| 1 | 1 | M&L for rectification of fault of electrical circuit of 11 KV VCB by checking, repair from CT/PT and programming of multifunctional meters and replacement of defective wiring with FRLSH multistranded PVC insulated copper conductor 1100 volts grade as per existing size of wire complete all as specified and directed | | 30 | Job |
|---|
| 2 | 2 | M&L for rectification of fault of control circuit of 11 KV VCB by checking, repair of close / trip / spring charging circuit replacement of defective wiring with FRLSH multistranded PVC insulated copper conductor 1100 volts grade as per existing size of wire complete all as specified and directed | | 30 | Job |
|---|
| 3 | 3 | M&L for rectification of fault of indication circuit of 11 KV VCB by checking, repair of indicating LED lamp circuit, annuciation system replacement of defective wiring with FRLSH multistranded PVC insulated copper conductor 1100 volts grade as per existing size of wire complete all as specified and directed | | 35 | Job |
|---|
| 4 | 4 | M&L for rectification of fault of heater circuit of 11 KV VCB by checking, repair of thermostat / heater circuit system replacement of defective wiring with FRLSH multistranded PVC insulated copper conductor 1100 volts grade as per existing size of wire complete all as specified and directed | | 45 | Job |
|---|
| 5 | 5 | M&L for rectification of fault of AC light circuit of 11 KV VCB by checking, repair of door switch, B-22 polycarbonate holder and replacement of defective wiring with FRLSH multistranded PVC insulated copper conductor 1100 volts grade as per existing size of wire, Lamp holder, door switch complete all as specified and directed | | 65 | Job |
|---|
| 6 | 6 | M&L for rectification of fault of DC 110V circuit of 11 KV VCB by checking, repair from battery charger to VCB and and internal distribution to other components /system and replacement of defective wiring with FRLSH multistranded PVC insulated copper conductor 1100 volts grade as per existing size of wire complete all as specified and directed | | 28 | Job |
|---|
| 7 | 7 | M&L for setting of 3 ph overcurrent + earth fault numerical relays by primary injection of current to CTs with suitable equipment for overcurrent & earth fault with high set and low set including checking of all other parameters of relays for proper tripping order after disconection of incoming or out going HT XLPE cable connection from VCB CTs and reconnection of cable ends at existing terminals after completion of relay setting complete all as specified and directed. (Note: (a) Relay setting shall be made considering corresponding values of upstream and down stream VCB relays and recorded maximum demand of VCB. Any further adjustment of values as many times require shall be carried out within the quoted rate. (b) Recovery shall be made double the quoted rate if VCB fails to trip in indicated fault and if group tripping recorded) | | 11 | Job |
|---|
| 8 | 8 | M&L for maintenence/servicing of PT unit 11KV / 110V by disconneting and taking out from panel mounted position, checking & cleaning of fixed and moving contact points, cleaning/decarbonising of busbar connections, resin cast PTs using hot blower, CTC solution,applying backtol (Red) solution to the epoxy PT body, tightening of all nuts, bolts, washers, and refixing the same PT to original position, testing complete all as specified and directed. | | 12 | Job |
|---|
| 9 | 9 | M&L for maintenance of 11KV CT chamber by disconneting all 3 phase cable connections, extended busbars and from VCB Bus and taking out from panel mounted position, testing for proper functioning, body leakage, checking & cleaning / decarbonising of all contact points of CT, epoxy body and Busbars, complete CT chamber using hot blower and CTC solution, applying backtol (Red) solution to the CT body and refixing the same CT to original position, re-connection of all existing cables, extended busbars, testing complete all as specified and directed. | | 50 | Job |
|---|
| 10 | 10 | Maintenance, servicing, cleaning of Busbur chamber of each VCB including conneting busbar from CT to Busbar, spout, support insulator, opening of covers, using CTC and clean cloth and hot air blower, checking for any loose contact, tigtening of all nuts & bolts, refixing all covers complete all as specified and directed | | 30 | Job |
|---|
| 11 | 11 | Maintenance, servicing, cleaning of vaccum circuit breaker unit of 11 KV VCB panel of capacity 400 Amps to 2500 Amps, taking out from panel, cleaning of all parts with CTC and clean cloth, removal of carbon deposited inside the moving contacts, greasing of all moving parts of the VCB, checking of complete operating mechanism for proper functioning, reporting for any defective parts, complete all as specified and directed. \n(Note: Replacement of defective parts of the VCB shall be measured and paid separately) | | 20 | Job |
|---|
| 12 | 12 | Supply and fixing Schneider Micom P-127 protection relay, 110V, 5A, type-BAOZ112Ca1 to Schneider make 11KV VCB including necessary connection testing complete including dismantling taking down unserviceable one complete all as specified and directed. | | 2 | Each |
|---|
| 13 | 13 | Supply and fixing Schneider High speed trip relay, type-VAJH, 110V to Schneider make 11KV VCB including necessary connection testing complete including dismantling taking down unserviceable one complete all as specified and directed. | | 2 | Each |
|---|
| 14 | 14 | Supply & fixing closing coil assembly 110 V DC to Schneider make 11KV VCB including necessary connection testing complete including dismantling taking down unserviceable one complete all as specified and directed.\nMake- Schneider, Part No- ECO39SN134900FN | | 21 | Each |
|---|
| 15 | 15 | Supply and fixing tripping coil 110 V DC to Schneider make 11KV VCB including necessary connection testing complete including dismantling taking down unserviceable one complete all as specified and directed. \nMake- Schneider, Part No- ECO39SN134100FN | | 22 | Each |
|---|
| 16 | 16 | Supply and fix including dismantling taking out unserviceable Closing Coil Box Assembly without Coil for 800A to 2500A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only. Part No-SPR39SASS0008FN_S | | 4 | Each |
|---|
| 17 | 17 | Supply and fix including dismantling taking out unserviceable Trip Coil Box Assembly without Coil for 800A to 2500A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only. Part No-SPR39SASS0007FN_S | | 3 | Each |
|---|
| 18 | 18 | Supply and fix including dismantling taking out unserviceable vacuum interrupter of suitable for VCB of capacity 2500 Amps complete all as specified and directed. \nMake-Schneider only. Part No-VSLVG4002-01 | | 3 | Each |
|---|
| 19 | 19 | Supply and fix including dismantling taking out unserviceable Breaker Nylon Wheel, for 800A to 2500A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No-MVIA00054-01 | | 10 | Set of 4 |
|---|
| 20 | 20 | Supply and fix including dismantling taking out unserviceable Trip Guide Roller for 800A to 2500A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No-MBR39S4323100FN | | 4 | Each |
|---|
| 21 | 21 | Supply and fix including dismantling taking out unserviceable Dashpot Assembly For 800A to 2500A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No-MHU39S3828900FN\n | | 4 | Each |
|---|
| 22 | 22 | Supply and fix including dismantling taking out unserviceable spring charging Universal motor with gear box 220V AC For 800A to 2500A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No-MVIJOO157-02 | | 3 | Each |
|---|
| 23 | 23 | Material & Labour for dismantling taking out burnt spring charging Universal motor with gear box 220V AC from 800A to 2500A Schneider make 11 KV VCB, transportation to civil workshop, rewinding complete motor with required size of super enamelled copper wire, heating, vernishing and transportation back to site, refixing to original position in VCB, connections, testing complete all as specified and directed.. | | 12 | Job |
|---|
| 24 | 24 | Supply and fix including dismantling taking out unserviceable micro switch assy (motor cut-off limit (micro) switch with 2 NO + 2 NC) for 800A to 2500A Schneider make 11 KV VCB complete all as specified and directed. Make-Schneider only, Part No- ESW-H-ABD00-001/ESW-H-ABC00-001 | | 8 | Each |
|---|
| 25 | 25 | Supply and fix including dismantling taking out unserviceable Release Lever (Nylon ) for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only , Part No- MVIJ00010-01 | | 6 | Each |
|---|
| 26 | 26 | Supply and fix including dismantling taking out unserviceable Buffer (For Opening Spring ) for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- MVIJ000980-1 | | 29 | Each |
|---|
| 27 | 27 | Supply and fix including dismantling taking out unserviceable Buffer (For Closing Spring ) for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- MVIJ00056-01 | | 29 | Each |
|---|
| 28 | 28 | Supply and fix including dismantling taking out unserviceable Breaker Auxiliary Switch 12Way Aux.Switch For 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- MVIE00114-01 | | 2 | Each |
|---|
| 29 | 29 | Supply and fix including dismantling taking out unserviceable Rectifier unit (Monoblock) for spring charging motor for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- ERC-A-A00DC-001 | | 15 | Each |
|---|
| 30 | 30 | Supply and fix including dismantling taking out unserviceable Push to Trip Knob (Red) assembly - With spring & Housing for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- SPR39SASS0001FM-S | | 3 | Each |
|---|
| 31 | 31 | Supply and fix including dismantling taking out unserviceable Push to close Knob (green) Assembly - With spring & Housing for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- SPR 39SASS0002FM-S | | 3 | Each |
|---|
| 32 | 32 | Supply and fix including dismantling taking out unserviceable ON -OFF Indicator Assembly-with spring for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- SPR 39SASS0003FM | | 4 | Each |
|---|
| 33 | 33 | Supply and fix including dismantling taking out unserviceable Charge -free indicator Assembly-with spring for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- SPR39SASS0004FM | | 4 | Each |
|---|
| 34 | 34 | Supply and fix including dismantling taking out unserviceable Secondary Plug & Scoket 24 pin for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- MHU39S0019000FM | | 2 | Each |
|---|
| 35 | 35 | Supply and fix space heater, 230V, 100 watt inside cable chamber including necessary connection, testing complete all as specified and directed. \nMake- Schneider, Part No-EHT-A-AA 000-001 | | 25 | Each |
|---|
| 36 | 36 | Supply and fix including dismantling taking out unserviceable thermostat for space heater for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- ETH-E-B000-001 | | 35 | Each |
|---|
| 37 | 37 | Supply and fix including dismantling taking out unserviceable HRC Fuse-Pt HT Side (VTF-11, 3A) for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- EHF-A-EV 000-001 | | 3 | Each |
|---|
| 38 | 38 | Supply and fix including dismantling taking out unserviceable Service /Test Position Limit Switch 1NO+1NC for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- ESW-B-AAA00-001 | | 2 | Each |
|---|
| 39 | 39 | Supply and fix including dismantling taking out unserviceable Breaker Control Switch for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake- L&T, Part No- 73257SEB03PGYR | | 6 | Each |
|---|
| 40 | 40 | Supply and fix including dismantling taking out unserviceable LED Indicating Lamp & Holder Red-Green-Blue-White-Amber Assembly for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only | | 175 | Each |
|---|
| 41 | 41 | Supply and fix including dismantling taking out unserviceable Control Circuit HRC Fuse : 2 A , 4 A , 6 A , 10A, complete all as specified and directed. \nMake- L&T, Type-HG, size-F1 Cat No- ST-30725 to ST-30728\n\n | | 30 | Each |
|---|
| 42 | 42 | Supply and fix including dismantling taking out unserviceable bakelite HRC Fuse holder : 2 A , 4 A , 6 A , 10A complete all as specified and directed. \nMake- L&T, Type-HD 20H , Fuse type-F1 Cat No- ST-30772\n\n\n | | 16 | Each |
|---|
| 43 | 43 | S&F multifunctional meter with LED disply, accuracy class-1, e-nevigator, including dismantling taking down unserviceable one and connection, programming, testing complete all as specified and directed. \nMake- Elmeasure, Model- EN-8400 | | 11 | Each |
|---|
| 44 | 44 | Supply and fix including dismantling taking out unserviceable Isolating Contact for 800A to 1600A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- MVIK00190-01 | | 24 | Each pair |
|---|
| 45 | 45 | Supply and fix including dismantling taking out unserviceable Isolating Contact for 2000A to 2500A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Schneider only, Part No- MVIK00190-02 | | 12 | Each pair |
|---|
| 46 | 46 | Supply and fix including dismantling taking out unserviceable Resin Cast CT dual core, CT racio- 100/50/5A-5A for 800A to 2500A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Kappa/Esun/Pragati\n | | 6 | Each |
|---|
| 47 | 47 | Supply and fix including dismantling taking out unserviceable Resin Cast CT dual core, CT racio- 600/300/5A-5A for 800A to 2500A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Kappa/Esun/Pragati\n\n | | 3 | Each |
|---|
| 48 | 48 | Supply and fix including dismantling taking out unserviceable Resin Cast CT dual core, CT racio- 800-400/5A-5A for 800A to 2500A Schneider make 11 KV VCB complete all as specified and directed. \nMake-Kappa/Esun/Pragati\n\n | | 3 | Each |
|---|
| 49 | 49 | M&L for painting to steel surface of CT Chamber inside wall all side with one coat of synthetic enamel paint after preparation of surface complete all as specified and directed. | | 33 | Job |
|---|