| 1 | 1 | Supply, laying and testing PVC insulated , PVC sheathed cable galvnized steel strip or wire armourned, elctric control cables (heavy duty) with stranded copper conductor of size 4 Sqmm, 4 core , 1100 volt grade complete laid on wall / roof all as specified and directed by Engr-in-charge. Make: Polycab/Havells/HPL | | 18 | RM |
|---|
| 2 | 2 | Material and labour for Chemical earthing complete with copper plate electrode 900mm X 600mm X 5mm buried directly in ground vertically to a depth not less than 4.70 meter below normal ground level (with top edge of earth plate not less than 3.60 meter below ground level) and size of earth pit 1.20M X 1.20M X 5.1M(depth) connected to copper earth strip 32mm x 6mm (main earthing lead) by means of tinned copper / brass bolts, nuts, check nuts and washers besides brazing at all joints all as directed and connected to earth test point all as specified and testing on completion with and including necessary excavation and earth work in any type of soil earth electrode ,earthing lead from electrode to test point and filling with and including 150mm thick layer of charcoal,150mm thick common salt and 150mm thick magnesium sulphate in alternative layer upto a height of 1800mm from bottom of pit all around the copper plate GI pipe 50mm dia medium grade for protection of earth lead ,20mm dia watering pipe ,MS funnel with wire mesh including necessary earth work and PCC (1:3:6) type C-1 for earth pit of size 300x300x300mm (Internal Size) and with 100 mm wall thickness over and including PCC base of size 1500mmx1500mmx150mm using PCC 1:4:8 mix type D2 and 40mm thick precast RCC cover in (1:2:4) type B1 with 3 Nos 8mm dia TMT bars both way with 8 mm dia round bar handle including watering before burried of electrode and before making of pit complete all as specified and directed.\nNOTE:- (i) The cost of earth lead and protection pipe upto and including 7.5 mtr only from the top of earth electrode are deemed to be included under this item and additional lead, if any, required at site shall be measured and paid for separately under appropriate item of Schedule 'A'.\n(ii) Any joint in earth lead from earth electrode to test point shall not be allowed/ permitted. | | 1 | Each\nJob |
|---|
| 3 | 3 | Material and labour for earthing complete with copper plate electrode 600mm x 900mm x 5mm thick buried directly in ground vertically to a depth not less than 4.7 meter below normal ground level (with top edge of earth plate not less than 3.6 meter below ground level & complete size of earth pit 1.60m x 1.60m x 5.00m) connected to copper strip 32mm x 6mm as main earthing lead by means of tinned copper / brass bolts, nuts, check nuts and washers besides brazing at all joints all as directed and connected to earth test point all as specified and testing on completion with and including necessary excavation and earth work in any type of soil, earth electrode, earthing lead from electrode to test point, made of phosphorous brongze/gun meter of size 75mmx75xmmx25mm dril and screwed including 03 Nos 8mm dia 25mm long hexagonal head screwed, 50mm bore GI medium grade for protection of earth lead from top of plate to test terminal complete, adequate quantity of charcoal dust, magnesium sulphate & common salt in alternate layers of 100mm thick all around the plate, under and above the plate and returning, filling of earth spread, levelled, watered and compected to required level, PCC (1:3:6) type C-1 (using 20mm graded stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast 40mm thick RCC cover of (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate), rainforced with 8mm dia TMT bars 3 Nos both way with 12mm dia MS round bar handle, GI medium watering pipe 25mm bore with funnel and wire mesh complete all as specified and directed . \n NOTE : (i) The cost of earth lead and its protection pipe upto and including 7.5 mtr only from the top of earth electrode are deemed to be included under this item and additional earth lead , if any, required at site shall be measured and paid for separately under appropriate item of Schedule `A’. \n(ii) Any joint in earth lead from earth electrode to test point shall not be allowed/permitted. | | 1 | Each Job |
|---|
| 4 | 4 | M&L for earthing complete with galvanised steel earth plate electrode 60cm x 60 cm x 6.3 mm thick buried directly in ground (earth pit not less than 2.25m below ground level) with top edge of the plate not less than 1.5m below ground level connected to and including galvanised iron strip 32 x 6mm as earthing lead by means of GI bolts nuts check nuts and washers of galvanised iron or steel all as shown in electric plate No 5 SSR Part-I, connected to earthing etc all as specified including testing on completion with all necessary excavation in any kind of strata, earth work, PCC earth Pit in 1:3:6 CI RCC cover, CI funnel, GI watering Pipe 20 mm complete. Note:- 1. The unit rate shall also include for earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I.\n2. The rate of earthing GI strip and GI protection pipe upto 7.5 m is deemed to be included in the quoted rate and additional earthing strip, if any, required shall be measured and paid for separately under appropriate item of shcedule 'A'\n3. Any joint in earth lead from earth electrode to test point shall not be allowed/ permitted. | | 2 | Each\nJob |
|---|
| 5 | 5 | M & L for earth continuity conductor or main earthing lead fixed to wall on batten or recess or chases or buried in ground or drawn in conduit/pipe or fixed to poles or any other indicated situation for loop earthing etc, as required of size 32 x 6mm copper strip complete all as specified and directed. Note: Cutting, chasing, conduit pipe etc shall be paid and measured separately. This item shall be measured in excess of strip already included in earthing. | | 26 | RM |
|---|
| 6 | 6 | Supply & fixing in replacement flame proof FLP Flood light 150 W LED fittings as per IS : 2148 / 1981 & 2206 (Part-I )1984, Temperature class T-4, & made of cast aluminum alloy LM-6 having inside & outside light grey powder coating shade No 631 as per IS: 5 & one No internal earthing terminal and 02 Nos external earthings of screw of M6- size with 02 Nos plain washers heat resistant glass complete all as specified and directed. \nMake : Sudhir Cat Part No FL/2C/1251 or equivalent make and model of Baliga/CG . | | 2 | Each |
|---|
| 7 | 7 | M&L for sub main wiring using two single core PVC insulated, unsheathed stranded copper conductor cable of size 1.5 Sqmm 1100 Volts grade drawn in and including steel conduit of dia not less than 20mm (medium grade) on wall/roof surface with standard accessories, along-with one run of PVC (green colour) insulated, unsheathed, stranded copper conductor of size 1.5 Sqmm as earth continuity conductor all as specified and directed. \nNOTE: Two run of single core PVC cable with one run of earth conductor and conduit shall be measured as one unit. | | 50 | RM |
|---|
| 8 | 8 | Supply & fixing for flame proof push button rotary type switch 16 Amps in LM 6 metal enclosures, conforming to cat part No PBS / OA /1010-1A of make Sudhir or equivalent model of other make as specified complete all as specified & directed. | | 6 | Each |
|---|
| 9 | 9 | S&F sub main wiring alongwith earth wire (green colour) with single core FRLS PVC insulated, unsheathed stranded copper conductor cable of voltage rating upto and including 1100 Volts drawn with and including concealed PVC conduit (medium grade) with standard accessories, of the following sizes of cable & dia of conduit complete all as specified and directed:-\n(a) 2x2.5 Sqmm + 1x2.5 Sqmm earth wire with PVC conduit 20 mm dia shall be measured as one unit\nNote:- Cutting chases in wall/ roof for concealing and making good to existing surface shall be included in quoted rate.\n\n | | 130 | RM |
|---|
| 10 | 10 | S&F sub main wiring alongwith earth wire (green colour) with single core FRLS PVC insulated, unsheathed stranded copper conductor cable of voltage rating upto and including 1100 Volts drawn with and including concealed PVC conduit (medium grade) with standard accessories, of the following sizes of cable & dia of conduit complete all as specified and directed:-\n(a) 2x1.5 Sqmm + 1x1.5 Sqmm earth wire with PVC conduit 20 mm dia shall be measured as one unit\nNote:- Cutting chases in wall/ roof for concealing and making good to existing surface shall be included in quoted rate. | | 130 | RM |
|---|
| 11 | 11 | S&F sub main wiring alongwith earth wire (green colour) with single core FRLS PVC insulated, unsheathed stranded copper conductor cable of voltage rating upto and including 1100 Volts drawn with and including concealed PVC conduit (medium grade) with standard accessories, of the following sizes of cable & dia of conduit complete all as specified and directed:-\n(a) 4x10 Sqmm + 2x10 Sqmm earth wire with PVC conduit 25 mm dia shall be measured as one unit\nNote:- Cutting chases in wall/ roof and making good to existing surface shall be included in quoted rate. | | 35 | RM |
|---|
| 12 | 12 | M & L for sub main wiring with Two RUNS of single core 4 Sq.mm for main wire and one run of single core 4 Sq.mm as earth wire of stranded copper conductor FRLS PVC insulated unsheathed cable conforming to IS : 694 drawn through and including concealed in wall rigid medium duty unplaticised PVC coduit conforming to IS : 9537 ( Part-3) and ISI marked not lass than 25 mm dia and all accessories all conforming to IS specification complete. Note:- Two run of main wire one run earth wire and one run PVC conduit shall be measure as one unit. Cutting chases in wall/ roof for concealing and making good to existing surface shall be included in quoted rate. | | 25 | RM |
|---|
| 13 | 13 | M & L for sub main wiring with four RUNS of single core 10 Sq.mm for main wire and two run of single core 4.0 Sq.mm as earth wire of stranded copper conductor FRLS PVC insulated unsheathed cable conforming to IS : 694 drawn through and including concealed in wall rigid medium duty unplaticised PVC coduit conforming to IS : 9537 ( Part-3) and ISI marked not lass than 32 mm dia and all accessories all conforming to IS specification complete. Note:- Four run of main wire two run earth wire and one run PVC conduit shall be measure as one unit. Cutting chases in wall/ roof and making good to existing surface shall be included in quoted rate. | | 10 | RM |
|---|
| 14 | 14 | M&L for sub main wiring with two runs of 4.00 Sqmm single core PVC unsheathed and insulated 1100 Volt grade, multi stranded copper conductor drawn through and including 25 mm cassing capping and accessories fixed an surface of walls, ceiling floors etc including one run of PVC insulated and unsheathed cable of copper conductor of 4 Sqmm single core as earth continuity wire all as specified and directed.\nNote :- Two runs of single core PVC insulated unshethed cables and one run of earth continuity conductor incl conduit will be measured and paid as one unit. | | 85 | RM |
|---|
| 15 | 15 | M&L for sub main wiring using four run of single core PVC insulated, unsheathed stranded copper conductor cable of size 16 Sqmm of voltage rating 1100 Volts drawn in and including surface PVC conduit of dia not less than 32mm/ casing caping with standard accessories, along-with one run of PVC (green colour) insulated, unsheathed, stranded copper conductor of size 1 x 16 Sqmm as earth continuity conductor all as specified and directed. \nNOTE: Four run of single core PVC cable with one run of earth conductor and conduit shall be measured as one unit. | | 20 | RM |
|---|
| 16 | 16 | M&L for sub main wiring using two run of single core PVC insulated, unsheathed stranded copper conductor cable of size 16 Sqmm of voltage rating 1100 Volts drawn in and including surface PVC conduit of dia not less than 32mm/ casing caping with standard accessories, along-with one run of PVC (green colour) insulated, unsheathed, stranded copper conductor of size 1 x 16 Sqmm as earth continuity conductor all as specified and directed. \nNOTE: Two run of single core PVC cable with one run of earth conductor and one run of conduit shall be measured as one unit. | | 10 | RM |
|---|
| 17 | 17 | M&L for sub main wiring using two run of single core PVC insulated, unsheathed stranded copper conductor cable of size 6 Sqmm of voltage rating 1100 Volts drawn in and including surface PVC conduit of dia not less than 25mm/ casing caping with standard accessories, along-with one run of PVC (green colour) insulated, unsheathed, stranded copper conductor of size 1 x 6 Sqmm as earth continuity conductor all as specified and directed. \nNOTE: Two run of single core PVC cable with one run of earth conductor and one run of conduit shall be measured as one unit. | | 140 | RM |
|---|
| 18 | 18 | M & L for sub main wiring with Two RUNS of single core 4 Sq.mm for main wire and one run of single core 2.5 Sq.mm as earth wire of stranded copper conductor FRLS PVC insulated unsheathed cable conforming to IS : 694 drawn through and including concealed in wall rigid medium duty unplaticised PVC coduit conforming to IS : 9537 ( Part-3) and ISI marked not lass than 25 mm dia and all accessories all conforming to IS specification complete. Note:- Two run of main wire one run earth wire and one run PVC conduit shall be measure as one unit. Cutting chases in wall/ roof for concealing and making good to existing surface shall be included in quoted rate. | | 58 | RM |
|---|
| 19 | 19 | M&L for sub main wiring with two runs of 6.00 Sqmm single core PVC unsheathed and insulated 1100 Volt grade, multi stranded copper conductor drawn through and including 25 mm cassing capping and accessories fixed an surface of walls, ceiling floors etc including one run of PVC insulated and unsheathed cable of copper conductor of 6 Sqmm single core as earth continuity wire all as specified and directed. \nNote :- Two runs of single core PVC insulated unshethed cables and one run of earth continuity conductor incl conduit will be measured and paid as one unit. | | 20 | RM |
|---|
| 20 | 20 | S&F switch socket combination 16A /5 A ,5 in 1 complete all as specified and directed. | | 4 | Each |
|---|
| 21 | 21 | S&F switch socket combination 2 in 1 , 5A flush type complete all as specified and directed. | | 8 | Each |
|---|
| 22 | 22 | Supply,fixing,connecting & testing sheet metal enclosure double door SPN 4 way DB complete all as specified and directed. | | 2 | Each |
|---|
| 23 | 23 | Supply and fixing MCB/Isolator TPN 63 Amps having current rating 10 KA complete all as specified and directed. | | 2 | Each |
|---|
| 24 | 24 | Supply and fixing copper strip 20x3.15 mm with saddles and fixing with screw etc for roof roof conductor and down conductor above ground complete all as specified and directed. | | 48 | RM |
|---|
| 25 | 25 | S&F switch socket out let 3 pin 5 Amps flush type 230 Volts multipurpose complete all as specifed and directed . | | 3 | Each |
|---|
| 26 | 26 | Supply, fixing, Sheet Metal Enclosure, Triple pole and earth encolsure with a three pin and earth plug withsocket complete with one triple pole MCB 32 Amps complete all as specified and directed by Engr-in-charge. \nMake :-Legrand/Havels/L&T\n | | 1 | Each |
|---|
| 27 | 27 | S & F Sheet metal enclosures with socket plug top with 20 Amps MCB DP enclouser with a two pin and earth plug and socket complete with one Single pole MCB of 240 volts complete all as specified and directed.\nMake: Havells/CG/Anchor. | | 6 | Each |
|---|
| 28 | 28 | M & L for point wiring for fan with standed copper conductor 1.5 Sqmm 1100 Volts grade PVC insulated and unsheathed including ISI marked PVC cassing capping of required sizes as indicated including all accessories and one run of PVC insulated multistranded copper conductor cable 1.5 Sqmm as earth continuity wire, GI teriminal boxes recessed type and 3 mm thick laminated hylum sheet for holding switches etc complete all as specified and directed by Eng-in-Charge. | | 2 | Per Point |
|---|
| 29 | 29 | M&L for point wiring using approved colour coding as per IS (Red, Black and Green for single phase circuits),with multi stranded copper conductor 1.5 sq mm nominal cross sectional area, single core, pvc insulated and unsheathed FRLS cable 1100 volts grade, ISI-694 marked with valid CML No in and including medium grade, PVC Concealed conduit of dia not less than 20mm and conduit accessories concealed in wall/roof/floor etc, ISI marked with valid CML No (IS-9537-1983 for conduits and IS: 3419:1976 for conduit accessories), with mild steel/pressed steel sunken boxes (with earth dolly) duly painted with two coats of anticorrosive paint/aluminium paint over a coat of red oxide primer internally and two coats of black bituminous paint over a coat of red oxide primer externally, covered with 3mm thick plastic laminated sheet cover for fixing of switches, sockets etc including PVC insulated multi stranded copper conductor 1.5 sqmm nominal cross sectional area single core FRLS cable as earth continuity conductor to common earth and connecting to earth dully complete all as specified and directed at site for the following : | | | |
|---|
| 30 | 29.01 | One light/ Fan/ point controlled by one way switch. | | 18 | Per Point |
|---|
| 31 | 29.02 | One 5 Amps switch socket combination on independent board. | | 8 | Per Point |
|---|
| 32 | 29.03 | One 5 Amps socket on same board with other switches. | | 3 | Per Point |
|---|
| 33 | 30 | All as per item No 29.00 here in above but 2.5 Sqmm stranded copper conductor and independent board for 15 Amps switch/ socket point as directed. | | 14 | Per Point |
|---|
| 34 | 31 | M & L for flame proof point wiring for one light point or one socket point controlled by one switch with using 2.5 Sqmm(nominal area) stranded copper conductor, single core, FRLS, 1100 Volts grade, PVC insulated, unsheathed drawn in & including steel conduit on wall surface conduit in walls/ ceiling/ steel structure and including fixing of clamps, with all accessories and using 1.5 Sqmm (nominal area) stranded copper conductor single core FRLS, PVC insulated & unsheathed cable as in earth wire connected to common earth dolly/ fittings etc complete all as specified and directed | | 4 | Each Point |
|---|
| 35 | 32 | S & F Switch socket outlet , Multipin, 15/5 Amps controlled complete all as directed. Make : Anchor/Leader/Cona | | 14 | Each |
|---|
| 36 | 33 | S & F switch piano flush type single pole one way 5 Amps 230 V complete all as specified and directed | | 23 | Each |
|---|
| 37 | 34 | S & F ceiling rose surface backelet ISI marked Make - Anchor 2 to 3 terminal all as specified. | | 12 | Each |
|---|
| 38 | 35 | Supply and fix exhaust fan 300 mm sweep AC, 900/950 RPM light duty SP 230 volts, metal body with frame & louvers all necessary fixing arrangement including making sutable size hole in brick / PCC block / stone masonary wall built in cement mortar and making good disturbed surface complete all as specified & directed.\nMake: Havells Model No Ventilair DS or Eq model of Bajaj & CG. | | 2 | Each |
|---|
| 39 | 36 | Supplying and Fixing MS angle iron bracket of angle iron size 40mmx40mm x4 mm and MS strip of suitable size in frame wok approx weight of frame 15 KG including drilling holes, cutting, welding etc.and grouting rigidly with small masonary work in wall and make good the surface for installation of L2 Unit complete all as specified and directed. | | 1 | Each Job |
|---|
| 40 | 37 | Supplying and Fixing industrial type Metallic Plug & socket DB FP suitable for and with P 17 Tempra Pro IP 44 panel mounting socket 3P+N+E for LV 32 Amps 380/415 volts & P 17 Tempra Pro IP 44 straight plug 3P+N+E for LV 32 Amps 380/415 volts, Make: legrand Cat part No 607872 all as specified and directed | | 1 | Each |
|---|
| 41 | 38 | Supplying and Fixing Lexic MCB 4 Pole 32 Amps -C curve-10 kA of Make:Legrand cat part No. 603322 all as specified and directed. | | 1 | Each |
|---|
| 42 | 39 | Supply and fixing earth continuity conductor or main earthing lead 32mm x 6mm, GI strip/earth lead, laid in pipe/fixed on walls or any other position including jointing by tinned copper/brass nuts, bolts and washers in addition to brazing at every joint complete all as specified and directed. | | 6 | RM |
|---|
| 43 | 40 | M & L for providing test point terminal block made out of Gun metal or phosphorous bronze of size 75 mmx75 mm x25 mm drilled and screwed including 03 nos 8 mm dia 25 mm long hexagonal head screws complete all as specified and directed | | 1 | Each |
|---|
| 44 | 41 | Supply install and Voltage stabilizer for automatic operation, three phase, naturally oil cooled, out door type & designed for input variation between 340 V to 460 V with output voltage stabilized at 415 with accuracy ± 2.5% and speed of correction 8 Volts per second and of capacity 30 KVA, in built stabilizer by pass , triac based servo controller, with single phasing prevention protection complete all as directed by Eng-in-Charge. \nMake: Volina /Blue bird / AE | | 1 | Each |
|---|
| 45 | 42 | Supply, installation, commissioning & testing Isolation transformer, Air cooled, copper wound, three phase, 415 Volt AC 50 Hz of 30 KVA capacity complete all as directed by Eng-in-Charge.\nMake: Volina /Blue bird / AE | | 1 | Each |
|---|
| 46 | 43 | Supply, laying and testing LT cable XLPE insulated, screened, PVC bedded, galvanised steel strip of wire armoured electric power cables (Heavy duty) 1100 volts grade with standard aluminium conductor of size 50 sqmm 3.5 core complete all as specified and directed. Make: Polycab / Havells / Finolex | | 95 | RM |
|---|
| 47 | 44 | Excavation in trenches not exceeding 1.5 m wide in depth and getting out soft/loose soil for laying of cables etc complete all as directed by engineer in charge. | | 25.02 | CUM |
|---|
| 48 | 45 | Returning filling including spreading levelling watering and well ramming in layar not exceeding 25 mm thick complete all as specified and as directed by Engineer in charge | | 13.47 | CUM |
|---|
| 49 | 46 | Removal of excavated material (soil) to a distance not excedding 50 m and depositing where diredted at a level not exc 1.5 m above the starting point complete all as directed by Engineer in charge | | 6.78 | CUM |
|---|
| 50 | 47 | M&L dry river sand in trenches for cable cushioning & protection including spreading, ramming all as specified and directed. | | 6.075 | Cum |
|---|
| 51 | 48 | Supply & Laying precast PVC cable concrete cable cover LV voltage type -I flat size 250 mm x 150 mm x 40 mm complete | | 470 | Each |
|---|
| 52 | 49 | Boring of holes under road, pavement, hard standing by trenchless technology using ultra sounding technique and necessary machine including M&L for HDPE pipe of 150 mm dia suitable for 0.4 mpa working pressure | | 15 | RM |
|---|
| 53 | 50 | Supply and fixing 4 way TPN MCB DB double door complete all as specified and directed Engr-in-charge | | 1 | Each |
|---|
| 54 | 51 | Supply and fixing four pole 63Amps MCB, 50 Hz 415V with rupturing capacity 10 KA complete all as specified and directed by Engr-in-charge | | 1 | Each |
|---|
| 55 | 52 | Supply and fixing four pole 32Amps MCB, 50 Hz 415V with rupturing capacity 10 KA complete all as specified and directed by Engr-in-charge | | 2 | Each |
|---|
| 56 | 53 | Supply and fix indoor Isolation transformer, copper wound, air cooled, capacity 15 KVA 3 Phase, 415 Volt complete all as speicified and directed. | | 1 | Each |
|---|
| 57 | 54 | Supply and fix indoor Isolation transformer, copper wound, air cooled, capacity 5 KVA Single Phase, 415 Volt complete all as speicified and directed. | | 1 | Each |
|---|
| 58 | 55 | Supply and fix indoor Isolation transformer, copper wound, air cooled, capacity 2 KVA Single Phase, 415 Volt complete all as speicified and directed. | | 26 | Each |
|---|
| 59 | 56 | Supply and fixing tempra plug socket and surface mounting box IP-66 3P+N+E, 415V 63 Amps with one MCB TPN 63Amps and surge protection device complete all as specified and directed Engr-in-charge. | | 1 | Each |
|---|
| 60 | 57 | Supply and fixing tempra plug & socket and surface mounting box IP-66 3P+N+E, 415V 32 Amps with one MCB TPN 32Amps and surge protection device complete all as specified and directed Engr-in-charge. | | 1 | Each |
|---|
| 61 | 58 | Supply and fixing tempra plug & socket and surface mounting box IP-66 2P+E, 250V 63 Amps with one MCB TPN 63Amps and surge protection device complete all as specified and directed Engr-in-charge. | | 1 | Each |
|---|
| 62 | 59 | Supply and fixing tempra plug socket and surface mounting box IP-66 2P+E, 250V 32 Amps with one MCB TPN 32Amps and surge protection device complete all as specified and directed Engr-in-charge. | | 26 | Each |
|---|
| 63 | 60 | Dismantling disconnecting connection refregerent pipe from outdoor/ indoor unit, taking outdoor unit of split AC 1.5/2TR from wall at 30 ft height safely carried out servicing , reinstalling on roof/ on wall at suitable height/ on angle iron frame including additional copper tubing of suitable existing pipe, 3 core pvc cable Brazing, pcc on roof, bracet on wall/ angle iron wall and testing compleat all as specified directed | | 5 | Each Job |
|---|
| 64 | 61 | S&F MCB single pole, 6 to 32 Amps (`C’ series) having current rating 10 KA complete all as specified and directed.\n | | 6 | Each |
|---|
| 65 | 62 | Supply and Fixing industrial type plug socket, SPN and earth plug 250V, 20 Amps with steel enclosure and one MCB SP 20/32 Amps complete all as specified and directed. | | 6 | Each |
|---|
| 66 | 63 | Supply, install, commissioning and testing of split type wall mounted Air conditioner of capacity 2.0 TR (6000 K Cal/hr) single phase, (Non CFC/HCHC) suitable for 230 Volt + 10% , 50 Hz, AC supply complete with cordless remote control unit , minimum 3 star rating complete comprise of following:-\nMake:- Voltas/ Carrier/ Decon/ Hitechi/ Blue Star\n(a) Indoor unit with three speed blower fan of appropriate capacity including PCB, thermostatic control, air filter and drain for condensing water.\n(b) Outdoor unit comprising of compressor with motor, air cooled copper condenser with fan and motor unit shall be installed out side the building/ on roof.\n(c) Refrigerant copper pipe for suction and discharge line with insulation, cndensing water drain pipe and protected by suitable size of flexible PVC conduit with control valves & safety accessories including control wiring for evaporator & condensing unit with suitable size of copper cable.\n(d) Making good the distrubed surface to match the existing surface after plugging the hole etc.\n(e) PCC (1:2:4) type B-1 (using 20 mm graded stone aggregate ) as in plinth suitable for installation of outdoor unit or powder coated MS bracket fixed on wall as per Manufacture's instruction with necessary grouting MS hold fast, bolts, washers duly painted and making good disturbed sufaces suitable for installing outdoor unit of 2 TR AC complete all as specified and directed.\n(f) Electric cable required to connect out door unit and indoor unit to voltage stablizer inclusive in above rate.\n | | 1 | Each |
|---|
| 67 | 64 | Supply and fixing voltage stablizer for automatic operation single phase, natural air cooled indoor wall mounted type designed for input variation between 170V to 250V with output voltage stablized at 230 Volts with accuracy of + 2.5% and capacity 5.0 KVA complete all as specified and directed.\nMake :- V Guard/Blue star/Volvoline | | 1 | Each |
|---|
| 68 | 65 | Supply, install, commissioning and testing of deep freezer ( Hard top ) of model No CHF 500 of capacity 500 litres single phase, suitable for 230 volt + 10%, 50 Hz, AC supply complete all as specified and directed. | | 1 | Each |
|---|
| 69 | 66 | Supply and fixing voltage stablizer for automatic single phase, indoor wall mounted type designed for input variation between 140V to 280V, 2 KVA with complete all as specified and directed.\nMake:- V Guard/ Blue bird/ Volvoline | | 1 | Each |
|---|
| 70 | 67 | S&F socket out let 3 pin, 5 Amps, 230 Volt multipurpose flush type complete as specified. | | 8 | Each |
|---|
| 71 | 68 | S&F step type fan regulator resistance type , 230 Volts, 50 hz complete all as specified and directed. | | 1 | Each |
|---|
| 72 | 69 | S&F lamp holder insulated body with back plate for battern fittings. Make: Bajaj/CG/Havells. | | 3 | Each |
|---|
| 73 | 70 | S&F LED light fitting 20 Watt complete with lamp holder & round bolck etc, incl PVC gutties and flexible wire and connecting to ceiling rose complete. Model Wipro Garnet 20W, D52065 of wipro or Equivalent of Bajaj/ Havells. | | 6 | Each |
|---|
| 74 | 71 | S&F recess mounting LED 36W 2 feet x 2 feet white/cool day light luminaire white powder coated CRCA housing with LEDs seamless gront frame with flat white high transmission arcylic cover complete all ad directed. Make BZRQL 36W GZ WH of bajaj or Equivalent of wipro/CG/Havells | | 6 | Each |
|---|
| 75 | 72 | Supply & fixing flame proof switch socket & plug combined made of aluminum alloy LM-6 having 2 pole + earth suitable for 250 volts supply and current rating of 16 Amps complete all as specified and directed. \nMake/model: Sudhir cat part No. SS/OA/1010-1 ir equivalent model of other make approved by the GE. | | 4 | Each |
|---|