Sales : +91-777 804 8217
| Name of Work: Construction of 33-11KV Sub-station in Sector-32 SS-5, Yamuna Expressway Development Authority | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1 | BOQ-A : | |||
| 2 | 1.01 | SUPPLY,UNLOADING, HANDLING, ERECTION, TESTING & COMMISSIONING OF FOLLOWING EQUIPMENTS | |||
| 3 | 1.02 | Rates for installation shall include all taxes.The work include Handling, Storage, shifting the equipment to site, assembly, alignment, cleaning,installation, testing and commissioning including labour, tools, tackles,consumables etc. (for specifications refer section D) | |||
| 4 | 1.03 | 33kV HT PANELS | |||
| 5 | 1.04 | Indoor type 6 panel board Vacuum circuit breaker (1 No. Incomer 1250 Amps+ 2 No. Outgoing 1250 Amp+ 2 No. Tie Feeder 1250 Amp+ 1 No. Bus Coupler 1250 Amp) 33 KV, 3 phase, 31.5 KA for 1 sec. HT switch gear with all necessary protection, metering and other accessories as required (M.R. ITEM NO. 1) | 1 | Nos. | |
| 6 | 1.05 | Indoor type 2 panel board Bus PT, 33 KV, 3 phase, 31.5 KA for 1 sec with all necessary protection, metering and other accessories as required (M.R. ITEM NO. 2(A)) | 1 | Nos. | |
| 7 | 2 | Supply, Installation, testing & commissioning of out door type 10 MVA with on load tap changer Power Transformer as per ISI specification including loading, unloading, local carriage & erection of the same on plinth & making all necessary connection etc. Complete in all respects as per specification(Make ABB/Crompton/Schinider) E-12.Cable termination box with disconnecting facility for 33 KV XLPE cable at 33 KV side.cable termination box with disconnecting facility for 11 KV XLPE cable at 11 KV side. | |||
| 8 | 2.01 | On load tap changer+/- [email protected]%,Bi directional roller,Conservator with drain valve,Earthing ferminals,Double diaphragm explosion vent,Radiator with top & bottom shut off valve,First filling of oil including make up fill,Silica gel breather with oil seal,Rating and diagram plate,Air Release plug,Buchholz relay with shut off valve,Winding temperature indicator (WTI),Oil temperature indicator (OTI),Megenatic oil level guage,Pressure relief device,Marshalling box.No load losses-8Kw, load losses 50KW,Toleronce as per I.S (Analysis of rates) | 2 | Nos. | |
| 9 | 3 | 11kV HT PANELS | |||
| 10 | 3.01 | Indoor type 12 panel board Vacuum circuit breaker (2 No. Incomer 1250 Amps, 1 No. bus coupler 1250 Amps and 9 Nos.630Amp Outgoing) 11 KV, 3 phase, 25 KA for 1 sec. HT switch gear VCB breaker with all necessary protection, metering and other accessories as required. (Analysis of rates-18) | 1 | No. | |
| 11 | 3.02 | Indoor type 2 panel board Bus PT, 11 KV, 3 phase, 25 KA for 1 sec with all necessary protection, metering and other accessories as required (M.R. ITEM NO. 2(B)) | 1 | Nos. | |
| 12 | 4 | DC BATTERY, CHARGER & DISTRIBUTION BOARD | |||
| 13 | 4.01 | Supplying, assembling, installation, commissioning of Sealed maintenance free (SMF) 110V D.C., 200 AH batteries. The batteries shall rest on treated wooden planks fabricated from MS angle and free standing floor mounted rack with acid resistant finish and complete with series connecting electrical leads and charging of batteries. The batteries shall be accompanied with tester. | |||
| 14 | 4.02 | This shall have incoming leads as well as outgoing leads and of suitable battery charger for 8 hrs charge of 200AH battery charger enclosed in sheet metal with fan on top and it should automatically charge the batteries With booster and trickle charge. Charger shall be complete with incoming & outgoing leads and D.C. Distribution board will have one set of 63 amps MCB as incomer and ten number of suitable rated MCB (as per coil rating of VCB) on outgoing side enclosed in metal sheet enclosure of 2mm thick and suitably painted. The unit will be complete with bus bars, accessories, links, terminal strip, clamps etc along with cables up to incoming & outgoing to VCB panels. (Analysis of rates E-7) | 1 | No. | |
| 15 | 5 | HT CABLES & CABLE TERMINATIONS | |||
| 16 | 5.01 | Supply, delivery, laying testing & commissioning of 33KV (E), XLPE cable having compacted circular staranded aluminium conductor, conductor screening of extruded semi conducting compound, cross linked polythylane (XLPE), insulation screening of the extruded semin conducting compound followed by copper tape, cores laid up, taped PVC inner sheath, single layer of steel strip armouring, overall PVC outer sheath conforming to IS: 7098 (Part-amendments) for following mentioned sizes. | |||
| 17 | 5.02 | It should be operational at 33 KV, 50 Hz. AC system in ground at a depth of 1200 mm below ground level over a cushion of 75 mm thick sand alround and protected with bricks on sides and top on surface the cable run shall be fixed on M.S. clamps etc of suitable size or as directed by the E/I. Complete in all respect. The price are inclusive of all earth work such as digging, back filling, supply & spreading of good earth all around the cable, supply & providing cable identification markers. The installation should be complete in all respects and as per requirement of the job. \n(CCI (Bombay/Nashik), Fort Gloster (Calcutta / Baripara), Asian (Thane / Silvasha), Universal (Satna), Nicco (Calcutta), ICL (Rajpura), Diamond, Havells make | |||
| 18 | 5.03 | 33kV, 3C X 400 sq. mm. from 33kV HT Panel to 33/11kV Power transformer (Analysis of rates-4e) | 50 | Mtrs. | |
| 19 | 5.04 | 11kV, 3C X 300 sq. mm. (From 33/11 Power Transformer to 11 KV HT Panles) (Analysis of rates-3g) | 200 | Mtrs. | |
| 20 | 6 | Supply, Delivery, Installation, Testing & Commissioning of 33KV, following type cable termination kit complete in all respects as required for proper completion of work. (make Raychem, CCI, Frontec) SOR-10 | |||
| 21 | 6.01 | 33kV, 3C X 400 sq. mm. XLPE insulated, Aluminum conductor E grade, strip armoured cable (Analysis of rates-10d) | 2 | Nos. | |
| 22 | 6.02 | 11kV, 3C X 300 sq. mm. XLPE insulated, Aluminum conductor E grade, strip armoured cable (Analysis of rates-5d) | 8 | Nos. | |
| 23 | 7 | Supply, Installation, testing and commissioning of Outdoor REYCHEM RPG push on type termination kits suitable for following sizes of 33 & 11 kV, XLPE insulated Aluminum conductor E grade, strip/round wire armoured cable. | |||
| 24 | 7.01 | 33kV, 3C X 400 sq. mm. XLPE insulated, Aluminum conductor E grade, strip armoured cable from 33kV HT Panel to 33/11kV Power transformer (Analysis of rates-10d) | 2 | Nos. | |
| 25 | 7.02 | 11kV, 3C X 300 sq. mm. XLPE insulated, Aluminum conductor E grade, strip armoured cable (Analysis of rates-6d) | 4 | Nos. | |
| 26 | 8 | CONTROL CABLE | |||
| 27 | 8.01 | Supply, Installation, testing and commissioning of Control cables of following sizes to be laid buried in ground or laid on cable trays for transformers and VCB | |||
| 28 | 8.02 | 1.1kV GRADE STRANDED COPPER CONDUCTOR, PVC INSULATED WRAPPED PVC INNER & OUTER SHEATHED CABLE. | |||
| 29 | 8.03 | CABLE 4CX2.5SQMM (Analysis of rates E-49) | 200 | Mtrs. | |
| 30 | 8.04 | CABLE 19CX1.5SQMM (M.R. ITEM NO. 21) | 200 | Mtrs. | |
| 31 | 8.05 | Supply, Installation, testing and commissioning of Cable end terminations/Glands/lugs for 1.1kV grade stranded copper conductor, pvc insulated wrapped pvc inner & outer sheathed cable for transformers and VCB. | |||
| 32 | 8.06 | CABLE 4CX2.5SQMM (M.R. ITEM NO. 23) | 4 | Nos. | |
| 33 | 8.07 | CABLE 19CX1.5SQMM (M.R. ITEM NO. 23) | 4 | Nos. | |
| 34 | 9 | DISTRIBUTION BOARDS | |||
| 35 | 9.01 | Supplying and fixing following way prewired TP&N MCB distribution board of steel sheet for 415 volts on surface/ recess complete with loose wire box, terminal connectors for all incoming and outgoing circuits, duly prewired with suitable size FR PVC insulated copper conductor up to terminal blocks, tinned copper bus bar, neutral link, earth bar, din bar, detachable gland plate, interconnections, powder painted including earthing etc of DB's (FOR LIGHTING & SMALL POWER) | |||
| 36 | 9.02 | Note- Each incoming and outgoing MCB's shall have Ics = 10 kA minimum | |||
| 37 | 9.03 | 12 Way TPN DB \nIncoming\n1 No. 63A 4P MCB \n3 Nos. 40A DP ELCB in each incomer (100 mA Sensitivity)\nOutgoing\n36 Nos 6/16A SP MCB's spread equally in each phase. (M.R. ITEM NO. 8) | 2 | Nos. | |
| 38 | 10 | POWER SOCKETS | |||
| 39 | 10.01 | Supply, Installation, testing and commissioning of OF POWER SOCKETS,SWITCH COMPLETE WITH ACCESSORIES LIKE GI BOXES,SHEET STEEL ENCLOSURE ETC. AS REQUIRED. | |||
| 40 | 10.02 | 2 Nos. 6/16 Amps 5 pin socket controlled by separate 16 Amps modular type switch for each socket housed in GI box of suitable size (UPS socket for computer). (DSR 1.24.5 & 1.32 (2016)) | 2 | Nos. | |
| 41 | 10.03 | 6/16 Amps 6 pin socket controlled by 16 Amps modular type switch housed in GI box of suitable size. (DSR 1.24.5 & 1.32 (2016)) | 33 | Nos. | |
| 42 | 10.04 | Flame proof/Retardent type 6/16 Amps 6 pin socket controlled by 16 Amps modular type switch housed in GI box of suitable size. (M.R.(MDS-LEGRAND)) | 3 | Nos. | |
| 43 | 10.05 | Supplying and fixing 20 A, 240 V, SPN Industrial type socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A, “C” curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete. [DSR(E&M)-2016/2.18/P-14] | 5 | Each | |
| 44 | 10.06 | 63 A TP metal clad industrial socket controlled by 63 A TP MCB housed in sheet steel enclosures (DSR 7.41 & 2.9.1 (2016)) | 2 | Nos. | |
| 45 | 11 | LIGHTING FIXTURES | |||
| 46 | 11.01 | Supply, Installation, testing and commissioning of lighting fixtures shall include the supporting steel structures, clamps/connectors and all other accessories required for proper fixing of the lighting fittings. | |||
| 47 | 11.02 | Supply of luminaires complete with accessories like lamps, ballasts, power factor improvement capacitors, starters etc as an integral part of luminaire. However, in case of Non-integral type luminaires rate shall include separate metal enclosed control gear box with terminal block suitable for loop-in, loop-out connection. Outdoor type fixtures shall be provided with outdoor type weather-proof box with IP 54 or better. All fixtures shall be wired with Electronic ballast. | |||
| 48 | 11.03 | 2x28W Surface mounted fixtures complete with choke, starter, T5 lamps etc.(Wipro catalogue no.WIF 20228/equivalent) (M.R. ITEM NO. 24) | 48 | Nos. | |
| 49 | 11.04 | 2x28/36W Surface mounted flame proof type fixtures complete with choke, starter, T5 lamps etc.(Crompton Greaves-EXTL240/equivalent) (M.R. ITEM NO. 29) | 2 | Nos. | |
| 50 | 11.05 | 2x18W surface type compact fluorescent fixtures complete with choke, starter, tube etc.(Wipro catalogue no.WVP 45218/equivalent) (M.R. ITEM NO. 30) | 4 | Nos. | |
| 51 | 11.06 | 2x28W recessed mounted fixtures complete with choke, starter, T5 lamps etc.(Wipro catalogue no.WVF 58228/equivalent) (M.R. ITEM NO. 31) | 10 | Nos. | |
| 52 | 11.07 | 2x28W outdoor type wall mounted fixtures complete with all accessories as required.(Philips HGS-120 or Equivalent) (M.R. ITEM NO. 33) | 5 | Nos. | |
| 53 | 11.08 | 250W Metal halide flood light including 1 X 250W Metal halide lamp, control gear box etc. complete with all accessories.(Wipro- WFZ 42250 or Equivalent) (M.R. ITEM NO. 32) | 2 | Nos. | |
| 54 | 12 | CEILING / WALL BRACKETS/ EXHAUST FANS | |||
| 55 | 12.01 | Supply, Installation, testing and commissioning of 1200mm dia sweep ceiling fan with standard down rod. (M.R. ITEM NO. 34) | 9 | Nos. | |
| 56 | 12.02 | Supply, Installation, testing and commissioning of Oscillating type wall fan 400mm dia. (M.R. ITEM NO. 35) | 2 | Nos. | |
| 57 | 12.03 | Supply, Installation, testing and commissioning of 300mm dia heavy duty 900 RPM exhaust fan complete with louvered shutters. (M.R. ITEM NO. 36) | 10 | Nos. | |
| 58 | 13 | POINT WIRING | |||
| 59 | 13.01 | Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. | |||
| 60 | 13.02 | Group C [DSR(E&M)-2016/1.10.3/P-2]\nNote:-Telephone, computer wiring are not in the scope of electrical works. | 92 | Point | |
| 61 | 14 | SUB-MAIN WIRING | |||
| 62 | 14.01 | Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface/ recessed medium class PVC conduit as required. | |||
| 63 | 14.02 | 2x2.5 Sqmm + 1x2.5 Sqmm earth wire [DSR(E&M)-2016/1.14.2/P-3] | 50 | Metre | |
| 64 | 14.03 | 2x4 Sqmm + 1x4 Sqmm earth wire [DSR(E&M)-2016/1.14.3/P-3] | 300 | Metre | |
| 65 | 14.04 | 2x6 Sqmm + 1x6 Sqmm earth wire [DSR(E&M)-2016/1.14.4/P-3] | 100 | Metre | |
| 66 | 14.05 | 4x16 Sqmm + 2x6 Sqmm earth wire [DSR(E&M)-2016/1.14.11/P-3] | 100 | Metre | |
| 67 | 15 | EARTHING SYSTEM | |||
| 68 | 15.01 | Supply, Installation, testing and commissioning of earthing system | |||
| 69 | 15.02 | GI PLATE EARTHING FOR TRANSFORMERS BODY AND HT PANELS | |||
| 70 | 15.03 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. [(DSR(E&M)-2016/5.4/P-27)] | 8 | Set | |
| 71 | 15.04 | CU PLATE EARTHING FOR TRANSFORMERS NEUTRALS | |||
| 72 | 15.05 | Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. [DSR(E&M)-2016/5.6/P-27] | 4 | Set | |
| 73 | 15.06 | PIPE EARTHING FOR LIGHTNING ARRESTER LPDB,BUILDING EARTHING ) | |||
| 74 | 15.07 | Earthing with G.I. earth pipe 4.5 meter long, 40 mm dia including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal/ coke and salt as required. [DSR(E&M)-2016/5.2/P-27] | 16 | Each | |
| 75 | 15.08 | ELECTRONIC EARTHING FOR INSTRUMENTATION SYSTEM | |||
| 76 | 15.09 | Earthing with G.I. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. (but without charcoal/ coke and salt) as required. [DSR(E&M)-2016/5.3/P-27] | 4 | Set | |
| 77 | 15.1 | Supply,fixing and terminating of following conductors with PVC sleeves and wires in trenches including providing sand cushioning, brick protection etc. or laying on surface with GI clamps, bolts and nuts etc. | |||
| 78 | 15.11 | 40 x 10 mm GI strip (M.R. ITEM NO. 20) | 300 | Meters | |
| 79 | 15.12 | 32 x 6 mm Copper strip (DSR 6.13 (2016)) | 80 | Meters | |
| 80 | 15.13 | 25 x 5 mm GI strip (DSR 5.9 (2016)) | 50 | Meters | |
| 81 | 15.14 | 25 x 5 mm braided copper tape (DSR 5.14 (2016)) | 75 | Meters | |
| 82 | 15.15 | 25 x 6 mm GI strip (DSR 5.9 (2016)) | 50 | Meters | |
| 83 | 16 | CABLE TRAYS | |||
| 84 | 16.01 | Fabrication /Supply and Installation of Cable trays with accessories such as coupling plates, bends, tees, reducers, coupling nut-bolts etc. of following width. The cost of installation shall include connection, bolting, cutting, etc.The supporting steel for cable trays shall be painted type and Cable trays, accessories and covers shall be painted with one shop coat of red oxide zinc chromate primer and two site coats of aluminium alkyd paint. | |||
| 85 | 16.02 | Ladder type trays– Prefabricated 2.5mm G.I.(Hot Dip Galvanised),75mm flange height | |||
| 86 | 16.03 | 600 mm width (M.R. ITEM NO. 12) | 200 | Meters | |
| 87 | 16.04 | 450 mm width (M.R. ITEM NO. 13) | 100 | Meters | |
| 88 | 16.05 | Perforated type trays– Prefabricated 2.5mm G.I.(Hot Dip Galvanised),75mm flange height . | |||
| 89 | 16.06 | 300 mm width (DSR 4.1.4 (2016)) | 100 | Meters | |
| 90 | 16.07 | 150 mm width (DSR 4.1.2 (2016)) | 50 | Meters | |
| 91 | 16.08 | 100 mm width (DSR 4.1.1(2016)) | 50 | Meters | |
| 92 | 16.09 | Cable tray covers: Cable tray Covers shall be of GI sheet of 1.6 mm thick with clip fix clamps | |||
| 93 | 16.1 | Cover for 150mm wide tray (M.R. ITEM NO. 18) | 50 | Meters | |
| 94 | 16.11 | Cover for 100mm wide tray (M.R. ITEM NO. 19) | 50 | Meters | |
| 95 | 17 | LIGHTNING PROTECTION SYSTEM | |||
| 96 | 17.01 | Supplying, fixing & commissioning vertical air terminating fixtures with spikes mounted on 25mm dia GI pipe of atleast 2000mm length with base plate, bonding of earth strips etc. DSR 6.2 (2016)) | 1 | Nos. | |
| 97 | 17.02 | Air Termination System | |||
| 98 | 17.03 | Supply & laying of 20 x 3 mm GI Strip as ring conductor. (DSR 6.7 (2016)) | 250 | Mtr. | |
| 99 | 17.04 | Down conductors | |||
| 100 | 17.05 | Supply & laying of 20 x 3 mm GI Strip as ring conductor. (DSR 6.8 (2016)) | 50 | Mtr. | |
| 101 | 17.06 | Testing Joints & earth termination system | |||
| 102 | 17.07 | Providing test links with enclouser (DSR 6.12 (2016)) | 3 | Nos. | |
| 103 | 17.08 | Earth pits G.I. pipe earthing complete as per specifications. (Ordinary type) (DSR 5.2 (2016)) | 3 | Nos. | |
| 104 | 17.09 | Iditification plate of earthing pit with associated work (MR Item No.-38) | 3 | Nos. | |
| 105 | 18 | MISCELLANEOUS ITEMS | |||
| 106 | 18.01 | Earth work in excavation in ordinary soil in all type of foundation trenches including dressing of the side and ramming of bottom. Lifts upto 1.5m including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50m. All kinds of soil. (MORTH/A.R./GNIDA) | |||
| 107 | 18.02 | Depth from 0.0 to 1.5 M below G.L. | 500 | Cum | |
| 108 | 18.03 | Supplying, fixing, testing & commissioning heavy duty PVC pipe with all necessary conduit accessories etc. of the following sizes | |||
| 109 | 18.04 | 100mm dia conduit (MR Item No-3) | 20 | Mtr | |
| 110 | 18.05 | 300mm dia conduit (MR Item No-4) | 20 | Mtr | |
| 111 | 18.06 | Supply & Laying of double wall corrugated ( DWC) pipes of following dia hume pipe/HDPE Pipes for crossing the cables under the roads and paved areas & underground cable protection as per IS 14930 Part II. With necessary connecting socket/couplings, tees of some material at required depth up to 900 mm below road ground surface. backfilling of with light ramming is included in the scope. | |||
| 112 | 18.07 | 120mm dia dwc (Analysis of rates-52) | 100 | Mtr | |
| 113 | 18.08 | Supply & Installation of following Items:- | |||
| 114 | 18.09 | 33 kV Danger Caution Boards (Danger Notice Plates) as per IS 2551 & IS 8923 (DSR 2.22 (2016)) | 2 | Nos. | |
| 115 | 18.1 | 11 kV Danger Caution Boards (Danger Notice Plates) as per IS 2551 & IS 8923 (DSR 2.22 (2016)) | 2 | Nos. | |
| 116 | 18.11 | HV insulating mats confirming to IS 15652-2006. The mats should have been type tested by CPRI or another third party lab of equivalent stature. The mats shall be moisture proof, fire retardant and resistant to acids, alkalies & transformer oil. | 2 | Nos. | |
| 117 | 18.12 | First Aid box (MR Item No-05) | 1 | Nos. | |
| 118 | 18.13 | Shock treatment chart (MR Item No-39) | 1 | Nos. | |
| 119 | 19 | Sub-Station Automation System | |||
| 120 | 19.01 | Supply, assembling, installation, commissioning and testing of SCADA gateway and system at sub-station level complete with 1 No. data concentrator in a panel, 1 No. ethernet switch, GPS clock, FOTE equipment 1 No. laptop, 1 No. Desktop for local HMI, 1 NO. UPS (5 KVA), Radio modem and all other accessories as reqiured. (MR Item No-41) | 1 | Set | |
| 121 | 20 | Optical Fiber Cable | |||
| 122 | 20.01 | Supply, Installation, testing and commissioning of Optical Fiber Cable armoured of following sizes to be buried in ground / laid in trays, installation of cable markers. Miscellaneous items such as clamp, cleat cable tags etc. are included in the scope. | |||
| 123 | 20.02 | 6 core, multi mode armoured optical fiber cable (for sub station local/data concentrator) (MR Item No-43) | 150 | Mtr. | |
| 124 | 20.03 | 12 core, single mode armoured optical fiber cable (from sub station to LDC) (MR Item No-43) | 5000 | Mtr. | |
| 125 | 21 | Part-B : (Structural Part) | |||
| 126 | 21.01 | Earth work | |||
| 127 | 21.02 | Earth work in excavation in ordinary soil in all type of foundation trenches including dressing of the side and ramming of bottom. Lifts upto 1.5m including getting out the excavated soil and disposal of surplus excavated soil as directed within a lead of 50m. All kinds of soil. (MORTH/A.R./GNIDA) | |||
| 128 | 21.03 | Depth from 0.0 to 1.5 M below G.L. | 1227.34 | Cum | |
| 129 | 22 | Filling available excavated earth (excluding rock) in trenches, plinth, sides of foundations etc. in layers not exceeding 20cm in depth, consolidating each deposited layer by ramming and watering, lead upto 50m and lift upto 1.5m. (AR/GNIDA) | 579.42 | Cum | |
| 130 | 23 | Carriage/disposal of earth/material by mechanical transport including loading, unloading and stacking. (AR/GNIDA). Earth: | |||
| 131 | 23.01 | Lead upto 2.0 Km. | 647.92 | Cum | |
| 132 | 24 | Concrete Work | |||
| 133 | 24.01 | Providing and laying in position cement concrete of specified grade excluding the cost of centring and shuttering - All work upto plinth level: (Cast-in-Situ) | |||
| 134 | 24.02 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size). (DSR-16/4.1.8/P-88) | 119.22 | Cum | |
| 135 | 24.03 | 1:4:8 (1 Cement : 4 coarse sand (zone-III) : 8 graded stone aggregate 40 mm nominal size). (DSR-16/4.1.8/P-88) | 20 | Cum | |
| 136 | 25 | Providing and laying in position machine batched and machine mixed design mix M-25 grade cement concrete for reinforced cement concrete work, using cement content as per approved design mix, including pumping of concrete to site of laying but excluding the cost of centering, shuttering, finishing and reinforcement, including admixtures in recommended proportions as per IS: 9103 to accelerate, retard setting of concrete, improve workability without impairing strength and durability as per direction of Engineer-in-charge. “(Note:- Cement content considered in this item is @ 330 kg/cum.“Excess/ less cement used as per design mix is payable/recoverable separately). | |||
| 137 | 25.01 | All works upto plinth level. (DSR-16/5.33.1/P-102) | 407.12 | Cum | |
| 138 | 25.02 | All works above plinth level upto floor V level. (DSR-16/5.33.2/P-102) | 334.84 | Cum | |
| 139 | 26 | Providing and laying damp-proof course 40mm thick with cement concrete 1:2:4 (1 cement : 2 coarse sand (zone-III): 4 graded stone aggregate 12.5mm nominal size) (DSR-16/4.10/P-90) | 45 | Sqm | |
| 140 | 27 | Reinforcement steel work/Steel Ebmeements | |||
| 141 | 27.01 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete upto plinth level. | |||
| 142 | 27.02 | Thermo-Mechanically Treated bars of grade Fe-500D or more./Cold twisted bars. (DSR-16/5.22.6/P-100) | 46000 | Kg. | |
| 143 | 28 | Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level. | |||
| 144 | 28.01 | Cold twisted bars (DSR-16/5.22A.3/P-99) | 55000 | Kg. | |
| 145 | 29 | Providing and fixing bolts including nuts and washers complete. (DSR-16/10.20/P-185) | 3938.76 | Kg. | |
| 146 | 30 | Form work | |||
| 147 | 30.01 | Centering and shuttering including strutting, propping etc. and removal of form for all heights : | |||
| 148 | 30.02 | Foundations, footings, bases of columns, etc. for mass concrete. (DSR-16/5.9.1/P-98) | 790.2 | Sqm | |
| 149 | 30.03 | Suspended floors, roofs, landings, balconies and access platform (DSR-16/5.9.3/P-98) | 3686.19 | Sqm | |
| 150 | 31 | Steel work | |||
| 151 | 31.01 | Structural steel work riveted, bolted or welded in built up sections, trusses and framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer all complete. (DSR-16/10.2/P-182) | 9399.44 | Kg. | |
| 152 | 32 | Brick work/Concrete block masonry | |||
| 153 | 32.01 | Brick work with bricks of class designation 150 in foundation and plinth in: | |||
| 154 | 32.02 | Cement mortar 1:6 (1 cement : 6 coarse sand) (DSR-16/6.1.2/P-111) | 101 | Cum | |
| 155 | 33 | Brick work with bricks of class designation 150 in superstructure above plinth level upto floor V level in all shapes and sizes in: | |||
| 156 | 33.01 | Cement mortar 1:6 (1 cement : 6 coarse sand) (DSR-16/6.4.2/P-111) | 298 | Cum | |
| 157 | 34 | Half brick masonry with bricks of class designation 150 in superstructure above plinth level upto floor V level. | |||
| 158 | 34.01 | Cement mortar 1:4 (1 cement : 4 coarse sand). (DSR-16/6.13.2/P-112) | 34 | Sqm | |
| 159 | 35 | Finishing work (Plaster) | |||
| 160 | 35.01 | 12mm cement plaster of mix: 1:6 (1 cement : 6 fine sand) (DSR-16/13.1.2/P-227) | 1440 | Sqm | |
| 161 | 36 | 6mm cement plaster of mix: 1:3 (1 cement : 3 fine sand) (DSR-16/13.16.1/P-228) | 670.4 | Sqm | |
| 162 | 37 | 18 mm cement plaster in two coats under layer 12 mm thick cement plaster 1:5 (1 cement : 5 coarse sand) finished with a top layer 6 mm thick cement plaster 1:6 (1 cement : 6 fine sand). (DSR-16/13.11/P-228) | 456 | Sqm | |
| 163 | 38 | Wall Finishing | |||
| 164 | 38.01 | White washing with lime to give an even shade: New work (three or more coats) (DSR-16/13.37.1/P-230) | 128.8 | Sqm | |
| 165 | 39 | Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade : \nTwo or more coats on new work. (DSR-16/13.60.1/P-232) | 808.8 | Sqm | |
| 166 | 40 | Finishing walls with water proofing cement paint of required shade : \nNew work (two or more coats applied @ 3.84 Kg/10 Sqm.) (DSR-16/13.44.1/P-230) | 147.2 | Sqm | |
| 167 | 41 | Painting with acid proof paint of approved brand and manufacture of required colour to give an even shade :\nTwo or more coats on new work. (DSR-16/13.64.1/P-233) | 491.2 | Sqm | |
| 168 | 42 | Wall Dado | |||
| 169 | 42.01 | Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. (DSR-16/11.36/P-196) | 158.4 | Sqm | |
| 170 | 43 | Wall Skirting | |||
| 171 | 43.01 | Cement plaster skirting up to 30 cm height, with cement mortar 1:3 (1 cement : 3 coarse sand), finished with a floating coat of neat cement. | |||
| 172 | 43.02 | 18mm thick. (DSR-16/11.6.1/P-191) | 123.7 | Sqm | |
| 173 | 44 | Providing and laying Vitrified tiles in different sizes (thickness to be specified by the manufacturer), with water absorption less than 0.08% and conforming to IS: 15622, of approved brand & manufacturer, in all colours and shade, in skirting, riser of steps, laid with cement based high polymer modified quick set tile adhesive (water based) conforming to IS: 15477, in average 6 mm thickness, including grouting of joints (Payment for grouting of joints to be made separately). | |||
| 174 | 44.01 | Size of tile 500x500mm (DSR-16/11.47.1/P-198) | 189.9 | Sqm | |
| 175 | 45 | Providing edge moulding to 18 mm thick marble stone counters, Vanities etc., including machine polishing to edge to give high gloss finish etc. complete as per design approved by Engineer-in-Charge. | |||
| 176 | 45.01 | Granite work. (DSR-16/8.3.2/P-128) | 19.2 | Metre | |
| 177 | 46 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. (DSR-16/11.27/P-195) | 32 | Sqm | |
| 178 | 47 | Floor finish | |||
| 179 | 47.01 | Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS: 15622, of approved make, in all colours and shades, laid on 20mm thick cement mortar 1:4 (1 cement : 4 coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including grouting the joints with white cement and matching pigments etc., complete. | |||
| 180 | 47.02 | Size of tile 1000x1000mm (DSR-16/11.41.4/P-197) | 180 | Sqm | |
| 181 | 48 | Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including pointing the joints with white cement and matching pigment etc., complete. (DSR-16/11.37/P-196) | 49.5 | Sqm | |
| 182 | 49 | Providing and fixing 10 mm thick acid and/or alkali resistant tiles of approved make and colour using acid and/or alkali resisting mortar bedding, and joints filled with acid and/or alkali resisting cement as per IS : 4457, complete as per the direction of Engineer-in- Charge. | |||
| 183 | 49.01 | In flooring on a bed of 10 mm thick mortar 1:4 (1 acid proof cement : 4 coarse sand). Acid and alkali resistant tile (DSR-16/11.21.1.1/P-194) | 413.1 | Sqm | |
| 184 | 50 | Kota stone slabs 20 mm thick in risers of steps, skirting, dado and pillars laid on 12 mm (average) thick cement mortar 1:3 (1 cement: 3 coarse sand) and jointed with grey cement slurry mixed with pigment to match the shade of the slabs, including rubbing and polishing complete. (DSR-16/11.27/P-195) | 67.5 | Sqm | |
| 185 | 51 | Ceiling finish | |||
| 186 | 51.01 | Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade : \nTwo or more coats on new work. (DSR-16/13.60.1/P-232) | 156.8 | Sqm | |
| 187 | 52 | Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade : \nNew work (two or more coats) over and including water thinnable priming coat with cement primer. (DSR-16/13.41.1/P-225) | 309.6 | Sqm | |
| 188 | 53 | External finish | |||
| 189 | 53.01 | Finishing walls with Acrylic Smooth exterior paint of required shade :\nNew work (Two or more coat applied @ 1.67 ltr/10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/10 sqm). (DSR-16/13.46.1/P-231) | 456 | Sqm | |
| 190 | 54 | Plinth Protection | |||
| 191 | 54.01 | Making plinth protection 50mm thick of cement concrete 1:3:6 (1 cement : 3 coarse sand : 6 graded stone aggregate 20 mm nominal size) over 75mm thick bed of dry brick ballast 40 mm nominal size, well rammed and consolidated and grouted with fine sand, including necessary excavation, levelling & dressing & finishing the top smooth. (DSR-16/4.17/P-90) | 72 | Sqm | |
| 192 | 55 | Terracing | |||
| 193 | 55.01 | Providing and fixing Heat Resistant Terrace Tiles (300 mm x 300 mm x 20 mm) with SRI (solar refractive index) > 78, solar reflection > 0.70 and initial emittance > 0.75 on waterproof and sloped surface of terrace, laid on 20 mm thick cement sand mortar in the ratio of 1:4 (1 cement : 4 coarse sand) and grouting the joints with mix of white cement & marble powder in ratio of 1:1, including rubbing and polishing of the surface upto 3 cuts complete, including providing skirting upto 150 mm height along the parapet walls in the same manner. (DSR-16/12.55/P-219) | 383.25 | Sqm | |
| 194 | 56 | Providing gola 75x75 mm in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 stone aggregate 10 mm and down gauge), including finishing with cement mortar 1:3 (1 cement : 3 fine sand) as per standard design : | |||
| 195 | 56.01 | In 75x75mm deep chase (DSR-16/12.21.1/P-211) | 76.5 | Metre | |
| 196 | 57 | Door shutters | |||
| 197 | 57.01 | Providing and fixing ISI marked flush door shutters conforming to IS : 2202 (Part I) decorative type, core of block board construction with frame of 1st class hard wood and well matched teak 3 ply veneering with vertical grains or cross bands and face veneers on both faces of shutters. | |||
| 198 | 57.02 | 35 mm thick including ISI marked Stainless Steel butt hinges with necessary screws. (DSR-16/9.20.1/P-148) | 55.8 | Sqm | |
| 199 | 58 | Door Frames | |||
| 200 | 58.01 | Providing and fixing pressed steel door frames conforming to IS: 4351, manufactured from commercial mild steel sheet of 1.60 mm thickness, including hinges, jamb, lock jamb, bead and if required angle threshold of mild steel angle of section 50x25 mm, or base ties of 1.60 mm, pressed mild steel welded or rigidly fixed together by mechanical means, including M.S. pressed butt hinges 2.5 mm thick with mortar guards, lock strike-plate and shock absorbers as specified and applying a coat of approved steel primer after pre-treatment of the surface as directed by Engineer-in-charge: | |||
| 201 | 58.02 | Profile C - Fixing with adjustable lugs with split end tail to each jamb (DSR-16/10.14.2.1/P-183-184) | 212 | Metre | |
| 202 | 59 | Supplying and fixing rolling shutters of approved make, made of required size M.S. laths, interlocked together through their entire length and jointed together at the end by end locks, mounted on specially designed pipe shaft with brackets, side guides and arrangements for inside and outside locking with push and pull operation complete, including the cost of providing and fixing necessary 27.5 cm long wire springs manufactured from high tensile steel wire of adequate strength conforming to IS: 4454 - part 1 and M.S. top cover of required thickness for rolling shutters. | |||
| 203 | 59.01 | 80x1.25mm M.S. laths with 1.25mm thick top cover. (DSR-16/10.6.1/P-182) | 10 | Sqm | |
| 204 | 60 | Aluminium windows Doors | |||
| 205 | 60.01 | Providing and fixing double glazed hermetically sealed glazing in aluminium windows, ventilators and partition etc. with 6 mm thick clear float glass both side, having 12 mm air gap, including providing EPDM gasket, perforated aluminium spacers, desiccants, sealant (Both primary and secondary sealant) etc. as per specifications, drawings and direction of Engineer-in-charge complete. (DSR-16/21.10/P-376) | 194 | Sqm | |
| 206 | 61 | Sanitary Fixtures | |||
| 207 | 61.01 | Providing and fixing water closet squatting pan (Indian type W.C. pan ) with 100 mm sand cast Iron P or S trap, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever) conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required: | |||
| 208 | 61.02 | White Vitreous china Orissa pattern W.C. pan of size 580x440 mm with integral type foot rests. (DSR-16/17.1.1/P-292) | 2 | Each | |
| 209 | 62 | Providing and fixing white vitreous china pedestal type water closet (European type) with seat and lid, 10 litre low level white vitreous china flushing cistern & C.P. flush bend with fittings & C.I. brackets, 40 mm flush bend, overflow arrangement with specials of standard make and mosquito proof coupling of approved municipal design complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : | |||
| 210 | 62.01 | W.C. pan with ISI marked white solid plastic seat and lid. (DSR-16/17.3.1/P-292) | 6 | Each | |
| 211 | 63 | Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings and brackets, cutting and making good the walls wherever require: | |||
| 212 | 63.01 | White vitreous China wash basin size 630x450 mm with a single 15mm C.P. brass pillar taps. (DSR-16/17.7.2/P-293) | 8 | Each | |
| 213 | 64 | Providing and fixing toilet paper holder: \nC.P. brass (DSR-16/17.34.1/P-297) | 8 | Each | |
| 214 | 65 | Providing and fixing white vitreous china flat back or wall corner type lipped front urinal basin of 430x260x350 mm and 340x410x265 mm sizes respectively with automatic flushing cistern with standard flush pipe and C.P. brass spreaders with brass unions and G.I clamps complete, including painting of fittings and brackets, cutting and making good the walls and floors wherever required : | |||
| 215 | 65.01 | One urinal basin with 5 litre white P.V.C. automatic flushing cistern. (DSR-16/17.4.1/P-292) | 4 | Each | |
| 216 | 66 | Providing and fixing C.P. brass long nose bib cock of approved quality conforming to IS standards and weighing not less than 810 gms. \n15mm nominal bore (DSR-16/18.50.1/P-334) | 2 | Each | |
| 217 | 67 | Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS: 8931 : \n15mm nominal bore (DSR-16/18.53.1/P-334) | 14 | Each | |
| 218 | 68 | Providing and placing on terrace (at all floor levels) polyethylene water storage tank, IS : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. (DSR-16/18.48/P-334) | |||
| 219 | 68.01 | Circular tank. (DSR-16/18.48.1/P-334) | 3000 | Per Ltr. | |
| 220 | 69 | Providing and fixing soil, waste and vent pipes: | |||
| 221 | 69.01 | 100mm dia: Centrifugally cast (spun) iron socket & spigot (S&S) pipe as per IS: 3989. (DSR-16/17.35.1.2/P-297) | 62 | Metre | |
| 222 | 69.02 | 75mm diameter: Centrifugally cast (spun) iron socketed pipe as per IS: 3989. (DSR-16/17.35.2.2/P-297) | 78.75 | Metre | |
| 223 | 70 | Providing lead caulked joints to sand cast iron/centrifugally cast (spun) iron pipes and fittings of diameter : | |||
| 224 | 70.01 | 100mm (DSR-16/17.58.1/P-304) | 40 | Each | |
| 225 | 70.02 | 75mm (DSR-16/17.58.2/P-304) | 50 | Each | |
| 226 | 71 | Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. | |||
| 227 | 71.01 | 100x100x100 mm: Sand cast iron S&S as per IS - 3989 (DSR-16/17.43.1.2/P-300) | 8 | Each | |
| 228 | 72 | Providing and fixing single equal plain junction of required degree with access door, insertion rubber washer 3 mm thick, bolts and nuts complete. | |||
| 229 | 72.01 | 75x75x75 mm: Sand cast iron S&S as per IS - 3989 (DSR-16/17.43.2.2/P-300) | 12 | Each | |
| 230 | 73 | Providing and fixing terminal guard: | |||
| 231 | 73.01 | 100 mm: Sand cast iron S&S as per IS - 3989 (DSR-16/17.56.1.2/P-303) | 5 | Each | |
| 232 | 73.02 | 75 mm: Sand cast iron S&S as per IS - 3989 (DSR-16/17.56.2.2/P-303) | 5 | Each | |
| 233 | 74 | Providing and fixing trap of self cleansing design with screwed down or hinged grating with or without vent arm complete, including cost of cutting and making good the walls and floors : | |||
| 234 | 74.01 | 100 mm inlet and 75 mm outlet: Sand cast iron S&S as per IS: 3989 (DSR-16/17.60.2.1/P-304) | 14 | Each | |
| 235 | 75 | Providing and fixing M.S. holder-bat clamps of approved design to Sand Cast iron/cast iron (spun) pipe embedded in and including cement concrete blocks 10x10x10 cm of 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), including cost of cutting holes and making good the walls etc. : | |||
| 236 | 75.01 | For 100mm dia pipe (DSR-16/17.37.1/P-298) | 40 | Each | |
| 237 | 75.02 | For 75mm dia pipe (DSR-16/17.37.2/P-298) | 50 | Each | |
| 238 | 76 | Constructing brick masonry manhole in cement mortar 1:4 ( 1 cement : 4 coarse sand ) with R.C.C. top slab with 1:2:4 mix (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size), foundation concrete 1:4:8 mix (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size), inside plastering 12 mm thick with cement mortar 1:3 (1 cement : 3 coarse sand) finished with floating coat of neat cement and making channels in cement concrete 1:2:4 (1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size) finished with a floating coat of neat cement complete as per standard design : | |||
| 239 | 76.01 | Inside size 90x80 cm and 45 cm deep including C.I. cover with frame (light duty) 455x610 mm internal dimensions, total weight of cover and frame to be not less than 38 kg (weight of cover 23 kg and weight of frame 15 kg) : | |||
| 240 | 76.02 | With brick of class designation-150 (DSR-16/19.7.1.1/P-356) | 5 | Each | |
| 241 | 77 | Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.\nInternal work - Exposed on wall | |||
| 242 | 77.01 | 15 mm nominal outer dia Pipes (DSR-16/18.7.1/P-325) | 72 | Metre | |
| 243 | 77.02 | 20 mm nominal outer dia Pipes (DSR-16/18.7.2/P-325) | 72 | Metre | |
| 244 | 77.03 | 25 mm nominal outer dia Pipes (DSR-16/18.7.3/P-325) | 90 | Metre | |
| 245 | 78 | Providing and laying non-pressure NP2 class (light duty) R.C.C. pipes with collars jointed with stiff mixture of cement mortar in the proportion of 1:2 (1 cement : 2 fine sand) including testing of joints etc. complete : | |||
| 246 | 78.01 | 150 mm dia R.C.C. pipe (DSR-16/19.6.2/P-355) | 45 | Metre | |
| 247 | 79 | Providing and laying cement concrete 1:5:10 (1 cement : 5 coarse sand : 10 graded stone aggregate 40 mm nominal size) all-round S.W. pipes including bed concrete as per standard design : | |||
| 248 | 79.01 | 150 mm diameter S.W. pipe (DSR-16/19.2.2/P-354) | 8.15 | Metre | |
| 249 | 80 | Providing and fixing C.P. brass bib cock of approved quality conforming to IS: 8931: \n15mm nominal bore (DSR-16/18.49.1/P-334) | 8 | Each | |
| 250 | 81 | Providing and fixing PTMT liquid soap container 109 mm wide, 125 mm high and 112 mm distance from wall of standard shape with bracket of the same materials with snap fittings of approved quality and colour, weighing not less than 105 gms. (DSR-16/17.71/P-306) | 6 | Each | |
| 251 | 82 | Providing and fixing Stainless Steel A ISi 304 (18/8) kitchen sink as per IS: 13983 with C.I. brackets and stainless steel plug 40 mm, including painting of fittings and brackets, cutting and making good the walls wherever required : | |||
| 252 | 82.01 | Kitchen sink with drain board: | |||
| 253 | 82.02 | 510x1040mm bowl depth 178mm (DSR-16/17.10.1.4/P-294-295) | 2 | Each | |
| 254 | 83 | Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fittings arrangement of approved quality and colour. | |||
| 255 | 83.01 | 600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighing not less than 190 gms. (DSR-16/17.73.2/P-306) | 6 | Each | |
| 256 | 84 | Providing and fixing 600x450 mm beveled edge mirror of superior glass (of approved quality) complete with 6 mm thick hard board ground fixed to wooden cleats with C.P. brass screws and washers complete. (DSR-16/17.31/P-297) | 8 | Each | |
| 257 | 85 | Miscellaneous Building works | |||
| 258 | 85.01 | Providing and fixing 18 mm thick gang saw cut, mirror polished, premoulded and prepolished, machine cut for kitchen platforms, vanity counters, window sills, facias and similar locations of required size, approved shade, colour and texture laid over 20 mm thick base cement mortar 1:4 (1 cement : 4 coarse sand), joints treated with white cement, mixed with matching pigment, epoxy touch ups, including rubbing, curing, moulding and polishing to edges to give high gloss finish etc. complete at all levels. | |||
| 259 | 85.02 | Granite of any colour and shade. \nArea of slab over 0.50 Sqm. (DSR-16/8.2.2.2/P-128) | 6.1 | Sqm | |
| 260 | 86 | Providing and fixing G.I. chain link fabric fencing of required width in mesh size 50x50 mm including strengthening with 2 mm dia wire or nuts, bolts and washers as required complete as per the direction of Engineer-in-charge. | |||
| 261 | 86.01 | Made of G.I. wire of dia 4 mm. (DSR-16/16.70.1/P-278) | 67.64 | Sqm | |
| 262 | 87 | Steel work welded in built up sections/ framed work, including cutting, hoisting, fixing in position and applying a priming coat of approved steel primer using structural steel etc. as required. | |||
| 263 | 87.01 | In gratings, frames, guard bar, ladder, railings, brackets, gates and similar works. (DSR-16/10.25.2/P-185) | 125 | Kg. | |
| 264 | 88 | Water proofing work on Terrace | |||
| 265 | 89 | Providing and laying integral cement based water proofing treatment including preparation of surface as required for treatment of roofs, balconies, terraces etc consisting of following operations: | |||
| 266 | 89.01 | (a) Applying a slurry coat of neat cement using 2.75 kg/sqm of cement admixed with water proofing compound conforming to IS. 2645 and approved by Engineer-in-charge over the RCC slab including adjoining walls upto 300 mm height including cleaning the surface before treatment. | |||
| 267 | 89.02 | (b) Laying brick bats with mortar using broken bricks/brick bats 25 mm to 115 mm size with 50% of cement mortar 1:5 (1 cement : 5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge over 20 mm thick layer of cement mortar of mix 1:5 (1 cement :5 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineer-in-charge to required slope and treating similarly the adjoining walls upto 300 mm height including rounding of junctions of walls and slabs. | |||
| 268 | 89.03 | (c) After two days of proper curing applying a second coat of cement slurry using 2.75 kg/ sqm of cement admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin-charge. | |||
| 269 | 89.04 | (d) Finishing the surface with 20 mm thick jointless cement mortar of mix 1:4 (1 cement :4 coarse sand) admixed with water proofing compound conforming to IS : 2645 and approved by Engineerin-charge including laying glass fibre cloth of approved quality in top layer of plaster and finally finishing the surface with trowel with neat cement slurry and making pattern of 300x300 mm square 3 mm deep. | |||
| 270 | 89.05 | (e) The whole terrace so finished shall be flooded with water for a minimum period of two weeks for curing and for final test. All above operations to be done in order and as directed and specified by the Engineer-in-Charge : | |||
| 271 | 89.06 | With average thickness of 120mm and minimum thickness at khurra as 65mm. (DSR-16/22.7.1/P-382-383) | 365.75 | Sqm | |
| 272 | 90 | Providing and laying water proofing treatment to vertical and horizontal surfaces of depressed portions of W.C., kitchen and the like consisting of: | |||
| 273 | 90.01 | (i) Ist course of applying cement slurry @ 4.4 kg/sqm mixed with water proofing compound conforming to IS 2645 in recommended proportions including rounding off junction of vertical and horizontal surface. | |||
| 274 | 90.02 | (ii) IInd course of 20 mm cement plaster 1:3 (1 cement : 3 coarse sand) mixed with water proofing compound in recommended proportion including rounding off junction of vertical and horizontal surface. | |||
| 275 | 90.03 | (iii) IIIrd course of applying blown or residual bitumen applied hot at 1.7 kg. per sqm of area. | |||
| 276 | 90.04 | (iv) IVth course of 400 micron thick PVC sheet. (Overlaps at joints of PVC sheet should be 100 mm wide and pasted to each other with bitumen @ 1.7 kg/ sqm). (DSR 16/22.3/P-381) | 24 | Sqm | |
| 277 | 91 | Sunken Area Filling | |||
| 278 | 91.01 | Provided and filling on Sunken areas with broken light weight concrete block bats of approximately six hundred kg per Cum dencity laid, consolidated, finished smooth with 50 mm to 60 mm thick PCC and including finishing and grouting the tope layer with water proof cement mortar of required thickness (mkt) | 10.8 | Cum | |
| 279 | 92 | Anti termite treatment | |||
| 280 | 92.01 | Diluting and injecting chemical emulsion for POST-CONSTRUCTIONAL anti-termite treatment (excluding the cost of chemical emulsion) : | |||
| 281 | 92.02 | Along external wall where the apron is not provided using chemical emulsion @ 7.5 litres / sqm of the vertical surface of the substructure to a depth of 300 mm including excavation channel along the wall & rodding etc. complete: \nWith Chlorpyriphos/ Lindane E.C. 20% with 1% concentration. (DSR-16/2.35.1.1/P-80-81) | 574 | Metre | |
| 282 | 93 | Add labour cess @ 1% on all above items | BI01010001010000000000000515BI0100001129 | 6.27549e+07 | Nos |
Copyright © 2026 · All Rights Reserved. Terms of Usage | Privacy Policy