| 1 | 1 | SH-I : Supply Works \nSupply of XLPE insulated & PVC sheathed armoured aluminium conductor cable 1.1KV grade conforming to I.S : 7098 (Part-I ) with upto date ammendments .\n(a)2x25 Sq mm | | 140 | Meter |
|---|
| 2 | 2 | Supply of XLPE insulated & PVC sheathed armoured aluminium conductor cable 1.1KV grade conforming to I.S : 7098 (Part-I ) with upto date ammendments.\n(b)2x35 Sq mm | | 60 | Meter |
|---|
| 3 | 3 | Supply of XLPE insulated & PVC sheathed armoured aluminium conductor cable 1.1KV grade conforming to I.S : 7098 (Part-I ) with upto date ammendments.\n(c) 3.5x35 Sq mm | | 1100 | Meter |
|---|
| 4 | 4 | Supply of XLPE insulated & PVC sheathed armoured aluminium conductor cable 1.1KV grade conforming to I.S : 7098 (Part-I ) with upto date ammendments.\n(d)3.5x70 Sq mm | | 80 | Meter |
|---|
| 5 | 5 | Supply of XLPE insulated & PVC sheathed armoured aluminium conductor cable 1.1KV grade conforming to I.S : 7098 (Part-I ) with upto date ammendments.\n(e)3.5x240 Sq mm | | 900 | Meter |
|---|
| 6 | 6 | Supply of 1C X 6 sq mm sizes copper conductor, 5 KV grade, PVC insulated, PVC sheathed, antitermite and antirodent AFL cable generally conforming to IS 1554/ Part-II as ammended uptodate and as specified in particular specification. | | 11600 | Meter |
|---|
| 7 | 7 | Supply of 1C X 16 sq mm sizes copper conductor, 5 KV grade, PVC insulated, PVC sheathed, antitermite and antirodent AFL cable generally confirming to IS 1554/ Part-II as ammended uptodate and as specified in particular specification. | | 3200 | Meter |
|---|
| 8 | 8 | Supply of XLPE insulated & PVC sheathed armoured copper conductor control cable 1.1KV grade conforming to I.S : 7098 (Part-I ) with upto date ammendments.\n(a)61x 2.5 Sq mm | | 400 | Meter |
|---|
| 9 | 9 | Supply of 40 mm outer dia PN-6, PE80, ISI Marked HDPE Pipe conforming to IS 4984/95 with up to date ammendments complete as required. | | 285 | Meter |
|---|
| 10 | 10 | Supply of 63 mm outer dia PN-6, PE80, ISI Marked HDPE Pipe conforming to IS 4984/95 with up to date ammendments complete as required. | | 7965 | Meter |
|---|
| 11 | 11 | Supply of 110 mm outer dia PN-6, PE80, ISI Marked HDPE Pipe conforming to IS 4984/95 with up to date ammendments complete as required. | | 1060 | Meter |
|---|
| 12 | 12 | Supply of all the equipment required to provide Airfield Lighting Control and Monitoring System (ALCMS),type 'L890BB' to the requirements of FAA Advisory Circular No. AC 150 / 5345-56B (current edition) including all hardware and software, licenses & other items as required for successful operation of the system in line with the scope of work as specified in technical specifications in details. ALCAMS System shall consists of two vault processor provided both running in parallel for redundancy in operation; ATC HMI-01No., ATC computer- 02No., ATC computer software-02No., ATC Display-01No., Network Adapter-2No., Monitoring equipment-01No.( consist of Electrical vault computer, software, Electrical vault display), Vault communication network- 01Set and UPS-03 Nos. etc complete as required to make the system complete in all respect. ALCAMS System shall compatible with our existing GLF system/ Landing H/ Windcone/Power cable/earthing etc. Supply & Interconnection of power cable/control cable /data cable are in scope of this item. (Supply / laying/termination of OFC cable & HDPE pipe are not included in this item) | | 1 | Each |
|---|
| 13 | 13 | Supply of single mode ,6 core armoured OFC cable suitable for ALCMS. | | 300 | Meter |
|---|
| 14 | 14 | Supply of IACO/CAR/FAA complaint indoor type microprocessor based, air cooled, Thyristor type constant current regulator suitable for use on 240/ 415 Volt AC, 50/60 Hz input AC supply with 4 KW output power at 6.6 amps with 5 steps variation of current output suitable for local and remote control operation with 24/48 Volt DC control supply complete with multifunction digital display and digital earth leakage indication meter. It shall have over current, over voltage, earth fault protection , positive back indication equipments relay contactor etc. as required as per specifications. | | 5 | Each |
|---|
| 15 | 15 | Supply of IACO/CAR/FAA complaint indoor type microprocessor based, air cooled, Thyristor type constant current regulator suitable for use on 240/ 415 Volt AC, 50/60 Hz input AC supply with 7.50 KW output power at 6.6 amps with 5 steps variation of current output suitable for local and remote control operation with 24/48 Volt DC control supply complete with multifunction digital display and digital earth leakage indication meter. It shall have over current, over voltage, earth fault protection , positive back indication equipments relay contactor etc. as required as per specifications. | | 1 | Each |
|---|
| 16 | 16 | Supply of IACO/CAR/FAA complaint indoor type microprocessor based, air cooled, Thyristor type constant current regulator suitable for use on 240/415 Volt AC, 50/60 Hz input AC supply with 50.0 KW output power at 20 amps with 5 steps variation of current output suitable for local and remote control operation with 24/48 Volt DC control supply complete with multifunction digital display and digital earth leakage indication meter. It shall have over current, over voltage, earth fault protection , positive back indication equipments relay contactor etc. as required as per specifications. | | 2 | Each |
|---|
| 17 | 17 | Supply of 1X 6 sq mm, 5 KV grade plug and receptacle of type 1 class B connector and suitable field attachment with 5 KV grade PVC insulated PVC sheathed single core following size copper conductor cable confirming to the specified specification etc complete as required. | | 40 | Each |
|---|
| 18 | 18 | Supply of 1X 16 sq mm, 5 KV grade plug and receptacle of type 1 class B connector and suitable field attachment with 5 KV grade PVC insulated PVC sheathed single core following size copper conductor cable confirming to the specified specification etc complete as required. | | 20 | Each |
|---|
| 19 | 19 | SH-II: ITC Works \nLaying of 40 mm dia HDPE/MS Pipe direct in under ground at depth of 75 cm below ground level including soil excavation and refilling the trench etc. as required. | | 100 | Meter |
|---|
| 20 | 20 | Laying of 63/110 mm dia HDPE/MS Pipe direct in under ground at depth of 75 cm below ground level including soil excavation and refilling the trench etc. as required. | | 2183 | Meter |
|---|
| 21 | 21 | Laying of additional 40 mm dia HDPE/MS Pipe direct in underground in the same trench in one tier horizontal formation at depth of 75 cm below ground level including soil excavation and refilling the trench etc. as required. | | 100 | Meter |
|---|
| 22 | 22 | Laying of additional 63/110 mm dia HDPE/MS Pipe direct in underground in the same trench in one tier horizontal formation at depth of 75 cm below ground level including soil excavation and refilling the trench etc. as required. | | 6323 | Meter |
|---|
| 23 | 23 | Laying of HDPE Pipe (upto outer dia of 110 mm) in underground for laying of cable across taxi or runway/road at depth of upto 3 mtr through HDD Method (HDPE Pipe is to be provided by AAI). | | 520 | Meter |
|---|
| 24 | 24 | Laying/ Fixing of HDPE Pipe (upto outer dia of 63 mm) on wall/surface as required. | | 85 | Meter |
|---|
| 25 | 25 | Laying of one number PVC insulated and PVC sheathed XLPE power cable of 1.1 kV grade/ OFC / Control cable of following size in the existing RCC/ HUME/ METAL / HDPE pipe as required.\n(a)upto 35 Sq mm | | 1220 | Meter |
|---|
| 26 | 26 | Laying of one number PVC insulated and PVC sheathed XLPE power cable of 1.1 kV grade/ OFC / Control cable of following size in the existing RCC/ HUME/ METAL / HDPE pipe as required.\n(b)Above 95 Sq mm and upto 185 sq mm | | 340 | Meter |
|---|
| 27 | 27 | Laying of one number PVC insulated and PVC sheathed XLPE power cable of 1.1 kV grade/ OFC / Control cable of following size in the existing RCC/ HUME/ METAL / HDPE pipe as required.\n(c)Above 185 Sq mm and upto 400 sq mm | | 720 | Meter |
|---|
| 28 | 28 | Laying of one number PVC insulated and PVC sheathed XLPE power cable of 1.1 kV grade/ control cable of following size in the existing masonry open duct as required.\n(a)upto 35 Sq mm | | 270 | Meter |
|---|
| 29 | 29 | Laying of one number PVC insulated and PVC sheathed XLPE power cable of 1.1 kV grade/ control cable of following size in the existing masonry open duct as required.\n(b)Above 35 Sq mm and upto 95 sq mm | | 64 | Meter |
|---|
| 30 | 30 | Laying of one number PVC insulated and PVC sheathed XLPE power cable of 1.1 kV grade/ control cable of following size in the existing masonry open duct as required.\n(c)Above 95 Sq mm and upto 185 sq mm | | 40 | Meter |
|---|
| 31 | 31 | Laying of one number PVC insulated and PVC sheathed XLPE power cable of 1.1 kV grade/ control cable of following size in the existing masonry open duct as required.\n(d)Above 185 Sq mm and upto 400 sq mm | | 90 | Meter |
|---|
| 32 | 32 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.\n(a)Upto 35 sq. mm (clamped with 1mm thick saddle) | | 50 | Meter |
|---|
| 33 | 33 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.\n(b)Above 35 sq. mm and upto 95 sq. mm (clamped with 25x3mm MS flat clamp) | | 50 | Meter |
|---|
| 34 | 34 | Laying and fixing of one number PVC insulated and PVC sheathed / XLPE power cable of 1.1 KV grade of following size on wall surface as required.\n(c)Above 185 sq. mm and upto 400 sq. mm (clamped with 40x3mm MS flat clamp) | | 50 | Meter |
|---|
| 35 | 35 | Laying of one. PVC insulated and PVC sheathed/ XLPE cable of 5 KV grade size upto 16 sqmm in existing RCC/Hume/Stoneware/GI pipes /HDPE pipe as required. | | 14060 | Meter |
|---|
| 36 | 36 | Laying of one. PVC insulated and PVC sheathed/ XLPE cable of 5 KV grade size upto 16 sqmm in the existing masonry open duct as required. | | 444 | Meter |
|---|
| 37 | 37 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of XLPE armoured aluminium conductor cable of 1.1 KVgrade as required.\n(a)2x25 Sq mm | | 14 | Each |
|---|
| 38 | 38 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of XLPE armoured aluminium conductor cable of 1.1 KVgrade as required.\n(b)2x35 Sq mm | | 6 | Each |
|---|
| 39 | 39 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of XLPE armoured aluminium conductor cable of 1.1 KVgrade as required.\n(c)3.5x35 Sq mm | | 6 | Each |
|---|
| 40 | 40 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of XLPE armoured aluminium conductor cable of 1.1 KVgrade as required.\n(d)3.5x70 Sq mm | | 8 | Each |
|---|
| 41 | 41 | Supplying and making end termination with brass compression gland and aluminium lugs for following size of XLPE armoured aluminium conductor cable of 1.1 KVgrade as required.\n(e)3.5x240 Sq mm | | 4 | Each |
|---|
| 42 | 42 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.\n(a)3.5x35 Sq mm | | 3 | Each |
|---|
| 43 | 43 | Supplying and making straight through joint with heat shrinkable kit including ferrules and other jointing materials for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required.\n(b)3.5x240 Sq mm | | 2 | Each |
|---|
| 44 | 44 | Earthing with G.l. earth plate 600 mm X 600 mm X 6 mm thick including accessories, and providing masonry 'enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required. This Item does not include GI strip required from earth plate./earth electrode and up to body terminal. | | 6 | Each |
|---|
| 45 | 45 | Providing· and fixing 25 mm X 5 mm· G.l. strip in 40 mm dia G.l. pipe from earth electrode including connection with G.l. nut, bolt, spring, washer excavation and refilling etc. as required. | | 30 | Meter |
|---|
| 46 | 46 | Providing and fixing 25 mm X 5 mm GI strip on surface or in recess for connections etc. as required. | | 50 | Meter |
|---|
| 47 | 47 | Reinstallation i/c testing and commissioning of old different capacities CCR panel of CCR room in safe manner by dismantling, disconnecting the power supply/cables, safe shifting i/c loading, unloading ,positioning of these CCR panel in safe manner in new Sub Station near New ATC Tower . Works includes required minor civil work i/c providing C- chanel as per site requirement and as per direction of E-I-C. | | 6 | Each |
|---|
| 48 | 48 | Installation, Testing and Commissioning of 6/16 sqmm size plug and receptacle as required at site. | | 60 | Each |
|---|
| 49 | 49 | Supplying and making straight through joint with heat shrinkable jointing kit including ferrules and other jointing materials for 1X6 Sqmm size AFL cable of PVC/ XLPE insulated and PVC sheathed copper conductor cable of 5.0 KV grade as required. | | 28 | Each |
|---|
| 50 | 50 | Supplying and making straight through joint with heat shrinkable jointing kit including ferrules and other jointing materials for 1X16 size Sqmm AFL cable of PVC/ XLPE insulated and PVC sheathed copper conductor cable of 5.0 KV grade as required. | | 8 | Each |
|---|
| 51 | 51 | Installation, Testing and Commissioning of Airfield Lighting Control and Monitoring System (ALCMS) i/c providing C- chanel , minor civil foundation work as required and as per direction of E-I-C. | | 1 | Each |
|---|
| 52 | 52 | Installation, Testing and Commissioning of microprocessor based, air cooled, Thyristor type constant current regulator of capacity 4/7.5/50 KW i/c providing C- chanel , minor civil works as required and as per direction of E-I-C. | | 8 | Each |
|---|
| 53 | 53 | Dismantling of existing CCRs including removing all connections from CCR panel and concerned electrical panel, foundation bolts, earthing, etc., as required and shifting it to store as directed by the Engineer- in- Charge. | | 7 | Each |
|---|
| 54 | 54 | Supply & Making end termination/ connection of 6 core single mode OFC cable etc complete as required. (For ALCMS) | | 4 | Each |
|---|
| 55 | 55 | SITC of indoor type Main Essential LT panel (TTA), made out of 2 mm CRCA sheet steel, totally enclosed, minimum IP 42 protection, free standing, floor mounting, dust and vermin proof ,compartmentalised, powder coated painting suitable for operation on 3 Phase and neutral, 415V, 50 Hz AC supply system with busbars extensible on both sides, interconnections with suitable size of copper lead/ solid aluminium strips, control circuit with breaker control switch , digital type ammeter and voltmeter,LED type indicating lamps, CT's as required, suitable electrical and mechanical interlocking as required between incomers and bus couplers , panel should have continous GI earth strip of suitable size throughout the length of panel with earth terminations at both the ends ,cable alleys suitable for bottom or top entry of cables as required including supply & installation of all items as below and as per detailed specifications. Works includes required civil foundation like providing C chanel and RCC work etc as required at site. Loading &unloading,Positioning,Testing and Commissioning of panel complete as per site requirement and as per Instruction of E-I-C. \nINCOMER'S CHANGEOVER: 400 Amp ,FP, Automatic Transfer Switch -02 Nos.\nINCOMERS: 400 Amp 35KA,FP, MCCB with thermal magnetic release O/L , S/C (Ics=Icu=100 %) -02 Nos.\nBUS COUPLER: 400 Amp 35KA,FP, MCCB with thermal magnetic release O/L , S/C (Ics=Icu=100 %) -01 Nos.\nOUTGOINGS: 160 A,4P, 35 kA,MCCB with thermal magnetic release O/L , S/C (Ics=Icu=100 %) -4 Nos.\n100A,4P,35 kA,MCCB with thermal magnetic release O/L , S/C (Ics=Icu=100 %) -3 Nos.\n63A,4P, 35 kA,MCCB with thermal magnetic release O/L , S/C (Ics=Icu=100 %) -17 Nos.\nRYB indicating lamps & Digital Ammeter with Selector Switch for all Outgoings. 01 Sets\n1 Lot of control wiring & 1 Set of designation plates. \nMultifunction Meter: Digital Multifunction Meter with all normal electrical parameter i/c MD setting;KWh etc.-02 set\nIndicating lamp and Metering: RYB,ON/OFF/TRIP LED type Indicating Lamps for all Incomers & Outgoings. - 01 set\nBUS BARS: Suitable size TPN Aluminium bus bar but not less than 500 Amps. | | 1 | Each |
|---|