Setting Up Of Dialysis Centre At Thqh,Nemom ,Trivandrum, DIALYSIS CENTRE AT THQH, NEMOM, TRIVANDRUM-Kerala

Kerala Medical Services Corporation Limited has published Setting Up Of Dialysis Centre At Thqh,Nemom ,Trivandrum. Submission Date for this Tender is 27-11-2019. Earth Moving Machinery Tenders in DIALYSIS CENTRE AT THQH, NEMOM, TRIVANDRUM Kerala. Bidders can get complete Tender details and download the document.




Tender Notice

22553525
Setting Up Of Dialysis Centre At Thqh,Nemom ,Trivandrum
Open Tender
Indian
Kerala
DIALYSIS CENTRE AT THQH, NEMOM, TRIVANDRUM
27-11-2019

Tender Details

Setting Up Of Dialysis Centre At Thqh, Nemom , Trivandrum - 1 Dismantling Tile Work In Floors And Roofs Laid In Cement Mortar Including Stacking Material Within 50 Metres Lead.For Thickness Of Tiles 10 Mm To 25 Mm 2 Dismantling Doors, Windows And Clerestory Windows ( Steel Or Wood ) Shutter Including Chowkhats, Architrave, Holdfasts Etc. Complete And Stacking Within 50 Metres Lead :Of Area 3 Sq. Metres And Below 3 Demolishing Brick Work Manually / By Mechanical Means Including Stacking Of Serviceable Material And Disposal Of Unserviceable Material Within 50 Metres Lead As Per Direction Of Engineer-In-Charge.In Cement Mortar 4 Demolishing R.C.C. Work Manually / By Mechanical Means Including Stacking Of Steel Bars And Disposal Of Unserviceable Material With In 50 Metres Lead As Per Direction Of Engineer -In-Charge. 5 Dismantling Of Flushing Cistern Of All Types ( C.I. / Pvc / Vitrious China ) Including Stacking Of Useful Materials Near The Site And Disposal Of Unserviceable Materials Within 50 Metres Lead. 6 Disposal Of Building Rubbish / Malba / Similar Unserviceable, Dismantled Or Waste Materials By Mechanical Means, Including Loading, Transporting, Unloading To Approved Municipal Dumping Ground Or As Approved By Engineer-In-Charge, Beyond 50 M Initial Lead, For All Leads Including All Lifts Involved 7 Dismantling Aluminium / Gypsum Partitions, Doors, Windows, Fixed Glazing And False Ceiling Including Disposal Of Unserviceable Surplus Material And Stacking Of Serviceable Material With In 50 Metres Lead As Directed By Engineer - In-Charge 8 Dismantling Old Plaster Or Skirting Raking Out Joints And Cleaning The Surface For Plaster Including Disposal Of Rubbish To The Dumping Ground Within 50 Metres Lead. 9 Earth Work In Excavation By Mechanical Means ( Hydraulic Excavator ) / Manual Means In Foundation Trenches Or Drains ( Not Exceeding 1.5 M In Width Or 10 Sqm On Plan ) , Including Dressing Of Sides And Ramming Of Bottoms, Lift Upto 1.5 M, Including Getting Out The Excavated Soil And Disposal Of Surplus Excavated Soil As Directed, Within A Lead Of 50 M.All Kinds Of Soil. 10 Solid Block Masonry Using Pre Cast Solid Blocks ( Factory Made ) Of Size 30X20x15cm Or Nearest Available Size Confirming To Is 2185 Part I Of 1979 For Super Structure Above Floor Two Level Upto Floor Five Level With Thickness 15Cm In : Cm 1:6 ( 1 Cement : 6 Coarse Sand ) Etc Complete 11 Reinforced Cement Concrete Work In Walls ( Any Thickness ) , Including Attached Pilasters, Buttresses, Plinth And String Courses, Fillets, Columns, Pillars, Piers, Abutments, Posts And Struts Etc. Up To Floor Five Level, Excluding Cost Of Centering, Shuttering, Finishing And Reinforcement :1:1.5:3 ( 1 Cement : 1.5 Coarse Sand : 3 Graded Stone Aggregate 20 Mm Nominal Size ) 12 Centering And Shuttering Including Strutting, Propping Etc. And Removal Of Form For :Lintels, Beams, Plinth Beams, Girders, Bressumers And Ncantilevers 13 Steel Reinforcement For R.C.C. Work Including Straightening, Cutting, Bending, Placing In Position And Binding All Complete Above Plinth Level.Thermo- Echanically Treated Bars 14 Providing And Laying Damp-Proof Course 50 Mm Thick With Cement Concrete 1:2:4 ( 1 Cement : 2 Coarse Sand : 4 Graded Stone Aggregate 20 Mm Nominal Size ) . 15 Providing And Laying In Position Cement Concrete Of Specified Grade Excluding The Cost Of Centering And Shuttering - All Work Up To Plinth Level :1:4:8 ( 1 Cement : 4 Coarse Sand : 8 Graded Stone Aggregate 40 Mm Nominal Size ) 16 12 Mm Cement Plaster Of Mix :1:4 ( 1 Cement: 4 Fine Sand ) 17 Repairs To Plaster Of Thickness 12 Mm To 20 Mm In Patches Of Area 2.5 Sq Meters And Under, Including Cutting The Patch In Proper Shape, Raking Out Joints And Preparing And Plastering The Surface Of The Walls Complete, Including Disposal Of Rubbish To The Dumping Ground Within 50 Meters Lead:With Cement Mortar 1:4 ( 1 Cement : Fine Sand ) 18 Providing And Laying Water Proofing Treatment In Sunken Portion Of Wcs, Bathroom Etc., By Applying Cement Slurry Mixed With Water Proofing Cement Compound Consisting Of Applying : A ) First Layer Of Slurry Of Cement @ 0.488 Kg / Sqm Mixed With Water Proofing Cement Compound @ 0.253 Kg / Sqm. This Layer Will Be Allowed To Air Cure For 4 Hours. B ) Second Layer Of Slurry Of Cement @ 0.242 Kg / Sqm Mixed With Water Proofing Cement Compound @ 0.126 Kg / Sqm. This Layer Will Be Allowed To Air Cure For 4 Hours Followed With Water Curing For 48 Hours. The Rate Includes Preparation Of Surface, Treatment And Sealing Of All Joints, Corners, Junctions Of Pipes And Masonry With Polymer Mixed Slurry. 19 Providing And Laying Vitrified Floor Tiles In Different Sizes ( Thickness To Be Specified By The Manufacturer ) With Water Absorption Less Than 0.08% And Conforming To Is : 15622, Of Approved Make, In All Colours And Shades, Laid On 20 Mm Thick Cement Mortar 1:4 ( 1 Cement : 4 Coarse Sand ) , Including Grouting The Joints With White Cement And Matching Pigments Etc., Complete.Size Of Tile 600 X 600 Mm. 20 Providing And Laying Mat Finish Ceramic Floor Tiles In Different Sizes ( Thickness To Be Specified By The Manufacturer ) With Water Absorption Less Than 0.08% And Conforming To Is : 15622, Of Approved Make, In All Colours And Shades, Laid On 20 Mm Thick Cement Mortar 1:4 ( 1 Cement : 4 Coarse Sand ) , Including Grouting The Joints With White Cement And Matching Pigments Etc., Complete.Size Of Tile 600 X 600 Mm. 21 Providing And Fixing I St Quality Ceramic Glazed Wall Tiles Conforming To Is : 15622 ( Thickness To Be Specified By The Manufacturer ) , Of Approved Make, In All Colours, Shades Except Burgundy, Bottle Green, Black Of Any Size As Approved By Engineer -In-Charge, In Skirting, Risers Of Steps And Dados, Over 12 Mm Thick Bed Of Cement Mortar 1:3 ( 1 Cement : 3 Coarse Sand ) And Jointing With Grey Cement Slurry @ 3.3 Kg Per Sqm, Including Pointing In White Cement Mixed With Pigment Of Matching Shade Complete. 22 Providing And Laying Polished Granite Stone Flooring In Required Design And Patterns, In Linear As Well As Curvilinear Portions Of The Building All Complete As Per The Architectural Drawings With 18 Mm Thick Stone Slab Over 20 Mm ( Average ) Thick Base Of Cement Mortar 1:4 ( 1 Cement : 4 Coarse Sand ) Laid And Jointed With Cement Slurry And Pointing With White Cement Slurry Admixed With Pigment Of Matching Shade Including Rubbing , Curing And Polishing Etc. All Complete As Specified And As Directed By The Engineer-In-Charge.Polished Granite Stone Slab Jet Black, Cherry Red, Elite Brown, Cat Eye Orequivalent. 23 Grouting The Joints Of Flooring Tiles Having Joints Of 3 Mm Width, Using Epoxy Grout Mix 0.70 Kg Of Organic Coated Filler Of Desired Shade ( 0.10 Kg Of Hardener And 0.20 Kg Of Resin Per Kg ) . Including Filling / Grouting And Finishing Complete As Per Direction Of Engineer-In-Charge.Size Of Tile 600X600 Mm 24 Providing And Laying 60 Mm Thick Factory Made Cement Concrete Interlocking Paver Block Of M - 30 Grade Made By Block Making Machine With Strong Vibratory Compaction, Of Approved Size, Design & Shape, Laid In Required Colour And Pattern Over And Including 50 Mm Thick Compacted Bed Of Coarse Sand, Filling The Joints With Fine Sand Etc. All Complete As Per The Direction Of Engineer-In-Charge. 25 Providing And Fixing Aluminium Work For Doors, Windows, Ventilators And Partitions With Extruded Built Up Standard Tubular Sections / Appropriate Z Sections And Other Sections Of Approved Make Conforming To Is: 733 And Is: 1285, Fixing With Dash Fasteners Of Required Dia And Size, Including Necessary Filling Up The Gaps At Junctions, I.E. At Top, Bottom And Sides With Required Epdm Rubber / Neoprene Gasket Etc. Aluminium Sections Shall Be Smooth, Rust Free, Straight, Mitred And Jointed Mechanically Wherever Required Including Cleat Angle, Aluminium Snap Beading For Glazing / Paneling, Nc.P. Brass / Stainless Steel Screws, All Complete As Per Architectural Drawings And The Directions Of Engineer-In-Charge. ( Glazing, Paneling And Dash Fasteners To Be Paid For Separately ) :Polyester Powder Coated Aluminium ( Minimum Thickness Of Polyester Powder Coating 50 Micron ) 26 Providing And Fixing Glazing In Aluminium Door, Window, Ventilator Shutters And Partitions Etc. With Epdm Rubber / Neoprene Gasket Etc. Complete As Per The Architectural Drawings And The Directions Of Engineer-In-Charge. ( Cost Of Aluminium Snap Beading Shall Be Paid In Basic Item ) :With Float Glass Panes Of 4.0 Mm Thickness 27 Providing And Fixing Pre -Laminated Medium Density Fibre Board Exterior Grade ( Grade-I ) Is:14587:1998 Marked, To Frame, Backing Or Studding With Screws Etc. Complete ( Frames, Backing Or Studding To Be Paid Separately ) . Pre-Laminated With Decorative Lamination On Both Side Exterior Grade - I Mdf Board 12 Mm Thick Confirming To Is:14587 28 Providing And Fixing False Ceiling At All Height Including Providing And Fixing Of Frame Work Made Of Special Sections, Power Pressed From M.S. Sheets And Galvanized With Zinc Coating Of 120 Gms / Sqm ( Both Side Inclusive ) As Per Is : 277 And Consisting Of Angle Cleats Of Size 25 Mm Wide X 1.6 Mm Thick With Flanges Of 27 Mm And 37 Mm, At 1200 Mm Centre To Centre, One Flange Fixed To The Ceiling With Dash Fastener 12.5 Mm Dia X 50 Mm Long With 6 Mm Dia Bolts, Other Flange Of Cleat Fixed To The Angle Hangers Of 25X10x0.50 Mm Of Required Length With Nuts & Bolts Of Required Size And Other End Of Angle Hanger Fixed With Intermediate G.I. Channels 45X15x0.9 Mm Running At The Spacing Of 1200 Mm Centre To Centre, To Which The Ceiling Section 0.5 Mm Thick Bottom Wedge Of 80 Mm With Tapered Flanges Of 26 Mm Each Having Lips Of 10.5 Mm, At 450 Mm Centre To Centre, Shall Be Fixed In A Direction Perpendicular To G.I. Intermediate Channel With Connecting Clips Made Out Of 2.64 Mm Dia X 230 Mm Long G.I. Wire At Every Junction, Including Fixing Perimeter Channels 0.5 Mm Thick 27 Mm High Having Flanges Of 20 Mm And 30 Mm Long, The Perimeter Of Ceiling Fixed To Wall / Partition With The Help Of Rawl Plugs At 450 Mm Centre, With 25 Mm Long Dry Wall Screws @ 230 Mm Interval, Including Fixing Of Gypsum Board To Ceiling Section And Perimeter Channel With The Help Of Dry Wall Screws Of Size 3.5X25 Mm At 230 Mm C / C, Including Jointing And Finishing To A Flush Finish Of Tapered And Square Edges Of The Board With Recommended Jointing Compound, Jointing Tapes, Finishing With Jointing Compound In 3 Layers Covering Upto 150 Mm On Both Sides Of Joint And Two Coats Of Primer Suitable For Board, All As Per Manufacturers Specification And Also Including The Cost Of Making Openings For Light Fittings, Grills, Diffusers, Cutouts Made With Frame Of Perimeter Channels Suitably Fixed, All Complete As Per Drawings, Specification And Direction Of The Engineer In Charge But Excluding The Cost Of Painting With: 12.5 Mm Thick Tapered Edge Gypsum Fire Resistant Board Conforming To Is; 2095-Part I 29 Providing And Fixing Double Action Hydraulic Floor Spring Of Approved Brand And Manufacture Conforming To Is: 6315, Having Brand Logo Embossed On The Body / Plate With Double Spring Mechanism And Door Weight Upto 125 Kg, For Doors Including Cost Of Cutting Floors, Embeding In Floors As Required And Making Good The Same Matching To The Existing Floor Finishing And Cover Plates With Brass Pivot And Single Piece M.S. Sheet Outer Box With Slide Plate Etc. Complete As Per The Direction Of Engineer -In- Charge.With Stainless Steel Cover Plate Minimum 1.25 Mm Thickness 30 Providing And Fixing Aluminium Tubular Handle Bar 32 Mm Outer Dia, 3.0Mm Thick & 2100 Mm Long With S.S. Screws Etc. Complete As Per Direction Of Engineer -In-Charge. Powder Coated Minimum Thickness 50 Micron Aluminium Tubular Handle Bar 31 Providing And Fixing Aluminium Tower Bolts, Isi Marked, Anodised ( Anodic Coating Not Less Than Grade Ac 10 As Per : 1868 ) , Transparent Or Dyed To Required Colour Or Shade, With Necessary Screws Complete:250X10 Mm 32 Providing And Fixing Aluminium Extruded Section Body Tubular Type Universal Hydraulic Door Closer ( Having Brand Logo With Isi, Is : 3564, Embossed On The Body, Door Weight Upto 36 Kg To 80 Kg And Door Width Form 701 Mm To 1000 Mm ) , With Double Speed Adjustment With Necessary Accessories And Screws Etc. Complete. 33 Providing And Fixing 100 Mm Brass Locks ( Best Make Of Approved Quality ) For Aluminium Doors Including Necessary Cutting And Making Good Etc. Complete 34 Providing And Fixing Aluminium Hanging Floor Door Stopper, Isi Marked, Anodised ( Anodic Coating Not Less Than Grade Ac 10 As Per Is: 1868 ) Transparent Or Dyed To Required Colour And Shade, With Necessary Screws Etc. Complete.Twin Rubber Stopper 35 Providing And Fixing Stainless Steel ( Grade 304 ) Railing Made Of Hollow Tubes, Channels, Plates Etc., Including Welding, Grinding, Buffing, Polishing And Making Curvature ( Wherever Required ) And Fitting The Same With Necessary Stainless Steel Nuts And Bolts Complete, I / C Fixing The Railing With Necessary Accessories & Stainless Steel Dash Fasteners, Stainless Steel Bolts Etc., Of Required Size On The Top Of The Floor Or The Side Of Waist Slab With Suitable Arrangement As Per Approval Of Engineer-In-Charge, ( For Payment Purpose Only Weight Of Stainless Steel Members Shall Be Considered Excluding Fixing Accessories Such As Nuts, Bolts, Fasteners Etc. ) 36 Providing And Fixing 3 Mm Thick Acp Sheet Fixed In Aluminum Doors With C.P. Brass / Stainless Steel Screws Etc. Complete. Including All Cost Conveyance And All Labour Charges Etc Complete. 37 Frosted Film - Supply And Installation Of 3M Make Frosted Film Pattern Throughout All The Internal Glass Panels Wherever Required Of Approx. 1.5 M Height As Per The Approved Pattern. 38 Applying One Coat Of Water Thinnable Cement Primer Of Approved Brand And Manufacture On Wall Surface:Water Thinnable Cement Primer 39 Finishing Walls With Premium Acrylic Smooth Exterior Paint With Silicone Additives Of Required Shade:New Work ( Two Or More Coats Applied @ 1.43 Ltr / 10 Sqm Over And Including Priming Coat Of Exterior Primer Applied @ 2.20 Kg / 10 Sqm ) 40 Providing And Applying White Cement Based Putty Of Average Thickness 1 Mm, Of Approved Brand And Manufacturer, Over The Plastered Wall Surface To Prepare The Surface Even And Smooth Complete. 41 Wall Painting With Acrylic Emulsion Paint Of Approved Brand And Manufacture To Give An Even Shade:Two Or More Coats On New Work 42 Painting With Synthetic Enamel Paint Of Approved Brand And Manufacture To Give An Even Shade:Two Or More Coats On New Work 43 Steel Work In Built Up Tubular ( Round, Square Or Rectangular Hollow Tubes Etc. ) Trusses Etc., Including Cutting, Hoisting, Fixing Position And Applying A Priming Coat Of Approved Steel Primer, Including Welding And Bolted With Special Shaped Washers Etc. Complete. Hot Finished Welded Type Tubes 44 Providing & Fixing Poly Carbonate Multi Wall Plain Sheet 5 Mm Thick As Approved By The Engineer In Charge And Should Be Supplied In A Single Length Of 12 M Or As Decide By The Engineer In Charge. The Sheets Shall Be Fixed Using Self Drilling / Self Tapping Screw Of Size ( 5.5X55 Mm ) With Epdm Seal Complete Upto Any Pitch In Horizontal / Vertical / Curved Surfaces, But Excluding The Cost Of Purlins, Rafters, Trusses, And Including Cutting To Size And Shapes Where Ever Required. 45 Fabricating And Providing Stainless Steel Table Of Size 120 X 60 X 85+15 Mounted With Bulk Washing Sink, Of Size 110 X 50 X 45 Cm And Drain Coupling, All Frame Works Shall Be Made With Stainless Steel 38Mm Dia Or Nearest Available 16Swg Round Hollow Sections Fitted With Adequate Horizontal Supports.The Sunken Table Top And Sink Will Be Of 16Ga, 304 Grade Ss Satin Finished, Table Top With All Resulting Edges Double Beeded On Three Sides With No Burrs Or Other Excess Material Left, And To Be Reinforced Underneath Edges With 32X32x3mm Thick Stainless Steel Angle Framework.The Underneath Support Shall Be Of 18X75x18 Ss Channel Sections.Unit To Have 150Mm High Back Splash.White Nylon Bullets To Be Fitted Into All Four Legs, As Per Drawings And Technical Specification, Including Cost And Conveyance Of All Materials, Labour And Other Incidentals Etc. Complete. 46 Fabricating And Providing Stainless Steel Sink Of Size 60 X30x30 Cm With And Drain Coupling, All Frame Works Shall Be Made With Stainless Steel 38Mm Dia Or Nearest Available 16Swg Round Hollow Sections Fitted With Adequate Horizontal Supports.The Sunken Table Top And Sink Will Be Of 16Ga, 304 Grade Ss Satin Finished, Table Top With All Resulting Edges Double Beeded On Three Sides With No Burrs Or Other Excess Material Left, And To Be Reinforced Underneath Edges With 32X32x3mm Thick Stainless Steel Angle Framework.The Underneath Support Shall Be Of 18X75x18 Ss Channel Sections.Unit To Have 150Mm High Back Splash.White Nylon Bullets To Be Fitted Into All Four Legs, As Per Drawings And Technical Specification, Including Cost And Conveyance Of All Materials, Labour And Other Incidentals Etc. Complete 47 Providing And Placing On Terrace ( At All Floor Levels ) Polyethylene Water Storage Tank, Isi : 12701 Marked, With Cover And Suitable Locking Arrangement And Making Necessary Holes For Inlet, Outlet And Overflow Pipes But Without Fittings And The Base Support For Tank. 48 Providing And Fixing Chlorinated Polyvinyl Chloride ( Cpvc ) Pipes, Having Thermal Stability For Hot & Cold Water Supply, Including All Cpvc Plain & Brass Threaded Fittings, Including Fixing The Pipe With Clamps At 1.00 M Spacing. This Includes Jointing Of Pipes & Fittings With One Step Cpvc Solvent Cement And Testing Of Joints Complete As Per Direction Of Engineer In Charge.20 Mm Cpvc Nominal Outer Dia Pipes 49 Providing And Fixing Chlorinated Polyvinyl Chloride ( Cpvc ) Pipes, Having Thermal Stability For Hot & Cold Water Supply, Including All Cpvc Plain & Brass Threaded Fittings, Including Fixing The Pipe With Clamps At 1.00 M Spacing. This Includes Jointing Of Pipes & Fittings With One Step Cpvc Solvent Cement And Testing Of Joints Complete As Per Direction Of Engineer In Charge.25 Mm Cpvc Nominal Outer Dia Pipes 50 Providing And Fixing Wash Basin With C.I. Brackets, 15 Mm C.P. Brass Pillar Taps, 32 Mm C.P. Brass Waste Of Standard Pattern, Including Painting Of Fittings An Brackets, Cutting And Making Good The Walls Wherever Require :White Vitreous China Wash Basin Size 550X400 Mm With A Pair Of 15 Mm C.P. Brass Pillar Taps 51 Providing And Fixing White Vitreous China Pedestal Type Water Closet ( European Type W.C. Pan ) With Seat And Lid, 10 Litre Low Level White P.V.C. Flushing Cistern, Including Flush Pipe, With Manually Controlled Device ( Handle Lever ) , Conforming To Is : 7231, With All Fittings And Fixtures Complete, Including Cutting And Making Good The Walls And Floors Wherever Required :W.C. Pan With Isi Marked White Solid Plastic Seat And Lid 52 Providing And Fixing C.P. Brass Long Body Bib Cock Of Approved Quality Conforming To Is Standards And Weighing Not Less Than 690 Gms.15 Mm Nominal Bore 53 Providing And Fixing Ptmt Bottle Trap For Wash Basin And Sink.Bottle Trap 31 Mm Single Piece Moulded With Height Of 270 Mm, Effective Length Of Tail Pipe 260 Mm From The Center Of The Waste Coupling, 77 Mm Breadth With 25 Mm Minimum Water Seal, Weighing Not Less Than 260 Gms 54 Supplying And Fixing Cp Health Faucet Superior Quality ( Jagur Or Equvalent Make ) Including Cost Of Materials And Labour Charges Etc Complete As Per The Direction Of Site Engineer-In-Charge. 55 Providing And Fixing Mirror Of Superior Glass ( Of Approved Quality ) And Of Required Shape And Size With Plastic Moulded Frame Of Approved Make And Shade With 6 Mm Thick Hard Board Backing :Rectangular Shape 453X357 Mm 56 Providing And Fixing Uplasticised Pvc Connection Pipe With Brass Unions:30 Cm Length 20 Mm Nominal Bore 57 Providing And Fixing Ptmt Soap Dish Holder Having Length Of 138 Mm, Breadth 102 Mm, Height Of 75 Mm With Concealed Fittings Arrangements, Weighing Not Less Than 106 Gms. 58 Providing And Fixing Ptmt Towel Rail Complete With Brackets Fixed To Wooden Cleats With Cp Brass Screws With Concealed Fitting Arrangement Of Approved Quality And Colour600 Mm Long Towel Rail With Total Length Of 645 Mm, Width 78 Mm And Effective Height Of 88 Mm, Weighting Not Less Than 190 Gms 59 Supplying And Fixing 20Mm Cpvc Valve Etc Complete N 60 Supplying And Fixing 25Mm Cpvc Valve Etc Complete N 61 Supplying And Fixing 15Mm L Bow Tap Etc Complete N 62 Supplying And Fixing 15 Mm Stainless Steel Tap Etc Complete Long Body N 63 Supplying And Fixing Steel S Hooks Etc Complete N 64 Supplying And Layin 50Mm Dia Pvc Pipe ( 10Kg / Cm2 ) Including Cost Of All Fittings Such As Tees, Elbows, Clamps, Screws Cost And Conveyance Of All Materials Etc. Complete N 65 Supplying And Laying 25Mm Dia Pvc Pipe ( 10Kg / Cm2 ) Including Cost Of All Fittings Such As Tees, Elbows, Clamps, Screws Cost And Conveyance Of All Materials Etc. Complete N 66 Supplying And Laying 110Mm Dia Pvc Pipe ( 10Kg / Cm2 ) Including Cost Of All Fittings Such As Tees, Elbows, Clamps, Screws Cost And Conveyance Of All Materials Etc. Complete 67 Supplying And Laying 75Mm Dia Pvc Pipe ( 6Kg / Cm2 ) Including Cost Of All Fittings Such As Tees, Elbows, Clamps, Screws Cost And Conveyance Of All Materials Etc. Complete 68 Supplying And Fixing 15Mm Cpvc Push Pull Conecter Including All Cost Conveyance All Labour Charges Etc Complete 69 Supplying And Fixing Isi Mark Pvc Frame With Door Shutter Including All Fittings And Locking Arrangement Etc Complete 70 Providing And Fixing Vertical Blinds As Per The Direction Of Engineer In Charge 71 Supplying And Laying Polyster , Washable And Stainfree Cloth ( Bio-Active Fabric Washable Germfree-Suitable For Diaysis Room ) Curtain System With Maximum Curtain Cloth Height 230Cm ( Top 30 Cm White Colour Net And 200Cm Light Blue Colour As Per Approval ) Stitching With Stifiner Tape, Pleats, Ironing And Laying In Dialysis Room Around Each Bed Using Pvc Runner With Hooks&Stopper For Hanging / Sliding Etc. As Per The Direction Of Engineer In Charge Including Conveyance To Site , Laying In Line And Level , Sealing All Cuttings In False Ceiling With Powder Coated Ms Cup , All Leads And Lifts Including All Labour Charges Etc. Complete. ( Unpleated Length Of The Cloth Maesurement Will Be Considered For Payment Also The Bottom And Top Foldings Will Not Be Considered In Cloth Measuremnet ) / Supplying And Fixing Powder Coated 20Mm Dia. Gi Round Tube Hanging Support Of Required Length ( App. Length 1.10M ) One End Fixing From Slab By Using 6Mm Dia. Expansion Bolt At A Distance Not More Than 2 M, C / C Down End Fixed To Powder Coated Aluminium Channel Frame 45X20mm X1mm Thick Section By Using Ss Screw As Per The Direction Of Engineer In Charge Including Conveyance To Site, Laying In Line And Level , Sealing All Gaps In False Ceiling Due To Hanging Supports , All Leads And Lifts, Including All Labour Charges Etc. Complete. 72 Supplying And Fixing Led Display Board With Projection Letter Of Size 0.90 M X 0.60 M Including Fixing Charges. 73 B.Electrical Work Point Wiring In Pvc Conduit With Modular Type Switch. Wiring For Light Point / Fan Point / Exhaust Fan Point / Call Bell Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Pvc , With Modular Switch, Modular Plate, Suitable Gi Box And Earthing The Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable Etc. As Required. Group B 74 Wiring For Light Point / Fan Point / Exhaust Fan Point / Call Bell Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable In Surface / Recessed Pvc , With Modular Switch, Modular Plate, Suitable Gi Box And Earthing The Point With 1.5 Sq.Mm Frls Pvc Insulated Copper Conductor Single Core Cable Etc. As Required. Group C 75 Wiring Through Pvc Conduit Wiring For Circuit / Submain Wiring Along With Earth Wire With The Following Sizes Of Fr Pvc Insulated Copper Conductor, Single Core Cable In Surface / Recessed Medium Class Pvc Conduit As Required. 2X1.5 Sq.Mm + 1X1.5 Sq.Mm Earth Wire 76 Wiring For Circuit / Submain Wiring Along With Earth Wire With The Following Sizes Of Fr Pvc Insulated Copper Conductor, Single Core Cable In Surface / Recessed Medium Class Pvc Conduit As Required.2X2.5 Sq.Mm + 1 X2.5 Sq Mm Earth Wire 77 Wiring For Circuit / Submain Wiring Along With Earth Wire With The Following Sizes Of Fr Pvc Insulated Copper Conductor, Single Core Cable In Surface / Recessed Medium Class Pvc Conduit As Required. 2X4 Sq.Mm + 1X4 Sq.Mm Earth Wire 78 Wiring For Circuit / Submain Wiring Along With Earth Wire With The Following Sizes Of Fr Pvc Insulated Copper Conductor, Single Core Cable In Surface / Recessed Medium Class Pvc Conduit As Required. 4X2.5 Sq.Mm + 2X2.5 Sq Mm Earth Wire 79 Wiring For Circuit / Submain Wiring Along With Earth Wire With The Following Sizes Of Fr Pvc Insulated Copper Conductor, Single Core Cable In Surface / Recessed Medium Class Pvc Conduit As Required. 4X4 Sq.Mm + 2X4 Sq.Mm Earth Wire 80 Supplying And Drawing Following Sizes Of Frls Pvc Insulated Copper Conductor, Single Core Cable In The Existing Surface / Recessed Steel / Pvc Conduit As Required 4X 6 Sqmm 81 Telephone Wiring In Existing Conduit: : Supplying And Drawing Following Pair 0.5 Sq Mm Fr Pvc Insulated Annealed Copper Conductor, Unarmored Telephone Cable In The Existing Surface / Recessed Steel / Pvc Conduit As Required. 2 Pair 82 Supplying And Drawing Co-Axial Tv Cable Rg-6 Grade, 0.7 Mm Solid Copper Conductor Pe Insulated, Shielded With Fine Tinned Copper Braid And Protected With Pvc Sheath In The Existing Surface / Recessed Steel / Pvc Conduit As Required 83 Supplying And Drawing Of Utp 4 Pair Cat 6 Lan Cable In The Existing Surface / Recessed Steel / Pvc Conduit As Required. 1 Run Of Cable 84 Modular Boxes, Bases & Cover Plate: Supplying And Fixing Following Modular Switch / Socket On The Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc As Required. 5 / 6 Amps Switch 85 Modular Boxes, Bases & Cover Plate: Supplying And Fixing Following Modular Switch / Socket On The Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc As Required. 3 Pin 5 / 6 Amp Socket Outlet 86 Modular Boxes, Bases & Cover Plate: Supplying And Fixing Following Modular Switch / Socket On The Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc As Required. 15 / 16 Amps Switch 87 Modular Boxes, Bases & Cover Plate: Supplying And Fixing Following Modular Switch / Socket On The Existing Modular Plate & Switch Box Including Connections But Excluding Modular Plate Etc As Required. 6Pin 15 / 16 Amps ( Universal ) Socket Outlet 88 Telephone Socket Outlet 89 Bell Push 90 Supplying And Fixing Modular Blanking Plate On The Existing Modular Plate & Switch Box Excluding Modular Plate As Required 91 Supplying And Fixing Following Size / Modules, Gi Box Alongwith Modular Base & Cover Plate For Modular Switches In Recess Etc. As Required.1 Or 2 Module ( 75 Mmx75 Mm ) 92 Supplying And Fixing Following Size / Modules, Gi Box Alongwith Modular Base & Cover Plate For Modular Switches In Recess Etc. As Required. 3 Module ( 100 Mmx75 Mm ) 93 Supplying And Fixing Following Size / Modules, Gi Box Alongwith Modular Base & Cover Plate For Modular Switches In Recess Etc. As Required. 6 Module ( 200 Mmx75 Mm ) 94 Supplying And Fixing Following Size / Modules, Gi Box Alongwith Modular Base & Cover Plate For Modular Switches In Recess Etc. As Required. 8 Module ( 200 Mmx150 Mm ) 95 Supplying And Fixing Following Modular Base & Cover Plate On Existing Modular Metal Boxes Etc. As Required 1 Or 2 Module ( 75 Mmx75 Mm ) 96 Supplying And Fixing Following Modular Base & Cover Plate On Existing Modular Metal Boxes Etc. As Required. 3 Module ( 100 Mmx75 Mm ) 97 Supplying And Fixing Following Modular Base & Cover Plate On Existing Modular Metal Boxes Etc. As Required . 6 Module ( 200 Mmx75 Mm ) 98 Supplying And Fixing Following Modular Base & Cover Plate On Existing Modular Metal Boxes Etc. As Required. 8 Module ( 200 Mmx150 Mm ) 99 S / F Pvc Conduit: Supplying And Fixing Of Following Sizes Of Medium Class Pvc Conduit Along With Accessories In Surface / Recess Including Cutting The Wall And Making Good The Same In Case Of Recessed Conduit As Required. ( Isi Make ) : 20 Mm 100 S / F Pvc Conduit: Supplying And Fixing Of Following Sizes Of Medium Class Pvc Conduit Along With Accessories In Surface / Recess Including Cutting The Wall And Making Good The Same In Case Of Recessed Conduit As Required. ( Isi Make ) : 25 Mm 101 S / F Pvc Conduit: Supplying And Fixing Of Following Sizes Of Medium Class Pvc Conduit Along With Accessories In Surface / Recess Including Cutting The Wall And Making Good The Same In Case Of Recessed Conduit As Required. ( Isi Make ) : 32 Mm 102 Supplying And Fixing 3 Pin, 5 A Ceiling Rose On The Existing Junction Box / Wooden Block Including Connections Etc. As Required. 103 Supplying And Fixing Brass Batten / Angle Holder Including Nconnections Etc. As Required 104 Supplying And Fixing Call Bell / Buzzer Suitable For Single Phase, 230 V, Complete As Required. 105 Installation Of Exhaust Fan In The Existing Opening, Including Making Good The Damage, Connection, Testing, Commissioning Etc. As Required. Upto 380 Mm Sweep 106 Extra For Fixing The Louvers / Shutters Complete With Frame For A Exhaust Fan Of All Sizes. 107 Supply And Fixing Of Mccb Providing And Fixing Following Rating And Breaking Capacity And Pole Mccb With Thermomagnetic Release And Terminal Spreaders In Existing Cubicle Panel Board Including Drilling Holes In Cubicle Panel, Making Connections, Etc. As Required. 25 / 35 Ka ( Ics=100%Icu ) , 4 Pole, Current Limiting Type Mccb Having Thermal Setting Range Of 80 - 100% With Thermal Magnetic Release Having Adjustable Ol N 125 A, 25 / 35 Ka, Fp Mccb 108 Supply And Fixing Supplying And Fixing Following Rating, Four Pole, 415 V, Isolator In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. Fp Isolator 40A 109 Supply And Fixing Supplying And Fixing Following Rating, Four Pole, 415 V, Isolator In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. 63 A 110 Supply And Fixing Dp Isolator : Supplying And Fixing Following Rating, Double Pole, 240 V, Isolator In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. 40 A 111 Supply And Fixing Fp Rccb Supplying And Fixing Following Rating, Double Pole, ( Single Phase And Neutral ) , 240 V, Residual Current Circuit Breaker ( Rccb ) , Having A Sensitivity Current 30 Ma In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. 25 A 112 Supply And Fixing Fp Rccb Supplying And Fixing Following Rating, Double Pole, ( Single Phase And Neutral ) , 240 V, Residual Current Circuit Breaker ( Rccb ) , Having A Sensitivity Current 30 Ma In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. 40 A 113 Supply And Fixing Of Tpn Mcb Db Supplying And Fixing Following Way, Horizontal Type Three Pole And Neutral, Sheet Steel, Mcb Distribution Board, 415 V, On Surface / Recess, Complete With Tinned Copper Bus Bar, Neutral Bus Bar, Earth Bar, Din Bar, Interconnections, Powder Painted Including Earthing Etc. As Required. ( But Without Mcb / Rccb / Isolator ) 4 Way ( 8 + 12 ) , Double Door 114 Supply And Fixing Of Tpn Mcb Db Supplying And Fixing Following Way, Horizontal Type Three Pole And Neutral, Sheet Steel, Mcb Distribution Board, 415 V, On Surface / Recess, Complete With Tinned Copper Bus Bar, Neutral Bus Bar, Earth Bar, Din Bar, Interconnections, Powder Painted Including Earthing Etc. As Required. ( But Without Mcb / Rccb / Isolator ) 6 Way ( 8 + 18 ) , Double Door 115 Supply And Fixing Of Mcb Vdb Supply And Installation Of Sheet Steel, Phosphatised And Painted, Dust And Vermin Proof Enclosure Of Mcb Db Including Copper / Brass Bus Bar, Neutral Link, Earth Bus And Din Rail Suitable For Fixing Mcb / Isolator Etc. Fixed On Wall Using Suitable Anchor Bolts Or Fixed In Recess Including Cutting Hole On The Wall , Making Good The Damages, Colour Washing Etc. As Required 8 Way ( 4 + 24 ) , Double Door N 116 Supply And Fixing Of Mcb Supplying And Fixing 5 A To 32 A Rating, 240 / 415 V, 10 Ka, “C” Curve, Miniature Circuit Breaker Suitable For Inductive Load Of Following Poles In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. 6 / 32 A Sp Mcb 117 Supply And Fixing Of Mcb Supplying And Fixing 5 A To 32 A Rating, 240 / 415 V, 10 Ka, “C” Curve, Miniature Circuit Breaker Suitable For Inductive Load Of Following Poles In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. 40 A Triple Pole Mcb 118 Supply And Fixing Fp Rccb Supplying And Fixing Following Rating, Four Pole, ( Three Phase And Neutral ) , 415 V, Residual Current Circuit Breaker ( Rccb ) , Having A Sensitivity Current 30 Ma In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required 40A 30 Ma 119 Supply And Fixing Fp Rccb Supplying And Fixing Following Rating, Four Pole, ( Three Phase And Neutral ) , 415 V, Residual Current Circuit Breaker ( Rccb ) , Having A Sensitivity Current 30 Ma In The Existing Mcb Db Complete With Connections, Testing And Commissioning Etc. As Required. 63A 100 Ma 120 End Terminations Supplying And Making End Termination With Brass Compression Gland And Aluminium Lugs For Following Size Of Pvc Insulated And Pvc Sheathed / Xlpe Aluminium Conductor Cable Of 1.1 Kv Grade As Required. 4 X 16 Sq. Mm 121 End Terminations Supplying And Making End Termination With Brass Compression Gland And Aluminium Lugs For Following Size Of Pvc Insulated And Pvc Sheathed / Xlpe Aluminium Conductor Cable Of 1.1 Kv Grade As Required. 4 X 25 Sq. Mm 122 End Terminations Supplying And Making End Termination With Brass Compression Gland And Aluminium Lugs For Following Size Of Pvc Insulated And Pvc Sheathed / Xlpe Aluminium Conductor Cable Of 1.1 Kv Grade As Required. 4 X 35 Sq. Mm 123 End Terminations Supplying And Making End Termination With Brass Compression Gland And Aluminium Lugs For Following Size Of Pvc Insulated And Pvc Sheathed / Xlpe Aluminium Conductor Cable Of 1.1 Kv Grade As Required. 4 X 50 Sq. Mm 124 End Terminations Supplying And Making End Termination With Brass Compression Gland And Aluminium Lugs For Following Size Of Pvc Insulated And Pvc Sheathed / Xlpe Aluminium Conductor Cable Of 1.1 Kv Grade As Required. 4 X 90 Sq. Mm 125 Earthing Earthing With Copper Earth Plate 600 Mm X 600 Mm X 3 Mm Thick Including Accessories, And Providing Masonry Enclosure With Cover Plate Having Locking Arrangement And Watering Pipe Of 2.7 Meter Long Etc. With Charcoal / Coke And Salt As Required 126 Providing And Fixing 4.00 Mm Dia Copper Wire On Surface Or In Recess For Loop Earthing As Required 127 Providing And Fixing 25 Mm X 5 Mm G.I. Strip In 40 Mm Dia G.I. Pipe From Earth Electrode Including Connection With G.I. Nut, Bolt, Spring, Washer Excavation And Re-Filling Etc. As Required. 128 Providing And Fixing 25 Mm X 5 Mm G.I. Strip On Surface Or In Recess For Connections Etc. As Required. 129 Cable Supply Supply, Laying And Clamping Of 1 No. Pvc Insulated And Pvc Sheathed Armoured Aluminium Power Cable, 1.1 Kv Grade Of The Following Sizes Using Clamps Noted Along With The Cables, Spacing Of Clamps Not Exceeding 60Cms, Making Good The Damages , Colour Washing Etc. As Required. 4 Core 95 Sq Mm With Factory Made Clamp 130 Supply, Laying And Clamping Of 1 No. Pvc Insulated And Pvc Sheathed Armoured Aluminium Power Cable, 1.1 Kv Grade Of The Following Sizes Using Clamps Noted Along With The Cables, Spacing Of Clamps Not Exceeding 60Cms, Making Good The Damages , Colour Washing Etc. As Required. 4 Core 50 Sq Mm With Factory Made Clamp 131 Supply, Laying And Clamping Of 1 No. Pvc Insulated And Pvc Sheathed Armoured Aluminium Power Cable, 1.1 Kv Grade Of The Following Sizes Using Clamps Noted Along With The Cables, Spacing Of Clamps Not Exceeding 60Cms, Making Good The Damages , Colour Washing Etc. As Required. 4 Core 35 Sq Mm With Factory Made Clamp 132 Supply, Laying And Clamping Of 1 No. Pvc Insulated And Pvc Sheathed Armoured Aluminium Power Cable, 1.1 Kv Grade Of The Following Sizes Using Clamps Noted Along With The Cables, Spacing Of Clamps Not Exceeding 60Cms, Making Good The Damages , Colour Washing Etc. As Required. 4 Core 25 Sq Mm With Factory Made Clamp 133 Supply, Laying And Clamping Of 1 No. Pvc Insulated And Pvc Sheathed Armoured Aluminium Power Cable, 1.1 Kv Grade Of The Following Sizes Using Clamps Noted Along With The Cables, Spacing Of Clamps Not Exceeding 60Cms, Making Good The Damages , Colour Washing Etc. As Required. 4 Core 16 Sq Mm With Factory Made Clamp 134 Supply, Conveyance, Installation, Testing And Commissioning Of Pre-Wired 36 W Led Light Fittings 60X60 Cms Squre With All Accessories And Led Lamps Etc. Suspended From Ceiling Using 2 Nos Steel Chain Of Length Not Exceeding 30 Cm Properly Hooked To Steel Hooks Anchored To The Ceiling And Giving Connections With Required Length Of 16 / 0.20Mm 3 Core Copper Conductor Flex Wire Conforming To Relevant Iss Or Extending The Original Wiring And Giving Connection Etc. As Required. 135 S&F Frame For Led Light 60 X 60 136 1X8w Led Lamp Including All Accessories For Mounting On The Existing Angle Batten 137 Sitc Of 18 W Round Recess Type Led Lamp. ( Edgeprorddlr 18W Led857s ) Or Equivalent 138 Sitc Of 18 W Led Tube Light ( Titaniasleek 1149T5 Dstl18w Led865spc ) Or Equivalent 139 Sitc Of 35 W Led Street Light In Gi Pipe Bend To Shape, ( Enduracity Liteplatplussl 35W Led757 Sasybopc ) Or Equivalent 140 Supplying And Fixing Following Fire And Safety Equipments 4 Kg Fire Extingushers ( Abc Powder Type With Nabl Approval ) 141 Supply And Fixing Of Exhaust Fan Supplying And Installing By Testing And Commissioning Of 380 Mm Exhaust Fan As Specified 142 Supplying And Installing By Testing And Commissioning Of 305 Mm Shuttered Exhaust Fan In Plastix Body As Specified 143 Supply, Conveyance, Installation Testing And Commissioning Of The 1 No. Audio System Consisting Of 45 W Medium Power Pa Amplifier Ac & 12 V Dc Operation ( Ahuja ) And Recess Mounting Ceiling Speakers 6 Nos And 2 Nos Box Type Speaker Cs 506It 6 W Rms Power Ahuja Pa System And 1 No. Dvd Player With All Accessories Best Quality Philips / Sony / Samsung / L.G. 144 Painting Letters Of Figures Of 2.50 Cm, 4Cm, 5 Cm Height Etc., 145 Rj 45 Data Outlet 146 Charges For Dismantling The Existing Ei Complete Making Good The Damages Of The Wall And Conveying The Dismantled Materials To Store Etc., As Required 147 63 A, Tp Mcb ( C Curve ) , 10 Ka Breaking Capacity 148 Fp Enclosure For Independent Mounting Of Mcb / Rccb / Rcbo 149 Supply And Providing The Following Sizes Of Cast Iron Gully Trap With Covering At The Top Of The Inspection Chamber Of Earth Pit As Required 300 X 300 X 6 Mm Cast Iron Gully Trap With Covering 150 Supply And Providing Earth Lead From The Test Joint To The Earth Electrode Using The Following Sizes Of Conductors / Strips Including Cutting, Drilling Necessary Holes ( In Case Of Strip ) And Fixing Firmly With Plate Test Joint Etc As Required.25 X 3 Mm Gi Strip 151 Dismantling The Existing Electrical Line And Fittings Complete And Conveying To The Store And Handed Over The List. 152 Supply And Drawing Bare Earthing Conductors Of The Along With Wiring / Cables And Giving Connection As Required. 2.00 Mm Copper Conductor ( 14 Swg ) 153 2.65 Mm Copper Conductor ( 12 Swg ) 154 Supplying And Providing Earth Clamps For Siemens / Tropodur Type Cable Glands Of Suitable Length And Other Dimensions Noted Along With Each Size Of Glands For The Following Sizes Of Cables As Required. 25 Sq - 95Sq Mm With 20 Mm Wide X 1.20 Mm Thick Clip 155 Supplying And Providing Earth Clamps For Siemens / Tropodur Type Cable Glands Of Suitable Length And Other Dimensions Noted Along With Each Size Of Glands For The Following Sizes Of Cables As Required. 4Sqmm-16 Sq Mm With 12 Mm Wide X 1 Mm Thick Clip 156 Sitc Of 400Mm Swept Area Wall Fan 157 Supply Of Lt Switch Board Cubicle Type, Made Out Of 2Mm Thick Crca Sheet, Totally Enclosed, Ip42, Free Standing, Floor Mounting, Dust And Vermin Proof, Powder Coated, Indoor, Compartmentalised, Suitable For Operation On 3 Phase And Neutral, 415 V, 50Hz Ac System With Busbars Extendable On Both Sides, Including All The Necessay Internal Wiring , Suitable Spreader Etc. The Panel Shall Be Fabricated From A Firm Having Cpri Certification With Test Certificates For Similar Panel ( Required For Short Circuit Rating, Temperature Rise And Ip Classification ) And With Following Switchgears, Metering Instruments And Accessories Etc. Complete As Required As Per Drawing & Specification. Nincomer N160a, Fp, Mccb 36Ka, Thermal Release Over Load And Adjustable Short Circuit-1 No Nbusbar-200A Tpn Busbar Chamber With Aluminium Busbar Nmeters-. N ( 0 To 500 ) V Voltmeter For 3 Phase, 4 Wire Operation With Selector Switch - 1 Set N ( 0-250 ) A Ammeter For 3 Phase, 4 Wire Operation -3 Nos200 / 5A 15Va Class 1 Resin Cast Ct - 3Nos Nintelligent Multifunction Panel Meter ( Voltage, Current , Kw, Kwh, Pf, Hz ) With Lcd Display - 1 No N4a, C Curve Sp Mcb - 3 Nos, Ryb Indication Lamp, Led Type - 3 Nos. Outgoings N63 A Fp Moulded Case Circuit Breaker With Thermal Release And Neutral Link ( Ics =100%Icu= 25Ka ) .-4 Nos 125 A Fp Moulded Case Circuit Breaker With Thermal Release And Neutral Link ( Ics =100%Icu= 25Ka ) .-1 Nos 158 Kseb Meter Board Nsupply, Installation, Testing And Commissioning Of Energymeter Box Of Cubicle Construction Made From 16Swg Crca Sheet Suitable For Accomodating One Number Of Three Phase Electronic Energymeter With 125 / 5A Class .5 Ct And 3 Nos Of 160A Hrc Fuse, 160 A Fp Sfdu And Neutral Link, Interconnections, Providing Necessary Supports Made From The Same Gauge Crca Sheet To Fix Energymeters, Etc.The Cubicle Shall Be Provided With Hinged Door Construction And Vision Panel For The Meter Compartment. Suitable Knock Out For Cable Entry And Exit Shall Be Provided. The Entire Board Shall Be Painted With 2 Coats Of Synthetic Enamel Paint Over A Coat Of Zinc Chromate Primer Etc As Required Including Fixing It On Wall, Making Good The Damages Colour Washing Etc. Complete.

Key Value

Document Fees
INR 2950 /-
EMD
INR 50000.0 /-
Tender Value
INR 29.21 Lakhs /-

BOQ Items

Name of Work: Setting up of Dialysis centre at THQH,Nemom ,Trivandrum
Sl. No. Item Description Item Code / Make Quantity (Q) Units
1 1 Dismantling tile work in floors and roofs laid in cement mortar including stacking material within 50 metres lead.For thickness of tiles 10 mm to 25 mm C1 315.6 Sqm
2 2 Dismantling doors, windows and clerestory windows (steel or wood) shutter including chowkhats, architrave, holdfasts etc. complete and stacking within 50 metres lead :Of area 3 sq. metres and below C2 8 Nos
3 3 Demolishing brick work manually / by mechanical means including stacking of serviceable material and disposal of unserviceable material within 50 metres lead as per direction of Engineer-in-Charge.In cement mortar C3 1.9 Cum
4 4 Demolishing R.C.C. work manually / by mechanical means including stacking of steel bars and disposal of unserviceable material with in 50 metres lead as per direction of Engineer -in-Charge. C4 1 Cum
5 5 Dismantling of flushing cistern of all types (C.I./PVC/Vitrious China) including stacking of useful materials near the site and disposal of unserviceable materials within 50 metres lead. C5 8 Nos
6 6 Disposal of building rubbish/ malba/ similar unserviceable, dismantled or waste materials by mechanical means, including loading, transporting, unloading to approved municipal dumping ground or as approved by Engineer-in-charge, beyond 50 m initial lead, for all leads including all lifts involved C6 2 Cum
7 7 Dismantling aluminium / Gypsum partitions, doors, windows, fixed glazing and false ceiling including disposal of unserviceable surplus material and stacking of serviceable material with in 50 metres lead as directed by Engineer - in-Charge C7 4.03 Sqm
8 8 Dismantling old plaster or skirting raking out joints and cleaning the surface for plaster including disposal of rubbish to the dumping ground within 50 metres lead. C8 10 Sqm
9 9 Earth work in excavation by mechanical means (Hydraulic excavator) / manual means in foundation trenches or drains (not exceeding 1.5 m in width or 10 sqm on plan), including dressing of sides and ramming of bottoms, lift upto 1.5 m, including getting out the excavated soil and disposal of surplus excavated soil as directed, within a lead of 50 m.All kinds of soil. C9 24 Cum
10 10 Solid block masonry using pre cast solid blocks (Factory made) of size 30x20x15cm or nearest available size confirming to IS 2185 part I of 1979 for super structure above floor two level upto floor five level with thickness 15cm in : CM 1:6 ( 1 cement : 6 coarse sand) etc complete C10 4.34 Cum
11 11 Reinforced cement concrete work in walls (any thickness), including attached pilasters, buttresses, plinth and string courses, fillets, columns, pillars, piers, abutments, posts and struts etc. up to floor five level, excluding cost of centering, shuttering, finishing and reinforcement :1:1.5:3 (1 cement : 1.5 coarse sand : 3 graded stone aggregate 20 mm nominal size) C11 1 Cum
12 12 Centering and shuttering including strutting, propping etc. and removal of form for :Lintels, beams, plinth beams, girders, bressumers and\ncantilevers C12 5 Sqm
13 13 Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding all complete above plinth level.Thermo- echanically Treated bars C13 100 Kg
14 14 Providing and laying damp-proof course 50 mm thick with cement concrete 1:2:4(1 cement : 2 coarse sand : 4 graded stone aggregate 20 mm nominal size). C14 125.93 Sqm
15 15 Providing and laying in position cement concrete of specified grade excluding the cost of centering and shuttering - All work up to plinth level :1:4:8 (1 Cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) C15 3.02 Cum
16 16 12 mm cement plaster of mix :1:4 (1 cement: 4 fine sand) C16 33.58 Sqm
17 17 Repairs to plaster of thickness 12 mm to 20 mm in patches of area 2.5 sq meters and under, including cutting the patch in proper shape, raking out joints and preparing and plastering the surface of the walls complete, including disposal of rubbish to the dumping ground within 50 meters lead:With cement mortar 1:4 ( 1 cement : fine sand) C17 10 Sqm
18 18 Providing and laying water proofing treatment in sunken portion of WCs, bathroom etc., by applying cement slurry mixed with water proofing cement compound consisting of applying : a) First layer of slurry of cement @ 0.488 kg/sqm mixed with water proofing cement compound @ 0.253 kg/sqm. This layer will be allowed to air cure for 4 hours. b) Second layer of slurry of cement @ 0.242 kg /sqm mixed with water proofing cement compound @ 0.126 kg/ sqm. This layer will be allowed to air cure for 4 hours followed with water curing for 48 hours. The rate includes preparation of surface, treatment and sealing of all joints, corners, junctions of pipes and masonry with polymer mixed slurry. C18 3.22 Sqm
19 19 Providing and laying vitrified floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm. C19 125.93 Sqm
20 20 Providing and laying Mat finish ceramic floor tiles in different sizes (thickness to be specified by the manufacturer) with water absorption less than 0.08% and conforming to IS : 15622, of approved make, in all colours and shades, laid on 20 mm thick cement mortar 1:4(1 cement : 4 coarse sand), including grouting the joints with white cement and matching pigments etc., complete.Size of Tile 600 x 600 mm. C20 27.38 Sqm
21 21 Providing and fixing I st quality ceramic glazed wall tiles conforming to IS : 15622 (thickness to be specified by the manufacturer), of approved make, in all colours, shades except burgundy, bottle green, black of any size as approved by Engineer -in-Charge, in skirting, risers of steps and dados, over 12 mm thick bed of cement mortar 1:3 (1 cement : 3 coarse sand) and jointing with grey cement slurry @ 3.3 kg per sqm, including pointing in white cement mixed with pigment of matching shade complete. C21 122.96 Sqm
22 22 Providing and laying Polished Granite stone flooring in required design and patterns, in linear as well as curvilinear portions of the building all complete as per the architectural drawings with 18 mm thick stone slab over 20 mm (average) thick base of cement mortar 1:4 (1 cement : 4 coarse sand) laid and jointed with cement slurry and pointing with white cement slurry admixed with pigment of matching shade including rubbing , curing and polishing etc. all complete as specified and as directed by the Engineer-in-Charge.Polished Granite stone slab jet Black, Cherry Red, Elite Brown, Cat Eye orequivalent. C22 3.13 Sqm
23 23 Grouting the joints of flooring tiles having joints of 3 mm width, using epoxy grout mix 0.70 kg of organic coated filler of desired shade (0.10 kg of hardener and 0.20 kg of resin per kg). including filling /grouting and finishing complete as per direction of Engineer-in-charge.Size of Tile 600x600 mm C23 125.93 Sqm
24 24 Providing and laying 60 mm thick factory made cement concrete interlocking paver block of M - 30 grade made by block making machine with strong vibratory compaction, of approved size, design & shape, laid in required colour and pattern over and including 50 mm thick compacted bed of coarse sand, filling the joints with fine sand etc. all complete as per the direction of Engineer-in-charge. C24 26 Sqm
25 25 Providing and fixing aluminium work for doors, windows, ventilators and partitions with extruded built up standard tubular sections/ appropriate Z sections and other sections of approved make conforming to IS: 733 and IS: 1285, fixing with dash fasteners of required dia and size, including necessary filling up the gaps at junctions, i.e. at top, bottom and sides with required EPDM rubber/ neoprene gasket etc. Aluminium sections shall be smooth, rust free, straight, mitred and jointed mechanically wherever required including cleat angle, Aluminium snap beading for glazing / paneling,\nC.P. brass / stainless steel screws, all complete as per architectural drawings and the directions of Engineer-in-charge. (Glazing, paneling and dash fasteners to be paid for separately) :Polyester powder coated aluminium (minimum thickness of polyester powder coating 50 micron) C25 633.61 Kg
26 26 Providing and fixing glazing in aluminium door, window, ventilator shutters and partitions etc. with EPDM rubber / neoprene gasket etc. complete as per the architectural drawings and the directions of engineer-in-charge. (Cost of aluminium snap beading shall be paid in basic item):With float glass panes of 4.0 mm thickness C26 34.52 Sqm
27 27 Providing and fixing Pre -laminated medium density fibre board exterior grade (Grade-I) IS:14587:1998 marked, to frame, backing or studding with screws etc. complete ( Frames, backing or studding to be paid separately). Pre-laminated with decorative lamination on both side exterior Grade - I MDF Board 12 mm thick confirming to IS:14587 C27 15.99 Sqm
28 28 Providing and fixing false ceiling at all height including providing and fixing of frame work made of special sections, power pressed from M.S. sheets and galvanized with zinc coating of 120 gms/ sqm (both side inclusive) as per IS : 277 and consisting of angle cleats of size 25 mm wide x 1.6 mm thick with flanges of 27 mm and 37 mm, at 1200 mm centre to centre, one flange fixed to the ceiling with dash fastener 12.5 mm dia x 50 mm long with 6 mm dia bolts, other flange of cleat fixed to the angle hangers of 25x10x0.50 mm of required length with nuts & bolts of required size and other end of angle hanger fixed with intermediate G.I. channels 45x15x0.9 mm running at the spacing of 1200 mm centre to centre, to which the ceiling section 0.5 mm thick bottom wedge of 80 mm with tapered flanges of 26 mm each having lips of 10.5 mm, at 450 mm centre to centre, shall be fixed in a direction perpendicular to G.I. intermediate channel with connecting clips made out of 2.64 mm dia x 230 mm long G.I. wire at every junction, including fixing perimeter channels 0.5 mm thick 27 mm high having flanges of 20 mm and 30 mm long, the perimeter of ceiling fixed to wall/partition with the help of rawl plugs at 450 mm centre, with 25 mm long dry wall screws @ 230 mm interval, including fixing of gypsum board to ceiling section and perimeter channel with the help of dry wall screws of size 3.5x25 mm at 230 mm c/c, including jointing and finishing to a flush finish of tapered and square edges of the board with recommended jointing compound, jointing tapes, finishing with jointing compound in 3 layers covering upto 150 mm on both sides of joint and two coats of primer suitable for board, all as per manufacturer's specification and also including the cost of making openings for light fittings, grills, diffusers, cutouts made with frame of perimeter channels suitably fixed, all complete as per drawings, specification and direction of the Engineer in Charge but excluding the cost of painting with: 12.5 mm thick tapered edge gypsum fire resistant board conforming to IS; 2095-Part I C28 125.93 Sqm
29 29 Providing and fixing double action hydraulic floor spring of approved brand and manufacture conforming to IS: 6315, having brand logo embossed on the body / plate with double spring mechanism and door weight upto 125 kg, for doors including cost of cutting floors, embeding in floors as required and making good the same matching to the existing floor finishing and cover plates with brass pivot and single piece M.S. sheet outer box with slide plate etc. complete as per the direction of Engineer -in- Charge.With stainless steel cover plate minimum 1.25 mm thickness C29 6 Nos
30 30 Providing and fixing aluminium tubular handle bar 32 mm outer dia, 3.0mm thick & 2100 mm long with S.S. screws etc. complete as per direction of Engineer -in-Charge. Powder coated minimum thickness 50 micron aluminium tubular handle bar C30 44 Nos
31 31 Providing and fixing aluminium tower bolts, ISI marked, anodised(anodic coating not less than grade AC 10 as per : 1868), transparent or dyed to required colour or shade, with necessary screws complete:250x10 mm C31 22 Nos
32 32 Providing and fixing aluminium extruded section body tubular type universal hydraulic door closer (having brand logo with ISI, IS : 3564, embossed on the body, door weight upto 36 kg to 80 kg and door width form 701 mm to 1000 mm), with double speed adjustment with necessary accessories and screws etc. complete. C32 6 Nos
33 33 Providing and fixing 100 mm brass locks ( best make of approved quality ) for aluminium doors including necessary cutting and making good etc. complete C33 9 Nos
34 34 Providing and fixing aluminium hanging floor door stopper, ISI marked, anodised (anodic coating not less than grade AC 10 as per IS: 1868) transparent or dyed to required colour and shade, with necessary screws etc. complete.Twin rubber stopper C34 12 Nos
35 35 Providing and fixing stainless steel (Grade 304) railing made of Hollow tubes, channels, plates etc., including welding, grinding, buffing, polishing and making curvature (wherever required) and fitting the same with necessary stainless steel nuts and bolts complete, i/c fixing the railing with necessary accessories & stainless steel dash fasteners, stainless steel bolts etc., of required size on the top of the floor or the side of waist slab with suitable arrangement as per approval of Engineer-in-charge, (for payment purpose only weight of stainless steel members shall be considered excluding fixing accessories such as nuts, bolts, fasteners etc.) C35 7.57 Kg
36 36 Providing and fixing 3 mm thick ACP Sheet fixed in aluminum doors with C.P. brass / stainless steel screws etc. complete. Including all cost conveyance and all labour charges etc complete. C36 43.85 Sqm
37 37 Frosted film - Supply and installation of 3M make frosted film pattern throughout all the internal glass panels wherever required of approx. 1.5 m height as per the approved pattern. C37 15.99 Sqm
38 38 Applying one coat of water thinnable cement primer of approved brand and manufacture on wall surface:Water thinnable cement primer C38 33.58 Sqm
39 39 Finishing walls with Premium Acrylic Smooth exterior paint with Silicone additives of required shade:New work (Two or more coats applied @ 1.43 ltr/ 10 sqm over and including priming coat of exterior primer applied @ 2.20 kg/ 10 sqm) C39 229.6 Sqm
40 40 Providing and applying white cement based putty of average thickness 1 mm, of approved brand and manufacturer, over the plastered wall surface to prepare the surface even and smooth complete. C40 81.17 Sqm
41 41 Wall painting with acrylic emulsion paint of approved brand and manufacture to give an even shade:Two or more coats on new work C41 335.27 Sqm
42 42 Painting with synthetic enamel paint of approved brand and manufacture to give an even shade:Two or more coats on new work C42 20 Sqm
43 43 Steel work in built up tubular (round, square or rectangular hollow tubes etc.) trusses etc., including cutting, hoisting, fixing position and applying a priming coat of approved steel primer, including welding and bolted with special shaped washers etc. complete. Hot finished welded type tubes C43 250 Kg
44 44 Providing & fixing poly carbonate multi wall plain sheet 5 mm thick as approved by the Engineer in charge and should be supplied in a single length of 12 M or as decide by the Engineer in charge. The sheets shall be fixed using self drilling/ self tapping screw of size ( 5.5x55 mm) with EPDM seal complete upto any pitch in horizontal/ vertical/ curved surfaces, but excluding the cost of purlins, rafters, trusses, and including cutting to size and shapes where ever required. C44 6.4 Sqm
45 45 Fabricating and Providing stainless steel table of size 120 X 60 X 85+15 mounted with Bulk washing Sink, of size 110 x 50 x 45 cm and drain coupling,All frame works shall be made with stainless steel 38mm dia or nearest available 16SWG round hollow sections fitted with adequate horizontal supports.The sunken table top and sink will be of 16GA, 304 Grade SS satin finished, table top with all resulting edges double beeded on three sides with no burrs or other excess material left,and to be reinforced underneath edges with 32x32x3mm thick stainless steel angle framework.The underneath support shall be of 18x75x18 SS channel sections.Unit to have 150mm high back Splash.White nylon bullets to be fitted into all four legs,as per drawings and technical specification, including cost and conveyance of all materials, labour and other incidentals etc. complete. C45 1 No
46 46 Fabricating and Providing stainless steel Sink of size 60 x30x30 cm with and drain coupling,All frame works shall be made with stainless steel 38mm dia or nearest available 16SWG round hollow sections fitted with adequate horizontal supports.The sunken table top and sink will be of 16GA, 304 Grade SS satin finished, table top with all resulting edges double beeded on three sides with no burrs or other excess material left,and to be reinforced underneath edges with 32x32x3mm thick stainless steel angle framework.The underneath support shall be of 18x75x18 SS channel sections.Unit to have 150mm high back Splash.White nylon bullets to be fitted into all four legs,as per drawings and technical specification, including cost and conveyance of all materials, labour and other incidentals etc. complete C46 1 No
47 47 Providing and placing on terrace (at all floor levels) polyethylene water storage tank, ISI : 12701 marked, with cover and suitable locking arrangement and making necessary holes for inlet, outlet and overflow pipes but without fittings and the base support for tank. C47 8000 Ltr
48 48 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.20 mm CPVC nominal outer dia Pipes C48 60 RM
49 49 Providing and fixing Chlorinated Polyvinyl Chloride (CPVC) pipes, having thermal stability for hot & cold water supply, including all CPVC plain & brass threaded fittings, including fixing the pipe with clamps at 1.00 m spacing. This includes jointing of pipes & fittings with one step CPVC solvent cement and testing of joints complete as per direction of Engineer in Charge.25 mm CPVC nominal outer dia Pipes C49 25 RM
50 50 Providing and fixing wash basin with C.I. brackets, 15 mm C.P. brass pillar taps, 32 mm C.P. brass waste of standard pattern, including painting of fittings an brackets, cutting and making good the walls wherever require :White Vitreous China Wash basin size 550x400 mm with a pair of 15 mm C.P. brass pillar taps C50 3 Nos
51 51 Providing and fixing white vitreous china pedestal type water closet (European type W.C. pan) with seat and lid, 10 litre low level white P.V.C. flushing cistern, including flush pipe, with manually controlled device (handle lever), conforming to IS : 7231, with all fittings and fixtures complete, including cutting and making good the walls and floors wherever required :W.C. pan with ISI marked white solid plastic seat and lid C51 2 Nos
52 52 Providing and fixing C.P. brass long body bib cock of approved quality conforming to IS standards and weighing not less than 690 gms.15 mm nominal bore C52 2 Nos
53 53 Providing and fixing PTMT Bottle Trap for Wash basin and sink.Bottle trap 31 mm single piece moulded with height of 270 mm, effective length of tail pipe 260 mm from the center of the waste coupling, 77 mm breadth with 25 mm minimum water seal, weighing not less than 260 gms C53 3 Nos
54 54 Supplying and fixing CP Health Faucet superior quality ( Jagur or equvalent make ) including cost of materials and labour charges etc complete as per the direction of site Engineer-in-charge. C54 2 Nos
55 55 Providing and fixing mirror of superior glass ( of approved quality) and of required shape and size with plastic moulded frame of approved make and shade with 6 mm thick hard board backing :Rectangular shape 453x357 mm C55 4 Nos
56 56 Providing and fixing uplasticised PVC connection pipe with brass unions:30 cm length 20 mm nominal bore C56 6 Nos
57 57 Providing and fixing PTMT Soap Dish Holder having length of 138 mm, breadth 102 mm, height of 75 mm with concealed fittings arrangements, weighing not less than 106 gms. C57 4 Nos
58 58 Providing and fixing PTMT towel rail complete with brackets fixed to wooden cleats with CP brass screws with concealed fitting arrangement of approved quality and colour600 mm long towel rail with total length of 645 mm, width 78 mm and effective height of 88 mm, weighting not less than 190 gms C58 4 Nos
59 59 Supplying and fixing 20mm CPVC valve etc complete\n C59 13 No
60 60 Supplying and fixing 25mm CPVC valve etc complete\n C60 2 No
61 61 Supplying and fixing 15mm L' bow tap etc complete\n C61 1 No
62 62 Supplying and fixing 15 mm stainless steel tap etc complete Long body\n C62 12 Nos
63 63 Supplying and fixing steel' S' hooks etc complete\n C63 40 Nos
64 64 Supplying and layin 50mm dia PVC pipe(10kg/cm2) including cost of all fittings such as tees,elbows, clamps,screws cost and conveyance of all materials etc. complete\n C64 10 RM
65 65 Supplying and laying 25mm dia PVC pipe(10kg/cm2) including cost of all fittings such as tees,elbows, clamps,screws cost and conveyance of all materials etc. complete\n C65 35 RM
66 66 Supplying and laying 110mm dia PVC pipe(10kg/cm2) including cost of all fittings such as tees,elbows, clamps,screws cost and conveyance of all materials etc. complete C66 45 RM
67 67 Supplying and laying 75mm dia PVC pipe(6kg/cm2) including cost of all fittings such as tees,elbows, clamps,screws cost and conveyance of all materials etc. complete C67 50 Sqm
68 68 Supplying and fixing 15mm CPVC Push pull conecter including all cost conveyance all labour charges etc complete C68 5 Nos
69 69 Supplying and fixing ISI mark PVC frame with door shutter including all fittings and locking arrangement etc complete C69 2 Nos
70 70 Providing and fixing Vertical blinds as per the direction of Engineer in charge C70 13.5 Sqm
71 71 Supplying and laying polyster , washable and stainfree cloth(Bio-Active fabric washable germfree-suitable for Diaysis room) curtain system with maximum curtain cloth height 230cm (top 30 cm white colour net and 200cm light blue colour as per approval) stitching with stifiner tape,pleats,ironing and laying in dialysis room around each bed using PVC runner with hooks&stopper for hanging/sliding etc. as per the direction of engineer in charge including conveyance to site , laying in line and level , sealing all cuttings in false ceiling with powder coated MS cup ,all leads and lifts including all labour charges etc. complete.(unpleated length of the cloth maesurement will be considered for payment also the bottom and top foldings will not be considered in cloth measuremnet)/Supplying and fixing powder coated 20mm dia. GI round tube hanging support of required length (app. length 1.10m) one end fixing from slab by using 6mm dia. expansion bolt at a distance not more than 2 m, c/c down end fixed to powder coated aluminium channel frame 45x20mm x1mm thick section by using SS screw as per the direction of engineer in charge including conveyance to site, laying in line and level ,sealing all gaps in false ceiling due to hanging supports ,all leads and lifts, including all labour charges etc. complete. C71 68.4 Sqm
72 72 Supplying and fixing LED display board with projection letter of size 0.90 m x 0.60 m including fixing charges. C72 1 No
73 73 B.ELECTRICAL WORK Point wiring in PVC conduit with modular type switch. Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed PVC , with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group B E1 30 No
74 74 Wiring for light point/ fan point/ exhaust fan point/ call bell point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable in surface / recessed PVC , with modular switch, modular plate, suitable GI box and earthing the point with 1.5 sq.mm FRLS PVC insulated copper conductor single core cable etc. as required. Group C E2 15 No
75 75 Wiring through PVC conduit Wiring for circuit/submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required. 2X1.5 sq.mm + 1X1.5 sq.mm earth wire E3 150 Meter
76 76 Wiring for circuit/submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required.2X2.5 sq.mm + 1 X2.5 sq mm earth wire E4 200 Metre
77 77 Wiring for circuit/submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required. 2X4 sq.mm + 1X4 sq.mm earth wire E5 40 Metre
78 78 Wiring for circuit/submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required. 4X2.5 sq.mm + 2X2.5 sq mm earth wire E6 100 Metre
79 79 Wiring for circuit/submain wiring along with earth wire with the following sizes of FR PVC insulated copper conductor, single core cable in surface/recessed medium class PVC conduit as required. 4X4 sq.mm + 2X4 sq.mm earth wire E7 50 Metre
80 80 Supplying and drawing following sizes of FRLS PVC insulated copper conductor, single core cable in the existing surface/recessed steel/ PVC conduit as required 4x 6 Sqmm E8 20 Metre
81 81 Telephone wiring in existing conduit: : Supplying and drawing following pair 0.5 sq mm FR PVC insulated annealed copper conductor, unarmored telephone cable in the existing surface/ recessed steel/ PVC conduit as required. 2 Pair E9 50 Meter
82 82 Supplying and drawing co-axial TV cable RG-6 grade, 0.7 mm solid copper conductor PE insulated, shielded with fine tinned copper braid and protected with PVC sheath in the existing surface/ recessed steel/ PVC conduit as required E10 40 Metre
83 83 Supplying and drawing of UTP 4 pair CAT 6 LAN Cable in the existing surface/ recessed Steel/ PVC conduit as required. 1 run of cable E11 120 Meter
84 84 Modular boxes, bases & cover plate: Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc as required. 5/6 Amps switch E12 32 Each
85 85 Modular boxes, bases & cover plate: Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc as required. 3 pin 5/6 Amp socket outlet E13 32 Each
86 86 Modular boxes, bases & cover plate: Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc as required. 15/16 Amps switch E14 44 Each
87 87 Modular boxes, bases & cover plate: Supplying and fixing following modular switch/socket on the existing modular plate & switch box including connections but excluding modular plate etc as required. 6pin 15/16 Amps (universal) socket outlet E15 44 Each
88 88 Telephone socket outlet E16 3 Each
89 89 Bell Push E17 2 Each
90 90 Supplying and fixing modular blanking plate on the existing modular plate & switch box excluding modular plate as required E18 20 Each
91 91 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required.1 or 2 Module (75 mmX75 mm) E19 20 Each
92 92 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 3 Module (100 mmX75 mm) E20 15 Each
93 93 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 6 Module (200 mmX75 mm) E21 15 Each
94 94 Supplying and fixing following size/ modules, GI box alongwith modular base & cover plate for modular switches in recess etc. as required. 8 Module (200 mmX150 mm) E22 5 Each
95 95 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required 1 or 2 Module (75 mmX75 mm) E23 20 Each
96 96 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 3 Module (100 mmX75 mm) E24 15 Each
97 97 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required . 6 Module (200 mmX75 mm) E25 15 Each
98 98 Supplying and fixing following Modular base & cover plate on existing modular metal boxes etc. as required. 8 Module (200 mmX150 mm) E26 5 Each
99 99 S/F PVC conduit: Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.(ISI Make) : 20 mm E27 120 Meter
100 100 S/F PVC conduit: Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.(ISI Make) : 25 mm E28 50 Meter
101 101 S/F PVC conduit: Supplying and fixing of following sizes of medium class PVC conduit along with accessories in surface/recess including cutting the wall and making good the same in case of recessed conduit as required.(ISI Make) : 32 mm E29 30 Meter
102 102 Supplying and fixing 3 pin, 5 A ceiling rose on the existing junction box/ wooden block including connections etc. as required. E30 40 Each
103 103 Supplying and fixing brass batten/ angle holder including\nconnections etc. as required E31 2 Each
104 104 Supplying and fixing call bell/ buzzer suitable for single phase, 230 V, complete as required. E32 2 Each
105 105 Installation of exhaust fan in the existing opening, including making good the damage, connection, testing, commissioning etc. as required. upto 380 mm sweep E33 6 Each
106 106 Extra for fixing the louvers/ shutters complete with frame for a exhaust fan of all sizes. E34 6 Each
107 107 Supply and Fixing of MCCB Providing and fixing following rating and breaking capacity and pole MCCB with thermomagnetic release and terminal spreaders in existing cubicle panel board including drilling holes in cubicle panel, making connections, etc. as required. 25/35 kA (Ics=100%Icu), 4 pole, current limiting type MCCB having thermal setting range of 80 - 100% with thermal magnetic release having adjustable OL\n 125 A, 25/35 kA, FP MCCB E35 1 Each
108 108 Supply and Fixing Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. FP ISOLATOR 40A E36 4 Each
109 109 Supply and Fixing Supplying and fixing following rating, four pole, 415 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63 A E37 3 Each
110 110 Supply and Fixing DP ISOLATOR : Supplying and fixing following rating, double pole, 240 V, isolator in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 A E38 4 Each
111 111 Supply and Fixing FP RCCB Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 25 A E39 1 Each
112 112 Supply and Fixing FP RCCB Supplying and fixing following rating, double pole, (single phase and neutral), 240 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 A E40 2 Each
113 113 Supply and Fixing of TPN MCB DB Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator) 4 way (8 + 12), Double door E41 2 Each
114 114 Supply and Fixing of TPN MCB DB Supplying and fixing following way, horizontal type three pole and neutral, sheet steel, MCB distribution board, 415 V, on surface/ recess, complete with tinned copper bus bar, neutral bus bar, earth bar, din bar, interconnections, powder painted including earthing etc. as required. (But without MCB/RCCB/ Isolator) 6 way (8 + 18), Double door E42 2 Each
115 115 Supply and Fixing of MCB VDB Supply and installation of sheet steel, phosphatised and painted, dust and vermin proof enclosure of MCB DB including copper /brass bus bar, neutral link, earth bus and DIN rail suitable for fixing MCB/ isolator etc. fixed on wall using suitable anchor bolts or fixed in recess including cutting hole on the wall , making good the damages, colour washing etc. as required 8 way (4 + 24), Double door\n E43 1 Each
116 116 Supply and Fixing OF MCB Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 6/32 A SP MCB E44 56 Each
117 117 Supply and Fixing OF MCB Supplying and fixing 5 A to 32 A rating, 240/415 V, 10 kA, “C” curve, miniature circuit breaker suitable for inductive load of following poles in the existing MCB DB complete with connections, testing and commissioning etc. as required. 40 A Triple pole MCB E45 3 Each
118 118 Supply and Fixing FP RCCB Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required 40A 30 mA E46 1 Each
119 119 Supply and Fixing FP RCCB Supplying and fixing following rating, four pole, (three phase and neutral), 415 V, residual current circuit breaker (RCCB), having a sensitivity current 30 mA in the existing MCB DB complete with connections, testing and commissioning etc. as required. 63A 100 mA E47 3 Each
120 120 END TERMINATIONS Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 4 X 16 sq. mm E48 6 Each
121 121 END TERMINATIONS Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 4 X 25 sq. Mm E49 4 Each
122 122 END TERMINATIONS Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 4 X 35 sq. mm E50 4 Each
123 123 END TERMINATIONS Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 4 X 50 sq. mm E51 2 Each
124 124 END TERMINATIONS Supplying and making end termination with brass compression gland and aluminium lugs for following size of PVC insulated and PVC sheathed / XLPE aluminium conductor cable of 1.1 kV grade as required. 4 X 90 sq. mm E52 2 Each
125 125 Earthing Earthing with copper earth plate 600 mm X 600 mm X 3 mm thick including accessories, and providing masonry enclosure with cover plate having locking arrangement and watering pipe of 2.7 meter long etc. with charcoal/ coke and salt as required E53 2 Each
126 126 Providing and fixing 4.00 mm dia copper wire on surface or in recess for loop earthing as required E54 30 Meter
127 127 Providing and fixing 25 mm X 5 mm G.I. strip in 40 mm dia G.I. pipe from earth electrode including connection with G.I. nut, bolt, spring, washer excavation and re-filling etc. as required. E55 20 Meter
128 128 Providing and fixing 25 mm X 5 mm G.I. strip on surface or in recess for connections etc. as required. E56 30 Meter
129 129 CABLE SUPPLY Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 95 sq mm with factory made clamp E57 25 Metre
130 130 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 50 sq mm with factory made clamp E58 20 Metre
131 131 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 35 sq mm with factory made clamp E59 30 Metre
132 132 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 25 sq mm with factory made clamp E60 35 Metre
133 133 Supply, laying and clamping of 1 no. PVC insulated and PVC sheathed armoured aluminium power cable, 1.1 KV grade of the following sizes using clamps noted along with the cables, spacing of clamps not exceeding 60cms, making good the damages , colour washing etc. as required. 4 core 16 sq mm with factory made clamp E61 40 Metre
134 134 Supply, conveyance, installation, testing and commissioning of pre-wired 36 W LED light fittings 60x60 cms squre with all accessories and LED lamps etc. suspended from ceiling using 2 nos steel chain of length not exceeding 30 cm properly hooked to steel hooks anchored to the ceiling and giving connections with required length of 16/0.20mm 3 core copper conductor flex wire conforming to relevant ISS or extending the original wiring and giving connection etc. as required. E62 11 Each
135 135 S&F Frame for LED Light 60 x 60 E63 11 Each
136 136 1x8W LED lamp including all accessories for mounting on the existing Angle batten E64 2 Each
137 137 SITC of 18 W Round Recess type LED Lamp. (EDGEPRORDDLR 18W LED857S) or equivalent E65 15 Each
138 138 SITC of 18 W LED Tube Light (TITANIASLEEK 1149T5 DSTL18W LED865SPC) or equivalent E66 4 Each
139 139 SITC of 35 W LED Street Light in GI pipe Bend to shape, (ENDURACITY LITEPLATPLUSSL 35W LED757 SASYBOPC) or equivalent E67 2 Each
140 140 Supplying and fixing following Fire and Safety equipments 4 kg FIRE EXTINGUSHERS ( ABC POWDER TYPE With NABL Approval) E68 4 Each
141 141 SUPPLY AND FIXING OF EXHAUST FAN Supplying and Installing by Testing and commissioning of 380 mm Exhaust fan as specified E69 4 Each
142 142 Supplying and Installing by Testing and commissioning of 305 mm Shuttered Exhaust fan in plastix body as specified E70 4 Each
143 143 Supply, conveyance, installation testing and commissioning of the 1 No. Audio System consisting of 45 W medium power PA Amplifier AC & 12 V DC operation (Ahuja) and recess mounting ceiling speakers 6 Nos and 2 Nos box type speaker CS 506IT 6 W RMS power Ahuja PA system and 1 No. DVD player with all accessories best quality Philips / Sony / Samsung / L.G. E71 1 LS
144 144 Painting letters of figures of 2.50 cm, 4cm, 5 cm height etc., E72 50 Each
145 145 RJ 45 Data Outlet E73 10 Each
146 146 Charges for dismantling the existing EI complete making good the damages of the wall and conveying the dismantled materials to store etc., as required E74 15 Each
147 147 63 A, TP MCB (C curve), 10 kA breaking capacity E75 3 Each
148 148 FP enclosure for independent mounting of MCB/ RCCB/ RCBO E76 4 Each
149 149 Supply and providing the following sizes of cast iron gully trap with covering at the top of the inspection chamber of earth pit as required 300 x 300 x 6 mm cast iron gully trap with covering E77 2 Each
150 150 Supply and providing earth lead from the test joint to the earth electrode using the following sizes of conductors/ strips including cutting, drilling necessary holes (in case of strip) and fixing firmly with plate test joint etc as required.25 x 3 mm GI strip E78 30 mtr
151 151 Dismantling the existing electrical line and fittings complete and conveying to the store and handed over the list. E79 40 Each
152 152 Supply and drawing bare earthing conductors of the along with wiring/ cables and giving connection as required. 2.00 mm copper conductor (14 SWG) E80 40 Each
153 153 2.65 mm copper conductor (12 SWG) E81 40 Each
154 154 Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required. 25 sq - 95sq mm with 20 mm wide x 1.20 mm thick clip E82 14 Each
155 155 Supplying and providing earth clamps for siemens/ tropodur type cable glands of suitable length and other dimensions noted along with each size of glands for the following sizes of cables as required. 4sqmm-16 sq mm with 12 mm wide x 1 mm thick clip E83 4 Each
156 156 SITC of 400mm swept area wall fan E84 9 Each
157 157 Supply of LT Switch board cubicle type, made out of 2mm thick CRCA sheet, totally enclosed, IP42, free standing, floor mounting, dust and vermin proof, powder coated, indoor, compartmentalised, suitable for operation on 3 phase and neutral, 415 V, 50Hz AC system with busbars extendable on both sides, including all the necessay internal wiring , suitable spreader etc. The panel shall be fabricated from a firm having CPRI certification with test certificates for similar panel(required for short circuit rating, temperature rise and IP classification) and with following switchgears, metering instruments and accessories etc. complete as required as per drawing & specification. \nIncomer\n160A, FP, MCCB 36kA, Thermal release over load and adjustable short circuit-1 No\nBusbar-200A TPN busbar chamber with Aluminium busbar \nMeters-.\n(0 to 500 )V Voltmeter for 3 phase, 4 wire operation with selector switch - 1 set\n(0-250)A ammeter for 3 phase, 4 wire operation -3 Nos200/5A 15VA class 1 resin cast CT - 3nos\nIntelligent multifunction panel meter (Voltage, Current , kW, kWh, pf, Hz ) with LCD display - 1 no\n4A, C curve SP MCB - 3 Nos, RYB indication lamp, LED type - 3 Nos. Outgoings\n63 A FP Moulded Case Circuit Breaker with thermal release and neutral link (Ics =100%Icu= 25KA).-4 Nos 125 A FP Moulded Case Circuit Breaker with thermal release and neutral link (Ics =100%Icu= 25KA).-1 Nos E85 1 Each
158 158 KSEB METER BOARD\nSupply, installation, testing and commissioning of energymeter box of cubicle construction made from 16SWG CRCA sheet suitable for accomodating one number of Three phase electronic energymeter with 125/5A Class .5 CT and 3 Nos of 160A HRC fuse,160 A FP SFDU and neutral link, interconnections, providing necessary supports made from the same gauge CRCA sheet to fix energymeters, etc.The cubicle shall be provided with hinged door construction and vision panel for the meter compartment. Suitable knock out for cable entry and exit shall be provided. The entire board shall be painted with 2 coats of synthetic enamel paint over a coat of zinc chromate primer etc as required including fixing it on wall, making good the damages colour washing etc. complete. E86 1 Each
Disclaimer :