| 1 | 1 | Supplying , laying , passing through pipe , connecting and testing LT XLPE insulated ,armoured heavy duty electric cable with aluminium conductor ,1100 volts grade of size 16 Sqmm, 4 Core MAKE:- Finolex/RR Kable/RPG (Asian)/Grandlay. | | 115 | RM |
|---|
| 2 | 2 | Supply, laying, jointing and connecting, LT UG cable XLPE insulated , PVC bedded , galvanised steel strip or wire armored, electric power cable ( heavy duty) 1100 volts grade with stranded aluminium conductor laid in trenches / on poles / walls / in ducts / passing through pipes etc including jointing materials such as cable glands, lugs etc complete all as specified and as directed of size 25 sqmm 4 core (Note:- Excavation , Earth Work etc will be measured and paid separately). MAKE:- Finolex/RR Kable/RPG (Asian)/Grandlay. | | 50 | RM |
|---|
| 3 | 3 | All as per item No 2 above but XLPE Cable of size 35 Sqmm, 4 Core . | | 190 | RM |
|---|
| 4 | 4 | Excavation in trenches in soft/loose soil not.exc 1.5 mtr wide and not.exc 1.5 mtr deep and getting out in soft/loose soil for laying of cable/foundation of pole and stay etc complete all as sepecified and directed. | | 36 | CUM |
|---|
| 5 | 5 | Removing excavated materials (soil) to a distance not exceeding 50 mtr and depositing where directed at a level not exceeding 1.5 mtr above ground level from starting point all as specified and directed. | | 16 | CUM |
|---|
| 6 | 6 | Returning filling in including spreading, levelling, watering and well ramming in layers n.exc 25 cm all as specified and directed. | | 15 | CUM |
|---|
| 7 | 7 | M&L for dry sand cushioning to underground cable provided with a layer of 8cm deep before laying the cable and 15cm deep after laying the cable and stretching the cable all as specified and directed. Note:- Punned/Compacted Thickness of sand shall be measured for the purpose of payment to contractor. | | 12 | CUM |
|---|
| 8 | 8 | Supply and laying well burnt sub class ‘B’ old size bricks, locally best available in trenches for protection of underground cable complete all as specified and directed. | | 1520 | Each |
|---|
| 9 | 9 | Supply and laying GI tube light grade 50 mm bore ISI marked for cable protection complete all as specified and directed. MAKE:- TATA/JINDAL/ZENITH. | | 6 | RM |
|---|
| 10 | 10 | Supply and laying GI tube light grade 25 mm bore ISI marked for cable protection complete all as specified and directed. MAKE:- TATA/JINDAL/ZENITH. | | 20 | RM |
|---|
| 11 | 11 | M& L for Earthing complete with galvanised steel earth plate electrode 60cm x 60cmx6 mm thick burried directly in ground (earth pit not less than 2.25 metres deep below normal ground level) with top edge of plate not less than 1.5 metre below normal ground level connected to galvanised earth lead G.I wire 4 mm dia by means of bolts, nuts, check nuts and washers of galvanised iron or steel all as shown in electrical plate No 3 of MES Schedule Part-I including and connecting to earthing test point and testing on completion with and including 15 mm bore light grade G.I. protection pipe 7.5 M beyond outer edge of earth pit, PCC pit in mix 1:3:6 type C1 with RCC 1:2:4 type B-1 40 mm thick cover reinforced with 6 mm dia M.S bars 3 Nos both ways with lifting hook made out of 6 mm dia bar, watering arrangement with funnel and wire mesh and 20 mm bore light grade G.I. watering pipe, common salt and charcoal filling, necessary excavation and earth work including Earthing pit marker/ identifier of Steel plate of size 300mm X 200mm X 3mm and alongwith 1 meter long medium grade GI pipe of size 15 mm dia welded with steel plate including painting with applying one coat of red oxide and two coats of painting with synthetic enameled paint of approved quality including writing letters, in different colors complete including testing on completion complete all as specified and directed. Note :- cost for the earthing lead / strip including protection pipe 7.5 RM from earthing pit is included in the unit rate. Note:- G.I wire earthing and protection pipe beyond 7.5m length shall be measured and paid separately. | | 1 | Each |
|---|
| 12 | 12 | Material and labour for earthing complete with galvanized steel earth plate electrode 600mm X 600mm X 6mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to GI strip 32mm X 6mm main earthing lead by means of galvanized bolts, nuts and washers all as shown in electrical plate no 3 of MES Schedule Part-I (2009) connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt all around earth plate, test point of phosphorous bronze / gun metal of size 75 mmx 75 mm x25 mm, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 8mm dia TMT bars 3 Nos both way with 12mm dia round bar handle, GI medium grade watering pipe 20 mm dia with funnel and wire mesh, and 40 mm dia GI medium grade earth lead protection pipe, complete all as specified and directed. \nNOTE : G.I earth strip 32 x 6mm and its protection pipe 40mm bore upto and including 7.5 mtr only is included in the quoted rate of this item. | | 2 | Each |
|---|
| 13 | 13 | Material and labour for earthing complete with Copper earth plate electrode 600mm X 600mm X 3.15 mm buried directly in ground vertically to a depth not less than 2.25 meter below normal ground level (with top edge of earth plate not less than 1.5 meter below ground level) connected to copper strip 20 mm X 3 mm main earthing lead by means of breezing (copper welding) all as shown in electrical plate no 3 of MES Schedule Part-I (2009) connected to earth test point & to main switch board etc with & including adequate quantity of charcoal dust and common salt all around earth plate, test point of phosphorous bronze / gun metal of size 75 mmx 75 mm x25 mm, PCC (1:3:6) type C-1 (using 20mm graded black trap/granite/Basalt stone aggregate) for earth pit with 40 x 40 x 6mm mild steel angle iron frame for cover, pre cast RCC (1:2:4) type B-1 (using 20mm graded black trap/granite/Basalt stone aggregate) 40mm thick cover reinforced with 8mm dia TMT bars 3 Nos both way with 12mm dia round bar handle, GI medium grade watering pipe 20 mm dia with funnel and wire mesh, and 40 mm bore GI medium grade earth lead protection pipe, complete all as specified and directed. \nNOTE : Copper earth strip 20 x 3 mm and its protection pipe 40 mm bore upto and including 7.5 mtr is included in the quoted rate of this item. | | 4 | Each Set |
|---|
| 14 | 14 | M&L for copper strip 20x3.15 mm with saddles ( PVC soild blocks ) and fixing screwes ( Non rusted/ steel type ) etc for roof conducotrs and down conductors above ground level mounting on soild PVC block in suitable size fittings with non rusted type/ steel nut , bolts and washers etc all as specified and directed. | | 120 | RM |
|---|
| 15 | 15 | Supply, install, testing and commissioning of 16 mtr High Mast, polygonal, continuous tapered, and flange mounted type single hot dip galvanized, non-circumferential weld and suitable for wind velocity as per IS 875 part 3 fabricated out of special steel plates as per BSEN-10025, grade mild steel, the mast shaft shall be supplied in two sections top dia : 150mm, bottom dia : 360mm approx, top section length 8.25 mtr,bottom section length 8.25 mtr and Terrain factor in TC-1(airport) and shall be stress fitted at site, mast door opening size 1200mmx300mm along with supply of accessories for 16 mtr high mast which includes head frame, lighting finial, stainless steel wire rope, compensating disc for three wire rope system, double drum winch with capacity of 750 kg, power trailing cable integral power tool, GLC aviation obstruction LED light, control panel housing comprising of suitable timer-contactor circuit for automatic ON/OFF of high mast lights galvanised lantern carriage suitable for mounting 08 Nos Luminaires LED 120 watt 240 Volt flood light symmetrically incl following items :\n | | 1 | Each Job |
|---|
| 16 | 15.01 | (a) Supply & fixing 08 No.s flood light luminaire with high power LED powder coated pressure die cast aluminium compact energy saving & environmental friendly long life heat resistant toughened glass of rating 120 watt,with lumen efficacy not less than 100 lumen per watt, CRI more than 85, colour temperature 5500K to 6000K surge Protection 5 KV (Min), for pole height 16 meter, Led driver constant voltage and current for input voltage of 140 to 285 Volt, power factor not less than 0.95, 240 volts, 50 Hz with not less than IP65 protection. Make of lights – Havells/Philips/ Crompton/Surya/Bajaj.Make of High mast – Philips/ Crompton/Bajaj/Wipro\n(b) Design, casting of suitable foundation for 16 meter high mast considering SBC as 10 Ton/sqm at the depth of 1.5 mtr, along with erection as per modern Engg practice.\nNote:- rate quoted is deemed to be included of followng also:-\n(i) The structure should be capable to withstand the wind load as per IS : 875, necessary backup with structural design to be provided for these purpose which should determine the basic geometric configuration of MAST to be used for given application.\n(ii) The luminaries should be mounted on the lantrn carrige by luminars mounting arm assembly and should aim properly to achive the desired lightning performance. Wind speed is 50M/Sec.\n(iii) The lantern carriage should be of raising and lowering type and for this purpose a THREE WIRE SUSPENSION system of stainless steel wire rope of adequate size along with a double drum winch to be provided for most optimum balancing of the lantern carriage. Tower tool should be integrated.\n | | | |
|---|
| 17 | 15.02 | (iv) COMPENSATING DISC and SAFETY WIRES to be provided for maximum safety and flexibility.\n(v) The self lubricating WINCH gear assembly should be made of phosphorus bronze.\n(vi) RCC foundation as per manufacturer's recomendations\n(vii) The power tool should be built in type. | | | |
|---|
| 18 | 16 | Supply install testing and commissioning of Diesel engine driven genrating set 415 Volts, 3 Phase 4 wire, engine as per IS : 10001/10002 and alteranator as per IS 13364 complete with relay panel for automatic starting on mains failure, control panel having meters, sound proof canopy including foundation complete for base of DG Set etc of capacity 15 KVA. Tools and spares complete all as specified and directed and comprising of the following :- | | 1 | Each |
|---|
| 19 | 16.01 | (a) Engine: Diesel engine, developing required BHP @ 1500 RPM for continuous duty of suitable for 15 KVA alternator with provision of 10% over load for one hour in every 12 hour running confirming to BS 5514/ISO 3046 standard. Totally enclosed, electric start, compression ignition, 4 stroke. The engine shall consists of following specification :- \nThe scope of supply includes: \n-Electrical starter motor 12V DC \n-Battery charging alternator \n-MICO fuel system with mechanical governor \n-Dual spin-on fuel filter \n-Spin-on full flow lub oil filter \n-Residential silencer \n-Dry type air cleaner \n-Recovery bottle \n-Shut-off coil with safeties for LLOP/HWT \n-Flywheel and flywheel housing \n | | | |
|---|
| 20 | 16.02 | (i) Alternator: suitable for operation at 1500 RPM, 415 Volts, \n0.8 pf (lag) suitable for 50 Hz, 3 phase, 4 wire system, \nconforming to BS 5000 / IS 4722. The Alternator is brushless \ntype, screen protected, revolving field, self excited, self \nregulated through an AVR. The alternator has the following \nfeatures: \n-+ 1.0 % Voltage regulation (max.) in static conditions \n-IP: 23 Enclosure \n-Permissible overload of 10% for one hour in 12 hours of \noperation as per standards | | | |
|---|
| 21 | 16.03 | (ii) Mounting arrangement: Engine and alternator are mounted \non a common MS fabricated base frame with AVM pads. The steel shall be TATA/SAIL/RINL or equivalent make | | | |
|---|
| 22 | 16.04 | (iii) Control panel: The control panel is manufactured with 14/16 gauge CRCA sheet and is powder coated for a weather-proof, long lasting finish. \nThe control panel consists of following parts: \n-Standard engine instrumentation \n-Multi function meter which measures: \n1) Individual phase current (Amps) \n2) Phase voltages (V) \n3) Generator output frequency (Hz) \n4) Engine water temperature (Deg.C) \n5) Lube oil pressure (kg/cm2) and equipped with hour \ncounter \n-MCCB of suitable rating \n-Key switch \n-Push button (Starter) \n-LED: Battery charging alternator fail indication \n-Current transformers \n-Instrument fuses duly wired and ferruled \n | | | |
|---|
| 23 | 16.05 | (iv) Others: -Fuel tank suitable for 8 hours of operation \n-One charged battery 12V, suitable rating AH with battery leads & cable | | | |
|---|
| 24 | 16.06 | Acoustic enclosure: \nThe acoustic enclosure should be of ARAI approved specification and structural/ sheet metal base frame duly painted. The walls of the enclosure are insulated with fire retardant foam so as to comply with the 75 dBA at 1mtr sound levels specified by Ministry of Environment & Forest. The enclosure has the following features: \n-Specially designed to meet stringent MOEF/ CPCB norms of 75 dBA @ 1mtr at 75% load under free field conditions, -Single point lifting for easy handling, -Designed to have optimum serviceability -Air inlet louvers specially designed to operate at rated load, -Made on special purpose CNC machines for consistency in quality and workmanship, -Powder coated for long lasting service life and superior finish, -With UV resistant powder coating to withstand extreme environmental conditions, -Use of special hardware for longer life, -Insulation material meets IS 8183 specifications for better sound attenuation, -Flush styling - no projections, -Fluid drains for lube oil and fuel, -Fuel filling point | | | |
|---|
| 25 | 16.07 | (v) One set of spare accessories (As per manufacturer's instructions : (a) Level indicator on fuel tank (b) Drain plug (c) MS class \"C\" piping, suitable dia and length for fuel inlet from tank to engine as per manufacturers instructions. (d) Fuel strainer and fuel tank with air vent. (e) Battery heavy duty 12 Volts lead acid type fully charged, indication of high flow charging changed. - 01 Nos. (f) Cable connection from alternator to DG set control panel as directed Make of Generator set Alternator : Kirloskar / Crompton Greaves / Stemford/Catterpillar/Mahindra & Mahindra Ltd. MAKE of DG Set Engine:- Cummins/Kirloskar/Catterpillar/Crompton Greaves/Mahindra & Mahindra Ltd. | | | |
|---|
| 26 | 17 | Taking down carefully old FTL fitting of any capacity and any type from wall/ceiling,and making good the disturbed surface of walls and ceiling etc as directed and S&F decorative box type LED fitting with LED tube 20 to 22 watt of 230 volt AC including electric connection from ceiling rose to fitting complete all as specified and directed Make :- C&S/Philips/Surya/Havells | | 740 | Each |
|---|
| 27 | 18 | Taking down carefully old CFL of any capacity and any type from wall/ceiling and making good the disturbed surface of walls and ceiling etc as directed and S&F new LED bulb of capacity 9 watt cool white complete all as specified and directed. Make :- C&S/Philips/Surya/Havells | | 150 | Each |
|---|
| 28 | 19 | Taking down carefully old CFL of any capacity and any type from wall/ceiling, and making good the disturbed surface of walls and ceiling etc as directed and S&F new LED bulb of capacity 5 watt complete all as specified and directed.Make :- C&S/Philips/Surya/Havells | | 130 | Each |
|---|
| 29 | 20 | Taking down carefully old CFL/FTL mirror light fitting of any capacity and any type from wall/ceiling and making good the disturbed surface of walls and ceiling etc as directed and S&F new LED mirror light fitting of capacity 10 watt complete all as specified and directed. Make :-C&S/Philips/Surya/Havells | | 30 | Each |
|---|
| 30 | 21 | M&L for Air Termination single pointed Copper conductor rod 12 mm dia and 300 mm long complete all as specifiedand directed | | 10 | Each |
|---|
| 31 | 22 | M&L for Test point terminal block made of gun metal or phosphorus bronze size 75 x75 x25 mm drilled and screwed including 3 Nos 8 MM dia 25 mm long hexagonal head screw complete all as per specified and directed. | | 3 | Each |
|---|
| 32 | 23 | Supply and fixing vertical DB 4 way TPN with provision for 4 Pole incommer MCCB with 200 Amps rated bus bar, double door type complete all as specified and directed. Make :- Legrand/C&S/L&T (Lexic)/Scheinder/GE (power) | | 6 | Each |
|---|
| 33 | 24 | S&F MCB TPN, 63 Amps, 240 Volts,rapturing capacity 10 KA \"c\" Series complete all as specified and directed. Make :- Legrand/C&S/L&T (Lexic)/Scheinder/GE (power) | | 6 | Each |
|---|
| 34 | 25 | S&F MCB SPN, 40 Amps, 240 Volts, rapturing capacity 10 KA \"c\" Series complete all as specified and directed. Make :- Legrand/C&S/L&T (Lexic)/Scheinder/GE (power) | | 6 | Each |
|---|
| 35 | 26 | S&F MCB SP, 6 to 32 Amps, 240 Volts, rapturing capacity 10 KA \"c\" Series complete all as specified and directed .Make :- Legrand/C&S/L&T (Lexic)/Scheinder/GE (power) | | 40 | Each |
|---|
| 36 | 27 | S&F industrial plug and socket surface mounting sockets IP-67 of capacity 32 Amps single phase 3 pin , 2P+E 240 Volts complete all as specified and directed. Make :- Legrand/C&S/L&T (Lexic)/Scheinder/GE (power) | | 12 | Each |
|---|
| 37 | 28 | S&F industrial plug and socket surface mounting sockets IP-67 of capacity 63 Amps Three phase 5 pin , 3P+N+E 240 Volts complete all as specified and directed. Make :- Legrand/C&S/L&T (Lexic)/Scheinder/GE (power) | | 12 | Each |
|---|
| 38 | 29 | Taking down old and unserviceable sub main wiring any size / type / core incl earth wire complete with batten/conduit etc and making good the disturbed surface to match the existing disturbed surface all as specified and directed. | | 985 | RM |
|---|
| 39 | 30 | Taking down old and unsrevicable sheet metal enclosure , switch fuse unit , distribution board any type /way / capacity including fuses,MCB's , insulator etc complete after removing all connections and making good the disturbed surface all as specified and directed. | | 30 | Each |
|---|
| 40 | 31 | Supply and fixing Highbay light fitting energy saving environemental friendly long life integral industrial LED with pressure dia - cast aluminium housing , anodised aluminium reflector including all fixing accessories, 90 Watt system wattage, IP-65, complete all as specified and directed. Note : Light fitting will be fixed in sunscreen shelter. Make: C&S Cat Part No. LTEHB90WHPLED/LS, Philips Cat Part No. BY325 PLEDI00S CWPSU GRFG MBNB, Havells Cat Part No:- ENDURAHIBRITEPLUS HBP90 WLED765S90 D TOLENS, CROMPTON CAT PART NO:- LHB - 90 - CDL/60 | | 55 | Each |
|---|
| 41 | 32 | M&L in repair for sub main wiring with two runs of 1.5 Sqmm ( 2x1.5 sqmm ) 1100 volts grade single core FRLS PVC insulated unsheathed multistranded copper conductor confoming to IS-694 drawn through and including ERW steel conduit 20 mm on walls /roofs / ceiling fixed with proper steel saddels etc with one run of 1.5 Sqmm (1x 1.5 sqmm ) single core FRLS PVC insulated unsheathed copper conductor cable as earth wire complete all as specified and directed. Note:- 2 runs of 1.5 Sqmm (2x1.5 sqmm ) ,one run of 1.5 Sqmm (1x1.5 sqmm ) cable and one meter of conduit will be measured as one unit. Make of Cable:- Finolex/RR Kable/RPG (Asian). MAKE of Steel Conduit:- Jindal/Finolex/MK india/Asian. | | 580 | RM |
|---|
| 42 | 33 | M&L in repair for sub main wiring with four runs of 6 Sqmm ( 4x6 sqmm ) 1100 volts grade single core FRLS PVC insulated unsheathed multistranded copper conductor confirming to IS-694 drawn through and including ERW steel conduit 20 mm dia ISI marked with all conduit accessories mounting on suface of walls /roofs / ceiling etc with one run of 6.0 Sqmm (1x6 sqmm ) single core FR PVC insulated unsheathed copper conductor cable as earth wire complete all as specified and directed. Note:- 4 runs of 6 Sqmm (4x6sqmm ) ,one run of 6 Sqmm (1x6 sqmm ) cable and one meter of conduit will be measured as one unit. Make of Cable:- Finolex/RR Kable/RPG (Asian). MAKE of Steel Conduit:- Jindal/Finolex/MK india/Asian. | | 280 | RM |
|---|
| 43 | 34 | M&L in repair for sub main wiring with four runs of 4 Sqmm ( 2 x 4 sqmm ) 1100 volts grade single core FRLS PVC insulated unsheathed multistranded copper conductor confirming to IS-694 drawn through and including ERW steel conduit 20 mm dia ISI marked with all conduit accessories mounting on suface of walls /roofs / ceiling etc with one run of 4.0 Sqmm (1x 4 sqmm ) single core FR PVC insulated unsheathed copper conductor cable as earth wire complete all as specified and directed. Note:- 2 runs of 4 Sqmm (2 x 4sqmm ) ,one run of 6 Sqmm (1x6 sqmm ) cable and one meter of conduit will be measured as one unit. Make of Cable:- Finolex/RR Kable/RPG (Asian). MAKE of Steel Conduit:- Jindal/Finolex/MK india/Asian. | | 125 | RM |
|---|