Orissa Industrial Infrastructure Development Corporation-IDCO has published Overhauling, Testing, Commissioning With Additional Spare Parts And Lubricants Of Hvac System (4 X 400Tr + 1 X 200Tr Chiller Of ‘Blue Star’ Make With Associated Pumps, Ahu, Cooling Tower And Chilled Water Pipe Lines) With Sitc Of Control Console Panel Wit. Submission Date for this Tender is 17-01-2020. Spare Part Tenders in Mancheswar, Bhubaneswar Odisha. Bidders can get complete Tender details and download the document.
Sr No | CorrigendumDate | Corrignedum | CorrigendumType | NewSubmissionDate |
1 | 04-Jan-2020 | Corrigendum | Date | 17-01-2020 |
Name of Work:Overhauling, testing, commissioning with additional spare parts and lubricants of HVAC system (4 x 400TR + 1 x 200TR Chiller of ‘Blue Star’ make with associated pumps, AHU, Cooling Tower and chilled water pipe lines) with SITC of Control Console panel with associates cabling works at Tower – 2010, Mancheswar I.E. Bhubaneswar. (The bidders are required to Quote their rates excluding of Goods & Service Tax (GST). GST as applicable will be paid extra. The existing rule of Govt. and any amendment made in future will be followed) | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | A) OVERHAULING/DAMAGE RECTIFICATION : | BI01010001010000000000000515BI0100001113 | ||
2 | 2 | CHW & CDS Motor Overhauling [Consider only Heat Burnishing] | BI01010001010000000000000515BI0100001114 | 15 | No. |
3 | 3 | CT Basin Leak Repairing and Motor Overhauling / Gear Oil Changing | BI01010001010000000000000515BI0100001115 | 3 | No. |
4 | 4 | Chilled Water Pipe Chemical Cleaning | BI01010001010000000000000515BI0100001116 | 1 | Lot |
5 | 5 | Condenser Water Pipe Chemical Cleaning | BI01010001010000000000000515BI0100001117 | 1 | Lot |
6 | 6 | Valves Actuator Checking and Overhauling [High and Low Site] | BI01010001010000000000000515BI0100001118 | 24 | No. |
7 | 7 | Pressurizing Tank Nitrogen Pressure Testing | BI01010001010000000000000515BI0100001119 | 1 | Lot |
8 | 8 | Insulation and Cladding Repairing | BI01010001010000000000000515BI0100001120 | 1 | Lot |
9 | 9 | Repainting of Condenser Line | BI01010001010000000000000515BI0100001121 | 1 | Lot |
10 | 10 | B) SPARE PARTS AND LUBRICANTS : | |||
11 | 11 | Suction Pressure Sensor-200-TI-200-20 | BI01010001010000000000000515BI0100001122 | 1 | No. |
12 | 12 | Discharge Pressure Sensor -200-TI-200-20 | BI01010001010000000000000515BI0100001123 | 1 | No. |
13 | 13 | Oil Pressure Sensor -200-TI-200-20 | BI01010001010000000000000515BI0100001124 | 1 | No. |
14 | 14 | Oil Level Sensor [OLC D1-347947901] | BI01010001010000000000000515BI0100001125 | 1 | No. |
15 | 15 | Refrigerant Level Sensor -F 7805070] | BI01010001010000000000000515BI0100001127 | 2 | No. |
16 | 16 | Keypad Display Card for MCS | BI01010001010000000000000515BI0100001128 | 1 | No. |
17 | 17 | ELEC.EX.VALVE ETS250 (DANFOSS) [Sporlan SEH-100 Electronic Expansion Valve] | BI01010001010000000000000515BI0100001129 | 1 | No. |
18 | 18 | Exv Card For LCWX1-1000 FI Compressor Unit Model No LCWX2-1580-FFA | BI01010001010000000000000515BI0100001130 | 2 | No. |
19 | 19 | Compressor -OIL -HBR -B08L | BI01010001010000000000000515BI0100001132 | 70 | Ltr. |
20 | 20 | Refrigerant R -134A | BI01010001010000000000000515BI0100001133 | 600 | Kg. |
21 | 21 | FILTER SHELL-SHELLR134A (4CORE) [CTG Dehydrator (48 Core)] | BI01010001010000000000000515BI0100001135 | 32 | No. |
22 | 22 | FILTER DRIER-EXT. RC 1090F VI.2.2 | BI01010001010000000000000515BI0100001136 | 8 | No. |
23 | 23 | MCS-MAGNUM VERSION 8.1 Self Card | BI01010001010000000000000515BI0100001138 | 2 | No. |
24 | 24 | CONTROLLER-MCS-MAGNUM VERSION 8.1 ve [ECCO-MC003-00] | BI01010001010000000000000515BI0100001139 | 2 | No. |
25 | 25 | Solenoid Coil SMG 01 | BI01010001010000000000000515BI0100001140 | 12 | No. |
26 | 26 | Suction Pressure Sensor-200-TI-200-20 | BI01010001010000000000000515BI0100001141 | 2 | No. |
27 | 27 | Discharge Pressure Sensor -200-TI-200-20 | BI01010001010000000000000515BI0100001142 | 2 | No. |
28 | 28 | Oil Pressure Sensor -200-TI-200-20 | BI01010001010000000000000515BI0100001143 | 2 | No. |
29 | 29 | SSPR For Compressor | BI01010001010000000000000515BI0100001144 | 4 | No. |
30 | 30 | INT 69 [ Motor Protector] | BI01010001010000000000000515BI0100001145 | 4 | No. |
31 | 31 | Motor Winding Temperature Sensor T 001580-FFA | BI01010001010000000000000515BI0100001146 | 1 | No. |
32 | 32 | MCS Temperature Sensor T-100-20 | BI01010001010000000000000515BI0100001147 | 6 | No. |
33 | 33 | MCS CT Card for 600Amps EATFZ0050 | BI01010001010000000000000515BI0100001148 | 2 | No. |
34 | 34 | Labour Charges for Pressure Testing Vacuumisation, Gas Charging | BI01010001010000000000000515BI0100001149 | 5 | No. |
35 | 35 | C) CONTROL CONSOLE PANEL : | |||
36 | 36 | 1) Supply, Erection, Testing and Commissioning of Control Console Panel as per the detailed Specifications and Drawings including Connections etc. including Door Interlocking and Expendable as required comprising of: | BI01010001010000000000000515BI0100001150 | 1 | Set |
37 | 37 | On Indicating Lamp - 23 Nos. | |||
38 | 38 | Off Indicating Lamp - 23 Nos. | |||
39 | 39 | Trip Indicating Lamp - 23 Nos. | |||
40 | 40 | On Push Button - 23 Nos. | |||
41 | 41 | Off Push Button - 23 Nos. | |||
42 | 42 | Aux.Contactor-2NO+2NC - 23 Nos. | |||
43 | 43 | PLA Relay-2C/O - 23 Nos. | |||
44 | 44 | Electronic Hooter - 1 Nos. | |||
45 | 45 | Stud Type Terminal - 50 Nos. | |||
46 | 46 | 6A SP 10KA MCB - 23 Nos. | |||
47 | 47 | 2) Supply and Laying of following sizes of 1.1 KV Grade Multicore PVC Sheathed Armoured XLPE/PVC Cable as per Relevant IS. | |||
48 | 48 | a) 3C*2.5 Sqmm YWY Cable. | BI01010001010000000000000515BI0100001151 | 2000 | Rmt |
49 | 49 | b) 5C*2.5 Sqmm YWY Cable. | BI01010001010000000000000515BI0100001153 | 1000 | Rmt |
50 | 50 | 3) Supplying and Making End Termination with suitable size Bimetallic Lugs (for Copper to Aluminum Connection) or Tinned Copper Lugs (for Copper to Copper Connection) including Double Compression Glands of following sizes of 1.1KV Grade Multicore Aluminum Conductor PVC Insulated | |||
51 | 51 | a) 3C*2.5 Sqmm YWY Cable. | BI01010001010000000000000515BI0100001154 | 150 | No. |
52 | 52 | b) 5C*2.5 Sqmm YWY Cable. | BI01010001010000000000000515BI0100001155 | 150 | No. |
53 | 53 | 4) Supply and Fixing of Hot Dip Galvanised, Factory Fabricated, GI Perforated type Cable Trays of following sizes with necessary Bends, Tees, Reducers Couplers etc. (Cost shall include all accessories necessary for Fixing and Supporting) | |||
54 | 54 | a) Cable Tray : 100mmwidth x 50mm depth x 1.6mm Thickness | BI01010001010000000000000515BI0100001156 | 150 | Rmt |
55 | 55 | b) Galvanised Threaded Rod M10 | BI01010001010000000000000515BI0100001157 | 251 | Rmt |
56 | 56 | c) 10 MM Anchor Fastener Hilti/Fisher Make | 250 | No. | |
57 | 57 | d) Slotted Channel 2mm, 50mm (W) G.I. Slotted Channel | 56 | Rmt | |
58 | 58 | 5) Modification of Existing HVAC Panel | 1 | Lot | |
59 | 59 | N.B: The bidders are required to Quote their rates excluding of Goods & Service Tax (GST). GST as applicable will be paid extra. The existing rule of Govt. and any amendment made in future will be followed. | BI01010001010000000000000515BI0100001158 |