Education Technical Government Polytechnic College Meenangadi Wayanad Rewiring Of The Renovated Electrical Machine Lab . --1 90.2.1.1 : Supply And Wiring Points According To Is 732-1989 Using Rigid Pvc Conduit Of Minimum Size 20 Mm With Specials Conforming To Is 9537 Part Iii 1983 And With Suitable Size Specials Conforming To Is 3419-1988, Fixing The Conduit Using Metal Saddles Spacing Not Exceeding 50 Cm Or Concealed Suitably And With 1.00 Sq Mm Frls Pvc Insulated Stranded Single Core Copper Conductor Cable 650V Grade, Including Providing Switch Board Main And Continuous Earthing With No.14 Swg Bare Copper, Required Quantity Of Copper Earth Socket, Brass Bolt And Nut Crimping / Soldering Etc Complete With Suitable Size Modular Type Metal Switch Boxes, Modular Type Front Plates ( White ) Etc. Up To And Including 6A Modular Type Sp Switches And Making Good The Surface Of Wall, Colour Washing Etc. Complete. All The Terminations In The Switch Boards And Dbs Shall Be Tinned And The Wires Shall Be Drawn And Fixed Along The Periphery Of The Box Using Suitable Ties, Tie Mounts Etc As Required. ( Rohs Compliant Modular Accessories ) .Single Control Light Point With 6A, Plate Ceiling Rose - Short Point 2 90.2.1.4 : Supply And Wiring Points According To Is 732-1989 Using Rigid Pvc Conduit Of Minimum Size 20 Mm With Specials Conforming To Is 9537 Part Iii 1983 And With Suitable Size Specials Conforming To Is 3419-1988, Fixing The Conduit Using Metal Saddles Spacing Not Exceeding 50 Cm Or Concealed Suitably And With 1.00 Sq Mm Frls Pvc Insulated Stranded Single Core Copper Conductor Cable 650V Grade, Including Providing Switch Board Main And Continuous Earthing With No.14 Swg Bare Copper, Required Quantity Of Copper Earth Socket, Brass Bolt And Nut Crimping / Soldering Etc Complete With Suitable Size Modular Type Metal Switch Boxes, Modular Type Front Plates ( White ) Etc. Up To And Including 6A Modular Type Sp Switches And Making Good The Surface Of Wall, Colour Washing Etc. Complete. All The Terminations In The Switch Boards And Dbs Shall Be Tinned And The Wires Shall Be Drawn And Fixed Along The Periphery Of The Box Using Suitable Ties, Tie Mounts Etc As Required. ( Rohs Compliant Modular Accessories ) .Single Control Ceiling Fan Point With 6 A, 3 Plate Ceiling Rose & With Socket Size Stepped Electronic Regulator. - Short Point 3 90.2.1.6 : Supply And Wiring Points According To Is 732-1989 Using Rigid Pvc Conduit Of Minimum Size 20 Mm With Specials Conforming To Is 9537 Part Iii 1983 And With Suitable Size Specials Conforming To Is 3419-1988, Fixing The Conduit Using Metal Saddles Spacing Not Exceeding 50 Cm Or Concealed Suitably And With 1.00 Sq Mm Frls Pvc Insulated Stranded Single Core Copper Conductor Cable 650V Grade, Including Providing Switch Board Main And Continuous Earthing With No.14 Swg Bare Copper, Required Quantity Of Copper Earth Socket, Brass Bolt And Nut Crimping / Soldering Etc Complete With Suitable Size Modular Type Metal Switch Boxes, Modular Type Front Plates ( White ) Etc. Up To And Including 6A Modular Type Sp Switches And Making Good The Surface Of Wall, Colour Washing Etc. Complete. All The Terminations In The Switch Boards And Dbs Shall Be Tinned And The Wires Shall Be Drawn And Fixed Along The Periphery Of The Box Using Suitable Ties, Tie Mounts Etc As Required. ( Rohs Compliant Modular Accessories ) .Combined Plug Point With 6 A, 5 Pin Plug Socket Controlled By 6 A, Switch In The Same Switch Board As That Of Light Points 4 90.2.1.7 : Supply And Wiring Points According To Is 732-1989 Using Rigid Pvc Conduit Of Minimum Size 20 Mm With Specials Conforming To Is 9537 Part Iii 1983 And With Suitable Size Specials Conforming To Is 3419-1988, Fixing The Conduit Using Metal Saddles Spacing Not Exceeding 50 Cm Or Concealed Suitably And With 1.00 Sq Mm Frls Pvc Insulated Stranded Single Core Copper Conductor Cable 650V Grade, Including Providing Switch Board Main And Continuous Earthing With No.14 Swg Bare Copper, Required Quantity Of Copper Earth Socket, Brass Bolt And Nut Crimping / Soldering Etc Complete With Suitable Size Modular Type Metal Switch Boxes, Modular Type Front Plates ( White ) Etc. Up To And Including 6A Modular Type Sp Switches And Making Good The Surface Of Wall, Colour Washing Etc. Complete. All The Terminations In The Switch Boards And Dbs Shall Be Tinned And The Wires Shall Be Drawn And Fixed Along The Periphery Of The Box Using Suitable Ties, Tie Mounts Etc As Required. ( Rohs Compliant Modular Accessories ) .Independent Plug - Short Point 5 90.3.20.3 : Supply & Installation Of Light Fittings On Tw Round Block Supply, Conveyance Installation Testing And Commissioning The Light Fittings Of Following Types Made Of Crca With 0.5Mm Thickness Complete With All Accessories And Lamps Etc. Directly On Wall Or Ceiling With Pvc Round Block Neatly Painted To Suit The Fitting And Giving Connection With Required Length Of 16 / 0.20Mm 3 Core Copper Conductor Flex Wire Conforming To Relevant Iss And Giving Connections As Required.1200 Mm 1X20w Led Lamp With Box Type Fixture 6 90.3.20.4 : Supply & Installation Of Light Fittings On Tw Round Block Supply, Conveyance Installation Testing And Commissioning The Light Fittings Of Following Types Made Of Crca With 0.5Mm Thickness Complete With All Accessories And Lamps Etc. Directly On Wall Or Ceiling With Pvc Round Block Neatly Painted To Suit The Fitting And Giving Connection With Required Length Of 16 / 0.20Mm 3 Core Copper Conductor Flex Wire Conforming To Relevant Iss And Giving Connections As Required.1200 Mm 2X20w Led Lamp With Box Type Fixture 7 90.3.21.3 : Supply & Installation Of Light Fittings On C / U Shaped Flat Iron Bracket Supply, Conveyance, Installation, Testing And Commissioning The Light Fittings Of Following Types Made From 0.5Mm Crca Sheet Complete With All Accessories And Lamps Etc. Directly On Wall Using 2 Nos. C / U Brackets Made From 20 X 3 Mm Ms Flat, Painting The Flat Iron Bracket And Giving Connections With Required Length Of 16 / 0.20Mm 3 Core Copper Conductor Flex Wire Conforming To Relevant Iss Or Extending The Original Wiring And Giving Connection Etc. As Required.1200 Mm 1X20w Led Lamp With Box Type Fixture 8 90.3.21.4 : Supply & Installation Of Light Fittings On C / U Shaped Flat Iron Bracket Supply, Conveyance, Installation, Testing And Commissioning The Light Fittings Of Following Types Made From 0.5Mm Crca Sheet Complete With All Accessories And Lamps Etc. Directly On Wall Using 2 Nos. C / U Brackets Made From 20 X 3 Mm Ms Flat, Painting The Flat Iron Bracket And Giving Connections With Required Length Of 16 / 0.20Mm 3 Core Copper Conductor Flex Wire Conforming To Relevant Iss Or Extending The Original Wiring And Giving Connection Etc. As Required.1200 Mm 2X20w Led Lamp With Box Type Fixture 9 Od161235 / 2019_2020 : Supply, Conveyance, Installation, Testing And Commissioning Of Led Bulk Head Fittings Ip65 Directly On Wall Including Cutting Necessary Holes, Giving Connections With The Extended Orginal Wiring, Making Good The Damgaes, Colour Washing Etc As Required. ( Philips / Bajaj / Havells / Wipro ) 10 90.15.4.1 : Supply Conveyance, Installation, Testing And Commissioning Of 20W Led Street Light Output Greater Than 105Lumen / W 4000-6000 K With Ip 66 Protection Led Chip Make Cree / Lumilled / Nichea With Power Factor Greater Than 0.95 At Full Load, Internal Surge Protection Up To 8 Kv, And Aluminium Pressure Die-Cast Powder Coated Housing, Acrylic Cover Complete With Thd Less Than10%, Power Factor Greater Than 0.98, Rohs Compliant, Duly Wired Up For Use On 230 V Ac Supply. Driver Compartment Should Be Seperatly Accessible For Maintenance ( Lm 79&80 Certificates From Nabl Accredited Third Party Lab To Be Produced Mentioning Chip Manufacturer ) 11 90.4.1 : Supply And Installation Of Suitable Size Ms Rod Type Fan Clamp In The Rcc Slab As Per Is 732 As Required. 12 90.4.5.2 : Supply, Conveyance, Installation, Testing And Commissioning Of Ceiling Fans Of The Following Sizes Using Standard Accessories Excluding Resistance Type Regulator, Wiring The Down Rod With 16 / 0.20Mm Pvc Insulated And Pvc Sheathed 650 / 1100V Grade 3 Core Round Copper Conductor Flex Wire Or With Extended Original Wiring Etc. As Required.1200Mm Sweep -5Star Rated Ceiling Fan Complete With 300Mm Down Rod , Canopies, Shackeles And Blades And Resistance Type Regulator Working On 230V / 240V Single Phase A / C 13 90.4.8 : Charges For Cutting Holes Suitable For Accommodating Exhaust Fans Up To 305Mm Sweep Including Plastering Colour Washing Etc. As Required. 14 Od161237 / 2019_2020 : Supply, Conveyance, Installation , Testing And Commissioning Of 250Mm Sweep Light Duty Exhaust Fans In Plastic Body With Self Opening Louvers In The Existing Opening, Fixing Necessary Anchor Bolts / Bolt And Nuts Etc., As Required Including Giving Connections With The Supplied Wire Along With The Exhaust Fan. 15 Od161239 / 2019_2020 : Supply, Conveyance, Installation , Testing And Commissioning Of 300 / 305 Mm Sweep Light Duty Exhaust Fans In Metal Frame In The Existing Opening, Fixing Necessary Anchor Bolts / Bolt And Nuts Etc., As Required Including Giving Connections With The Supplied Wire Along With The Exhaust Fan. 16 90.6.10.1 : Supply And Fixing Of Following Sizes Of Light Gauge Pvc Conduit Along With Accessories In Surface / Recess Including Cutting The Wall And Making Good The Same In Case Of Recessed Conduit As Required20 Mm 17 90.6.10.2 : Supply And Fixing Of Following Sizes Of Light Gauge Pvc Conduit Along With Accessories In Surface / Recess Including Cutting The Wall And Making Good The Same In Case Of Recessed Conduit As Required25 Mm 18 Od209435 / 2018_2019 : Supply And Clamping Of The Following Sizes Of Corrugated Pvc Flexible Conduit With Necessary Compression Gland With Locking Ring And Check Nut At Termination Point Using Suitable Size Gi / Painted Ms Saddles Spacing Not Exeeding 60Cm On Surface Including Making Good The Damages , Colour Washing Etc. As Required. 19 1.27.2 : Supplying And Fixing Following Size / Modules, Gi Box Alongwith Modular Base & Cover Plate For Modular Switches In Recess Etc As Required.3 Module ( 100Mmx75mm ) 20 1.27.5 : Supplying And Fixing Following Size / Modules, Gi Box Alongwith Modular Base & Cover Plate For Modular Switches In Recess Etc As Required.8 Module ( 125Mmx125mm ) 21 1.24.1 : Supplying And Fixing Following Modular Switch / Socket On The Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc. As Required.5 / 6 Amps Switch 22 1.24.3 : Supplying And Fixing Following Modular Switch / Socket On The Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc. As Required.15 / 16 Amp Switch 23 1.24.4 : Supplying And Fixing Following Modular Switch / Socket On The Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc. As Required.3 Pin 5 / 6 Amp Socket Outlet 24 1.24.5 : Supplying And Fixing Following Modular Switch / Socket On The Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc. As Required.6 Pin 15 / 16 Amp Socket Outlet 25 2.16 : Supplying And Fixing Dp Sheet Steel Enclosure On Surface / Recess Along With 25 / 32Amps 240 Volts C Curve Dp Mcb Complete With Connections, Testing And Commissioning Etc. As Required. 26 Od208828 / 2018_2019 : Supplying And Fixing 4P Sheet Steel Enclosure On Surface / Recess Din Bar, Interconnections, Powder Painted Including Earthing Etc. As Required. ( But Without Mcbirccb / Isolator ) Complete With Connections, Testing And Commissioning Etc. As Required. 27 90.11.1.10 : Supply And Installation Of Sheet Steel, Phosphatised And Painted, Dust And Vermin Proof Enclosure Of Mcb Db Including Copper / Brass Bus Bar, Neutral Link, Earth Bus And Din Rail Suitable For Fixing Mcb / Isolator Etc. Fixed On Wall Using Suitable Anchor Bolts Or Fixed In Recess Including Cutting Hole On The Wall , Making Good The Damages, Colour Washing Etc. As Required4 Way ( 8+12 ) - Three Phase Double Cover ( Ip 42 / 43 ) 28 90.11.1.15 : Supply And Installation Of Sheet Steel, Phosphatised And Painted, Dust And Vermin Proof Enclosure Of Mcb Db Including Copper / Brass Bus Bar, Neutral Link, Earth Bus And Din Rail Suitable For Fixing Mcb / Isolator Etc. Fixed On Wall Using Suitable Anchor Bolts Or Fixed In Recess Including Cutting Hole On The Wall , Making Good The Damages, Colour Washing Etc. As Required6 Way ( 8+18 ) - Double Cover Tpn Vertical Db With Provision For Fixing 4P Mcb / Isolator / Rccb / Rcbo As Incomer And Sp / Tp Mcb As Outgoing ( Ip 42 / 43 ) 29 2.13.1 : Supplying And Fixing Following Rating, Four Pole, 415 Volts, Isolator In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required.40 Amps 30 2.13.2 : Supplying And Fixing Following Rating, Four Pole, 415 Volts, Isolator In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required.63 Amps 31 2.10.1 : Supplying And Fixing 5 Amps To 32 Amps Rating, 240 / 415 Volts, C Curve, Miniature Circuit Breaker Suitable For Inductive Load Of Following Poles In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required.Single Pole 32 2.10.3 : Supplying And Fixing 5 Amps To 32 Amps Rating, 240 / 415 Volts, C Curve, Miniature Circuit Breaker Suitable For Inductive Load Of Following Poles In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required.Double Pole 33 2.10.4 : Supplying And Fixing 5 Amps To 32 Amps Rating, 240 / 415 Volts, C Curve, Miniature Circuit Breaker Suitable For Inductive Load Of Following Poles In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required.Triple Pole 34 2.15.2 : Supplying And Fixing Following Rating, Four Pole, ( Three Phase And Neutral ) , 415 Volts, Residual Current Circuit Breaker ( Rccb ) , Having A Sensitivity Current Upto 300 Milliamperes In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required.40 Amps 35 2.15.3 : Supplying And Fixing Following Rating, Four Pole, ( Three Phase And Neutral ) , 415 Volts, Residual Current Circuit Breaker ( Rccb ) , Having A Sensitivity Current Upto 300 Milliamperes In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required.63 Amps 36 Od209423 / 2018_2019 : Supply And Fixing The Connecting Terminal On The Existing Panel Etc. As Required Including Drilling Necessary Holes And Giving Connection As Required 37 90.6.4.52 : Supply And Drawing 650 / 1100 V Grade Frls Pvc Insulated Stranded Single Core Copper Conductor Cables Conforming To Is 694 Part I 1990 In The Existing Surface / Recess Conduit As Required Including Giving Necessary Connections Of The Following Sizes.10.00 Sq.Mm 2 Run 38 90.6.4.54 : Supply And Drawing 650 / 1100 V Grade Frls Pvc Insulated Stranded Single Core Copper Conductor Cables Conforming To Is 694 Part I 1990 In The Existing Surface / Recess Conduit As Required Including Giving Necessary Connections Of The Following Sizes.10.00 Sq.Mm 4 Run 39 90.6.4.63 : Supply And Drawing 650 / 1100 V Grade Frls Pvc Insulated Stranded Single Core Copper Conductor Cables Conforming To Is 694 Part I 1990 In The Existing Surface / Recess Conduit As Required Including Giving Necessary Connections Of The Following Sizes.16.00 Sq.Mm 4 Run 40 90.12.7.2 : Supply, Laying And Clamping Of 1 No. Pvc Insulated And Pvc Sheathed Armoured Aluminium Power Cable, 1.1 Kv Grade Of The Following Sizes Using Clamps Noted Along With The Cables, Spacing Of Clamps Not Exceeding 60Cms, Making Good The Damages , Colour Washing Etc. As Required.2 Core 6 Sq Mm With Factory Made Clamp 41 90.12.7.3 : Supply, Laying And Clamping Of 1 No. Pvc Insulated And Pvc Sheathed Armoured Aluminium Power Cable, 1.1 Kv Grade Of The Following Sizes Using Clamps Noted Along With The Cables, Spacing Of Clamps Not Exceeding 60Cms, Making Good The Damages , Colour Washing Etc. As Required.2 Core 10 Sq Mm With Factory Made Clamp 42 90.12.7.30 : Supply, Laying And Clamping Of 1 No. Pvc Insulated And Pvc Sheathed Armoured Aluminium Power Cable, 1.1 Kv Grade Of The Following Sizes Using Clamps Noted Along With The Cables, Spacing Of Clamps Not Exceeding 60Cms, Making Good The Damages , Colour Washing Etc. As Required.3.5 Core 70 Sq Mm 43 90.12.7.38 : Supply, Laying And Clamping Of 1 No. Pvc Insulated And Pvc Sheathed Armoured Aluminium Power Cable, 1.1 Kv Grade Of The Following Sizes Using Clamps Noted Along With The Cables, Spacing Of Clamps Not Exceeding 60Cms, Making Good The Damages , Colour Washing Etc. As Required.4 Core 4 Sq Mm With Factory Made Clamp 44 90.12.7.39 : Supply, Laying And Clamping Of 1 No. Pvc Insulated And Pvc Sheathed Armoured Aluminium Power Cable, 1.1 Kv Grade Of The Following Sizes Using Clamps Noted Along With The Cables, Spacing Of Clamps Not Exceeding 60Cms, Making Good The Damages , Colour Washing Etc. As Required.4 Core 6 Sq Mm With Factory Made Clamp 45 90.12.7.40 : Supply, Laying And Clamping Of 1 No. Pvc Insulated And Pvc Sheathed Armoured Aluminium Power Cable, 1.1 Kv Grade Of The Following Sizes Using Clamps Noted Along With The Cables, Spacing Of Clamps Not Exceeding 60Cms, Making Good The Damages , Colour Washing Etc. As Required.4 Core 10 Sq Mm With Factory Made Clamp 46 90.12.7.42 : Supply, Laying And Clamping Of 1 No. Pvc Insulated And Pvc Sheathed Armoured Aluminium Power Cable, 1.1 Kv Grade Of The Following Sizes Using Clamps Noted Along With The Cables, Spacing Of Clamps Not Exceeding 60Cms, Making Good The Damages , Colour Washing Etc. As Required.4 Core 25 Sq Mm With Factory Made Clamp 47 9.1.2 : Supplying And Making End Termination With Brass Compression Gland And Aluminium Lugs For Following Size Of Pvc Insulated And Pvc Sheathed / Xlpe Aluminium Conductor Cable Of 1.1 Kv Grade As Required.2 X 10 Sq. Mm ( 19Mm ) 48 9.1.23 : Supplying And Making End Termination With Brass Compression Gland And Aluminium Lugs For Following Size Of Pvc Insulated And Pvc Sheathed / Xlpe Aluminium Conductor Cable Of 1.1 Kv Grade As Required.3 1 / 2X 70 Sq. Mm ( 38Mm ) 49 9.1.32 : Supplying And Making End Termination With Brass Compression Gland And Aluminium Lugs For Following Size Of Pvc Insulated And Pvc Sheathed / Xlpe Aluminium Conductor Cable Of 1.1 Kv Grade As Required.4 X 10 Sq. Mm ( 25Mm ) 50 9.1.34 : Supplying And Making End Termination With Brass Compression Gland And Aluminium Lugs For Following Size Of Pvc Insulated And Pvc Sheathed / Xlpe Aluminium Conductor Cable Of 1.1 Kv Grade As Required.4 X 25 Sq. Mm ( 28Mm ) 51 5.4 : Earthing With G.I. Earth Plate 600 Mm X 600 Mm X 6 Mm Thick Including Accessories, Andproviding Masonry Enclosure With Cover Plate Having Locking Arrangement And Watering Pipe Of 2.7 Metre Long Etc. With Charcoal / Coke And Salt As Required. 52 Od194680 / 2018_2019 : Supply And Providing And Fixing 2 X 25 Mm X 3 Mm Copper Strip Test Joint For Earthing System 53 Od194681 / 2018_2019 : Supply And Providing And Fixing 25 Mm X 3 Mm Copper. Strip Earth Lead From The Test Joint To The Earth Plate 54 90.16.1.1 : Supply And Drawing Bare Earthing Conductors Of The Following Sizes Along With Wiring / Cables And Giving Connection As Required2.00 Mm Copper Conductor ( 14 Swg ) 55 90.16.1.2 : Supply And Drawing Bare Earthing Conductors Of The Following Sizes Along With Wiring / Cables And Giving Connection As Required2.65 Mm Copper Conductor ( 12 Swg ) 56 90.16.1.3 : Supply And Drawing Bare Earthing Conductors Of The Following Sizes Along With Wiring / Cables And Giving Connection As Required3.15 Mm Copper Conductor ( 10 Swg ) 57 90.16.1.6 : Supply And Drawing Bare Earthing Conductors Of The Following Sizes Along With Wiring / Cables And Giving Connection As Required6.00 Mm Copper Conductor ( 4 Swg ) 58 90.16.5.1 : Supply Of Superior Quality Copper Earth Socket For The Following Size Of Earth Conductor Including Crimping Etc. As Required.2.00 Mm ( 14 Swg ) 59 90.16.5.2 : Supply Of Superior Quality Copper Earth Socket For The Following Size Of Earth Conductor Including Crimping Etc. As Required.2.65 Mm ( 12 Swg ) 60 90.16.5.3 : Supply Of Superior Quality Copper Earth Socket For The Following Size Of Earth Conductor Including Crimping Etc. As Required.3.15 Mm ( 10 Swg ) 61 90.16.5.6 : Supply Of Superior Quality Copper Earth Socket For The Following Size Of Earth Conductor Including Crimping Etc. As Required.6. Mm ( 4 Swg ) 62 Od194687 / 2018_2019 : Providing And Fixing Earth Bus Of 25Mm X 3 Mm Copper Strip On Surface For Connections Etc. As Required. 63 Od217468 / 2018_2019 : Supply And Providing 12X3mm Brass Nut And Bolt Etc. As Required. 64 Od217470 / 2018_2019 : Supply And Providing 25X3mm Brass Nut And Bolt Etc. As Required. 65 Od217472 / 2018_2019 : Supply And Providing 25X6mm Brass Nut And Bolt Etc. As Required. 66 90.14.1.2 : Fabrication, Supply, Conveyance, Installation Testing And Commissioning Of Floor Or Wall Mounting, Dust And Vermin Proof, Cubicle Type Mv Panel Board Comprising Of The Following Components / Devices & Complying To Is 8623. Fabrication Of Fully Partitioned, Dust And Vermin Proof Enclosure For Panel Assembly As Per Form 4 Of Is 8623 ( With Latest Amendments ) Using Crca Sheet As Per Approved Design And Requirement, With Front And Rear Access Facility, Bus Bar Chambers, Hinged Doors For All Switch Gear Compartments, Earthing The Doors Using 4 Sq Mm Braided Copper Conductor, Providing Necessary Cut-Outs For Mounting Meters, Relays, Indication Lamps, Bus Bar Interconnection Etc, Detachable Covers For Bus Bar Chamber And Cable Alley, Powder Coating The Assembly After Subjecting To 7 Tank Process Etc As Required. Crca Sheet Alone Be Used For The Fabrication. Angles / Flats / Slotted Angles Etc Shall Not Be Used For The Fabrication Of Panel Assembly. The Measurments Will Be Taken The Area Of The Complete Sheets Used For Panel Board Including Partitions, Folding, Shrouding Etc.Supply And Fabrication Of Mv Panel Board Using 1.6Mm Crca Sheet, Powder Coated ( Excluding Base Frame ) 67 90.14.2.1 : Supply And Providing 2Mm Smc Sheet As Shrouding For Bus Interconnection / Terminations Etc. Including Required Nut & Bolt Etc. 68 90.14.2.3 : Supply And Providing 4Mm Smc Sheet As Shrouding For Bus Interconnection / Terminations Etc. Including Required Nut & Bolt Etc. 69 90.14.3.2 : Supply And Providing Heavy Duty A Section Neoprene Gasket In The Panel Boardu Section Rubber Beeding Suitable For 1.60 / 2.00 Mm Sheet 70 90.14.4 : Supply And Fabrication Conveyance And Installation Of Base Frame Of Panel Board Using 75 X 40 Mm Rolled Steel Channel ( Ismc ) 71 90.14.6 : Supply And Providing Copper Bus Bars Including Finger Type Smc Bus Bar Supports In The Bus Chamber, Suitable Size Nut & Bolt, Providng Heat Shrink Sleeves Etc. As Required. 72 90.14.7 : Supply And Providing Copper Earth Bus In The Panel Board 73 90.14.5 : Supply And Fabrication Conveyance And Installation Of Angle Iron Frame Work For Wall Mounting Panel Board 74 2.1.3 : Providing And Fixing Following Capacity Tp&N Disconnector Fuse Switch Unit Inside The Existing Panel Board With Isi Marked Hrc Fuses Including Drilling Holes In Cubicle Panel, Making Connections, Etc. As Required.100 Amp Tp&N 75 2.1.4 : Providing And Fixing Following Capacity Tp&N Disconnector Fuse Switch Unit Inside The Existing Panel Board With Isi Marked Hrc Fuses Including Drilling Holes In Cubicle Panel, Making Connections, Etc. As Required.125 Amp Tp & N 76 2.1.5 : Providing And Fixing Following Capacity Tp&N Disconnector Fuse Switch Unit Inside The Existing Panel Board With Isi Marked Hrc Fuses Including Drilling Holes In Cubicle Panel, Making Connections, Etc. As Required.160 Amp Tp&N 77 90.14.10.10 : Supply, Conveyance And Fixing The Following Types & Current Rated Control Gears & Switchgears Conforming To Is 13947 Suitable For 440 V, 50 Hz, Ac Supply In The Existing Panel Assembly As Required.16A -100A, 35 / 36 Ka ( Ics=100%Icu ) , 4 Pole, Current Limiting Type Mccb With Microprocessor Based Release With Overload Setting Of 50 - 100% Having Adjustable Ol & Sc 78 90.14.11.14 : Mccb Accessoriessupply And Fixing Rotary Handle, Direct Type ( Including Buc Handle With Door Interlock ) In The Existing Mccb Of Rating Up To 250 A 79 Od194702 / 2018_2019 : Supply And Wiring With Pvc Insulated Stranded Single Core Copper Conductor Cables For Interconnecting The Control Devices / Equipments Including The Wiring Firm By Suitable Tie / Tie Mounts / Pvc Duct Etc As Required. 1.5Sqmm Single Run 80 Od194703 / 2018_2019 : Supply And Wiring With Pvc Insulated Stranded Single Core Copper Conductor Cables For Interconnecting The Control Devices / Equipments Including The Wiring Firm By Suitable Tie / Tie Mounts / Pvc Duct Etc As Required. 6.00Sqmm Single Run 81 Od194704 / 2018_2019 : Supply And Wiring With Pvc Insulated Stranded Single Core Copper Conductor Cables For Interconnecting The Control Devices / Equipments Including The Wiring Firm By Suitable Tie / Tie Mounts / Pvc Duct Etc As Required. 16.00Sqmm Single Run 82 90.12.24.3 : Supply Of Superior Quality Copper Tubular Cable Socket And Making Core Termination Of Cables Of The Following Sizes Including Crimping Etc. As Required.6 Sq Mm 83 90.12.24.5 : Supply Of Superior Quality Copper Tubular Cable Socket And Making Core Termination Of Cables Of The Following Sizes Including Crimping Etc. As Required.16 Sq Mm 84 Od209427 / 2018_2019 : Supply Of Superior Quality Copper Bare Ring Terminal And Making Core Termination Of Cables Of The 16.00 Sq Mm Including Crimping Etc. As Required. 85 Od209429 / 2018_2019 : Supply Of Superior Quality Copper Bare Ring Terminal And Making Core Termination Of Cables Of The 10.00 Sq Mm Including Crimping Etc. As Required. 86 Od209431 / 2018_2019 : Supply Of Superior Quality Copper Bare Ring Terminal And Making Core Termination Of Cables Of The 6.00 Sq Mm Including Crimping Etc. As Required. 87 Od209433 / 2018_2019 : Supply Of Superior Quality Copper Bare Ring Terminal And Making Core Termination Of Cables Of The 4.00 Sq Mm Including Crimping Etc. As Required. 88 Od194710 / 2018_2019 : Supply And Fixing Danger Notice Board Of Size, 125 X 75 Mm 89 Od164177 / 2019_2020 : Supply And Providing Red, Green, Black, Yellow, Orange Colours Led Indicators, Ac / Dc 22.5Mm Cut Out Dia 90 Od164179 / 2019_2020 : Supply And Providing Blue Colour Led Indicators, Ac / Dc 22.5Mm Cut Out Dia 91 Od194712 / 2018_2019 : Supply And Fixing 150 / 5 A, 5 Va, Accuracy Class 0.5, Tape Wound Metering Ct 92 Od194715 / 2018_2019 : Supply And Fixing Digital Multifunction Meter To Read: V, A, F, Pf-3 Phase Accuracy Class 1 Led 93 Od194716 / 2018_2019 : Supply And Fixing Three Phase Digital Volt Meter To Read: V, Accuracy Class 1 94 Od194717 / 2018_2019 : Painting Letters Or Figures With Enamel Paint As Identification Mark To Sb, Db, Panel Board Etc As Required 95 Od194718 / 2018_2019 : Supply And Providing First Aid Chart Duly Framed And Placed In A Conspicuous Location For Clear Vision. 96 Od164181 / 2019_2020 : Supply And Providing 5Kg Abc Type Fire Extinguisher With Hose And Clamps Including Fixing It To Wall As Required. 97 Od164183 / 2019_2020 : Supply And Providing 2.00 Mm Thick, 3.3 Kv, Synthetic Elastromeric Fire Retardant Insulating Sheet 98 Od164185 / 2019_2020 : Supply And Providing 9 Litre Capacity Gi Fire Bucket Painted In Post Office Red With Primer Coat Of Red Oxide And Written With White Paint Fire Mounted On Ms Angle Frame Work / Wall Bracket Filled With Fine Sand, Painting The Bracket / Floor Stand Including Making Good The Damages, Colour Washing Etc. As Required 99 Od209869 / 2018_2019 : Supply And Providing Ms Chequered Plate Of 7 Mm Thickness Including Cutting, Welding, Painting Etc. As Required For The Cable Trench Covering. 100 Od209879 / 2018_2019 : Charges Towards The Preparation Of Necessary Plan, Scheme And Other Related Papers For Submission To Kselb & Kseb ( For Preparing Scheme & Records For Scrutiny & Completion ) First A3 Sheet 101 Od209881 / 2018_2019 : Charges Towards The Preparation Of Necessary Plan, Scheme And Other Related Papers For Submission To Kselb & Kseb ( For Preparing Scheme & Records For Scrutiny & Completion ) Additional Sheet 102 Od209883 / 2018_2019 : Fee To Be Paid To Kselb Towards Scrutiny & Inspection , Meter Testing Etc ( Actual Amount Will Be Reimbursed On Production Of Original Documents )