Housing Urban and Rular Development Government Departments Closing in 0 days TDR #22842392

Setting Up Of Medical College At Painavu Idukki Electrification Works For The Residential Facilities Setting Up Of Medical College At Painavu Idukki Electrification Works For TheResidential Facilities

Issued by Government Departments · Painavu Idukki, Kerala
Tender Value
4.80 Crore
Estimated cost
Bid Submission
30 Dec 2019
0 days left
EMD
1 Lakhs
Bank guarantee accepted
Document Fee
8850
Non-refundable
Tender Type
Online

Tender Overview

Competition Type
NCB
Bidding Type
Tender
Location / State
Painavu Idukki → Kerala
EMD Exemption
Not Available
Quantity
Not Available

Project Description

Setting Up Of Medical College At Painavu Idukki Electrification Works For The Residential Facilities Setting Up Of Medical College At Painavu Idukki Electrification Works For TheResidential Facilities

BOQ

Work Name : Setting up of Medical College at Painavu, Idukki - SH: Electrification works for the Residential facilities.
Sl.No.Item DescriptionItem Code / MakeQuantityUnits
11HT EQUIPMENTSBI01010001010000000000000515BI0100001113
21.01od75620/2019_2020 : 315 KVA 11KV Unitized Substation;Design, fabrication, supply,installation testing commisioning of indoor type Packaged (Unitized) Substation enclosure consiting 315 kVA, 11kV/433V 3 Ph, 50 Hz, vector Dyn -11, dry type, Transformer with IP23 enclosure, winding temperature alarm and trip, necessary louvers,all standard fittings and accessories, LV chamber suitable for termination of 300sq mm cables, necessary power and control cabling for alarm, tripping indication, all required internal cabling etc complete and as per specifications in all respects.The rate shall be inclusive of all materials, lead, lift etc. complete as per single line diagram technical specification. Minor civil works included in the scope. HT Compartment 11kV, 630A, 21kA VCB for 3 sec with spring charging motor rated for 230V AC , tripping coil and closing coil rated for 24V DC-1 No. 630 Amp continously rated Al busbar Self powered microprocessor based three phase over current and earthfault relay with protection CTs - 1 set Transformer Compartment315 kVA, 11kV/433V 3 Ph, 50Hz, dry type, vector Dyn -11 Transformer, copper wound, laser scribed core, Class F insulation, indoor distribution Transformer with forced cooling. The transformer shall have Delta on HV side and Star on LV side with off load tap changer range: + 5% to -5% in steps of 2.5%. The transformer shall also have suitable enclosure including supply and fixing of neutral CT of 100/5A 15VA 5P10 on earthed star point with connector for connection to Earth Fault relay in HT/LT LT Chamber Suitable for terminating LT XLPE cables. The rate quoted shall be inclusive of required foundation, mounting etc.BI01010001010000000000000515BI01000011141no
31.02od75621/2019_2020 : 11kV Outdoor RMU panel-1 (Extensible Type) Design, Fabrication, Supply, Installation Testing and Commissioning of 11KV electrically Operated 21kA for 3 sec, 630A SF6 Insulated,Ring Main Unit outdoor type (IP-54) with 2 nos Load break switch as incomer and 1 no motorized VCB (fully rated earth switch) with fully encapsulated vacuum interrupter panel as outgoings, 630 Amp continously rated Cu busbar complete with all accessories, protective relays, indicators,battery and battery charger, Manometer for indicating SF6 gas pressure with green zone marked on the scale,provision for padlocking for open, close, earth and test position etc. on a suitable foundation. The RMU must be both side extensible type .The rate quoted shall be inclusive of required foundation, mounting accessories, hoisting to its location,assembling of units,lining up, bolting the units and checking all control wiring complete as per single line diagram technical specification.BI01010001010000000000000515BI01000011152no
41.03od75622/2019_2020 : 11kV Outdoor RMU panel-2 (Extensible Type) Design, Fabrication, Supply, Installation Testing and Commissioning of 11KV electrically Operated 21kA for 3 sec, 630A SF6 Insulated,Ring Main Unit outdoor type (IP-54) with 2 nos Load break switch as incomer and 2 nos motorized VCB (fully rated earth switch) with fully encapsulated vacuum interrupter panel as outgoings, 630 Amp continously rated Cu busbar complete with all accessories, protective relays, indicators,battery and battery charger, Manometer for indicating SF6 gas pressure with green zone marked on the scale,provision for padlocking for open, close, earth and test position etc. on a suitable foundation. The RMU must be both side extensible type .The rate quoted shall be inclusive of required foundation, mounting accessories, hoisting to its location,assembling of units,lining up, bolting the units and checking all control wiring complete as per single line diagram technical specification.BI01010001010000000000000515BI01000011161no
51.04od75623/2019_2020 : HT Meteing Kiosk with Meteing Supply, installation, testing and commissioning of TOD meter KIOSK withTOD meter (with RS485 communication facility), CT(0.2S) and PT(0.2) ,test terminal block, control fuses,armoured copper cable between CT PT unit. The KIOSK shall be made out of 2mm thick CRCA sheet steel, totally enclosed, IP 65 with canopy, weather proof,undergone seven tank process,powder coated finish ,earthing,entire civil work including suitable foundation and all mounting accessories as required complete as per the rquirement of State Electricity Board. The metering cubicle shall have glass window for meter reading. 11kV, 21 kA, 630A Load Break Switch with earth switch - 1 no HT HRC fuse 50A - 3 nos Seal off Bushing - 1 set 11kV Outdoor CT(0.2S) and 11kV/110V PT(0.2) units-1set 30/5A ,110V Class 0.2s TOD meter- 1no Shunt trip coil, 230V AC - 1 set Space heater with thermostat - 1 set Suitably rated Aluminium busbars and support insulators ON-OFF indication- 1 set The rate is inclusive of transportation, insurance, lift, lead and all associated works. The panel shall be with bottom entry to receive incoming outgoing cable, all necessary interconnection accessories as per particular specification single line diagram.BI01010001010000000000000515BI01000011171no
61.05od75624/2019_2020 : Supplying and filling the proposed yard with 40 mm size blue jelly of 150 mm thick including cost and conveyance of all materials, labour charges etc. complete.BI01010001010000000000000515BI01000011183.6cum
71.06od75625/2019_2020 : 11 kV DP structure Supply, Installation testing and commissioning of 11 KV DP structure using 200x100 mm ISMB for poles and cross channel of ISMC 100x50mm and supporting structure for 11 KV components with 65x65x6 mm MS angle bracings between consumer and supplier structure,cross arms,11 KV pin,disc and stay insulators, supports, jumpering / interconnecting conductors with '0'SWG Cu, anticlimbig arrangement using barbed wire,earthing etc. on a suitable concrete foundation including the civil foundation .The DP structure shall consists of the following (Note:All the MS items shall be hot dip galvanised) 11 KV,400A ,TP,AB switch - 1 No. 11 KV Lighting Arrestor -1 set of 3 Nos 11 KV DO fuses-1 set of 3 NosBI01010001010000000000000515BI01000011191no
81.07od75629/2019_2020 : 200 KVA 11KV Unitized Substation Design, fabrication, supply,installation testing commisioning of indoor type Packaged (Unitized) Substation enclosure consiting 200 kVA, 11kV/433V 3 Ph, 50 Hz, vector Dyn -11, dry type, Transformer with IP23 enclosure, winding temperature alarm and trip, necessary louvers,all standard fittings and accessories, LV chamber suitable for termination of 300sq mm cables, necessary power and control cabling for alarm, tripping indication, all required internal cabling etc complete and as per specifications in all respects.The rate shall be inclusive of all materials, lead, lift etc. complete as per single line diagram technical specification. Minor civil works included in the scope. HT Compartment 11kV, 630A, 21kA VCB for 3 sec with spring charging motor rated for 230V AC , tripping coil and closing coil rated for 24V DC-1 No. 630 Amp continously rated Al busbar Self powered microprocessor based three phase over current and earthfault relay with protection CTs - 1 set Transformer Compartment 200 kVA, 11kV/433V 3 Ph, 50Hz, dry type, vector Dyn -11 Transformer, copper wound, laser scribed core, Class F insulation, indoor distribution Transformer with forced cooling. The transformer shall have Delta on HV side and Star on LV side with off load tap changer range: + 5% to -5% in steps of 2.5%. The transformer shall also have suitable enclosure including supply and fixing of neutral CT of 75/5A 15VA 5P10 on earthed star point with connector for connection to Earth Fault relay in HT/LT LT Chamber Suitable for terminating LT XLPE cables . The rate quoted shall be inclusive of required foundation, mounting etc.BI01010001010000000000000515BI01000011202no
91.08od75636/2019_2020 : Chain link fencing :Supply, Installation testing and commissioning of 1.8 mtr high chain link fencing over 600 mm high random rubble masonry as per drawing and specification, using 4 mm thick PVC coated chain link with a framework of 50x50x6 mm MS angle between vertical posts of ISMC 75 mm at 2400 mm interval, which are fixed to the concrete footing (1:3:6) of size 450x450x300 mm (above GL) with adequate footing depth, between the RR masonry. RR masonry (450 mm thick) and 300 mm from ground level for foundation plinth in cement mortar (1:6). The random rubble masonry is to be pointed using cement mortar 1:3 to have a flush finish. Earthing as per KSEI/KSEB standards shall be done around the periphery of the fencing.The MS frame work for chain link fencing is finished using zinc chromate primer 2 coats of synthetic enamel paint. 1.5 mtr wide gate shall be provided with suitable locking arrangements.The rate shall be inclusive of all materials, labour, lead, lift, etc including excavation works and fabrication and assembly works including all nuts, bolts other miscellaneuos items, etc. complete as per drawing.BI01010001010000000000000515BI010000112120metre
102PANEL BOARD AND ACCESSORIESBI01010001010000000000000515BI0100001122
112.01od75465/2019_2020 : DG PANEL (TYPICAL)Supply, Installation, Testing Commissioning of LT Switch Board (DG PANEL) ,cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification. The Panel shall be of Form 4b Construction.Incomer160A, FP 35kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos.Meters4A, C curve SP MCB - 3 Nos.RYB indication lamp, LED type - 3 Nos.(0-500)V voltmeter, Acc. class 1 with 90 deg defl. scale - 3 Nos(0-160)A ammeter Acc. class 1 with 90 deg defl. scale - 3 Nos.160/5A 5VA class 1 resin cast CT - 3 NosDigital multi function meter with RS485 communication facility to read V,A.Hz,PF,kWH -1 Nos. Type 1&2 SPD - As mentioned in SLD. Busbar160A TPN busbar chamber with Aluminium busbar.Out goings100A,TP+NL 35kA MCCB with thermal based adjustable release with OL SC protection - 3 Nos.BI01010001010000000000000515BI01000011233no
122.02od75468/2019_2020 : SSB QUARTERS -1 (TYPICAL PANEL ) Supply, Installation, Testing Commissioning of LT Switch Board (SSB QUARTERS-1), cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing & specification.Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction.The panel shall be lockable type as per requirements of EB.Incomer160A, FP 25kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos.Busbar 415V, 25 kA, 160A TPN busbar chamber with Aluminium busbar Outgoings3 phase kWh meter - 8 No.s40A HRC fuse with fuse link - 24 nosNeutral link - 8 no. s40A, FP MCB isolator - 8 nos40A TPN /2.5A SPN Automatic current changerover with current limiter(ACCL)-8NosAll outgoing feeders should have glass window for meter reading and locking facility.BI01010001010000000000000515BI01000011245no
132.03od75473/2019_2020 : SB QUARTERS (TYPICAL PANEL ) Supply, Installation, Testing Commissioning of LT Switch Board ( SB Quarters) , cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing .Type 1&2 SPD - As mentioned in SLD. specification. The Panel shall be of Form 4b Construction.The panel shall be lockable type as per requirements of EB.Incomer320A, FP 35kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos.Busbar 415V, 25 kA, 320A TPN busbar chamber with Aluminium busbar Outgoings160A,TPN SDFU with necessary fuses - 2 No160/5 A 5 VA Class 1 CTs -3 NosThree Phase kWH meter-1 No, 160A FP MCCB Isolator - 1 No. 160A cutout fuse with fuse link and neutral link - 3 Nos. Necessary outgoing feeders should have glass window for meter reading and all outgoing feeders shall have locking facility.BI01010001010000000000000515BI01000011254no
142.04od75475/2019_2020 : COMMON PANEL (TYPICAL)Supply, Installation, Testing Commissioning of LT Switch Board (Common Panel) ,cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification..Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction.Incomer 100A,FP 25kA MCCB with thermal based adjustable release with OL SC protection - 2 Nos.100A, FP ATS with inbuilt power pack- 1 NosBusbar 415V, 25 kA, 100A TPN busbar chamber with Aluminium busbar Meters(0-500)V Class 1 with 90 deg defl. Scale with voltmeter selector switch-2 NosDigital multi function meter with RS485 communication facility to read V,A.Hz,PF,kWH -2 NosRYB Indicating lamps LED type - 6 Nos.Ammeter (0- 100) A - 6 NosON/OFF/ TRIP Indicaion lamp - 2 setOutgoings40A, TP+NL MCCB with thermal release and neutral link ( Ics = 100% Icu = 16kA) - 1Nos63A, FP , MCB ISOLATOR - 1 No63A, TP+NL MCCB with thermal release and neutral link ( Ics = 100% Icu = 16kA) - 4 NosBI01010001010000000000000515BI01000011269no
152.05od75479/2019_2020 : MSB (Teaching Quarters 2 BHK )Supply, Installation, Testing Commissioning of LT Switch Board, MSB cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be lockable type as per requirements of EB.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification. .Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction.630A,FP 50kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos.630A TPN busbar chamber with Aluminium busbar.Out goings3 phase 4 wire 415V, kWH meter -2 Nos100/5 A 5 VA Class 1 CTs -6 Nos100A HRC fuse with fuse link - 6 nosNeutral link - 2 nos 100A, TPN MCCB Isolator - 2 No400A TPN SDFU with necessary fuses - 2 NoNecessary outgoing feeders should have glass window for meter reading and all outgoing feeders shall have locking facility. Necessary relays for protection of transformer, control cabling etc. is in the scope.BI01010001010000000000000515BI01000011271no
162.06od75482/2019_2020 : MSB (Non Teaching staff Quarters (2 BHK) -No.3)Supply, Installation, Testing Commissioning of LT Switch Board (MSB-Non Teaching staff Quarters (2 BHK) No.3), cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc. .The panel shall be lockable type as per requirements of EB.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification. .Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction.Incomer160A,FP 25kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos.Busbar 415V,160A TPN busbar chamber with Aluminium busbar Outgoings63A HRC fuse with fuse link - 3 nos40A HRC fuse with fuse link - 24 nosNeutral link - 9 nos 40A, FP MCB isolator - 8 nos63A, FP MCB isolator - 1 nos3 phase 4 wire 415V, kWH meter -9 Nos40A TPN /2.5A SPN Automatic current changerover with current limiter(ACCL)-8Nos.Necessary relays for protection of transformer, control cabling etc. is in the scope.Necessary outgoing feeders should have glass window for meter reading and all outgoing feeders shall have locking facility.BI01010001010000000000000515BI01000011281no
172.07od75487/2019_2020 : SB PANEL- HOSTEL (TYPICAL)Supply, Installation, Testing Commissioning of LT Switch Board( SB Panel - HOSTEL ), cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification. .Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction.The panel shall be lockable type as per requirements of EB.Incomer250A,FP 35kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos.Busbar 415V, 25 kA, 250A TPN busbar chamber with Aluminium busbar Meters4A,C curve SP MCB-3nosRYB Indicating lamps LED type -3 Nos.(0-500)V Class 1 with 90 deg defl. Scale-3 Nos(0-250)A Class 1 with 90 deg defl. Scale-3 Nos250/5 A 5 VA Class 1 CTs -3 NosDigital multi function meter with RS485 communication facility to read V,A.Hz,PF,kWH -1 Nos.Outgoing100A, 25kA, TP+NL MCCB with thermal release and neutral link (Ics = 100% Icu = 25kA) - 2 Nos63A, 25kA, TP+NL MCCB with thermal release and neutral link (Ics = 100% Icu = 25kA) - 3 NosBI01010001010000000000000515BI01000011294no
182.08od76820/2019_2020 : SSB QUARTERS-2 ( TYPICAL) Supply, Installation, Testing Commissioning of LT Switch Board (SSB QUARTERS-2), cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification..Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction..The panel shall be lockable type as per requirements of EB. Incomer 160A, FP 25kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos. Busbar 415V, 25kA, 160A TPN busbar chamber with Aluminium busbar Outgoings 40A HRC fuse with fuse link - 21 nos Neutral link - 7 nos 40A, FP MCB isolator - 7no 3 phase 4 wire direct reading type, 415V kWH meter- 7 No. Necessary outgoing feeders should have glass window for meter reading and all outgoing feeders shall have locking facility.BI01010001010000000000000515BI01000011302no
192.09od76821/2019_2020 : MSB- HOSTEL (TYPICAL) Supply, Installation, Testing Commissioning of LT Switch Board(MSB- HOSTEL), cubicle type, made out of 2mm thick CRCA sheet,totally enclosed, IP 42, free standing, floor mounting, dust and vermin proof, indoor, compartmentalised, suitable for operation on 3 phase , 415 V, 50Hz AC system with busbars , including internal wiring with suitable size HFFR wires/cable, interconnection, duly powder coated with seven tank process etc.The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel (required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing specification..Type 1&2 SPD - As mentioned in SLD. The Panel shall be of Form 4b Construction. Incomer 400A,FP 35kA MCCB with thermal based adjustable release with OL SC protection - 1 Nos. Busbar 400A TPN busbar chamber with Aluminium busbar Meters 4A,C curve SP MCB-3 Nos RYB Indicating lamps LED type -3 Nos. (0-500)V Class 1 with 90 deg defl. Scale-3 Nos (0-400)A Class 1 with 90 deg defl. Scale-3 Nos 400/5 A 5 VA Class 1 CTs -6 Nos Digital multi function meter with RS485 communication facility to read V,A.Hz,PF,kWH -1 Nos Outgoings 250A TP+NL Moulded Case Circuit Breaker with thermal release and neutral link (Ics =100%Icu= 25KA).- 3 Nos 100 A TP+NL Moulded Case Circuit Breaker with thermal release and neutral link (Ics =100%Icu= 25KA).- 1 NosBI01010001010000000000000515BI01000011312no
202.1od76827/2019_2020 : 40 kVAR APFC PANEL (TYPICAL) "Supply, Installation, Testing and Commissioning of totally enclosed, free standing, floor mounting, dust and vermin proof,form 3 b construction, cubicle type capacitor panel board of total 40 KVAR capacity to be fabricated out of 2mm thick CRCA sheet steel Powder coated with provision for capacitor mounted inside the panel with adequate number of louvers, internal wiring with suitavle wires and powder coated with approved shade and having following components as per SLD and Technical specification .The panel shall be Top/Bottom Entry/Exit and suitable for termination of cable/Bus system as per SLD and technical specification Incomer "100A, FP, 25kA, MCCB with Thermal based release with OL SC protection - 1 Nos .Instruments 4A, C curve SP MCB, Ammeters, Voltmeters, Selector Switches,Multifunction Meters Indication Lamps, CTs , IPFC Relay as per SLD . Busbar 100A TPN AL BUSBAR Outgoing 32A, 25kA, TP MCCB with adjustable thermal magnetic release with OL SC protection - 5 nos. 20 kVAr capacitor duty contactor(AC6B) with illuminated ON- OFF pushbuttons (LED type) -1 No. 10 kVAr capacitor duty contactor(AC6B) with illuminated ON- OFF pushbuttons (LED type) -1 No. 5 kVAr capacitor duty contactor(AC6B) with illuminated ON- OFF pushbuttons (LED type) -1 No. 20 kVAr,480 V,50 Hz heavy duty capacitor(APP-H) with 7 % Seriesreactor - 1No 10 kVAr,480 V,50 Hz heavy duty capacitor(APP-H) with 7 % Seriesreactor - 1No 5 kVAr,480 V,50 Hz heavy duty capacitor(APP-H) with 7 % Seriesreactor - 2 No Control wiring required for no load compensation capacitor.BI01010001010000000000000515BI01000011322no
213CABLE AND CABLINGBI01010001010000000000000515BI0100001133
223.01od75448/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 3.5C 400 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.BI01010001010000000000000515BI010000113450metre
233.02od75454/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 3.5C 300 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.BI01010001010000000000000515BI0100001135100metre
243.03od75457/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 3.5C 240 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.BI01010001010000000000000515BI0100001136395metre
253.04od75461/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 3.5C 185 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.BI01010001010000000000000515BI0100001137490metre
263.05od77633/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured Aluminium conductor cable conforming to IS 7098 (Part 1) amended upto date. 3.5C 120sqmm cableBI01010001010000000000000515BI0100001138240metre
273.06od75466/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 3.5C 70 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.BI01010001010000000000000515BI0100001139789metre
283.07od75469/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 4C 35 Sqmm Aluminium conductor cable conforming to IS 7098 (Part 1) amended upto date.BI01010001010000000000000515BI0100001140805metre
293.08od75474/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 4C 16 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.BI01010001010000000000000515BI01000011413130metre
303.09od75476/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 4C 10 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.BI01010001010000000000000515BI0100001142280metre
313.1od75485/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 2C 6sqmm AlBI01010001010000000000000515BI0100001143958metre
323.11od75490/2019_2020 : Supply of following size 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured Aluminium /copper conductor cable conforming to IS 7098 (Part 1) amended upto date. 4C 2.5sqmm CuBI01010001010000000000000515BI01000011441754metre
333.12od77635/2019_2020 : Supply of following sizes of XLPE insulated PVC sheathed, FRLS , Aluminium conductor armoured power cable of 11 KV grade conforming to IS 7098 amended upto date.. 12C 2.5 Sq.mm AlBI01010001010000000000000515BI0100001145435metre
343.139.1.1 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.2 X 6 sq. mm (19mm)BI01010001010000000000000515BI0100001146164set
353.149.1.35 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 35 sq. mm (32mm)BI01010001010000000000000515BI010000114766set
363.159.1.23 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 70 sq. mm (38mm)BI01010001010000000000000515BI010000114832set
373.169.1.27 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 185 sq. mm (57mm)BI01010001010000000000000515BI010000114932set
383.179.1.25 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2 X 120 sq. mm (45mm)BI01010001010000000000000515BI01000011506set
393.189.1.29 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 240 sq. mm (62mm)BI01010001010000000000000515BI010000115110set
403.199.1.30 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 300 sq. mm (70mm)BI01010001010000000000000515BI01000011528set
413.29.1.31 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.3 1/2X 400 sq. mm (82mm)BI01010001010000000000000515BI01000011532set
423.219.1.32 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 10 sq. mm (25mm)BI01010001010000000000000515BI010000115420set
433.229.1.33 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required.4 X 16 sq. mm (28mm)BI01010001010000000000000515BI0100001155250set
443.23od75503/2019_2020 : Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed copper conductor cable of 1.1 kV grade as required. 4C 2.5 sqmm CuBI01010001010000000000000515BI010000115678no
453.24od75505/2019_2020 : Supplying and making end termination with brass compression gland and aluminium/Copper lugs for following size of XLPE insulated PVC sheathed aluminium/copper conductor cable of 1.1 kV grade as required. 3C 4sqmm AlBI01010001010000000000000515BI010000115776no
463.25od77788/2019_2020 : Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 KV grade as required. 12 C X 2.5 sq. mmBI01010001010000000000000515BI010000115814set
473.267.1.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Upto 35 sq. mmBI01010001010000000000000515BI01000011591403.5metre
483.277.1.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 35 sq. mm and upto 95 sq. mmBI01010001010000000000000515BI0100001160395metre
493.287.1.3 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 95 sq. mm and upto 185 sq. mmBI01010001010000000000000515BI0100001161300metre
503.297.1.4 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 185 sq. mm and upto 400 sq. mmBI01010001010000000000000515BI0100001162280metre
513.37.2.1 : Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Upto 35 sq. mmBI01010001010000000000000515BI0100001163670metre
523.317.2.4 : Laying of one number additional PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size direct in ground in the same trench in one tier horizontal formation including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 185 sq. mm and upto 400 sq. mmBI01010001010000000000000515BI010000116440metre
533.327.5.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Upto 35 sq. mmBI01010001010000000000000515BI0100001165520metre
543.337.5.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 35 sq. mm and upto 95 sq. mmBI01010001010000000000000515BI010000116630metre
553.347.5.3 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 95 sq. mm and upto 185 sq. mmBI01010001010000000000000515BI01000011675metre
563.357.5.4 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required. Above 185 sq. mm and upto 400 sq. mmBI01010001010000000000000515BI010000116825metre
573.367.6.1 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Upto 35 sq. mmBI01010001010000000000000515BI0100001169150metre
583.377.6.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 35 sq. mm and upto 95 sq. mmBI01010001010000000000000515BI010000117020metre
593.387.6.4 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size in the existing masonry open duct as required.Above 185 sq. mm and upto 400 sq. mmBI01010001010000000000000515BI01000011715metre
603.397.7.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Upto 35 sq. mm (clamped with 1mm thick saddle)BI01010001010000000000000515BI01000011721674metre
613.47.7.2 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)BI01010001010000000000000515BI0100001173104metre
623.417.7.3 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)BI01010001010000000000000515BI0100001174145metre
633.427.7.4 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)BI01010001010000000000000515BI010000117576metre
643.437.8.1 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Upto 35 sq. mm (clamped with 1mm thick saddle)BI01010001010000000000000515BI01000011764594metre
653.447.8.2 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp)BI01010001010000000000000515BI0100001177240metre
663.457.8.3 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 95 sq. mm and upto 185 sq. mm (clamped with 25/40x3mm MS flat clamp)BI01010001010000000000000515BI0100001178280metre
673.467.8.4 : Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on cable tray as required.Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp)BI01010001010000000000000515BI0100001179136metre
683.4714.13.1 : Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required50 mm diaBI01010001010000000000000515BI010000118085metre
693.4814.13.3 : Providing, laying and fixing following dia G.I. pipe (medium class) in ground complete with G.I. fittings including trenching (75 cm deep)and re-filling etc as required100 mm diaBI01010001010000000000000515BI010000118195metre
703.49od75517/2019_2020 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanization thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.l. suspenders including G.l. bolts nuts, etc. as required. 300 mm width X 50 mm depth X 1.6 mm thicknessBI01010001010000000000000515BI0100001182700metre
713.5od75518/2019_2020 : Supplying and installing following size of perforated Hot Dipped Galvanised Iron cable tray (galvanization thickness not less than 50 microns) with perforation not more than 17.5%, in convenient sections, joined with connectors, suspended from the ceiling with G.l. suspenders including G.l. bolts nuts, etc. as required. 150 mm width X 50 mm depth X 1.6 mm thicknessBI01010001010000000000000515BI0100001183400metre
723.517.10 : Supplying and fixing cable route marker with 10 cm X 10 cm X 5 mm thick G.I. plate withinscription there on, bolted /welded to 35 mm X 35 mm X 6 mm angle iron, 60 cm long and fixingthe same in ground as required.BI01010001010000000000000515BI010000118449no
733.52od75519/2019_2020 : Providing fixing Fire Barrier mortar with minimum 2 hours fire rating when tested in accordance with BS 476 part 20 and UL 1479 for horizontal openings in fire rated floors or slabs and vertical openings in walls for passing service shafts. The service lines could be of various types like electrical cables trays, metal pipes, GI Ducts for AC, etc.The mortar shall have minimum hardened density of 0.8 g/cm3 and It should have a compressive strength of 2.9N/Sq mm . The product shall be Smoke Air Seal and 30 years Age tested as per Dafstb and DIBT standards. The product shall be tested and approved by third party agencies such as UL and FM. The mortar should be tested in accordance with IEC 60068-2-57:1999-11 (Environmental Testing) as per Part 2-57: Test for Vibration-Time-history method and VERTEQII for seismic zone 4. The product shall bear the UL and FM approval logo on the packing where applicable.BI01010001010000000000000515BI010000118510sqm of door area
743.53od75520/2019_2020 : Supply, fabricating and installing MS items such as Tees/ angles/ channels etc. on floor/ ceiling/ wall including necessary civil work such as grouting, finishing etc. and painting with two coats of primer and two coats of synthetic enamel paint as requiredBI01010001010000000000000515BI0100001186500kg
753.5410.4.4 : Supplying and making indoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required:300 sq. mmBI01010001010000000000000515BI01000011873each
763.5510.5.4 : Supplying and making outdoor cable end termination with heat shrinkable jointing kit complete with all accessories including lugs suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mmBI01010001010000000000000515BI01000011888each
773.5610.6.4 : Supplying and making straight through cable jointing with heat shrinkable jointing kit complete with all accessories including ferrules suitable for following size of 3 core, XLPE aluminium conductor cable of 11 KV grade as required :300 sq. mmBI01010001010000000000000515BI01000011892each
783.578.1.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size direct in ground including excavation, sand cushioning, protective covering and refilling the trench etc as required.Above 120 sq. mm and upto 400 sq. mmBI01010001010000000000000515BI0100001190700metre
793.588.3.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing RCC/ HUME/ METAL pipe as required.Above 120 sq. mm and upto 400 sq. mmBI01010001010000000000000515BI010000119170metre
803.598.4.2 : Laying of one number PVC insulated and PVC sheathed / XLPE power cable of 11 KV grade of following size in the existing masonry open duct as required.Above 120 sq. mm and upto 400 sq. mmBI01010001010000000000000515BI010000119250metre
813.6od75521/2019_2020 : Supply of following sizes of XLPE insulated PVC sheathed, FRLS , Aluminium conductor armoured power cable of 11 KV grade conforming to IS 7098 amended upto date. 3C X 300 sq.mm.BI01010001010000000000000515BI0100001193820metre
823.61od75522/2019_2020 : Supply of 1.1 KV grade XLPE insulated, PVC sheathed, FRLS , armoured 3C 4 Sq.mm Aluminium conductor cable conforming to IS 7098 (Part 1) amended up to date.BI01010001010000000000000515BI01000011941704metre
833.62od77645/2019_2020 : Providing, laying and fixing following dia RCC pipe NP 4 class (heavy duty) in ground complete with RCC collars, jointing with cement mortar 1:2 (1 cement : 2 fine sand) including trenching upto 1.5 m depth and refilling etc. as required. 300 mm diaBI01010001010000000000000515BI010000119590metre
843.63od77787/2019_2020 : Supply and fixing of chequered plate of 6 mm thick including cutting to required size using gas cutter and lay the same over the trench, fixing of nosing angle and supports for chequered plate, related civil works, finishing etc. and painting with two coats of enamel paint over one coat of Zinchromate primer as required.BI01010001010000000000000515BI0100001196550.12kg
854WIRING AND ACCESSORIESBI01010001010000000000000515BI0100001197
864.011.10.3 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group CBI01010001010000000000000515BI01000011982592point
874.021.10.1 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group ABI01010001010000000000000515BI0100001199720point
884.031.10.2 : Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.Group BBI01010001010000000000000515BI0100001200618point
894.041.11 : Wiring for twin control light point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed medium class PVC conduit, 2 way modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm. FRLS PVC insulated copper conductor single core cable etc as required.BI01010001010000000000000515BI010000120186point
904.051.14.1 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2x1.5 sq.mm + 1x1.5 sq.mm earth wireBI01010001010000000000000515BI010000120212391.5metre
914.061.14.2 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2X 2.5 sq. mm + 1 X 2.5 sq. mm earth wireBI01010001010000000000000515BI010000120319920.4metre
924.071.14.3 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 4 sq. mm + 1 X 4 sq. mm earth wireBI01010001010000000000000515BI01000012048366metre
934.081.14.4 : Wiring for circuit/ submain wiring alongwith earth wire with the following sizes of FRLS PVC insulated copper conductor, single core cable in surface / recessed medium class PVC conduit as required2 X 6 Sq.mm + 1 x 6 sq.mm earth wireBI01010001010000000000000515BI01000012051200metre
944.091.24.1 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.5/6 amps switchBI01010001010000000000000515BI010000120610each
954.11.24.2 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.2 way 5/6 amps switchBI01010001010000000000000515BI010000120710each
964.111.24.3 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.15/16 amp switchBI01010001010000000000000515BI0100001208256each
974.121.24.4 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.3 pin 5/6 amp socket outletBI01010001010000000000000515BI010000120910each
984.131.24.5 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.6 pin 15/16 amp socket outletBI01010001010000000000000515BI0100001210256each
994.141.24.6 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Telephone socket outletBI01010001010000000000000515BI010000121173each
1004.151.24.7 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.TV antenna socket outletBI01010001010000000000000515BI010000121273each
1014.161.24.8 : Supplying and fixing following modular switch/ socket on the existing modular plate & switch box including connections but excluding modular plate etc. as required.Bell pushBI01010001010000000000000515BI010000121368each
1024.171.55.3 : Wiring for group controlled (looped) light point/fan point/exhaust fan point/ call bell point ( without independent switch etc.) with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable in surface/ recessed PVC conduit, and earthing the point with 1.5 sq. mm FRLS PVC insulated copper conductor single core cable etc. as required.Group CBI01010001010000000000000515BI0100001214447point
1034.181.21.1 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.20 mmBI01010001010000000000000515BI0100001215440metre
1044.191.21.2 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.25 mmBI01010001010000000000000515BI0100001216510metre
1054.21.21.3 : Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/ recess including cutting the wall and making good the same in case of recessed conduit as required.32 mmBI01010001010000000000000515BI0100001217405metre
1064.211.25 : Supplying and fixing two module stepped type electronic fan regulator on the existing modular plate switch box including connections but excluding modular plate etc. as required.BI01010001010000000000000515BI01000012181028each
1074.221.27.1 : Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc as required.1 or 2 Module (75mmX75mm)BI01010001010000000000000515BI01000012191784each
1084.231.31 : Supplying and fixing suitable size GI box with modular plate and cover in front on surface or inrecess, including providing and fixing 3 pin 5/6 amps modular socket outlet and 5/6 ampsmodular switch, connection etc. as required. (For light plugs to be used in non residential buildings).BI01010001010000000000000515BI01000012201951each
1094.241.32 : Supplying and fixing suitable size GI box with modular plate and cover in front on surface or in recess, including providing and fixing 6 pin 5/6 & 15/16 amps modular socket outlet and 15/16 amps modular switch, connection etc. as required.BI01010001010000000000000515BI0100001221229each
1104.251.17.3 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 X 1.5 sq.mmBI01010001010000000000000515BI0100001222440metre
1114.261.17.12 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 2.5 sq. mmBI01010001010000000000000515BI0100001223510metre
1124.271.17.21 : Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface / recessed steel/ PVC conduit as required.3 x 4 sq. mmBI01010001010000000000000515BI0100001224405metre
1134.281.38 : Supplying and fixing call bell/ buzzer suitable for single phase, 230 volts, complete as required.BI01010001010000000000000515BI010000122568each
1145MCBs AND MCB DISTRIBUTION BOARDSBI01010001010000000000000515BI0100001226
1155.012.11 : Supplying and fixing single pole blanking plate in the existing MCB DB complete etc. as required.BI01010001010000000000000515BI010000122790each
1165.022.16 : Supplying and fixing DP sheet steel enclosure on surface/ recess along with 25/32amps 240 volts \"C\" curve DP MCB complete with connections, testing and commissioning etc. as required.BI01010001010000000000000515BI010000122822each
1175.03od75489/2019_2020 : Supply and fixing outdoor type START/STOP (2way) push button station (IP65) including all the necessary accessories as required complete with suitable mounting arrangement.(Cat No Hensel-PBS 0201 or equivalent approved make)BI01010001010000000000000515BI010000122936no
1185.042.10.1 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Single poleBI01010001010000000000000515BI01000012301838each
1195.052.10.4 : Supplying and fixing 5 amps to 32 amps rating, 240/415 volts, \"C\" curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required.Triple poleBI01010001010000000000000515BI010000123162each
1205.06od75500/2019_2020 : Supply and fixing of 40A DP Isolator in sheet steel enclosure with all other accessories as required completeBI01010001010000000000000515BI010000123218each
1215.07od78173/2019_2020 : Supplying and fixing following rating, four pole, 415 volts, MCCB in the existing DB complete with connections, testing and commissioning etc. as required. 100A FP MCCB 16 kABI01010001010000000000000515BI01000012333no
1225.08od78174/2019_2020 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required. (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 6 way (8 + 18), Double doorBI01010001010000000000000515BI01000012348no
1235.09od78175/2019_2020 : Supplying and fixing following ways surface/ recess mounting, vertical type, 415 volts, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of160 amps tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB., with provision of 100/125 amps TP 16 KA MCCB as incomer, interconnection between incomer MCCB and bus bars (but without MCB./ MCCB) as required . (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 6 WayBI01010001010000000000000515BI01000012352no
1245.12.3.2 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator8 way, Double doorBI01010001010000000000000515BI010000123618each
1255.112.3.4 : Supplying and fixing following way, single pole and neutral, sheet steel, MCB distribution board, 240 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCBIRCCB/Isolator16 way, Double doorBI01010001010000000000000515BI01000012372each
1265.12od75502/2019_2020 : Supplying and fixing 40 amps to 63 amps rating, 240/415 volts, "C.curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. Triple poleBI01010001010000000000000515BI010000123854each
1275.13od75504/2019_2020 : Supply installation, testing and commissioning of DOL starter upto 5HP,3ph motor including auxilliary contactors, 2kVAR capacitor and all necessary accessories as required complete with single phase preventor, function indiaction etc.BI01010001010000000000000515BI010000123936no
1285.14od75506/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 2 pole 25 amps. (230 Volts),30mA sensitivity.BI01010001010000000000000515BI010000124018no
1295.15od75507/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 40 amps. (415 Volts),30mA sensitivity.BI01010001010000000000000515BI0100001241103no
1305.16od75508/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 40 amps. (415 Volts),100mA sensitivity.BI01010001010000000000000515BI01000012424no
1315.17od75509/2019_2020 : Supply and fixing of following rating residual current circuit breaker with MCB having earth leakage and overload protection (RCCB+MCB) as per specification as required 4 pole 63 amps. (415 Volts),100mA sensitivity.BI01010001010000000000000515BI010000124322no
1325.18od75510/2019_2020 : Supplying and fixing of following ways surface/ recess mounting, horizontal type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required • 8 way (8 + 24), Double doorBI01010001010000000000000515BI010000124436no
1335.19od75512/2019_2020 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required • (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 8 way (8 + 24), Double doorBI01010001010000000000000515BI010000124510no
1345.2od75515/2019_2020 : Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 volts, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/Isolator) 4 way (8 + 12), Double doorBI01010001010000000000000515BI010000124671no
1355.21od75516/2019_2020 : Supplying and fixing of following ways surface/ recess mounting, vertical type, 415 V, TPN MCB distribution board of sheet steel, dust protected, duly powder painted, inclusive of 200 A tinned copper bus bar, common neutral link, earth bar, din bar for mounting MCB's (but without MCB's and incomer ) as required • (Note : Vertical type MCB TPDB is normally used where 3 phase outlets are required.) 4 way (8 + 12), Double doorBI01010001010000000000000515BI01000012474no
1365.22od78144/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for 12 way double door horizontal type SPN DBBI01010001010000000000000515BI01000012482no
1375.23od78145/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for 4 way double door horizontal type TPN DBBI01010001010000000000000515BI010000124971no
1385.24od78146/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for 8 way double door horizontal type TPN DBBI01010001010000000000000515BI010000125036no
1395.25od78147/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for 6 way Vertical TPN DB (MCCB incomer)BI01010001010000000000000515BI01000012512no
1405.26od78148/2019_2020 : Supply and fixing of following way IP 43 rated cable end box with all accessories as required compete for suitable DB Cable end box for vertical TPN DB (MCB incomer)BI01010001010000000000000515BI010000125222no
1415.27od78172/2019_2020 : Supplying and fixing following way,cable end box with all accessories as required compete for the following DBs-8 way double door horizontal type SPN DBBI01010001010000000000000515BI010000125318no
1426LIGHT FIXTURES AND FANSBI01010001010000000000000515BI0100001254
1436.011.50.1 : Installation of exhaust fan in the existing opening, including making good the damage connection testing, commissioning etc. as required.Upto 450 mm sweepBI01010001010000000000000515BI0100001255389each
1446.02od75449/2019_2020 : Installation, testing and commissioning of LED down lighter fittings on false ceiling with all mounting accessories as required complete including interconnections using 3 runs of 1.5 sqmm FRLS PVC insulated stranded copper conductor as required.BI01010001010000000000000515BI0100001256580each
1456.03od75452/2019_2020 : Supply and fixing of 12W LED lamp in the angle holder including all necessary accessories and connections as required complete suitable for 230V, 50 Hz, AC supplyBI01010001010000000000000515BI0100001257444no
1466.04od75462/2019_2020 : Supply of LED Street Lighting luminaire of IP65 protected, pressure die cast aluminium housing body with optimal heat sink, with system wattage less than 40 (+/-5)W with rated life of L70 @ 50,000 hours, CRI greater than or equal to 70 and system efficacy greater than or equal to 90%. The luminaire shall be mounted on GI pipe with 0.5m overhang and necessory accessories and connection.Make Wipro skyline LR02-451-XXX-57-XX or CG LSTS-40-CDL or equivalent approved makeBI01010001010000000000000515BI010000125832no
1476.05od75464/2019_2020 : Supply of LED surface mounted down light made of die cast aluminium with proper diffusers, along with driver,system wattage of 18+/-2 Watts,lumen output of lamp greater than 1800 lumens, power factor > 0.9, rated life of L70 @ 50,000 hours, system efficacy greater than 100lumen/watt and including all necessary accessories as required complete.Make:- PHILIPS DN 395B LED20S-6500 PSU WH or WIPRO LD901-231-XXX-65-XX or CG LCDN-18-CDLL or equivalent approved makeBI01010001010000000000000515BI0100001259580no
1486.06od75470/2019_2020 : Supply of indoor decorative surface mounted LED Batten with High Efficiency Extruded aluminium housing and Polycarbonate Diffuser ,along with driver,system wattage of 20+/-2 Watts,lumen output of lamp greater than 1500, power factor > 0.9,rated life of L70 @ 50,000 hours, system efficacy greater than 80lumen/watt and including all the necessary accessories as required complete.Make:-PHILIPS BN021C LED20S PSU CW GR S2 or WIPRO LL20-221-XXX-65NE3 or CG LCTL 18 CDL or equivalent approved makeBI01010001010000000000000515BI01000012601515no
1496.07od75478/2019_2020 : Installation, testing and commissioning of pre - wired,LED/ fluorescent fitting/ compact fluorescent fitting of all types, complete with all accessories and tube etc. directly on ceiling/ wall, including connection with 1.5 sq.mm FRLS PVC insulated, copper conductor, single core cable and earthing etc. as required.BI01010001010000000000000515BI01000012612471each
1506.08od75484/2019_2020 : Supply of indoor decorative surface mounted LED Batten with High Efficiency Extruded aluminium housing and Polycarbonate Diffuser,along with driver,system wattage of 10+/-2 Watts,lumen output of lamp greater than 800, power factor > 0.9,rated life of L70 @ 50,000 hours, system efficacy greater than 80lumen/watt and including all the necessary accessories as required complete.Make:- PHILIPS BN 021 LED10S- 6500 PSU GR S1 or WIPRO LL20-111-XXX-65NE3 or CG LCTL 9 CDL or equivalent approved makeBI01010001010000000000000515BI0100001262476no
1516.091.45 : Installation, testing and commissioning of ceiling fan, including wiring the down rods of standardlength (upto 30 cm) with 1.5 sq. mm FRLS PVC insulated, copper conductor, single core cable,including providing and fixing phenolic laminated sheet cover on the fan box etc. as required.BI01010001010000000000000515BI01000012631028no
1526.1od75492/2019_2020 : Installation, testing and commissioning of High bay/LED/ FLOOD type fittings on wall/Column/truss/false ceiling using suitable MS clamps, nuts, bolts/ 20mm heavy duty GI chain/ pipe (upto 50cm)etc including connections with 3C 1.5 Sq.mm PVC insulated flexible copper conductor cable as required.BI01010001010000000000000515BI010000126432no
1536.111.49 : Numbering of ceiling fan / exhaust fan/ fluorescent fittings as required.BI01010001010000000000000515BI01000012654500each
1546.121.58 : Supplying and fixing PVC batten/ angle holder including connection etc. as required.BI01010001010000000000000515BI0100001266444each
1556.13od75496/2019_2020 : Supply of 250 mm sweep,900 rpm light duty exhaust fan in plastic body with self opening louvers working on 230 V AC supply complete with all accessories as required. (Crompton Brisk Air or equivalant approved make)BI01010001010000000000000515BI0100001267389no
1566.14od75497/2019_2020 : Supply of 380 mm sweep heavy duty exhaust fan indie cast aluminium with self opening louvers working on 230 V AC supply complete with all accessories as required. (Crompton EXHD-380-6-1 or equivalant approved make)BI01010001010000000000000515BI01000012685no
1576.15od75498/2019_2020 : Supply of following sizes of 1200 mm sweep. 5 star rated ceiling fan, with double ball bearing, Aluminium pressure die cast body with Aluminium blades, canopies, hanging shackle, 30 cm down rod and without speed regulator suitable for 240V 50 HZ, AC supply confirms to IS 374/1979 as required complete. (Make crompton-Entrust 50 or equivalent approved make).BI01010001010000000000000515BI01000012691028no
1586.16od75499/2019_2020 : Supply of indoor industrial surface mounted LED tube with Batten along with driver , surge protector,,system wattage of 40+/-4 Watts(2x20 watts),lumen output of lamp greater than 3000 lumen, power factor > 0.9,rated life of L70 @ 50,000 hours, system efficacy greater than 70lumen/watt and including all necessary accessories as required complete.Make:- Cat No: Wipro WIO922208 + 2 Nos. of 18W LED Tube Light or Crompton Greaves IGP132LT8-16+LT8-20BI01010001010000000000000515BI010000127036no
1597EARTHING AND SAFETY EQUIPMENTSBI01010001010000000000000515BI0100001271
1607.012.21 : Providing and fixing M.V. danger notice plate of 200 mm X 150 mm, made of mild steel, at least 2mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.BI01010001010000000000000515BI010000127240each
1617.022.22 : Providing and fixing H.T. danger notice plate of 250 mm X 200 mm, made of mild steel, at least 2mm thick, and vitreous enameled white on both sides, and with inscription in single red colour on front side as required.BI01010001010000000000000515BI01000012736each
1627.03od75444/2019_2020 : Supply and fixing single line diagram, schematic diagrams etc. of A1 size on suitable Aluminium sheet including lamination etc. as required complete on wall.BI01010001010000000000000515BI010000127410no
1637.04od75450/2019_2020 : Supply and fixing anodised aluminum glass framed shock treatment chart.BI01010001010000000000000515BI010000127510no
1647.05od75455/2019_2020 : Supplying of Rubber hand gloves suitable for 1.1 KV.BI01010001010000000000000515BI010000127610no
1657.06od75456/2019_2020 : Supply and fixing of First aid boxBI01010001010000000000000515BI010000127710no
1667.07od75459/2019_2020 : Supplying and laying 6.00 mm GI conductor (4 SWG) at 0.50 metre below ground as strip earth electrode, including onnection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm)BI01010001010000000000000515BI010000127860metre
1677.08od75467/2019_2020 : Supplying and laying 4.00 mm GI conductor (8 SWG) at 0.50 metre below ground as strip earth electrode, including onnection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm)BI01010001010000000000000515BI01000012791162metre
1687.09od75471/2019_2020 : Supplying and laying 3.15mm Cu (10 SWG) at 0.50 metre below ground as strip earth electrode, including onnection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm)BI01010001010000000000000515BI0100001280342metre
1697.1od75472/2019_2020 : Supplying and laying 32mmx6mm GI strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm)BI01010001010000000000000515BI0100001281150metre
1707.11od75477/2019_2020 : Supplying and laying 50mmx6mm GI strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt spring washer spaced at 50mm)BI01010001010000000000000515BI0100001282100metre
1717.12od75481/2019_2020 : Providing and fixing 6.00 mm GI conductor (4 SWG) on surface or in recess for connections etc. as required.BI01010001010000000000000515BI010000128330per metre
1727.13od75483/2019_2020 : Providing and fixing 4.00 mm GI conductor (8 SWG) on surface or in recess for connections etc. as required.BI01010001010000000000000515BI0100001284432per metre
1737.14od75486/2019_2020 : Supply providing 10 SWG Cu wire on surface/recess using saddlesBI01010001010000000000000515BI01000012852831per metre
1747.15od75488/2019_2020 : Providing and fixing 50mm x 6mm GI tape (2.4kg/ mtr) on surface or in recess for connections etc. as required.BI01010001010000000000000515BI010000128660per metre
1757.16od75491/2019_2020 : Supply and installation of all the materials required for maintenance free earthing system including 3 mtrs length,17.2mm dia or above 250 microns molecularly copper bonded steel rod with stainless steel connectors and fasteners for connecting earth strip, earth enhancing compound (12.5 kg mineral compound / 22.6 kg low resistivity graphite compound) and providing masonry enclosure with heavy duty CI cover plate of 300X300 mm having locking arrangement.BI01010001010000000000000515BI010000128740no
1767.175.6 : Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 metre long etc. with charcoal/ coke and salt as required.BI01010001010000000000000515BI010000128818set
1777.18od75493/2019_2020 : Supply and providing ISI marked electrical 3.3 kV grade anti-skid rubber mat(2mx1mx2mm thick ) as per IS:15652BI01010001010000000000000515BI010000128920each
1787.19od78185/2019_2020 : Supply and providing ISI marked electrical 3.3 kV grade anti-skid rubber mat as per IS:15652.forthe following sizes. 2mx1mx2.5 mm thickBI01010001010000000000000515BI01000012906no
1797.2od75494/2019_2020 : Supplying and laying 25 mm X 3 mm copper strip at 0.50 metre below ground as strip earth electrode, including connection/ terminating with nut, bolt, spring, washer etc. as required. (Jointing shall be done by overlapping and with 2 sets of brass nut bolt spring washer spaced at 50mm)BI01010001010000000000000515BI0100001291108metre
1807.21od75495/2019_2020 : Providing and fixing 25 mm X 3 mm copper strip on surface or in recess for connections etc. as required.BI01010001010000000000000515BI010000129248metre
1817.225.9 : Supplying and laying 25 mm X 5 mm G.I strip at 0.50 metre below ground as strip earthelectrode, including connection/ terminating with G.I. nut, bolt, spring, washer etc. as required.(Jointing shall be done by overlapping and with 2 sets of G.I. nut bolt & spring washer spaced at 50mm)BI01010001010000000000000515BI0100001293884metre
1827.235.15 : Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required.BI01010001010000000000000515BI0100001294447metre
1837.24od75501/2019_2020 : Providing and fixing 32 mm X 6 mm G.I. Tape (1.475 kg/mtr) on surface or in recess for connections etc. as required.BI01010001010000000000000515BI010000129542per metre
1848LIGHTNING PROTECTIONSBI01010001010000000000000515BI0100001296
1858.01od75442/2019_2020 : Supply and Fixing of 8 mm Aluminum Round Conductor as vertical down conductor with the required mounting clamps , cross connectors, T connectors , expansion piece and other accessories required as per IEC 62305-3 and DIN EN 50164-2 suitable for installation on surface as needed.BI01010001010000000000000515BI0100001297830metre
1868.02od75443/2019_2020 : Supply and Fixing of 8 mm Aluminum Round Conductor as horizontal air terminal with the required mounting clamps , cross connectors, T connectors ,glue, expansion piece and other accessories required as per IEC 62305-3 and DIN EN 50164-2 suitable for installation on sheet roofBI01010001010000000000000515BI010000129825metre
1878.03od75446/2019_2020 : Supply and Fixing of 8 mm Aluminum Round Conductor as horizontal air terminal with the required mounting clamps , cross connectors, T connectors , expansion piece and other accessories required as per IEC 62305-3 and DIN EN 50164-2 suitable for installation on parapetBI01010001010000000000000515BI0100001299800metre
1888.046.14 : Providing and laying G.l. tape 32 mm X 6 mm from earth. electrode directly in ground as required.BI01010001010000000000000515BI0100001300740metre
1898.05od75463/2019_2020 : Providing and Fixing of Test Joint , suitable to fix 8 mm Aluminium conductor to 32 X 6 GI stripBI01010001010000000000000515BI010000130149each
1909DG SETS AND ANCILLERIESBI01010001010000000000000515BI0100001302
1919.01od75963/2019_2020 : 30KVA DG SET Supply, Installation, Testing and Commissioning of outdoor 30kVA prime rated D.G Set with acoustic enclosure and Control panel ,protection and digital metering,controls and interlocks, CTs and transducers for all metering and protection and suitable FP MCCB etc. , including antivibration mountings, exhaust silencer and exhaust pipe conforming to latest environment protection regulations for emission and noise levels complete with , water/ coolant cooled, (radiator type) four stroke, electric start conforming to BS: 5514 30 KVA prime rating, brushless, self excited, self regulated and suitable for continuous operation at 1500RPM, generating 415 V+/-5% Volts at 0.8 p.f (lag), 50Hz,3 phase, 4 wire system generally conforming to BS: 2613 IS: 4722. Both Engine and Alternator shall be mounted on common channel iron base frame, and with standard accessories such as lead acid batteries and engine driven battery charger along with leads,battery stand, necessary control wiring with control cables, first fill of lubricating oil, and earthing as per standards Fuel tank , fuel piping from fuel tank to Engine, Residential silencer, suitable size Cable termination box with extended Alternator terminal with bus bars etc as required and as per specifications.Rate shall be inclusive of all the civil work including RCC foundation. The work should be as per Electrical Inspectorate/ Pollution control board standards.BI01010001010000000000000515BI01000013033no
1929.02od75964/2019_2020 : 100KVA DG SET Supply, Installation, Testing and Commissioning of outdoor 100kVA prime rated D.G Set with acoustic enclosure and Control panel ,protection and digital metering,controls and interlocks, CTs and transducers for all metering and protection and suitable FP MCCB etc. , including antivibration mountings, exhaust silencer and exhaust pipe conforming to latest environment protection regulations for emission and noise levels complete with , water/ coolant cooled, (radiator type) four stroke, electric start conforming to BS: 5514 100 KVA prime rating, brushless, self excited, self regulated and suitable for continuous operation at 1500RPM, generating 415 V+/-5% Volts at 0.8 p.f (lag), 50Hz,3 phase, 4 wire system generally conforming to BS: 2613 IS: 4722. Both Engine and Alternator shall be mounted on common channel iron base frame, and with standard accessories such as lead acid batteries and engine driven battery charger along with leads,battery stand, necessary control wiring with control cables, first fill of lubricating oil, and earthing as per standards Fuel tank , fuel piping from fuel tank to Engine, Residential silencer, suitable size Cable termination box with extended Alternator terminal with bus bars etc as required and as per specifications.Rate shall be inclusive of all the civil work including RCC foundation. The work should be as per Electrical Inspectorate/ Pollution control board standards.BI01010001010000000000000515BI01000013043no

AI Tender Summary

OUR REF NO 22842392
AUTHORITY Government Departments
TENDER VALUE 4.80 Crore
LAST DATE 30-12-2019
Authority
Authority Name Kitco Limited
Work Description Setting Up Of Medical College At Painavu Idukki Electrification Works For The Residential Facilities Setting Up Of Medical College At Painavu Idukki Electrification Works For TheResidential Facilities
Basic Detail
Tender No HFWD/KITCO/EL/06/2019
Bidding Type Tender
Location
City Painavu Idukki
State Kerala
Key Dates
Publish Date 11 Dec 2019
Submission Date 30 Dec 2019
Open Date 02 Jan 2020
Finance
Tender Value 4.80 Crore
Tender Fee 8850
EMD 1 Lakhs
Exemption Not Available
Document List
Tendernotice_1.pdf
BOQ_456669.xls
B713772E-F8A4-422D-8FA6-42405B86D79D.html
Technicalbid.pdf

Unlock Full AI Tender Summary

Get instant access to the complete AI-generated analysis — scope, eligibility, timeline & more.

Instant Access Secure Free
Your details are secure and used only for document delivery.

Tender Timeline

Dec 11, 2019
11:30 IST

Tender Published

Tender notice published.

Completed
Dec 30, 2019
17:00 IST

Bid Submission Deadline

Online submission via eProcurement portal.

Completed
Jan 02, 2020

Bid Opening Date

Technical bids will be opened and evaluated.

Completed

Tender Documents

Download All (ZIP) ↓
pdf

Tendernotice_1.pdf

xls

BOQ_456669.xls

html

B713772E-F8A4-422D-8FA6-42405B86D79D.html

pdf

Technicalbid.pdf

Disclaimer

We takes all possible care for accurate & authentic tender information. However users are requested to refer Original source of Tender Notice / Tender Document published by Tender Issuing Agency before taking any call regarding this tender