 15VA square type, range 0-500 volts including selector switch and making necessary connection with FRLS copper wire of suitable size complete all as specified and directed.\n(Make: AE/L&T/Seimens or equivalent make in Appx 'B' duly approved by AGE (I). Size and model shall be approved by AGE (I)) 4 Each
77 77 S&F in replacement of Ammeter with accuracy class 1.5 in size as required square type, range 0-300 Amps maximum voltage range 0-500 V with selector switch and making necessary connection with copper wire of suitable size complete all as specified and directed.\n(Make: AE/L&T/Seimens or equivalent make in Appx 'B' duly approved by AGE (I). Size and model shall be approved by AGE (I) 4 Each
78 78 S&F replacement of LED type indication lamps in different colours with base and making internal connection complete all as specified and directed.\n(Make: AE/L&T/Seimens or equivalent make in Appx 'B' duly approved by AGE (I). Size and model shall be approved by AGE (I)) 4 SET OF THREE
79 79 S&F replacement of CTs of suitable range (100/5 ratio) with making necessary connection complete all as specified and directed.\n(Make: AE/L&T/Seimens or equivalent make in Appx 'B' duly approved by AGE (I). Size and model shall be approved by AGE (I)) 6 SET OF THREE
80 80 All as per item No 79 above but CTs of suitable range (200/5 ratio) 4 SET OF THREE
81 81 Disconnection/dismantling /taking out open to body for removing to unserviceable spares of ACB (Air Cercuit Breaker) in any rating/make/model etc incl replacing to deffective spares, refixing, connecting, testing , commissioing and required minor spare to made functional of ACB complete all as specified and directed\n(Note:- Spare of ACB's shall be measured and paid seperately against respective items of BOQ) 1 Each Job
82 82 S&F testing commissioning to spare of ACB (Air Cercuit Breaker) of capacity 630 Amps rating in original manufacturers (OEM) specification and model of make : Crompton Greaves as under:-\n(Note: Make & model number of spare parts of OEM shall be approved by AGE (I))
83 82.01 (a) Microprocessor base OCR (IPR) 1 Each
84 82.02 (b) Spring Charging Motor 1 Each
85 82.03 (c) Shunt trip/closing coil 110V to 415 V as suitable 1 Each
86 82.04 (d) Maint CTs 1/ 800A 6 Each
87 82.05 (e) Neutral CTs 1/800A 1 Each
88 82.06 (f) Under voltage trip device (UVT) 1 Each
89 82.07 (g) Key interlock (lock+key) 1 Each
90 82.08 (h) Filed Test unit 1 Each
91 83 Labour only for servicing/testing and relay re-setting of APFC panel in any rating Make model up to 125 KVA DG Set etc by technical representative of authorised agency all to made serviceable compete all as specified and directed. \n(Note: Required spare shall be measured and paid seperately against respective items of BOQ as under) 4 Each Job
92 84 Supply and fixing, testing etc to under mentioned spare suitable for APFC panel rating upto 125 KVA DG Set in any make model rating etc in original manufactrers as per existing make & model of Kirloskar/Po`wer green/Mahindra) as under:-
93 84.01 (a) Capacitor metalized poly propylene heavy duty (MPP-H) for 3 phase 440 volts & 50 Hz system for permissible non-linear load 15% of 1 KVAR capacity\n(Make: Havells/Seimens/Schiender or equivalent make in Appx 'B' duly approved by AGE (I)) 8 Each
94 84.02 (b) All as per item No 84.01 above but in rating 2 KVAR 3 Each
95 84.03 (c) All as per item No 84.01 above but in rating 3 KVAR 4 Each
96 84.04 (d) All as per item No 84.01 above but in rating 4 KVAR 4 Each
97 84.05 (e) All as per item No 84.01 above but in rating 5 KVAR 4 Each
98 84.06 (f) All as per item No 84.01 above but in rating 7.5 KVAR 4 Each
99 84.07 (g) All as per item No 84.01 above but in rating 10 KVAR 4 Each
100 84.08 (h) All as per item No 84.01 above but in rating 12.5 KVAR 4 Each
101 84.09 (j) All as per item No 84.01above but in rating 15 KVAR 4 Each
102 84.1 (k) All as per item No 84.01 above but in rating 20 KVAR 4 Each
103 84.11 (l) All as per item No 84.01 above but in rating 25 KVAR 4 Each
104 84.12 (m) Contactors for capacitor heavy duty, type MOC for rating 30 KVAR, 440 Volt, 3 Phase, 50 Hz\n(Make: Havells cat part No CS96148 or equivalent make in Appx 'B' duly approved by AGE (I) 4 Each
105 84.13 (n) Contactors for capacitor heavy duty, type MOC for rating 50 KVAR, 440 Volt, 3 Phase, 50 Hz\n(Make: Havells cat part No CS96324 or equivalent make in Appx 'B' duly approved by AGE (I) 4 Each
106 84.14 (m) Contactors for capacitor heavy duty, type MOC for rating 80 KVAR, 440 Volt, 3 Phase, 50 Hz.\n(Make: Havells cat part No CS96148 or equivalent make in Appx 'B' duly approved by AGE (I) 4 Each
107 85 Supply and fixing in replacement of heavy duty solar battery 12 Volt, 75 Ah suitable for solar street lighting system including connecting lead with contact made out by copper and applying petrolium jelly layer on terminal post complete all as specified and directed.\n(Make: Exide model 6LSM 75L or Okaya or Amron or equivalent make in Appx 'B' duly approved by AGE (I) 4 Each Job
108 86 M & L for earthing complete with galvanized steel earth plate electrode of size 60cm x 60 cm x 3.15mm thick buried directly in ground (earth pit not less than 2.25 metre deep below the ground level) with top edge of earth plate not less than 1.50 metre below normal ground level connected to galvanized earth lead strip 32 x 6 mm size by means of nut, bolts & check nuts and washers of galvanized iron or steel connected to Earthing test point complete all as specified or indicated , including earthing pit with PCC 1 : 3 : 6 type C 1 using 20mm graded stone aggregate & RCC cover slab 80 mm thick as in RCC 1:2:4 type B-1 using 20mm graded stone aggregate, with x PM Jali with two Nos lifting handle, GI pipe 20 mm dia 'light grade' with funnel and wire mesh for watering and 40 mm dia 'light grade' GI pipe for GI earth strip 32 x 6mm protection etc complete all as shown in electrical plate No. 3 of SSR Part - I (2009) including testing on completion complete all as specified and directed. \n(Note: RCC pit cover shall be precast of RCC (1:2:4) type B-1, 80mm thick reinforced with xPM Jali weighing not less than 4Kg/Sqm in lieu of CI cover) 3 Each Set
109 87 Supply, jointing, commissioning and testing heat shrinkable cable end termination/straight through jointing kit suitable for 1100 volt grade (Earthed) cable for outdoor type complete with jointing material and required accessories suitable for under ground XLPE cable of size 4 Core x 16 Sqmm complete all as specified and directed. \n(Make: Dension/3M/Rahycam or equivalent make in Appx 'B' duly approved by AGE (I)) 3 EACH
110 87.01 (a) All as per item No 87 above but in rating 4 core x 25 Sqmm 3 Each
111 87.02 (b) All as per item No 87 above but in rating 3.5 core x 50 Sqmm 3 Each
112 87.03 (c) all as per item No 87 but in rating 3.5 core x 70 Sqmm 2 Each
113 87.04 (d) All as per item No 87 above but in rating 3.5 core x 95 Sqmm 2 Each
114 87.05 (e) All as per item No 87 above but in rating 3.5 core x 120 Sqmm 2 Each
115 87.06 (f) All as per item No 87 above but in rating 3.5 core x 150 Sqmm 4 Each
116 87.07 (f) All as per item No 87 above but in rating 3.5 core x 240 Sqmm\n(Note: Net contract sum shall be arrived after deduction of "schedule of credit" amount from total quoted amount of BOQ) 2 Each