Kerala Minerals And Metals Limited has published Erection , Installation , Testing And Commissioning Of Pmccfor U400and Apfc Panel For Pcc2 Erection , Installation , Testingand Commissioning Of Pmccfor U400and Apfc Panel For Pcc2. Submission Date for this Tender is 13-12-2019. Power Factor Panel Tenders in TP Unit,KMML Kerala. Bidders can get complete Tender details and download the document.
Name of Work: Erection, Installation and testing of PMCC for U-400 and APFC panels for PCC-2 | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Erection, installation, testing & commissioning of floor mounting type PMCC at U-400 MCC, of dimension 2430(H) x 4460(L) x 1254 (D) mm comprising of 400A MCCB change over incomer and MCCB incomers and outgoing feeders after coupling of 3 sections as per GA drawing attached. Minor civil works and necessary fabrication works related to the work shall be done by the contractor by supplying materials required for the civil works.Panel, MS items and Cement shall be supplied by KMML. Panel shall be earthed as per standards.(Apprx 10mtr).Transportation of panles and other free issue items from central stores to U-400 MCC room is in the scope of contractor. | item1.0 | 1 | Nos. |
2 | 2 | Installation & commissioning of 300 kVAR Automatic Power Factor Correction Panel (APFC) at Substation-2 of dimension 1100 x 800 x 2175 mm comprising of 630 A Incomer MCCB, 27.5 VAR capacitors, reactors and MCCBs.Earthing shall be done as per standards to the nearest main earth (Approx. 10 M).GI Strip and APFC panels shall be supplied by KMML. All other materials required shall be supplied by the contractorMinor civil works related to the work shall be done by the contractor by supplying materials required for the civil works.Cement shall be supplied by KMML.(Lifting of the panels 600mm above ground level using civil PCC work as per the panel base dimension and removal of false sealing are included in this work.) | item2.0 | 2 | Nos. |
3 | 3 | Laying, dressing and clamping of following cables through existing and newly fabricated cable trays/structures/racks/trenches etc. Cables shall be supplied by KMML. All other materials required are under the scope of contractor. 3/1/2 x 400 sqmm AYFY Cable | item3.0 | 850 | Mtrs. |
4 | 3.01 | 3/1/2 x 300 sqmm AYFY Cable | item3.01 | 200 | Mtrs. |
5 | 3.02 | 3/1/2 x 95 sqmm AYFY Cable | item3.02 | 60 | Mtrs. |
6 | 3.03 | 3/1/2 x 70 sqmm AYFY Cable | item3.03 | 15 | Mtrs. |
7 | 3.04 | 4 X 16 Sq.mm sqmm AYFY Cable | item3.04 | 45 | Mtrs. |
8 | 3.05 | 4 X 10 Sq.mm AYFY Cable | item3.05 | 10 | Mtrs. |
9 | 3.06 | 4 X 6 Sq.mm AYFY Cable | item3.06 | 60 | Mtrs. |
10 | 3.07 | 4 X 4 Sq.mm AYFY Cable | item3.07 | 15 | Mtrs. |
11 | 3.08 | 8C x 1.5 sqmm YWY Cable | item3.08 | 310 | Mtrs. |
12 | 3.09 | 3C x 1.5 sqmm YWY Cable | item3.09 | 320 | Mtrs. |
13 | 3.1 | 3C x 2.5 sqmm YWY Cable | item3.10 | 195 | Mtrs. |
14 | 4 | Disconnection of the following cables from MCC panel/LDB, removal those cables from existing trays/structures and shift the same to central store/ERS. 3/1/2 x 300 sqmm AYFY Cable | item4.0 | 100 | Mtrs. |
15 | 4.01 | 3/1/2 x 70 sqmm AYFY Cable | item4.01 | 200 | Mtrs. |
16 | 4.02 | 3/1/2 x 35 sqmm AYFY Cable | item4.02 | 300 | Mtrs. |
17 | 4.03 | 4 x 16 sqmm AYFY Cable | item4.03 | 80 | Mtrs. |
18 | 4.04 | 4 x 10 sqmm AYFY Cable | item4.04 | 40 | Mtrs. |
19 | 4.05 | 4 x 6 sqmm AYFY Cable | item4.05 | 100 | Mtrs. |
20 | 4.06 | 4 x 4 sqmm AYFY Cable | item4.06 | 15 | Mtrs. |
21 | 4.07 | 5 x 1.5 sqmm YWY Cable | item4.07 | 130 | Mtrs. |
22 | 5 | Glanding and termination of following AYFY/YWYcables using DC galsnds and and lugs including earthing. 3/1/2 x 400 sqmm AYFY Cable | item5.0 | 2 | Nos |
23 | 5.01 | 3/1/2 x 300 sqmm AYFY Cable | item5.01 | 8 | Nos |
24 | 5.02 | 3/1/2 x 95 sqmm AYFY Cable | item5.02 | 2 | Nos |
25 | 5.03 | 3/1/2 x 70 sqmm AYFY Cable | item5.03 | 1 | Nos |
26 | 5.04 | 4 x 16 sqmm AYFY Cable | item5.04 | 3 | Nos |
27 | 5.05 | 4 x 10 sqmm AYFY Cable | item5.05 | 1 | Nos |
28 | 5.06 | 4 x 6 sqmm AYFY Cable | item5.06 | 4 | Nos |
29 | 5.07 | 4 x 4 sqmm AYFY Cable | item5.07 | 1 | Nos |
30 | 5.08 | 5C x 1.5 sqmm YWY Cable | item5.08 | 4 | Nos |
31 | 5.09 | 8C x 1.5 sqmm YWY Cable | item5.09 | 12 | Nos |
32 | 5.1 | 3C x 1.5 sqmm YWY Cable | item5.10 | 8 | Nos |
33 | 5.11 | 3C x 2.5 sqmm YWY Cable | item5.11 | 6 | Nos |
34 | 6 | Erection of new 600/300mm GI cable trays on newly fabricated supports . Tray shall be joined with GI side couplers with bolts and nuts. The cables shall be dressed and clamped as per standards. GI nut and bolts shall be supplied by the contractor. | item6.0 | 120 | Nos |
35 | 7 | Fabrication and erection of cable tray supports using MS items. All the inserts and structures shall be propoerly cleaned and painted with two coats of epoxy paint over one coat of epoxy primer. Paint shall be Berger/Asian/Nerolac & shall be supplied by the contractor. | item7.0 | 2 | MT |
36 | 8 | Preparation of all electrical drawings and obtaining approval from electrical inspecorate for PMCC for U-400 & new APFC Panel for PCC-2 | item8.0 | 1 | Set |