Tender For Civil And Electrical Works For Setting-Up Of Micro-Biology Lab At Second Floor Of State Dairy Laboratory, Thiruvananthapuram, PATTOM-Kerala

Hll Lifecare Limited-HLL has published Tender For Civil And Electrical Works For Setting-Up Of Micro-Biology Lab At Second Floor Of State Dairy Laboratory, Thiruvananthapuram. Submission Date for this Tender is 30-12-2019. Bottles Tenders in PATTOM Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

22927348
Tender For Civil And Electrical Works For Setting-Up Of Micro-Biology Lab At Second Floor Of State Dairy Laboratory, Thiruvananthapuram
Open Tender
Indian
Kerala
PATTOM
30-12-2019

Tender Details

Tender For Civil And Electrical Works For Setting-Up Of Micro-Biology Lab At Second Floor Of State Dairy Laboratory, Thiruvananthapuram - 2 Demolishing Brick Work Manually / By Mechanical Means Including Stacking Of Serviceable Material And Disposal Of Unserviceable Material Within 50 Metres Lead As Per Direction Of Engineer-In-Charge. In Cement Mortar 3 Taking Out Doors, Windows And Clerestory Window Shutters ( Steel Or Wood ) Including Stacking Within 50 Metres Lead : Nof Area Beyond 3 Sq. Metres 4 Dismantling Aluminium / Gypsum Partitions, Doors, Windows, Fixed Glazing And False Ceiling Including Disposal Of Unserviceable Surplus Material And Stacking Of Serviceable Material With In 50 Metres Lead As Directed By Engineer - In-Charge 5 Brick Work With Common Burnt Clay F.P.S. ( Non Modular ) Bricks Of Class Designation 7.5 In Superstructure Above Plinth Level Up To Floor V Level In All Shapes And Sizes In:Cement Mortar 1:4 ( 1 Cement : 4 Coarse Sand ) 6 Providing And Fixing Aluminium Work For Doors, Windows, Ventilators And Partitions With Extruded Built Up Standard Tubular Sections / Appropriate Z Sections And Other Sections Of Approved Make Conforming To Is : 733 And Is: 1285, Fixing With Dash Fasteners Of Required Dia And Size, Including Necessary Filling Up The Gaps At Junctions, I.E. At Top, Bottom And Sides With Required Epdm Rubber / Neoprene Gasket Etc. Aluminium Sections Shall Be Smooth, Rust Free, Straight, Mitred And Jointed Mechanically Wherever Required Including Cleat Angle, Aluminnium Snap Beading For Glazing / Paneling, C.P. Brass / Stainless Steel Screws, All Complete As Per Architectural Drawings And The Directions Of Engineer-In-Charge. ( Glazing, Paneling And Dash Fasteners To Be Paid For Separately ) : 7 For Fixed Portionpowder Coated Aluminium ( Minimum Thickness Of Powder Coating 50 Micron ) 8 For Shutters Of Doors, Windows & Ventilators Including Providing And Fixing Hinges / Pivots And Making Provision For Fixing Of Fittings Wherever Required Including The Cost Of Epdm Rubber / Neoprene Gasket Required ( Fittings Shall Be Paid For Separately ) Powder Coated Aluminium ( Minimum Thickness Of Powder Coating 50 Micron ) 9 Providing And Fixing 12 Mm Thick Prelaminated Particle Board Flat Pressed Threelayer Or Graded Wood Particle Board Conforming To Is: 12823 Grade L Type Ll, In Panelling Fixed In Aluminum Doors, Windows Shutters And Partition Frameswith C.P. Brass / Stainless Steel Screws Etc. Complete As Per Architecturaldrawings And Directions Of Engineer-In-Charge. Pre-Laminated Particle Board With Decorative Lamination On Both Sides 10 Providing And Fixing Glazing In Aluminium Door, Window, Ventilator Shutters And Partitions Etc. With Epdm Rubber / Neoprene Gasket Etc. Complete As Per The Architectural Drawings And The Directions Of Engineer-In-Charge . ( Cost Of Aluminium Snap Beading Shall Be Paid In Basic Item ) : Nwith Float Glass Panes Of 5.50 Mm Thickness 11 Providing And Fixing Aluminium Extruded Section Body Tubular Type Universal Hydraulic Door Closer ( Having Brand Logo With Isi, Is : 3564, Embossed On The Body, Door Weight Upto 36 Kg To 80 Kg And Door Width Form 701 Mm To 1000 Mm ) , With Double Speed Adjustment With Necessary Accessories And Screws Etc. Complete. 12 Providing And Fixing Aluminium Hanging Floor Door Stopper, Isi Marked, Anodised ( Anodic Coating Not Less Than Grade Ac 10 As Per Is: 1868 ) Transparent Or Dyed To Required Colour And Shade, With Necessary Screws Etc. Complete.Single Rubber Stopper 13 Providing And Fixing Bright Finished Brass 100 Mm Mortice Latch And Lock With 6 Levers And A Pair Of Lever Handles Of Approved Quality With Necessary Screws Etc. Complete. 14 Providing And Fixing Is : 12817 Marked Stainless Steel Butt Hinges With Stainless Steel Screws Etc. Complete:100X58x1.90 Mm 15 Providing And Fixing Bright Finished Brass Handles With Screws Etc. Complete:125 Mm 16 Providing And Fixing False Ceiling At All Height Including Providing And Fixing Of Frame Work Made Of Special Sections, Power Pressed From M.S. Sheets And Galvanized With Zinc Coating Of 120 Gms / Sqm ( Both Side Inclusive ) As Per Is : 277 And Consisting Of Angle Cleats Of Size 25 Mm Wide X 1.6 Mm Thick With Flanges Of 27 Mm And 37 Mm, At 1200 Mm Centre To Centre, One Flange Fixed To The Ceiling With Dash Fastener 12.5 Mm Dia X 50 Mm Long With 6 Mm Dia Bolts, Other Flange Of Cleat Fixed To The Angle Hangers Of 25X10x0.50 Mm Of Required Length With Nuts & Bolts Of Required Size And Other End Of Angle Hanger Fixed With Intermediate G.I. Channels 45X15x0.9 Mm Running At The Spacing Of 1200 Mm Centre To Centre, To Which The Ceiling Section 0.5 Mm Thick Bottom Wedge Of 80 Mm With Tapered Flanges Of 26 Mm Each Having Lips Of 10.5 Mm, At 450 Mm Centre To Centre, Shall Be Fixed In A Direction Perpendicular To G.I. Intermediate Channel With Connecting Clips Made Out Of 2.64 Mm Dia X 230 Mm Long G.I. Wire At Every Junction, Including Fixing Perimeter Channels 0.5 Mm Thick 27 Mm High Having Flanges Of 20 Mm And 30 Mm Long, The Perimeter Of Ceiling Fixed To Wall / Partition With The Help Of Rawl Plugs At 450 Mm Centre, With 25 Mm Long Dry Wall Screws @ 230 Mm Interval, Including Fixing Of Gypsum Board To Ceiling Section And Perimeter Channel With The Help Of Dry Wall Screws Of Size 3.5X25 Mm At 230 Mm C / C, Including Jointing And Finishing To A Flush Finish Of Tapered And Square Edges Of The Board With Recommended Jointing Compound, Jointing Tapes, Finishing With Jointing Compound In 3 Layers Covering Upto 150 Mm On Both Sides Of Joint And Two Coats Of Primer Suitable For Board, All As Per Manufacturers Specification And Also Including The Cost Of Making Openings For Light Fittings, Grills, Diffusers, Cutouts Made With Frame Of Perimeter Channels Suitably Fixed, All Complete As Per Drawings, Specification And Direction Of The Engineer In Charge But Excluding The Cost Of Painting With:12.5 Mm Thick Tapered Edge Gypsum Plain Board Conforming To Is : 2095-Part 1 17 Steel Work In Built Up Tubular ( Round, Square Or Rectangular Hollow Tubes Etc. ) Trusses Etc., Including Cutting, Hoisting, Fixing Position And Applying A Priming Coat Of Approved Steel Primer, Including Welding And Bolted With Special Shaped Washers Etc. Complete.Hot Finished Welded Type Tubes 18 Re-Installation Of Doors, Window Etc. With Suitable Fittings And Accessories. The Cost Includes Work I.E., Installation For All The Above Mentioned Works As A Whole Including Required Accessories. Nfor Refixing One Wooden Door 19 Painting 20 12 Mm Cement Plaster Of Mix:1:4 ( 1 Cement : 4 Fine Sand ) 21 Providing And Applying White Cement Based Putty Of Average Thickness 1 Mm, Of Approved Brand And Manufacturer, Over The Plastered Wall Surface To Prepare The Surface Even And Smooth Complete. 22 Applying One Coat Of Water Thinnable Cement Primer Of Approved Brand And Manufacture On Wall Surface:Water Thinnable Cement Primer 23 Wall Painting With Premium Plastic Emulsion Paint Of Approved Brand And Manufacture To Give An Even Shade: One Or More Coats On Old Work ( Minimum Rate Of Material Should Be Rs. 400 / Litre ) 24 Painting With Synthetic Enamel Paint Of Approved Brand And Manufacture To Give An Even Shade: Two Or More Coats On New Work 25 Distempering With Oil Bound Washable Distemper Of Approved Brand And Manufacture To Give An Even Shade: Old Work ( One Or More Coats ) 26 Plumbing 27 Dismantling W.C. Pan Of All Sizes Including Disposal Of Dismantled Materials I / C Malba All Complete As Per Directions Of Engineer-In- Charge. 28 Dismantling Of Flushing Cistern Of All Types ( C.I. / Pvc / Vitrious China ) Including Stacking Of Useful Materials Near The Site And Disposal Of Unserviceable Materials Within 50 Metres Lead. 29 Dismantling Tile Work In Floors And Roofs Laid In Cement Mortar Including Stacking Material Within 50 Metres Lead. For Thickness Of Tiles 10 Mm To 25 Mm 30 Re-Fixing Of Water Closet, Flushing Cistern Etc. With Suitable Fittings And Accessories 31 Providing And Laying Ceramic Glazed Floor Tiles Of Size 300X300 Mm ( Thickness To Be Specified By The Manufacturer ) Of 1St Quality Conforming To Is : 15622 Of Approved Make In Colours Such As White, Ivory, Grey, Fume Red Brown, Laid On 20 Mm Thick Cement Mortar 1:4 ( 1 Cement : 4 Coarse Sand ) , Jointing With Grey Cement Slurry @ 3.3Kg / Sqm Including Pointing The Joints With White Cement And Matching Pigment Etc., Complete. 32 Providing And Fixing Ist Quality Ceramic Glazed Wall Tiles Conforming To Is: 15622 ( Thickness To Be Specified By The Manufacturer ) , Of Approved Make, In All Colours, Shades Except Burgundy, Bottle Green, Black Of Any Size As Approved By Engineer-In-Charge, In Skirting, Risers Of Steps And Dados, Over 12 Mm Thick Bed Of Cement Mortar 1:3 ( 1 Cement : 3 Coarse Sand ) And Jointing With Grey Cement Slurry @ 3.3Kg Per Sqm, Including Pointing In White Cement Mixed With Pigment Of Matching Shade Ncomplete. 33 Providing And Fixing Ptmt Bottle Trap For Wash Basin And Sink.Bottle Trap 38 Mm Single Piece Moulded With Height Of 270 Mm, Effective Length Of Tail Pipe 260 Mm From The Center Of The Waste Coupling, 77 Mm Breadth With 25 Mm Minimum Water Seal, Weighing Not Less Than 263 Gms 34 Providing And Fixing C.P. Brass Angle Valve For Basin Mixer And Geyser Points Of Approved Quality Conforming To Is:8931 ( 20 Mm Nominal Bore ) 35 Providing And Fixing Chlorinated Polyvinyl Chloride ( Cpvc ) Pipes, Having Thermal Stability For Hot & Cold Water Supply, Including All Cpvc Plain & Brass Threaded Fittings Including Fixing The Pipe With Clamps At 1.00 M Spacing. This Includes Jointing Of Pipes & Fittings With One Step Cpvc Solvent Cement And Testing Of Joints Complete As Per Direction Of Engineer -In-Charge. Internal Work - Exposed On Wall 36 20 Mm Nominal Outer Dia Pipes 37 32 Mm Nominal Outer Dia Pipes 38 Providing And Fixing Chlorinated Polyvinyl Chloride ( Cpvc ) Pipes, Having Thermal Stability For Hot & Cold Water Supply Including All Cpvc Plain & Brass Threaded Fittings. This Includes Jointing Of Pipes & Fittings With One Step Cpvc Solvent Cement, Trenching , Refilling & Testing Of Joints Complete As Per Direction Of Engineer- In-Charge. External Work40 Mm Nominal Outer Dia Pipes 39 Providing And Fixing Ball Valve ( Cpvc ) Of Approved Quality, High Or Low Pressure, With Plastic Floats Complete : 40 20 Mm Nominal Bore 41 32 Mm Nominal Bore 42 Supply, Installation, Testing And Commissioning Of Ci Gate Valve As Per Is 4846 ( Pn 16 ) Rating For Sections With Flanges, Bolts, Nuts, Washers, Gaskets Etc. Size 20 Mm 43 Supply, Installation, Testing And Commissioning Of Wire Reinforced Rubber Gas Hose As Per Is 9573, With Suitable Hose Clip. Diameter As Per The Site Requirement. Hose Should Bear Isi Mark. Warranty As Per Manufacturer Specifications. 44 Providing And Fixing G.I. Pipes Complete With G.I. Fittings And Clamps, Including Cutting And Making Good The Walls Etc. Internal Work - Exposed On Wall 20Mm Dia Nominal Bore ( Minimum Thickness Of 2.6 Mm ) . The Item Should Be In Accordance With Schedule 80 And Is 1239. 45 Capital Items 46 Almirah Type Storage Unit Made Of Up 20Swg Powder Coated Sheet Steel With Ribs. The Door Shall Be Glass Door With Metal Frame. Good Quality Hinges , Handle And Lock Shall Be Provided. The Minimum Number Of Racks Shall Be 3 Nos.Minimum Dimensions : 900 X 450 X 1900 Mm ( W X D X H ) 47 Supply And Installation Of Metal Locker Cum Storage Unit Material Of Construction : Mild Steel Finish : Powder Coated Min Thickness : 1 Mm Colour : As Per The Instruction From Hll Engineer In Charge 3 Columns X 5 Rows ( 15 Compartments ) Min Dimension : 2.00 M ( Height ) X .9 M ( Width ) X .45 M ( Depth ) 48 Electrical Works 49 Wiring For Light Point / Fan Point / Exhaust Fan Point / Call Bell Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Steel Conduit, With Modular Switch, Modular Plate, Suitable Gi Box And Earthing The Point With 1.5 Sq.Mm. Frls Pvc Insulated Copper Conductor Single Core Cable Etc As Required 50 Wiring For Twin Control Light Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Medium Class Pvc Conduit, 2 Way Modular Switch, Modular Plate, Suitable Gi Box And Earthing The Point With 1.5 Sq.Mm. Frls Pvc Insulated Copper Conductor Single Core Cable Etc As Required 51 Wiring For Circuit / Submain Wiring Alongwith Earth Wire With The Following Sizes Of Frls Pvc Insulated Copper Conductor, Single Core Cable In Surface / Recessed Medium Class Pvc Conduit As Required 52 2X 1.5 Sq. Mm + 1 X 1.5 Sq.Mm Earth Wire 53 2X 2.5 Sq. Mm + 1 X 2.5 Sq. Mm Earth Wire 54 2X 4 Sq. Mm + 1 X 4 Sq. Mm Earth Wire 55 2X 6 Sq. Mm + 1 X 6 Sq. Mm Earth Wire 56 4X 10 Sq. Mm + 2 X 6 Sq. Mm Earth Wire 57 4X 16 Sq. Mm + 2 X 6 Sq. Mm Earth Wire 58 Laying And Fixing Of One Number Pvc Insulated And Pvc Sheathed Power Cable Of 1.1 Kv Grade Of Following Size On Cable Tray As Required. Above 35 Sq. Mm And Upto 95 Sq. Mm ( Clamped With 25X3mm Ms Flat Clamp ) 59 Supplying And Making End Termination With Brass Compression Gland And Aluminium Lugs For Following Size Of Pvc Insulated And Pvc Sheathed / Armoured Aluminium Conductor Cable Of 1.1 Kv Grade As Required. 3.5 C X 70 Sqmm 60 Supply Of Following Size 1.1 Kv Grade Insulated, Pvc Sheathed, Armoured Aluminium Conductor Power Cable Conforming To Is 7098 ( Part 1 ) Amended Upto Date. 3.5C X 70 Sqmm. 61 Supplying The Following Types Of Sockets 62 Supplying And Fixing Suitable Size Gi Box With Modular Plate And Cover In Front On Surface Or In Recess, Including Providing And Fixing 6 Pin 5 / 6 & 15 / 16 Amps Modular Socket Outlet And 15 / 16 Amps Modular Switch, Connection Etc. As Required By The Site Engineer 63 Supplying And Fixing Modular Plate And Cover In Front On Surface Or In Recess, Including Providing And Fixing 6 Pin 5 / 6 & 15 / 16 Amps Modular Socket Outlet And 15 / 16 Amps Modular Switch, Connection Etc. On The Modular Furniture As Required By The Site Engineer 64 Supplying And Fixing Modular Blanking Plate On The Existing Modular Plate & Switch Box Excluding Modular Plate As Required. 65 Supplying And Fixing Of Following Sizes Of Medium Class Pvc Conduit Along With Accessories In Surface / Recess Including Cutting The Wall And Making Good The Same In Case Of Recessed Conduit As Required. 25 Mm 66 Supplying And Installing Following Size Of Perforated Hot Dipped Galvanised Iron Cable Tray ( Galvanisation Thickness Not Less Than 50 Microns ) With Perforation Not More Than 17.5%, In Convenient Sections, Joined With Connectors, Suspended From The Ceiling With G.I. Suspenders Including G.I. Bolts & Nuts, Etc. As Required Including Earthing As Advised By The Site Engineer 67 100 Mm Width X 50 Mm Depth X 1.6 Mm Thickness 68 Supplying And Installation Of 3 Blade, 300 Mm Sweep, 1400 Rpm Exhaust Fan Including All Accessories Complete. Recommended Make: Usha / Havells / Bajaj 69 Supplying And Installation Of Ceiling Fan 1200 Mm Sweep Including All Accessories Complete. Recommended Make: Usha / Havells / Bajaj 70 Dismantling Of Ceiling Fan And Painting The Same With With One Or More Coats Of Spray Painting With Synthetic Enamel Paint Of Approved Brand And Manufacture To Give An Even Shade, Including Cleaning Of Surface With Detergent And Replacing The Damaged Rubber Reel, Nuts And Bolts With Washers And Safety Pins, Reinstalling The Same As Required. 71 Supplying And Fixing 5 Amps To 32 Amps Rating, 240 / 415 Volts, C Curve, Miniature Circuit Breaker Suitable For Inductive Load Of Following Poles In The Existing Mcb Db Complete With Connections, Testing Nand Commissioning Etc. As Required. Single Pole 72 Supplying And Fixing Spn Sheet Steel Enclosure On Surface / Recess Along With 32 A, 230 V “C” Curve Spn Mcb Complete With Connections, Testing And Commissioning Etc. As Required 73 Supplying And Fixing Tpn Sheet Steel Enclosure On Surface / Recess Along With 40 A, 415 V “C” Curve Tpn Mcb Complete With Connections, Testing And Commissioning Etc. As Required 74 Supplying And Fixing Tpn Sheet Steel Enclosure On Surface / Recess Along With 63 A, 415 V “C” Curve Tpn Mcb Complete With Connections, Testing And Commissioning Etc. As Required 75 Supplying And Fixing Following Rating, Four Pole, ( Three Phase And Neutral ) , 415 Volts, Residual Current Circuit Breaker ( Rccb ) , Having A Sensitivity Current Upto 30 Ma In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. 63 Amps 76 Supplying And Fixing Following Rating, Four Pole, ( Three Phase And Neutral ) , 415 Volts, Residual Current Circuit Breaker ( Rccb ) , Having A Sensitivity Current Upto 30 Ma In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. 40 Amps 77 Supplying And Fixing Following Rating, Double Pole, ( Single Phase And Neutral ) , 240 V, Residual Current Circuit Breaker ( Rccb ) , Having A Sensitivity Current 30 Ma In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. 25 Amps 78 Supply And Installation Of Sheet Steel, Phosphatised And Painted, Dust And Vermin Proof Enclosure Of Mcb Db Including Copper / Brass Bus Bar, Neutral Link, Earth Bus And Din Rail Suitable For Fixing Mcb / Isolator Etc. Fixed On Wall Using Suitable Anchor Bolts Or Fixed In Recess Including Cutting Hole On The Wall , Making Good The Damages, Colour Washing Etc. As Required 4 Way ( 8+12 ) - Double Cover Tpn Vertical Db With Provision For Fixing 4P Mcb / Isolator / Rccb / Rcbo As Incomer And Sp / Tp Mcb As Outgoing ( Ip42 / 43 ) 79 Supply And Installation Of Sheet Steel, Phosphatised And Painted, Dust And Vermin Proof Enclosure Of Mcb Db Including Copper / Brass Bus Bar, Neutral Link, Earth Bus And Din Rail Suitable For Fixing Mcb / Isolator Etc. Fixed On Wall Using Suitable Anchor Bolts Or Fixed In Recess Including Cutting Hole On The Wall , Making Good The Damages, Colour Washing Etc. As Required 4 Way ( 8+12 ) - Three Phase Double Cover ( Ip42 / 43 ) 80 Supplying And Fixing Following Way, Single Pole And Neutral, Sheet Steel, Mcb Distribution Board, 240 V, On Surface / Recess, Complete With Tinned Copper Bus Bar, Neutral Bus Bar, Earth Bar, Din Bar, Interconnections, Powder Painted Including Earthing Etc. As Required. ( But Without Mcb / Rccb / Isolator. 12 Way, Double Door 81 Supplying And Fixing Cable End Box ( Loose Wire Box ) ( Ip 43 ) Suitable For Following Triple Pole And Neutral, Sheet Steel, Mcb Distribution Board, 415 V, On Surface / Recess, Complete With Testing And Commissioning Etc. As Required. For 4 Way, Double Door Tpn Mcbdb 82 Supplying And Fixing Cable End Box ( Loose Wire Box ) ( Ip 43 ) Suitable For Following Single Pole And Neutral, Sheet Steel, Mcb Distribution Board, 240 V, On Surface / Recess, Complete With Testing And Commissioning Etc. As Required. For 12 Way, Double Door Spn Mcbdb 83 Supplying And Fixing Modular Blanking Plate On The Existing Modular Plate & Switch Box Excluding Modular Plate As Required 84 Supplying And Fixing 20 A, 240 V, Spn Industrialtype Socket Outlet, With 2 Pole And Earth, Metal Enclosed Plug Top Alongwith 20 A C Curve, Sp, Mcb, In Sheet Steel Enclosure, On Surface Or In Recess, With Chained Metal Cover For The Socket Out Let And Complete With Connections, Testing And Commissioning Etc. As Required. 85 Supply And Installation Of Compact Recess Mounted 36W Led Luminaire With High Transculent Diffuser Gives Soft Glare Free Light & Complete With Electronic Driver Including All Required Mounting Accessories Complete. ( Philips / Wipro / Havells Or Equivalent 86 Supply And Installation Of Round Recessed Led Fitting - 12 W / 15W With All Accessories And Connections Complete. Recommended Make - Bajaj / Philips Or Equivalent 87 Earthing With Copper Earth Plate 600 Mm X 600 Mm X 3 Mm Thick Including Accessories, And Providing Masonry Enclosure With Cover Plate Having Locking Arrangement And Watering Pipe Of 2.7 Metre Long Etc. ( But Without Charcoal / Coke And Salt ) As Required. 88 Providing And Fixing 25 Mm X 5 Mm Copper Strip On Surface Or In Recess For Connections Etc. As Required. 89 Providing And Fixing Flexible 10.00 Mm Dia Copper Wire On Surface Or In Recess For Loop Earthing Along With Existing Surface / Recessed Conduit / Submain Wiring / Cable As Per The Instruction Of Site Engineer 90 Providing 10 Sq. Mm Isi Marked, Frls Pvc Insulated, Single Core Copper Conductor Cable Along With All Necessary Terminations And Lugs As Required For Equipment Earthing 91 Supply, Installation, Testing And Commissioning Of Split Air Conditioner Of Following Capacity And Specifications: Consisting Of High Wall-Mounted Type Room Unit ( Fan Coil ) With Cordless Remote Control And One Number Outdoor Condensing Unit Comprising Of Energy-Efficient Suitable Rotary Compressor For Operation On Single-Phase, 230 V, 50Hz Supply, Fixing The Outdoor Unit On A Raised Platform As Per Manufacturers Recommendation And Fixing Of Room ( Fan Coil ) Unit On Wall, Standard 4 M Distance Refrigerant Copper Piping With 13Mm Nitrile Rubber Insulation, Providing And Making Interconnection Between Room & Condenser As Per Site Conditions, Comprising Of 1 Dia Drain Pvc Pipe With Insulation Up To 4 M, Canvas Connections, Full Electrical Cabling From Power Plug Near Indoor Unit And To Outdoor Unit, Odu Ms Stand, First Charge Refrigerant Gas, Suitable Stabilizer Etc Complete As Required. ( Make: Voltas, Blue Star, Hitachi, Carrier Or Equivalent ) . 1.5 Tr 3 Star Rated ( Inverter Type Ac ) As Per Bee 92 Supply, Installation, Testing And Commissioning Of Split Air Conditioner Of Following Capacity And Specifications: Consisting Of High Wall-Mounted Type Room Unit ( Fan Coil ) With Cordless Remote Control And One Number Outdoor Condensing Unit Comprising Of Energy-Efficient Suitable Rotary Compressor For Operation On Single-Phase, 230 V, 50Hz Supply, Fixing The Outdoor Unit On A Raised Platform As Per Manufacturers Recommendation And Fixing Of Room ( Fan Coil ) Unit On Wall, Standard 4 M Distance Refrigerant Copper Piping With 13Mm Nitrile Rubber Insulation, Providing And Making Interconnection Between Room & Condenser As Per Site Conditions, Comprising Of 1 Dia Drain Pvc Pipe With Insulation Up To 4 M, Canvas Connections, Full Electrical Cabling From Power Plug Near Indoor Unit And To Outdoor Unit, Odu Ms Stand, First Charge Refrigerant Gas, Suitable Stabilizer Etc Complete As Required. ( Make: Voltas, Blue Star, Hitachi, Carrier Or Equivalent ) . 2.0 Tr 3 Star Rated ( Inverter Type Ac ) As Per Bee 93 16 Port Network Switch: Supply And Installation At Site: 10 / 100 Mbps 16-Ports Gigabit Switch. ( Make: Dlink Or Equivalent ) 94 Supply And Fixing Of Rj 45 Data Outlet In Separate 2 Modular Box With Connections Complete 95 Supplying And Drawn Of Utp 4 Pair Cat 6 Lan Cable In The Existing Surface / Recessed Steel / Pvc Conduit As Required 1 Run Of Cable 96 Supply, Installation And Commissioning Of Powder Coated Dvr 6U Wall Mounted Server Rack Of Iso Standard Of Size 400X 400X 200Mm Having Depth Adjustable Mounting Slots, Top And Bottom Panel With Nventilation And Cable Entry Facility, Provision To Mount The Cooling Fans On The Top Panel, Lock And Key Etc. And Having Capacity To Carry A Max Load Of 60 Kg All Complete As Per The Manufacturer Specifications And Ninstructions Of Engineer In Charge 97 Supplying And Fixing Of Abc Type Fire Extinguisher Type 6Kgs Capacity Of Approved Make With Wall Mounting Bracket As Required Conforming To Is: 2878 / 1976 ( Push Type ) 98 Supply, Installation, Testing And Commissioning Of Ul Listed Microprocessor Based Intelligent Fire Alarm Panel With Min. 6 Lcd Display Multiple Access Level Event History File. The Panel Shall Support Programmable Relay Controlled By Power Full Boolean Equation. The Panel Shall Have 240V Ac Supply Automatic Battery Charger 24Volts, Sealed Lead Acid Maintenance Free Batteries For 24Hour Normal Working And Then Be Capable Of Operating The System For 60 Minutes During Emergency Condition. The Panel Shall Be Ul Main Fire Alarm Panel Complete 99 Supply, And Laying Of 2 Cx1.5Sqmm Fire Survival Armored Cable ( 600 / 1000V ) With Class 2 Copper Conductor Having Cross-Linkable ( Lszh ) Insulation & Lszh Inner And Outer Sheath As Per Bs7846:2009. Should Meet Fire Performance Circuit Integrity Test As Per Bs:8434-2:2009 100 Supply, Installation, Testing And Commissioning Of Hooters Com Strobes Of The Same Make And Listing As Fire Alarm Panel Complete With At Least 4 Selectable Tone Setting 2 Volume Setting. ( Lpcb / Ul / Vds Approved ) 101 Supply, Installation, Testing And Commissioning Of Manual Call Station ( Lpcb / Ul / Vds Approved ) With Address Switch And All Mounting Accessories, Complete With Ms Coated Junction Box For Mounting On Surface, Cable Lugs At Ends, Cable Compression Gland Tag And Ferruling. 102 Supply, Installation, Testing And Commissioning Of Addressable Smoke Detectors With Decentralized Intelligence And Fault Isolator Either Built-In The Detector Or As A Separate Isolator Base / Module. Detector Shall Be Complete With Base And Lpcb / Ul / Vds Approved 103 Supplying And Fixing Of Co2 Type Fire Extinguisher Type 5 Kgs Capacity Of Approved Make With Wall Mounting Bracket As Required 104 Cctv 105 Supply, Installation, Testing & Commissioning Of 15-16 Led Color Monitors. ( Lg / Samsung / Panasonic / Sony Or Equivalent ) 106 Supply, Installation, Testing & Commissioning Of Indoor Ir Dome Night Vision Cameras : 1Mp, 0.1 Lux, Resolution 720 P , Awb / Blc / Agc, Min 20M Range, Built-In Ir Illumination, White Color Case, Palce / Fcc Approved. Make: Cp Plus / Hikvision / Honeywell Or Equivalent 107 Supply, Installation, Testing & Commissioning Of Power Supply Unit For Above Camera As Speficied By Camera Manufacturer -12Vdc 10A 108 Supply And Laying Of Coaxial Cable 2+1 Rg59 / Rg6 Premium Quality Cctv Power And Video Cable With Isi Marked Pvc Conduit Including Terminations With Suitable Bnc Connector, Power Jack Etc Complete 109 Supply, Installation, Testing & Commissioning Of Digital Video Recorder: 16-Channel Embedded Hd Dvr, 720P, Real-Time, With 4 Tb Hdd And English Osd, 230Vac. Rate Shall Be Inclusive Of All Naccessories, Termination Of Cables, Etc Complete.

Key Value

Document Fees
INR 2800 /-
EMD
INR 50000.0 /-
Tender Value
INR 30 Lakhs /-

BOQ Items

Name of Work: Civil and Electrical works for setting-up of Micro-Biology Lab at Second floor of State Dairy Laboratory, Thiruvananthapuram
Sl. No. Item Description Item Code / Make Quantity Units
1 1 CIVIL WORKS
2 1.01 Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge. In cement mortar 1.5 Cum
3 1.02 Taking out doors, windows and clerestory window shutters (steel or wood) including stacking within 50 metres lead :\nOf area beyond 3 sq. metres 2 Each
4 1.03 Dismantling aluminium / Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable surplus material and stacking of serviceable material with in 50 metres lead as directed by Engineer - in-Charge 89 Sqm
5 1.04 Brick work with common burnt clay F.P.S. (non modular) bricks of class designation 7.5 in superstructure above plinth level up to floor V level in all shapes and sizes in:Cement mortar 1:4 ( 1 cement : 4 coarse sand) 4 Cum
6 1.05 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS : 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminnium snap beading for glazing /paneling, C.P. brass/ stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge.(Glazing, paneling and dash fasteners to be paid for separately):
7 1.051 For fixed portionPowder coated aluminium (minimum thickness of powder coating 50 micron) 800 kg
8 1.052 For shutters of doors, windows & ventilators including providing and fixing hinges / pivots and making provision for fixing of fittings wherever required including the cost of EPDM rubber/ neoprene gasket required (Fittings shall be paid for separately)Powder coated aluminium (minimum thickness of powder coating 50 micron) 180 kg
9 1.06 Providing and fixing 12 mm thick prelaminated particle board flat pressed threelayer or graded wood particle board conforming to IS: 12823 Grade l Type ll,in panelling fixed in aluminum doors, windows shutters and partition frameswith C.P. brass / stainless steel screws etc. complete as per architecturaldrawings and directions of engineer-in-charge. Pre-laminated particle board with decorative lamination on both sides 145 Sqm
10 1.07 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge . (Cost of aluminium snap beading shall be paid in basic item):\nWith float glass panes of 5.50 mm thickness 70 Sqm
11 1.08 Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete. 12 Each
12 1.09 Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Single rubber stopper 12 Each
13 1.1 Providing and fixing bright finished brass 100 mm mortice latch and lock with 6 levers and a pair of lever handles of approved quality with necessary screws etc. complete. 12 Each
14 1.11 Providing and fixing IS : 12817 marked stainless steel butt hinges with stainless steel screws etc. complete:100x58x1.90 mm 35 Each
15 1.12 Providing and fixing bright finished brass handles with screws etc. complete:125 mm 15 Each
16 1.13 Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with:12.5 mm thick tapered edge gypsum plain board conforming to IS : 2095-Part 1 105.75 Sqm
17 1.14 Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete.Hot finished welded type tubes 350 kg
18 1.15 Re-installation of doors, window etc. with suitable fittings and accessories. The cost includes work i.e., installation for all the above mentioned works as a whole including required accessories.\nFor refixing one wooden door 1 Job
19 2 PAINTING
20 2.01 12 mm cement plaster of mix:1:4 ( 1 cement : 4 fine sand) 37 Sqm
21 2.02 Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. 35 Sqm
22 2.03 Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer 35 Sqm
23 2.04 Wall painting with premium plastic emulsion paint of approved brand and manufacture to give an even shade: One or more coats on old work (Minimum rate of material should be Rs. 400/litre) 153 Sqm
24 2.05 Painting with synthetic enamel paint of approved brand and manufacture to give an even shade: Two or more coats on new work 42 Sqm
25 2.06 Distempering with oil bound washable distemper of approved brand and manufacture to give an even shade: Old work ( one or more coats) 177 Sqm
26 3 PLUMBING
27 3.01 Dismantling W.C. Pan of all sizes including disposal of dismantled materials i/c malba all complete as per directions of Engineer-in- Charge. 1 Each
28 3.02 Dismantling of flushing cistern of all types (C.I./PVC/Vitrious China) including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead. 1 Each
29 3.03 Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead. For thickness of tiles 10 mm to 25 mm 4 Sqm
30 3.04 Re-fixing of water closet, flushing cistern etc. with suitable fittings and accessories 1 Job
31 3.05 Providing and laying Ceramic glazed floor tiles of size 300x300 mm (thickness to be specified by the manufacturer) of 1st quality conforming to IS : 15622 of approved make in colours such as White, Ivory, Grey, Fume Red Brown, laid on 20 mm thick cement mortar 1:4 (1 Cement : 4 Coarse sand), jointing with grey cement slurry @ 3.3kg/sqm including pointing the joints with white cement and matching pigment etc., complete. 2 Sqm
32 3.06 Providing and fixing Ist quality ceramic glazed wall tiles conforming to IS: 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer-in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3kg per sqm, including pointing in white cement mixed with pigment of matching shade\ncomplete. 2 Sqm
33 3.07 Providing and fixing PTMT Bottle Trap for Wash basin and sink.Bottle trap 38 mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the center of the waste coupling, 77 mm breadth with 25 mm minimum water seal, weighing not less than 263 gms 5 Each
34 3.08 Providing and fixing C.P. brass angle valve for basin mixer and geyser points of approved quality conforming to IS:8931 (20 mm nominal bore) 5 Each
35 3.09 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer -in-Charge. Internal work - Exposed on wall
36 3.091 20 mm nominal outer dia pipes 50 Metre
37 3.092 32 mm nominal outer dia Pipes 25 Metre
38 3.1 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply including all CPVC plain & brass threaded fittings. This includes jointing of pipes & fittings with one step CPVC solvent cement, trenching , refilling & testing of joints complete as per direction of Engineer- in-Charge. External work40 mm nominal outer dia pipes 40 Metre
39 3.11 Providing and fixing ball valve (CPVC) of approved quality, High or low pressure, with plastic floats complete :
40 3.111 20 mm nominal bore 5 Each
41 3.112 32 mm nominal bore 2 Each
42 3.12 Supply, Installation, Testing and Commissioning of CI Gate valve as per IS 4846 (PN 16) Rating for sections with flanges, bolts, nuts, washers, gaskets etc. Size 20 mm 7 Each
43 3.13 Supply, Installation, Testing and Commissioning of Wire Reinforced Rubber Gas Hose as per IS 9573, with suitable hose clip. Diameter as per the site requirement. Hose should bear ISI mark. Warranty as per manufacturer specifications. 25 Metre
44 3.14 Providing and fixing G.I. pipes complete with G.I. fittings and clamps, including cutting and making good the walls etc. Internal work - Exposed on wall 20mm dia nominal bore (minimum thickness of 2.6 mm). The item should be in accordance with schedule 80 and IS 1239. 50 Metre
45 4 CAPITAL ITEMS
46 4.01 Almirah Type storage unit made of up 20SWG powder coated sheet steel with ribs. The door shall be glass door with metal frame. Good quality hinges , handle and lock shall be provided. The minimum number of racks shall be 3 nos.Minimum Dimensions : 900 x 450 x 1900 mm (W x D x H) 1 Each
47 4.02 Supply and Installation of Metal Locker cum Storage Unit Material of construction : Mild steel Finish : Powder coated Min Thickness : 1 mm Colour : as per the instruction from HLL Engineer In charge 3 columns x 5 Rows (15 Compartments) Min Dimension : 2.00 m (Height) x .9 m (width) x .45 m (depth) 1 Each
48 5 ELECTRICAL WORKS
49 5.01 Wiring for light point/ fan point / exhaust fan point / call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed steel conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required 10 Point
50 5.02 Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required 15 Point
51 5.03 Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required
52 5.031 2X 1.5 sq. mm + 1 X 1.5 sq.mm earth wire 600 Metre
53 5.032 2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wire 350 Metre
54 5.033 2X 4 sq. mm + 1 X 4 sq. mm earth wire 250 Metre
55 5.034 2X 6 sq. mm + 1 X 6 sq. mm earth wire 30 Metre
56 5.035 4X 10 sq. mm + 2 X 6 sq. mm earth wire 30 Metre
57 5.036 4X 16 sq. mm + 2 X 6 sq. mm earth wire 90 Metre
58 5.04 Laying and fixing of one number PVC insulated and PVC sheathed power cable of 1.1 KV grade of following size on cable tray as required. Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) 40 Metre
59 5.05 Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / armoured aluminium conductor cable of 1.1 KV grade as required. 3.5 C x 70 sqmm 10 Each
60 5.06 Supply of following size 1.1 KV grade insulated, PVC sheathed, armoured Aluminium conductor power cable conforming to IS 7098 (Part 1) amended upto date. 3.5C x 70 sqmm. 40 Metre
61 5.07 Supplying the following types of Sockets
62 5.071 Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required by the Site Engineer 35 Each
63 5.072 Supplying and fixing modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. on the modular furniture as required by the Site Engineer 35 Each
64 5.08 Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required. 10 Each
65 5.09 Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required. 25 mm 100 Metre
66 5.1 Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (Galvanisation thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.I. suspenders including G.I. bolts & nuts, etc. as required including earthing as advised by the Site Engineer
67 5.101 100 mm width X 50 mm depth X 1.6 mm thickness 40 Metre
68 5.11 Supplying and Installation of 3 blade, 300 mm sweep, 1400 rpm Exhaust Fan including all accessories complete. Recommended Make: USHA/ Havells/ Bajaj 2 Each
69 5.12 Supplying and Installation of ceiling fan 1200 mm sweep including all accessories complete. Recommended Make: USHA/ Havells/ Bajaj 4 Each
70 5.13 Dismantling of ceiling fan and painting the same with with one or more coats of spray painting with synthetic enamel paint of approved brand and manufacture to give an even shade, including cleaning of surface with detergent and replacing the damaged rubber reel, nuts and bolts with washers and safety pins, reinstalling the same as required. 3 Each
71 5.14 Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, "C" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing\nand commissioning etc. as required. Single pole 45 Each
72 5.15 Supplying and fixing SPN sheet steel enclosure on surface/ recess along with 32 A, 230 V “C” curve SPN MCB complete with connections, testing and commissioning etc. as required 2 Each
73 5.16 Supplying and fixing TPN sheet steel enclosure on surface/ recess along with 40 A, 415 V “C” curve TPN MCB complete with connections, testing and commissioning etc. as required 3 Each
74 5.17 Supplying and fixing TPN sheet steel enclosure on surface/ recess along with 63 A, 415 V “C” curve TPN MCB complete with connections, testing and commissioning etc. as required 7 Each
75 5.18 Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 amps 3 Each
76 5.19 Supplying and fixing following rating, four pole, (three phase and neutral), 415 volts, residual current circuit breaker (RCCB), having a sensitivity current upto 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 amps 1 Each
77 5.2 Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 amps 1 Each
78 5.21 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required 4 way (8+12) - double cover TPN vertical DB with provision for fixing 4P MCB / Isolator/ RCCB/ RCBO as incomer and SP/ TP MCB as outgoing (IP42/43) 2 Each
79 5.22 Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required 4 way (8+12) - three phase double cover (IP42/43) 4 Each
80 5.23 Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator. 12 way, Double door 1 Each
81 5.24 Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following triple pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with testing and commissioning etc. as required. For 4 way, Double door TPN MCBDB 4 Each
82 5.25 Supplying and fixing Cable End Box (Loose Wire Box) (IP 43) suitable for following single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with testing and commissioning etc. as required. For 12 way, Double door SPN MCBDB 1 Each
83 5.26 Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required 10 Each
84 5.27 Supplying and fixing 20 A, 240 V, SPN Industrialtype socket outlet, with 2 pole and earth, metal enclosed plug top alongwith 20 A "C" curve, SP, MCB, in sheet steel enclosure, on surface or in recess, with chained metal cover for the socket out let and complete with connections, testing and commissioning etc. as required. 2 Each
85 5.28 Supply and Installation of compact Recess mounted 36W LED luminaire with High transculent diffuser gives soft glare free light & complete with electronic driver including all required mounting accessories complete. (Philips/WIPRO/Havells or equivalent 22 Each
86 5.29 Supply and Installation of Round Recessed LED Fitting - 12 W/ 15W with all accessories and connections complete. Recommended make - Bajaj / Philips or equivalent 5 Each
87 5.3 Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. (but without charcoal/ coke and salt ) as required. 3 Set
88 5.31 Providing and fixing 25 mm X 5 mm copper strip on surface or in recess for connections etc. as required. 50 Metre
89 5.32 Providing and fixing flexible 10.00 mm dia copper wire on surface or in recess for loop earthing along with existing surface/ recessed conduit/ submain wiring/ cable as per the instruction of Site Engineer 30 Metre
90 5.33 Providing 10 sq. mm ISI marked, FRLS PVC insulated, single core copper conductor cable along with all necessary terminations and lugs as required for equipment earthing 80 Metre
91 5.34 Supply, installation, testing and commissioning of Split Air Conditioner of following capacity and specifications: Consisting of high wall-mounted type room unit (fan coil) with cordless remote control and one number outdoor condensing unit comprising of energy-efficient suitable rotary compressor for operation on single-phase, 230 V, 50Hz supply, fixing the outdoor unit on a raised platform as per manufacturers recommendation and fixing of room (fan coil) unit on wall, standard 4 m distance refrigerant copper piping with 13mm nitrile rubber insulation, providing and making interconnection between room & condenser as per site conditions, comprising of 1" dia drain PVC pipe with insulation up to 4 m, canvas connections, full electrical cabling from power plug near indoor unit and to outdoor unit, ODU MS stand, first charge refrigerant gas, suitable stabilizer etc complete as required. (Make: Voltas, Blue Star, Hitachi, Carrier or equivalent). 1.5 TR 3 Star rated (inverter type AC) as per BEE 2 Set
92 5.35 Supply, installation, testing and commissioning of Split Air Conditioner of following capacity and specifications: Consisting of high wall-mounted type room unit (fan coil) with cordless remote control and one number outdoor condensing unit comprising of energy-efficient suitable rotary compressor for operation on single-phase, 230 V, 50Hz supply, fixing the outdoor unit on a raised platform as per manufacturers recommendation and fixing of room (fan coil) unit on wall, standard 4 m distance refrigerant copper piping with 13mm nitrile rubber insulation, providing and making interconnection between room & condenser as per site conditions, comprising of 1" dia drain PVC pipe with insulation up to 4 m, canvas connections, full electrical cabling from power plug near indoor unit and to outdoor unit, ODU MS stand, first charge refrigerant gas, suitable stabilizer etc complete as required. (Make: Voltas, Blue Star, Hitachi, Carrier or equivalent). 2.0 TR 3 Star rated (inverter type AC) as per BEE 5 Set
93 5.36 16 Port Network Switch: Supply and Installation at site: 10/100 Mbps 16-Ports Gigabit Switch. (Make: DLink or equivalent) 1 Set
94 5.37 Supply and Fixing of RJ 45 data outlet in separate 2 modular box with connections complete 10 Each
95 5.38 Supplying and drawn of UTP 4 pair CAT 6 LAN cable in the existing surface/recessed steel/PVC conduit as required 1 run of Cable 130 Metre
96 5.39 Supply, Installation and commissioning of powder coated DVR 6U Wall Mounted Server Rack of ISO Standard of size 400X 400X 200mm having depth adjustable mounting slots, top and bottom Panel with\nventilation and cable entry facility, provision to mount the cooling fans on the top panel, lock and key etc. and having capacity to carry a max Load of 60 kg all complete as per the manufacturer specifications and\ninstructions of Engineer In Charge 1 Each
97 5.4 Supplying and fixing of ABC type fire extinguisher type 6Kgs Capacity of approved make with wall mounting bracket as required conforming to IS: 2878/1976 (Push type) 3 Each
98 5.41 Supply, Installation, testing and commissioning of UL listed microprocessor based intelligent fire alarm panel with min. 6" LCD display multiple access level event history file. The panel shall support programmable relay controlled by power full Boolean equation. The panel shall have 240v AC supply automatic battery charger 24volts, sealed lead acid maintenance free batteries for 24hour normal working and then be capable of operating the system for 60 minutes during emergency condition. The panel shall be UL Main Fire alarm panel complete 1 Set
99 5.42 Supply, and Laying of 2 Cx1.5sqmm Fire Survival armored cable (600/1000V) with class 2 copper conductor having Cross-linkable (LSZH) insulation & LSZH inner and outer sheath as per BS7846:2009. Should meet fire performance circuit integrity test as per BS:8434-2:2009 80 Metre
100 5.43 Supply, Installation, testing and commissioning of Hooters com strobes of the same make and listing as fire alarm panel complete with at least 4 selectable tone setting 2 volume setting. (LPCB/UL/VdS approved) 2 Each
101 5.44 Supply, Installation, testing and commissioning of Manual Call Station (LPCB/UL/VdS approved) with Address switch and all mounting accessories, complete with MS coated Junction Box for mounting on surface, cable lugs at ends, cable compression gland tag and ferruling. 2 Each
102 5.45 Supply, Installation, testing and commissioning of addressable smoke detectors with decentralized intelligence and fault isolator either built-in the detector or as a separate isolator base/module. Detector shall be complete with base and LPCB/UL/VdS approved 10 Each
103 5.46 Supplying and fixing of CO2 type fire extinguisher type 5 Kgs Capacity of approved make with wall mounting bracket as required 3 Each
104 6 CCTV
105 6.01 Supply, Installation, Testing & Commissioning of 15''-16" LED Color Monitors. (LG/Samsung/Panasonic/Sony or equivalent) 1 Each
106 6.02 Supply, Installation, Testing & Commissioning of Indoor IR Dome night vision cameras : 1MP, 0.1 lux, Resolution 720 P ,AWB/ BLC/ AGC, min 20m range, Built-in IR illumination, white color case, PALCE/ FCC approved. Make: CP PLUS/HIKVISION/Honeywell or equivalent 8 Each
107 6.03 Supply, Installation, Testing & Commissioning of Power supply unit for above camera as speficied by camera manufacturer -12VDC 10A 3 Each
108 6.04 Supply and Laying of Coaxial cable 2+1 RG59/RG6 premium quality CCTV power and video cable with ISI marked PVC conduit including terminations with suitable BNC Connector, power Jack etc complete 150 Metre
109 6.05 Supply, Installation, Testing & Commissioning of Digital Video Recorder: 16-Channel Embedded HD DVR, 720p, Real-time, with 4 TB HDD and English OSD, 230VAC. Rate shall be inclusive of all\naccessories, termination of cables, etc complete. 1 Set