Providing Of Lt Capacitor Apfc Panels , Central Hot Water System ( Solar ) , Exhaust Fans And Special Repair To Lightening Conductor On Esh Sheds And Certain Minor And Revenue Works At 18 Fad Unchibassi Under Ge ( South ) Pathankot . Provn Of Lt C, Unchibassi-Punjab

Military Engineer Services-MES has published Providing Of Lt Capacitor Apfc Panels , Central Hot Water System ( Solar ) , Exhaust Fans And Special Repair To Lightening Conductor On Esh Sheds And Certain Minor And Revenue Works At 18 Fad Unchibassi Under Ge ( South ) Pathankot . Provn Of Lt C. Submission Date for this Tender is 13-01-2020. Conductor Tenders in Unchibassi Punjab. Bidders can get complete Tender details and download the document.




Tender Notice

23025382
Corrigendum : Providing Of Lt Capacitor Apfc Panels , Central Hot Water System ( Solar ) , Exhaust Fans And Special Repair To Lightening Conductor On Esh Sheds And Certain Minor And Revenue Works At 18 Fad Unchibassi Under Ge ( South ) Pathankot . Provn Of Lt C
Open Tender
Indian
Punjab
Unchibassi
13-01-2020

Tender Details

Providing Of Lt Capacitor Apfc Panels , Central Hot Water System ( Solar ) , Exhaust Fans And Special Repair To Lightening Conductor On Esh Sheds And Certain Minor And Revenue Works At 18 Fad Unchibassi Under Ge ( South ) Pathankot . Provn Of Lt Capacitor Apfc Panels , Central Hot Water System ( Solar ) , Exhaust Fans And Special Repair To Lightening Conductor On Esh Sheds And Certain Minor And Revenue Works At 18 Fad Unchibassi Under Ge ( South ) Pathankot .

Corrigendum Details

Sr No CorrigendumDate Corrignedum CorrigendumType NewSubmissionDate
1 08-Jan-2020 GES/PKT/T-44/2019-20 Date 13-01-2020

Key Value

Document Fees
INR 500 /-
EMD
INR 98000.0 /-
Tender Value
INR 49 Lakhs /-

BOQ Items

Name of Work: Provn of LT Capacitor APFC Panels, Central Hot water system (Solar), Exhaust fans and Special repair to lightening conductor on ESH Sheds and certain Minor and Revenue works at 18 FAD Unchibassi under GE (South) Pathankot.
Sl. No. Item Description Item Code / Make Quantity Units
1 1 Supply, install, testing and commissioning of Automatic Power Factor correction (APFC) Panel 30 KVAR with auto/Manual option, factory made, outdoor type, double door, slopy canopy, fabricated out of 3.15mm thick CRCA sheet with angle iron base frame made of 50x50x6mm, 45cm height, dust and vermin proof, suitable for voltage 415V 3 phase 4 wire weather proof with IP-54 protection, with separate hinge door for each compartment for incoming and outgoing switchgear/MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC including painting with two coats of epoxy powder paint over a coat of primer after undergoing a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate, suitable double compression copper cable glands compete in all respects for main panel for transformer and including provn of the following : - Note : The panel shall be of CPRI type tested, PCC will be measured and paid separately. (a)  No of steps- 03 steps and 1 fixed step of capacity 5 KVAR 3 Each
2 2 INCOMING:-
3 3 63 Amp TPN 25 KA MCCB with Handle & fixed Thermal Magnetic Release -01 No
4 4 Digital Type Ammeter with Inbuilt Selector switch. - 01 No
5 5 Digital Type Voltmeter with inbuilt selector switch. - 01 No
6 6 LED Type Indicating Lamps R,Y,B -03 Nos
7 7 Control Fuse, 4 Amps - 03 Nos
8 8 Ring Type CT 200/5A, 10 VA, CL1 Tape Wounded -01 No.
9 9 APFC SECTION (10+10+10=30 KVAR)
10 10 32 Amp TP MCB for 10 KVAR - 03 Nos
11 11 25 Amp capacitor switching TP contractor for 10 KVAR, - 03 Nos
12 12 Auxiliary Contactor, - 03 Nos
13 13 3 Stage APFC Relay, intelegent - 01 No
14 14 On Delay Timer, 0-180 Sec, - 01 No
15 15 MDXL capacitors (10+10+10=30 KVAR),
16 16 Flush type Start Push Button with 1 No, -03 Nos
17 17 Flush type Stop Push Button with 2 NC, -03 Nos
18 18 LED Type On Indicating Lamp - RED , -03 Nos
19 19 Note :- (i)The capacitors shall be housed in self extinguishing insulation material operated on 3 phase, 415 Volts AC, frequency 50 Hz. The dielectric should be mixed dielectric type (MD XL), with built in over pressure safety device, tolerance 0% to 10% protection degree IP 30 and maximum temperature 55o C.
20 20 (ii) Rate shall be deemed to include provision of suitable size of aluminium bus bar three phase 4 wire.
21 21 Supply, install, testing and commissioning of Automatic Power Factor correction (APFC) Panel 50 KVAR with auto/Manual option, factory made, outdoor type, double door, slopy canopy, fabricated out of 3.15mm thick CRCA sheet with angle iron base frame made of 50x50x6mm, 45cm height, dust and vermin proof, suitable for voltage 415V 3 phase 4 wire weather proof with IP-54 protection, with separate hinge door for each compartment for incoming and outgoing switchgear/MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC including painting with two coats of epoxy powder paint over a coat of primer after undergoing a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate, suitable double compression copper cable glands compete in all respects for main panel for transformer and including provn of the following : - Note : The panel shall be of CPRI type tested, PCC will be measured and paid separately. (a)  No of steps- 03 steps and 1 fixed step of capacity 5 KVAR 2 Each
22 22 INCOMING:-
23 23 80 Amp TPN 25 KA MCCB with Handle & fixed Thermal Magnetic Release -01 No
24 24 Digital Type Ammeter with Inbuilt Selector switch. - 01 No
25 25 Digital Type Voltmeter with inbuilt selector switch. - 01 No
26 26 LED Type Indicating Lamps R,Y,B -03 Nos
27 27 Control Fuse, 4 Amps - 03 Nos
28 28 Ring Type CT 200/5A, 10 VA, CL1 Tape Wounded -01 No.
29 29 APFC SECTION (10+10+15+15=50 KVAR)
30 30 32 Amp TP MCB for 10 KVAR - 04 Nos
31 31 25 Amp capacitor switching TP contractor for 10 KVAR, - 04 Nos
32 32 Auxiliary Contactor, - 04 No
33 33 3 Stage APFC Relay, intelegent - 01 No
34 34 On Delay Timer, 0-180 Sec, - 01 No
35 35 MDXL capacitors (10+10+15+15=50 KVAR),
36 36 Flush type Start Push Button with 1 No, -04 Nos
37 37 Flush type Stop Push Button with 2 NC, -04 Nos
38 38 LED Type On Indicating Lamp - RED , -04 Nos
39 39 Note :- (i)The capacitors shall be housed in self extinguishing insulation material operated on 3 phase, 415 Volts AC, frequency 50 Hz. The dielectric should be mixed dielectric type (MD XL), with built in over pressure safety device, tolerance 0% to 10% protection degree IP 30 and maximum temperature 55o C.
40 40 (ii) Rate shall be deemed to include provision of suitable size of aluminium bus bar three phase 4 wire.
41 41 Supply, install, testing and commissioning of Automatic Power Factor correction (APFC) Panel 100 KVAR with auto/Manual option, factory made, outdoor type, double door, slopy canopy, fabricated out of 3.15mm thick CRCA sheet with angle iron base frame made of 50x50x6mm, 45cm height, dust and vermin proof, suitable for voltage 415V 3 phase 4 wire weather proof with IP-54 protection, with separate hinge door for each compartment for incoming and outgoing switchgear/MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC including painting with two coats of epoxy powder paint over a coat of primer after undergoing a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate, suitable double compression copper cable glands compete in all respects for main panel for transformer and including provn of the following : - Note : The panel shall be of CPRI type tested, PCC will be measured and paid separately. (a)  No of steps- 03 steps and 1 fixed step of capacity 5 KVAR 1 Each
42 42 INCOMING:-
43 43 160 Amp TPN 25 KA MCCB with Handle & fixed Thermal Magnetic Release -01 No
44 44 Digital Type Ammeter with Inbuilt Selector switch. - 01 No
45 45 Digital Type Voltmeter with inbuilt selector switch. - 01 No
46 46 LED Type Indicating Lamps R,Y,B -03 Nos
47 47 Control Fuse, 4 Amps - 05 Nos
48 48 Ring Type CT 200/5A, 10 VA, CL1 Tape Wounded -01 No.
49 49 APFC SECTION (10+15+25+25+25=100 KVAR)
50 50 32 Amp TP MCB for 10 KVAR - 05 Nos
51 51 25 Amp capacitor switching TP contractor for 10 KVAR, - 05 Nos
52 52 Auxiliary Contactor, - 05 No
53 53 3 Stage APFC Relay, intelegent - 01 No
54 54 On Delay Timer, 0-180 Sec, - 01 No
55 55 MDXL capacitors (10+15+25+25+25=100 KVAR),
56 56 Flush type Start Push Button with 1 No, -05 Nos
57 57 Flush type Stop Push Button with 2 NC, -05 Nos
58 58 LED Type On Indicating Lamp - RED , -05 Nos
59 59 Note :- (i)The capacitors shall be housed in self extinguishing insulation material operated on 3 phase, 415 Volts AC, frequency 50 Hz. The dielectric should be mixed dielectric type (MD XL), with built in over pressure safety device, tolerance 0% to 10% protection degree IP 30 and maximum temperature 55o C.
60 60 (ii) Rate shall be deemed to include provision of suitable size of aluminium bus bar three phase 4 wire.
61 61 Supply, install, testing and commissioning of Automatic Power Factor correction (APFC) Panel 120 KVAR with auto/Manual option, factory made, outdoor type, double door, slopy canopy, fabricated out of 3.15mm thick CRCA sheet with angle iron base frame made of 50x50x6mm, 45cm height, dust and vermin proof, suitable for voltage 415V 3 phase 4 wire weather proof with IP-54 protection, with separate hinge door for each compartment for incoming and outgoing switchgear/MCCB etc with locking arrangement, with back door openable (Screwed), legs grouted in PCC including painting with two coats of epoxy powder paint over a coat of primer after undergoing a rigorous metal treatment process involving alkaline degreasing, descaling in dilute sulphuric acid or any other acid and phosphate, suitable double compression copper cable glands compete in all respects for main panel for transformer and including provn of the following : - Note : The panel shall be of CPRI type tested, PCC will be measured and paid separately. (a)  No of steps- 03 steps and 1 fixed step of capacity 5 KVAR 2 Each
62 62 INCOMING:-
63 63 200 Amp TPN 25 KA MCCB with Handle & fixed Thermal Magnetic Release -01 No
64 64 Digital Type Ammeter with Inbuilt Selector switch. - 01 No
65 65 Digital Type Voltmeter with inbuilt selector switch. - 01 No
66 66 LED Type Indicating Lamps R,Y,B -03 Nos
67 67 Control Fuse, 4 Amps - 06 Nos
68 68 Ring Type CT 200/5A, 10 VA, CL1 Tape Wounded -01 No.
69 69 APFC SECTION (10+10+25+25+25+25=120 KVAR)
70 70 32 Amp TP MCB for 10 KVAR - 06 Nos
71 71 25 Amp capacitor switching TP contractor for 10 KVAR, - 06 Nos
72 72 Auxiliary Contactor, - 06 Nos
73 73 3 Stage APFC Relay, intelegent - 01 No
74 74 On Delay Timer, 0-180 Sec, - 01 No
75 75 MDXL capacitors (10+15+25+25+25=100 KVAR),
76 76 Flush type Start Push Button with 1 No, -06 Nos
77 77 Flush type Stop Push Button with 2 NC, -06 Nos
78 78 LED Type On Indicating Lamp - RED , -06 Nos
79 79 Note :- (i)The capacitors shall be housed in self extinguishing insulation material operated on 3 phase, 415 Volts AC, frequency 50 Hz. The dielectric should be mixed dielectric type (MD XL), with built in over pressure safety device, tolerance 0% to 10% protection degree IP 30 and maximum temperature 55o C.
80 80 (ii) Rate shall be deemed to include provision of suitable size of aluminium bus bar three phase 4 wire.
81 81 Supply, laying and testing in trenches or fixing to wall/pole or passing through pipe XLPE insulated heavy duty electric cable with aluminium conductor 1100 volts grade cross sectional area 120 Sqmm 3.5 core complete all as specified and directed. (Note : Incl making good all distributed wall surfaces/ flooring/tilling to match with existing specification) 20 RM
82 82 All as per item No 81 above but size 95 sqmm 3.5 Core complete all as specified and directed. 15 RM
83 83 All as per item No 81 above but size 50 sqmm 3.5 Core complete all as specified and directed. 20 RM
84 84 All as per item No 81 above but size 35 sqmm 3.5 Core complete all as specified and directed. 20 RM
85 85 All as per item No 81 above but size 10 sqmm 2 Core complete all as specified and directed. 180 RM
86 86 Excavation in trenches in any type of soil n exc 1.5 mtr in width and n. exc 1.5 mtr in depth and getting out all as required for laying of cables, Pipe line,foundation filling of poles or stays and for rerouting of cables complete all as specified and directed. 79 Cum
87 87 All as per item No-86 but depth exc 1.5 mtr but not exc 3.00 mtr complete all as specified and directed. 1 Cum
88 88 Returning filling, in including spreading ,leveling, watering and well ramming in layers not exc 25 cm each complete all as specified and directed. 62 Cum
89 89 Removing excavated material to a distance not exceeding 50 meters and depositing where directed at a level not exc 1.5 mtr above the starting point complete all as specified and directed. 18 Cum
90 90 M&L for sand cushioning to under ground cables 8 cm thick before laying the cable and 15 cm, thick after laying, stretching and testing the cable complete all as specified and directed. 16 Cum
91 91 M&L for Sub class ‘B’ bricks old size. laid dry flat over the cable abutting each other, length of cable equal to width of brick complete all as specified and directed. 3.1 Per 1000 Nos
92 92 M&L for Cable jointing kit for 1100 volt grade cable for outdoor/indoor termination end joint heat shrinkable type complete with jointing material and accessories suitable for XLPE/PVC armoured aluminium conductor cable of size 50 to 95 Sqmm 3.5/4 core complete all as specified and directed. 8 Each
93 93 All as per item No 92 but for 120 to 185 Sqmm size complete all as specified and directed. 8 Each
94 94 M&L for Earthing complete with galvanised steel earth plate electrode 600mmx600mm thickness not less than 6mm thick buried directly in ground (earth pit not less than 2.25 mtr deep below normal ground level) with top edge of earth plate not less than 1.5m below normal ground level connected to galvanised iron strip 32x6mm Earthing lead by means of bolts, nuts, check nuts and washers of galvanised iron/steel all as shown in electric plate No 3 connected to earth test point/MCB DBs all as specified and indicated compete with funnel, charcoal, dust, salt etc and GI protection pipe, medium grade 15mm bore and GI watering pipe 20mm bore light grade, 40mm thick precast RCC M-15 (nomial mix) cover reinforced with XPM weight not less than 4 Kg/Sqm with suitable handle of 6mm dia MS bar and angle iron 40x40x3mm frame for cover, PCC M-15 (Nominal mix) pit, excavation and earth work in any type of soil and connected all as specified or indicated including testing on completion. 8 Each Set
95 95 Supply, install, testing and commissining of Solar water heater system (ETC Type ) capacity 300 LPD at 60 degree C (Average) temperature with electric heating backup with the following specifications recommended by manufacturer complete :- 5 Each
96 96 (a) Inner tank : SS 304-2B
97 97 (b) Outer tank : PP color coated GI
98 98 (c) Frame /Stand : MS and GI Structure with epoxy and PU coating
99 99 (d) Linear welding : High Frequency Seam Welding
100 100 (e) Circular welding : High Frequency Seam Welding
101 101 (f) Tank connections : Robotic Arm Argon Welding Machie
102 102 (g) Insulation : 50 MM PUF
103 103 (h) Hot water tank (SS-304) TIG welded with PUF insulation & Stainless steel outer cladding
104 104 (j) Hydraulic steam hose pipe with check nut
105 105 (k) Stand for hor water tank
106 106 (l) Air vent 1 No for each system
107 107 Supply, install, testing and commissining of Solar water heater system (ETC Type ) capacity 100 LPD at 60 degree C (Average) temperature with electric heating backup with the following specifications recommended by manufacturer complete :- 2 Each
108 108 (a) Inner tank : SS 304-2B
109 109 (b) Outer tank : PP color coated GI
110 110 (c) Frame /Stand : MS and GI Structure with epoxy and PU coating
111 111 (d) Linear welding : High Frequency Seam Welding
112 112 (e) Circular welding : High Frequency Seam Welding
113 113 (f) Tank connections : Robotic Arm Argon Welding Machie
114 114 (g) Insulation : 50 MM PUF
115 115 (h) Hot water tank (SS-304) TIG welded with PUF insulation & Stainless steel outer cladding
116 116 (j) Hydraulic steam hose pipe with check nut
117 117 (k) Stand for hor water tank
118 118 (l) Air vent 1 No for each system
119 119 Note for Item No 95 & 107:- The angle iron supports for solar stand, Hot and cold water tanks, pipe line and PCC will be measured and paid separately under relevant schedule items.
120 120 S & F triple layered Rotational moulded polyethylen water storage tanks (Cylindrical vertical with closed top) hoisted and fixed in position incl civil works and all fittings all as specified and directed by Engr-In-Charge of following capacity :-
121 121 (a) 500 Ltrs 3 Each
122 122 (b) 1000 Ltrs 2 Each
123 123 S & F Hot water pipe duly insulated with glass wool and aluminium cladding of size 20 mm bore complete all as specified and directed. 180 RM
124 124 S & F Hot water pipe duly insulated with glass wool and aluminium cladding of size 25 mm bore complete all as specified and directed. 129 RM
125 125 Supply, fixing and laying in trenches/on wall/on roof GI water tubing of size 25 mm dia medium grade ISI marked with all required fittings such as bends elbows, tees short pieces, connector check nuts & threading complete all as specified and directed. 400 RM
126 126 All as per Item No 125 above but 20 mm dia complete all as specified and directed. 350 RM
127 127 Supply and fixing Gun metal gate valve ISI marked with iron wheel head screwed both ends for pipe of size 25 mm complete all as specified and directed. 14 Each
128 128 All as per Item No127 above but 20 mm dia complete all as specified and directed. 20 RM
129 129 M&L for PCC (1:2:4) type B1 with 20 mm graded stone aggregate for the bottom basement layer of the sloar stands complete all as specified and directed. 2 Cum
130 130 M & L for PCC 1:4:8 type D-2 using 40 mm grade aggregate as in foundation of pole, stay and filling and mass concrete) inclproviding necessery form work complete all as specified and directed. 2 Cum
131 131 M & L for PCC 1:3:6 type C-2 using 40 mm grade aggregate as in coping of pole, inclproviding necessery form work complete all as specified and directed. 0.5 Cum
132 132 Supply and fix sheet metal enclosure MCB distribution board, double door with IP-43 IK-09 protection with metal door single phase 240 volts 4 way, including suitable size copper bus bar and neutral link fixed flush in wall including chases wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and directed. 7 Each
133 133 M&L for MCB single pole 240 volts 5 to 40 amps, with rupturing capacity 10 KA using thimbles of required size complete all as specified and directed. 7 Each
134 134 M&L MCB single pole & neutral 240 volts 30 to 63 amps,with rupturing capacity 10 KA using thimbles of required size complete all as specified and directed. 7 Each
135 135 M&L for submain wiring with two single core PVC insulated flexible copper conductor multistranded cable (FR) of size 10 sqmm with proper color coding and one single core PVC insulated flexible copper conductor multistranded cable green colour of size 6 Sqmm as earth lead in & including concealed PVC conduit medium grade cutting chases to walls for laying conduit and making good the disturbed wall surfaces to match with existing specification all as required at site or directed by Engr-in- charge. 230 RM
136 136 S & F bib tap brass CP fancy type screwed down for iron pipe or for brass ferrule 15mm bore and fixed complete all as specified and directed. 15 Each
137 137 Supply and fix angle iron stand made out of 50 x 50 x 6 mm angle iron and 50 x 6 mm flat suitable for stand for Cold water tanks incl painting the stand with two coat of synthetic enemel paint over a coat of red oxide primer complete all as specified and directed. 700 Kg
138 138 Supply & fix exhaust fans AC single phase 230/ 240 V of size 300 mm sweep heavy duty with 1400 RPM incl louver shutter complete all as specified and directed. 174 Each
139 139 M & L for making a hole on wall with drill machine suitable for fixing of exhaust fan of size 300 mm sweep including plastering, paint with existing colour complete all as specified and directed. 174 Each Job
140 140 M & L for point wiring with 1.50 sqmm in copper conductor cable ( multistrand) FRLS single core PVC insulated cable for one light point or one fan point or bell point controlled by one switch SP one way 230 Volts in and including PVC concealed conduit ( ISI Marked) of heavy duly with all accessories ie PVC gutties etc terminated in CI sunken/pressed steel terminal boxes covered with new 3mm thick plastic laminated bakelite sheet fitted with brass screws and washers for mounting of switches /sockets/ fan regulators etc and continuous earth wire 1.5 Sqmm copper cable PVC insulated FRLS controlled by one switch for one light/fan/sockets point/ all as specified and directed by Engr-in-Charge in ceiling Portion surface conduit wiring to be done. 174 Per\n Point
141 141 M & L for switch piano flush type single pole one way 5/6 Amp, 240 volts complete all as specified and directed by Engr-in-charge. 174 Each
142 142 M & L for ceiling rose surface bakelite 2 to 3 terminals complete all as specified and directed. 174 Each
143 143 Supply, testing and commissioning of Trolly mounted non clog sewage cleaning pumpset diesel engine driven with bronze impler capable of pumping sewage contains solides 2.5" size dia capacity 6 HP, suitable for 80 mm suction/delivery pipe , RPM 1500 complete all as specified and directed. 1 Each
144 144 Supply and install foot valve of size 80 mm dia including necessary fittings conforming to IS-4038 complete all as specified and directed. 1 Each
145 145 Supply and fix PVC Green Flexible hose pipe size 80 mm dia complete all as specified and directed. 40 RM
146 146 M&L for PCC pole, 9 Meters long 102 mm x 152 mm at top and 102 mm x 289 mm at bottam, class 10 and painting with complete with one cot of alternative white and black straps of 30 cm each upto 1.5 mtr height using synthetic enamel paint. Colour washing the pole remaining part using snowcem of approved colour ad writing No of pole with letters/figures of size nt exc 30 cm with black paint on a yellw circle of dia 75 mm complete all as specified and directed by engr-in-charge. 4 Each
147 147 Material and labour for replacement of GI tubing light grade 50 mm bore for passing through cables under the floor ,along the wall or along the pole with necessery clamps and fittings complete all as specified and directed . 15 RM
148 148 Material and labour for LED flood light fitting 105 Watts, IP 66, having pressure die cast alumn alloy housing with heat resistant toughned glass with individual LED lenses and Driver shall be IP-67 for water protection complete including suitable size bracket/ clamp as required at site , including making connections with PVC insulated and sheathed single core multi stranded alumn conductor cable of size 2.5 Sqmm complete all as specified and directed by Engr-in-charge. \nNote:- (i) Contractor shall submit Lm79& LM80 test certficate from company's own NABL accredited laboratory of LED fittings before incorporating the material at site.\n(ii) guarantee of complete LED fitting shall be 2 years from the date of completion. 4 Each
149 149 Supply and fixing Junction box outdoor type made out 3 mm CRCA sheet of suitable size duly painted and fixed with suitable MS clamps of 3.00 mm thick confirming to relevent IS ,nut bolts including 2 Nos alluminium bus bar ,50 Amps ,single phase duly insulated and fixed for terminating single phase 10 sqmm alluminium UG cable etc with 01 No ,MCB SP 10 Amps,10 KA complete all as specified and directed. 4 Each
150 150 Disconnecting, dismentling and taking down carefully single pointed air termination alumn rod incl GI pipe any size incl nuts & bolts and seggregating U/S or serviceable parts incl removing from site or setting aside for reuse complete all as specified and directed. 370 Each
151 151 Disconnecting, dismentling and taking down carefully aluminium strip any size upto 32 x 6 mm complete with saddles GI tubing insulators ad seggregating U/S or serviceable parts incl removing from site or setting aside for reuse complete all as specified and directed. 5500 RM
152 152 Disconnecting, dismentling and taking down carefully GI strip of any size up to 32 x 6 mm and seggregating U/S or serviceable parts incl removing from site or setting aside for reuse complete all as specified and directed. 2600 RM
153 153 Supply and fix single pointed air termination alum rod 12 mm dia 300 mm long incl insulator, nuts & bolts for fixing air termination rod to pole pipe complete all as specified and directed. 370 Each
154 154 Supply and fix aluminium strip 25 x 3.15 mm complete incl providing nuts, bolts & saddle/Insulators made out of porcelain or fibre for roof conductor/down conductor incl welding or brazing /nut bolts for joints complete all as specified and directed. 5500 RM
155 155 Supply and fix GI strip 32 x 6 mm, buried in ground upto 50 cm depth or fixed to wall with nuts, bolts & saddles/insulators etc for loop earthing incl welding / nut bolts for joints complete all as specified and directed. (Note ; earth work will not be paid seperately) 2600 RM
156 156 Dismentling and taking down old unserviceable earthing any type incl removing from site complete all as specified and directed. 40 Each
157 157 Material and labour earthing with copper earth plate electrode of size 600 mm x600 mm x3.15 mm thick buried directly in ground to a depth not less than 2.25 mtr deep below normal ground level with top edge of the earth plate not less than 1.5 mtr deep below normal ground level connected with 25 x 4 mm copper strip as earth lead electrode by means of nuts, bolts and washers, GI medium grade pipe 40 mm bore protection pipe upto test point, 20mm dia GI light grade watering pipe with funnel and wire mesh, RCC pit cover of size 300x300x40mm reinforced with XPM having weight not less than 4Kg/sqmm including 6mm thick MS bar handle made to shape, PCC pit with 1:3:6 type C1 with angle iron frame made of angle iron of size 40x40x4mm, adequate qty of gem all around the earth plate, excavation , earth work in any type of soil, removal of excavated soil and returning filling in all as required at site complete all as specified in plate No 3 of SSR Part-I and all as specified or indicated including testing on completion.NOTE :-Rates inclusive of necessary excavation in any type of soil, earth work, PCC pit, RCC cover, funnel with watering pipe, copper earth strip upto 7.5 m long for connecting to test point etc. all as required at site for complete earthing). 40 Each
158 158 S&F in replacement GI Pipe medium grade 20 mm bore with all fittings for fixing of ATR complete all as specified and directed. 500 RM
159 159 M & L Test point terminal block made of gun metal or phosphorus bronze size incliding 3 Nos 8 mm dia 25 mm long hex. Head screw all as specified and directed by Engr-in-charge. 40 Each
160 160 M & L for pre cast cement concrete (1:4:8) type D2 using 40 mm graded stone aggregate for earth pits as mass concrete complete all as specified and directed. 5 Cum
161 161 Sch of Credit = 139600.00
162 162 Note: In case the tenderer quotes different rates for similar item then lowest rate shall only be applicable for payment and contractor shall not have any claim on this account.