| 1 | 1 | GALVANIZED STEEL OCTAGONAL POLES FOR WIND VELOCITY OF 160 Km/ HOUR: | | | |
|---|
| 2 | 1.01 | Supply and erection of galvanized steel octagonal pole of suitable length conforming to IS 2629/IS 2633/ IS4759. The pole shall be in single piece (single hot dip galvanized) and shall tapered towards the top.The bottom section shall have open able slot with exterior surface door & shall have suitable locking arrangement for housing three phase 4wire cable onnection, bakelite sheet, MCB, loop in and out arrangement for incoming/ outgoing cables. There shall also be suitable arrangement for the purpose of earthing. Rigid Base plate of suitable size and thickness shall be welded inside and outside at the bottom of pole with provision for fixing 4 foundation bolts.The octagonal pole shall be bolted on a pre- cast foundation with a set of four foundation bolts for greater rigidity. The foundation shall be erected over cement concrete M20 with steel of given size as per design of original pole manufacturer to fixed up to a required planting depth below ground level as required :- | | | |
|---|
| 3 | 1.02 | Galvanized octagonal pole overall length 7 metre (sheet thickness 3mm), top dia.(A/F) 70mm and bottom dia. (A/F) 130mm, foundation size below ground level 550mm x 550mm x 1400mm, 4Nos. foundation bolts size 20mm dia., length 700mm with base plate dimensions 240mm x 240mm x 16mm thick. | | 90 | Each |
|---|
| 4 | 1.03 | GALVANIZED OCTAGONAL POLE BRACKETS | | | |
|---|
| 5 | 1.04 | Supply and erection of single arm bracket 1 metre long for 7 to 8 metre long galvanized octagonal pole, the bracket should be fixed on the top of the pole having top outer dia. 70mm (A/F) complete in all respect as approved by the Engineer-in-charge at site. | | 90 | Each |
|---|
| 6 | 2 | XLPE/ PVC INSULATED UN-ARMOURED CABLES (LOOSE IN THE EXISTING TRENCH OR PIPE): | | | |
|---|
| 7 | 2.01 | Supply and laying of XLPE/ P.V.C. insulated P.V.C. sheathed aluminium conductor un-armoured cable working voltage upto and including 1100 volts grade to be laid loose in the existing trench or pipe as per PWD General Specifications 2010:- | | | |
|---|
| 8 | 2.02 | XLPE/ PVC insulated PVC sheathed aluminium conductor unarmoured cable working voltage 1100volts grade 16sq.mm (4 Core) | | 5000 | Mtr |
|---|
| 9 | 2.03 | XLPE/ PVC insulated PVC sheathed aluminium conductor unarmoured cable working voltage 1100volts grade 35 sq.mm (3½ Core) | | 100 | Mtr |
|---|
| 10 | 3 | G.I. EARTHING: | | | |
|---|
| 11 | 3.01 | Supply and Erection of earth rod 20 mm dia for providing earth connections upto line earth with G.I. Wire No. 8SWG. The rod shall be tapered at one end and flatted on other end. The hole size 10mm dia shall be drilled on the flatened side for facilitating connection with G.I. wire and thimble etc. The road shall be grouted upto complete length vertically. | | | |
|---|
| 12 | 3.02 | GI Earth rod 20 mm dia. 3 mtr. Long | | 95 | Mtr |
|---|
| 13 | 4 | GALVANIZED IRON PIPES AND G.I. EARTHING: | | | |
|---|
| 14 | 4.01 | Earthing of Sheet metal/ iron clad Switches and metallic cases etc., with No. 7/14 S.W.G. (7/2.18mm dia.) G.I. wire in 20mm dia G.I. pipe partly recessed and partly on surface complete with 135cm long 50mm dia. G.I. earth pipe with G.I. reducing socket (50mm x 20mm) including erection of the same, 4metre below ground level with necessary charcoal & salt mixture etc., up to 7 metre in length (including boring & refilling). | | 2 | Each |
|---|
| 15 | 5 | MOULDED CASE CIRCUIT BREAKERS: | | | |
|---|
| 16 | 5.01 | Supply and erection of Moulded Case Circuit Breaker (Panel mounting Cubicle type) in the existing Cubical Panel conforms to IEC:60947-II) and relevant PWD general specifications 2010 complete with G.I. Bolts, Nuts & Connection on both sides of MCCB with sutiable size of Thimbles etc and bonding to the existing earth as per PWD General | | | |
|---|
| 17 | 5.02 | MCCB (Fixed Type Thermal and Magnetic Protection Make: L&T (DU/DH), ABB (T-MAX), Schneider (CVS), Seimens(3VT1/3VL)): | | | |
|---|
| 18 | 5.03 | 40-80amp. 415 volts breaking capacity = four pole fixed type thermal and magnetic setting MCCB unit | | 3 | Each |
|---|
| 19 | 5.04 | 100amp. 415 volts breaking capacity =25kA four pole fixed type thermal and magnetic setting MCCB unit | | 1 | Each |
|---|
| 20 | 6 | S/E of Microprocessor Based St. Light Controller with digital time switch daily programmed with stand by lithium battery with back up of 6 years with min. time between 2 switching operations is 1 minute, 3 nos. three pole power contactors 40A. with coil voltage 220-230V AC with 1 no. aux. contact NO, 1 no. aux. contactor 6 amp.(2NO+2NC) with coil voltage 220V AC, 3 nos. MCB 2 pole 40amp. (Ccurve, 10kA)& power wiring with single core PVC insulated FRLS cable 10 sq. mm and control wiring with PVC insulated FRLS cable 1 sq. mm, 1 no. two position selecto switch to bypass timer and other accessories & petty material (din rail, 2 nos. 4 pole bakelite terminal strip 63A/ 440V AC, required nut bolts) should be fixed on bakelite sheet 6mm thick to be mounted in a IP54 surface/ flush mounting powder coated sheet metal (1.60mm thick) cabinet having size 450mmx600mmx150mm to switch ‘ON’ all the 3 phases & switch ‘OFF’ 3 phases pre-fixed timings complete in all respect as per satisfaction of Engineer-in-charge. | | 1 | Each |
|---|
| 21 | 7 | DOUBLE WALLED CORRUGATED (DWC) HDPE PIPES: | | | |
|---|
| 22 | 7.01 | Supply and erection of double walled corrugated (DWC) HDPE pipe to be laid 1mtr. below ground level including excavation (making necessary trench), placing the pipe in position and back filling with excavated soil etc. of the required size. | | | |
|---|
| 23 | 7.02 | Double walled corrugated (DWC) HDPE pipe 50/ 38mm (outer/ inner dia.) | | 750 | Mtr |
|---|
| 24 | 8 | SHEET METAL BUS BAR CHAMBERS (COPPER STRIPS): | | | |
|---|
| 25 | 8.01 | Supply and erection of sheet metal bus-bar chamber (factory fabricated) duly powder coated on existing surface with required no. of bus-bar strips of suitable length and crosssectional area. Copper strips of suitable length and crosssectional area should be tinned and mounted on DMC/ SMC moulds at sufficient distance enclosure made of M.S. sheet 1.6mm thick with hinged cover and lock, fitted with dust excluding gaskets and secured with sufficient no. of cadmium plated iron screws and of given overall dimensions and to be fixed with G.I. bolts and nuts/ rag bolts and nuts etc. complete with all accessories including connections with suitable size of thimbles, bonding to the existing earth and painting etc. as desired by the Engineer-in-charge at site. | | | |
|---|
| 26 | 8.02 | Sheet metal bus bar chamber suitable for 100amp. 415 volts capacity with 4 tinned copper strip bus bars each of length 270mm and cross sectional area (25mm x 3.3mm) enclosure having over all dimensions (350mm x 450mm x 150mm) nominal | | 1 | Each |
|---|
| 27 | 9 | SHEET METAL CUBICAL PEDESTAL, TOWER STRUCTURES, HT & LT MISCELLANEOUS ITEMS: | | | |
|---|
| 28 | 9.01 | S/E of SMCpedestal made from 50mmx50mmx6mm thick MS angle iron frame with 5 sides welded & covered with MS sheet 2mm thick & front side hinged with 4\" hinges & locking system with heavy duty 12\" sliding door.Placed on MS strip of size 12.5mmx2.5mm thick welded with MS sheet with 4no. legs of 50mmx50mmx6mm thick MS angle iron each of 600mm long with MS sheet 100mmx100mmx6mm thick at the bottom end of the legs.Front door welded x-actionally with MS flat 25mmx5mm.The front side with MS sheet each 75mm wide & a bend of 75mm width outwards & inwards on all sides with tappered top 200mm high.And pedestial with 4 Nos supporting members each of MS flat 50mmx6mm thick acc. to cubical size duly welded & complete pedestal to be painted with 1 coat of red oxide & 2 coats of paint &bonding to the existing earth to be erected in the 1:2:4 CC, the platform of 150mm high from ground level & 450mm thick & 150mm from the top of the CCplatform as per Drawing attached. | | | |
|---|
| 29 | 9.02 | Cubical Size 900mm high, 600mm wide and 350mm deep | | 1 | Each |
|---|
| 30 | 9.03 | Cubical Size 1400mm high, 1200mm wide and 500mm deep | | 1 | Each |
|---|
| 31 | 10 | PVC INSULATED SINGLE CORE FR COPPER CONDUCTOR CABLE: | | | |
|---|
| 32 | 10.01 | Supply and erection of PVC insulated single core FR copper conductor cable ISI marked left bare in pipe or casing of suitable size excluding the cost of supply and erection of pipe or casing. | | | |
|---|
| 33 | 10.02 | PVC insulated copper conductor single core FR cable (ISI marked) overall 1.5 sq.mm, 1100volts grade | | 2000 | Mtr |
|---|
| 34 | 10.03 | PVC insulated copper conductor single core FR cable (ISI marked) overall 10 sq.mm, 1100volts grade | | 175 | Mtr |
|---|
| 35 | 11 | supply and erection of MS box made out of 1,6 mm thick sheet for housing 63 Amp and 100 Amp 4 poles MCCB,s complete with all necessary arrangement for housing the MCCB,s | | 4 | Each |
|---|
| 36 | 12 | Supply, erection, testing and commissioning of 45 Watt LED street lighting fitting of Philips Cat no. BRP 409LED 040 CW H0 MR FG S1 PSU GR , C&S MAKE Cat. noINDUS/45/LS. or Crompton cat no.LSTS-45-CDL-1 complete in all respects with drivers etc. and as per following specifications Approved by Technical advisor to Hon’ble CM, Punjab vide Letter No ATPB/20/GL Dated 30 Nov 2017 | | | |
|---|
| 37 | 12.01 | ELECTRICAL PARAMETERS: | | | |
|---|
| 38 | 12.02 | Input Operating Voltage - 140 to 270 volts | | | |
|---|
| 39 | 12.03 | Input AC Frequency - AC 50 Hz +-1% | | | |
|---|
| 40 | 12.04 | Efficiency of driver - Morethan 85%, the control gear should be complying with IEC 61347 -2-13, IEC 62384 & IEC 62031 as per requirement. The driver should comply with CISPR-15 for limit and methods of measurement of ratio disturbance characteristic. Current waveform shouldmeet 61000-3-2 the driver should be constant current driver. | | | |
|---|
| 41 | 12.05 | Driver Type - Shall be potted driver | | | |
|---|
| 42 | 12.06 | THD) Total Harmonic Disortion- < 10% | | | |
|---|
| 43 | 12.07 | LED Driver current - Less than 750 mA | | | |
|---|
| 44 | 12.08 | Minimum 100 lumens per watt | | | |
|---|
| 45 | 12.09 | Efficacy of LED lamp - More than 130 lumens per watt | | | |
|---|
| 46 | 12.1 | Working humidity - 10% to 90% RH | | | |
|---|
| 47 | 12.11 | Surge Protection - 4 KV and above as per IEC 61000-4-5 | | | |
|---|
| 48 | 12.12 | OPTICAL PARAMETERS | | | |
|---|
| 49 | 12.13 | LED Make - Nichia/Philips/Lumiled/Cree/Osram/Seoul | | | |
|---|
| 50 | 12.14 | LED life - Above 50000 operating hours at 70% lumens | | | |
|---|
| 51 | 12.15 | CRI (Color Rendering Index) - More than 70 | | | |
|---|
| 52 | 12.16 | Lenses - Each LED shall be of high power LED with wattage 1 watt to 3 watt with mandatory Modular Lenses. | | | |
|---|
| 53 | 12.17 | THERMAL PARAMETERS | | | |
|---|
| 54 | 12.18 | Working Temperature - 0 degree C to 50 degree C | | | |
|---|
| 55 | 12.19 | Color Temperature - 5000 to 6500 degree kelvin | | | |
|---|
| 56 | 12.2 | Heat Sink - Pressure Diecast or Extruded Aluminium | | | |
|---|
| 57 | 12.21 | Junction Temperature - 100 degree C | | | |
|---|
| 58 | 12.22 | GENERAL PARAMETERS | | | |
|---|
| 59 | 12.23 | Body of fitting - Pressure diecast Aluminium housing with control gear (with IP 65/IP 66 Protection) with company logo engraved/embossed in the housing LM-6 Grade. | | | |
|---|
| 60 | 12.24 | Ingres Protection - IP66 as per IEC 60529:2001 with test certificate | | | |
|---|
| 61 | 12.25 | Impact code - Min IK05 or more | | | |
|---|
| 62 | 12.26 | Fitting Glass - i) Toughened Glass / Polycarbonatecover upto 25W ii) Only toughened Glass more than 25W | | | |
|---|
| 63 | 12.27 | Preciation life duly supported with relevant LM79-80 reports from NABL/UL accredited laboratory/Certificates from manufactures of Luminaries duly counter signed by Branch Manager/Area Manager - LM 79 & LM 80 | | | |
|---|
| 64 | 12.28 | Indentification - Logo and Brand Name shall be Printed/Embossed on Luminaire | | | |
|---|
| 65 | 12.29 | The fittings should have a low/high voltage, reverse polarity, overload and short circuit protection inbuilt in the fixture itself- Provided | | | |
|---|
| 66 | 12.3 | The Contractor should submit the certificate from the manufacture of Luminaie supplier regarding the authenticity and specification of fittings duly signed by Area Manager/Branch Manager - As per annexure ‘A’ attached i.e The contractor should submit the certificate from the manufacturer of Luminaries Supplier to the Department regarding the authenticity , five year warranty and undertaking that the material supplied is as per PWD specifications approved by the Department. The Undertaking should be signed by area Manager or Branch Manager or higher hirerchacy of manufacturer of Luminaire suppliers. | | | |
|---|
| 67 | 12.31 | MARKING | | | |
|---|
| 68 | 12.32 | Manufactures name/year of manufacture - Marking Sticker on the fitting. | | | |
|---|
| 69 | 12.33 | Rated voltage (makred \"v\" or volts) - Marking Sticker on the fitting. | | | |
|---|
| 70 | 12.34 | Rated Wattage (marked \"W\" or watt) - Marking Sticker on the fitting. | | | |
|---|
| 71 | 13 | Batch No./Serial No.- Marking Sticker on the fitting. | | 90 | Each |
|---|