Repair And Replacement Of Fire Pump , Panel , Dg Set , Wiring , Rewiring , Fan Fitting , Fire System Water Cooler And Ro System , Compound Lighting At Family Court Dheerpur , Delhi . ( Sh- Fire Fighting Work And D . G . Set ) , Repairing And Servicing Of Main Fire Pump& Motor Kirloskar Make , 50/60 , Hp . Including -Dismantling , Rewinding , Replacement , Of Bearings , Gland , Sleeve Set , Seal , Repair/Replacement Of Base Frame , Avm Pads And Refixing , Alignment , Testing And Commissioning Etc . I/C Buy Back Of Old Dismantled Material , Repairing And Servicing Of Jockey Pump& Motor Kirloskar Make , 15/20Hp , Including , Dismantling , Rewinding , Replacement Of Bearings , Gland , Sleev Set , Seal , Repair/Replacement Of Base Frame , Avm Pads And Refixing , Alignment , Testing And Commissioning Etc . I/C Buy Back Of Old Dismantled Material , Repair And Replacement Of Fire Hydrant Main Pipe Line Including Repairing/Replacement Of Damaged And Defective 3Nos Butterfly Valves , 3Nos Nrv , Pressure Switch , Pressure Gauges , Flanges , Gaskets Etc . As Reqd . I/C Buy Back Of Old Dismentaled Material , Major Overhauling Of Kirloskar Make Fire Engine Model 4R1040 Coupled With Kirloskar Pump Dsm Incudingcomplete Dismantling Of Engine And Pump And Reassemble The Same By Repair And Replacement Of Crank Shaft , Cam Shaft , , Liner , Piston , Rings , Bearings , Cylinderhead , Fuel Pump , Nozzle , Gaskets , Self , Starter , Charging Alternator , Battary , Engine Wiring , Control Wiring , Etc And Mechanical Seal , Gland Bush , Sleeve , Nut Bolt , Gaskets , Alignment Etc As Required . I/C Buy Back Of Old Dismentaled Material , Painting Of Hydrant Moter And Pump , Jockey Pump , Fire Engine And Pump , Fire Main Pipe Line And Others Pipe Line In Fire Room . , Fabrication , Supply , Insallation Testing & Commissioning Of Electrical Control Panel Of Cubical Construction , Floor Mounted Type , Fabricated Out Of 2Mm Thick Crca Sheet , Compartmentalised With Hinged Lockable Doors , Dust And Vermin Proof , Powder Coated Of Approved Shade After 7 Tank Treatment Process , Cable Alley , Interconnection With Suitable Size Copper Conductor Cable/Solid Copper Strip , Having Switchgears And Accessories , Mountings And Internal Wiring , Earth Terminals , Numbering Etc . Complete In All Respect , Suitable For Main Fire Pump , Pressurisation Pump & Diesel Pump Set Complete As Per Cpwd Specification With Following In Coming And Outgoings , Suitable For Operation On 415V , 3 Phase , 50Hz Ac Supply With Enclosure Protection Class Ip 42 As Required , Incomings400A , 50Ka 4 Pole Mccb , Ics=100% Icu Rating Digital Voltmeter 0-500V With Selector Switch Ammeter ( 0-400 A ) With Selector Swtich & Cts Etc . Led Type Ryb Phase Indicating Lamps , On , Off , TripIndicating Lamps Set Of Copper Bus Bar 500A , Outgoings ( Note : All Outgoing Feeders For Pumps Should Have Digital Ammeter With Selector Switches , And Led Type On , Off , Trip Indicating Lamps ) , Main Fire Pump200 A , 50Ka Tpn Mccb , Ics=100% Icu , With Fully Automatic Star/Delta Starter Suitable For 75 Hp Pump With Overload Protection , Current Sensing Type Single Phase Preventor Complete With All Acceessories And Internal Wiring Required For Automatic Operation , Selector Switch For Local/Remote , Auto/Manual/Off Operation . , Jockey Pump 100 A , 50Ka Tpn Mccb , Ics=100% Icu , With Suitable Hp Fully Automatic Star/Delta Starter With Overload Protection , Current Sensing Type Single Phase Preventor Complete With All Acceessories And Internal Wiring Required For Automatic Operation , Selector Switch For Local/Remote , Auto/Manual/Off Operation . , Diesel Engine Control Control For Diesel Engine Comprising - Automatic/Manual Selctor Switch & 3 Attempt Starting Device , Timers And Relays As Required , Push Buttons , Start/Stop In Manual Mode Indicating Lamp For High/ Low Lub . Oil Pressure , High Water Temp And Engine On Indication Battery Charger Suitbale For 12V/24 V Dc With Boost And Trickle Selector Switch , 0-30 V Dc Volt Meter , And 0-20 A Dc Ammeter All Standard Relays And Accessories For Automatic Operation Of Diesel Engine System Controller Designing , Supply , Installation , Testing And Commissioning Of System Controller To Control Operation Of Main Electric Fire Pump , Diesel Pump , Pressurization Pump , Terrace Pump In Sequence As Per Specification Consisting Of Relays , Timers . Sensors , Annunciation Window For Fault Indication , Complete As Per Specifications . , Providing , Fixing , Testing & Commissioning Of 15Mm Dia Quartzoid Bulb Type Sprinklers Of Rating 68 Degree Centigrade With Required Accessories : , Pendent Sprinkler , Supplying And Fixing 63 Mm Dia , 15 M Long Rrl Hose Pipe With 63 Mm Dia Male And Female Couplings Duly Bound With Gi Wire , Rivets Etc . Conforming To Is 636 ( Type-A ) As Required : , Stainless Steel ( Grade 304 ) , Supplying And Fixing 20 Mm Nominal Internal Dia Water Hose Thermoplastic ( Textile Reinforced ) Type -2 As Per Is: 12585 For First-Aid Hose Reel , 20 Mm Nominal Internal Dia With Gun Metal Globe Valve & Nozzle . , 30 M Long With Gun Metal Globe Valve & Nozzle , Supplying & Fixing 63 Mm Dia Gun Metal Short Branch Pipe With 20 Mm Nominal Internal Diameter Size Nozzle Conforming To Is 903 Suitable For Instantaneous Connection To Interconnect Hose Pipe Coupling As Required : , Stainless Steel ( Grade 304 ) , Providing And Placing On Terrace ( At All Floor Levels ) Polyethylene Water Storage Tank , Isi : 12701 Marked , With Cover And Suitable Locking Arrangement And Making Necessary Holes For Inlet , Outlet And Overflow Pipes But Without Fittings And The Base Support For Tank . , Supplying & Fixing Of Hose Cabinet Of Size 900Mm X 600Mm X 300Mm Made Up 2 Mm Thick Ms Sheet With 6 Mm Thick Glazed Glass Doors I/C Necessary Locking Arrangement Suitable To Accommodate External Hydrant 2 Nos 15 Mtr Long Hose Pipe & Duly Painted With Post Office Red Externally & White Internally With Synthetic Enamel Paint Complete In All Respect And With Brick Work Foundation Etc As Reqd , Supplying And Fixing Single Headed Internal Hydrant Valve With Instantaneous Gunmetal/Stainless Steel Coupling Of 63 Mm Dia With Cast Iron Wheel Isi Marked Conforming To Is 5290 ( Type -A ) With Blank Gunmetal/Stainless Steel Cap And Chain As Required : , Single Headed Stainless Steel , Supplying And Fixing Of Fire Brigade Connection Of Cast Iron Body With Gun Metal Male Instantaneous Inlet Couplings Complete With Cap And Chain As Reqd . For Suitable Dia Ms Pipe Connection Conforming To Is 904 As Required : , 3 Way - 150 Mm Dia M . S . Pipe , Supplying , Installation , Testing And Commissioning Of Electric Driven Terrace Pump Suitable For Automatic Operation And Consisting Of Following , Complete In All Respects , As Required: ( Terrace Pump ) , Horizontal Type , Multistage , Centrifugal , Split Casing Pump Of Cast Iron Body & Bronze Impeller With Stainless Steel Shaft , Mechanical Confirming To Is : 1520 , Suitable Hp Squirell Cage Induction Motor Tefc Type Suitable For Operation On 415 Volts , 3 Phase , 50 Hz , Ac Supply With Ip55 Class Of Protection For Enclosure , Horiziontal Foot Mounted Type With Class-F Insulation , Conforming To Is-325 . , M . S . Fabricated Common Base Plate , Coupling , Coupling Guard , Foundation Bolts Etc . As Required . , Suitable Cement Concrete Foundation Duly Plastered And With Anti Vibration Pads . 900 Lpm At 35 M Head , Supplying , Installation , Testing & Commissioning Of Intelligent Analog Addressable Photothermal Detector Complete With Mounting Base Complete As Required , Supplying , Installation , Testing & Commissioning Of Addressable Manual Call Point Complete As Required . , Supplying , Installation , Testing & Commisssioning Of Intelligent Addressable Programmable S