Military Engineer Services-MES has published Special Repair / Replacement Of Apfc Panel And Certain Sanction Works Under Ge Ludhiana. Submission Date for this Tender is 06-12-2019. Power Factor Panel Tenders in Under GE Ludhiana Punjab. Bidders can get complete Tender details and download the document.
Name of Work: Spacial repair / replacement of APFC panel and certain sanction works under GE Ludhiana. | |||||
---|---|---|---|---|---|
Sl. No. | Item Description | Item Code / Make | Quantity | Units | |
1 | 1 | Sch 'A' | |||
2 | 1.01 | Taking down current transformers any make/capacity complete all as specified & directed by Engineer-in- charge. | 15 | Each | |
3 | 2 | S&F current transformer CT25/5A CL 1 5VA Spare suitable for APFC Panel complete all as specified & directed by Engineer-in- charge.\nMake:- Neptune/Havells/L&T/Indo Asian | 5 | Each | |
4 | 3 | S&F current transformer CT50/5A CL 1 5VA Spare suitable for APFC Panel complete all as specified & directed by Engineer-in- charge.\nMake:- Neptune/Havells/L&T/Indo Asian | 5 | Each | |
5 | 4 | S&F current transformer CT 75/5A CL 1 5VA Spare suitable for APFC Panel complete all as specified & directed by Engineer-in- charge.\nMake:- Neptune/Havells/L&T/Indo Asian | 5 | Each | |
6 | 5 | Taking down power factor controller any make/ capacity complete all as specified & directed by Engineer-in- charge. | 7 | Each | |
7 | 6 | S&F power factor controller relay latest micro controller based tech with true RMS sensing alarm avilable , delay adjustment , LCD display range 08 steps , 7 segment LED display size 144 X 144mm Auxillary supply 90-550 VAC, NTC tempature sensor , power factor measurement range 0.8 lag to 0.8 le suitable for APFC Panel complete all as specified & directed by Engineer-in- charge.Make:- Neptune/Havells/L&T/Indo Asian | 4 | Each | |
8 | 7 | S&F power factor controller relay latest micro controller based tech with true RMS sensing alarm avilable , delay adjustment , LCD display range 12 steps , 7 segment LED display size 144 X 144mm Auxillary supply 90-550 VAC, NTC tempature sensor , power factor measurement range 0.8 lag to 0.8 le suitable for APFC Panel complete all as specified and as directed by Enginner- in- Charge.Make:-Neptune/Havells/L&T/Indo Asian/ C&S electric | 3 | Each | |
9 | 8 | Taking down old capacitor any make/ capacity complete all as specified and as directed by Enginner- in- Charge. | 63 | Each | |
10 | 9 | S&F super heavy duty cylindrical capicitos 5 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and as directed by Enginner- in- Charge.Make:- Neptune/Havells/L&T/Indo Asian | 15 | Each | |
11 | 10 | S&F super heavy duty cylindrical capicitos 10 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and as directed by Enginner- in- Charge.Make:- EPCOS / Neptune /Havells / L&T/Indo Asian | 15 | Each | |
12 | 11 | S&F super heavy duty cylindrical capicitos 15 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and as directed by Enginner- in- Charge.Make:- EPCOS/Neptune/Havells/L&T/Indo Asian | 15 | Each | |
13 | 12 | Supply & fixing super heavy duty cylindrical capicitos 20 KVAr, 3 Phase, 440 V , 50Hz suitable for APFC Panel complete all as specified and as directed by Enginner- in- Charge. Make:- Neptune/Havells/L&T/Indo Asian | 18 | Each | |
14 | 13 | Supply and install ,Commssioning ,testing 125 KVAr APFC Panel with suitable MPP-H heavy duty capacitor with incomer suitable MCCB , 4 pole incl with connector , relay latest micro controller based tech with true RMS sensing alarm avilable , delay adjustment , LCD display 8 stage and MCB 63 Amp for back up protection complete all as specified and as directed by Enginner- in- Charge. Make:- Neptune/Havells/L&T/Indo Asian/ABB/ C&S Electric | 1 | Each | |
15 | 14 | S&F in replacement Power contactor 4P, AC3 -65(2NO, 2NC) of suitable up to 125 KVAR APFC panel ratings for APFC Panels complete all as specified and as directed by Enginner- in- Charge.Make:- Havells/L&T/ Indo Asian / C&S Electric | 10 | Each | |
16 | 15 | S&F in replacement contactor 4P, (4NO, 4NC) of suitable for up to 125 KVAR APFC panel ratings for APFC Panels complete all as specified and as directed by Enginner- in- Charge.Make:- Havells/L&T/Indo Asian / C&S Electric | 10 | Each | |
17 | 16 | S&F in replacement MCCB of current rating 63 Amp 50 Hz having thermal magnetic release with adjustable thermal range, 4 pole, 415 volts, AC, 25 KA rupturing capacity all as specified & directed by Engineer-in- charge.Make:- Havells/L&T/Indo Asian / C&S Electric / Hager | 5 | Each | |
18 | 17 | S&F in replacement MCCB of current rating 100 Amp 50 Hz having thermal magnetic release with adjustable thermal range, 4 pole, 415 volts, AC, 25 KA rupturing capacity all as specified & directed by Engineer-in- charge.Make:- Havells/L&T/Indo Asian / C&S Electric / Hager | 5 | Each | |
19 | 18 | S&F in replacement MCCB of current rating 125 Amp 50 Hz having thermal magnetic release with adjustable thermal range, 4 pole, 415 volts, AC, 25 KA rupturing capacity all as specified & directed by Engineer-in- charge.Make:- Havells/L&T/Indo Asian / C&S Electric / Hager | 6 | Each | |
20 | 19 | S&F in replacement MCCB of current rating 160 Amp 50 Hz having thermal magnetic release with adjustable thermal range, 4 pole, 415 volts, AC, 36 KA rupturing capacity all as specified & directed by Engineer-in- charge.Make:- Havells/L&T/Indo Asian / C&S Electric / Hager | 5 | Each | |
21 | 20 | S&F in replacement MCCB of current rating 250 Amp 50 Hz having thermal magnetic release with adjustable thermal range, 4 pole, 415 volts, AC, 36 KA rupturing capacity all as specified & directed by Engineer-in- charge.Make:- Havells/L&T/Indo Asian / C&S Electric / Hager | 5 | Each | |
22 | 21 | Supply & fixing in replacement MCB three pole 415 volt, 63 Amp, 50 HZ, with 10 KA rupturing capacity 'C' series all as specified & directed by Engineer-in- charge. Make:- Havells/L&T/Indo Asian / C&S Electric / Hager | 12 | Each | |
23 | 22 | Supply & fixing in replacement MCB three pole 415 volt, 32 Amp, 50 HZ, with 10 KA rupturing capacity 'C' series all as specified & directed by Engineer-in- charge. Make:- Havells/L&T/Indo Asian / C&S Electric / Hager | 12 | Each | |
24 | 23 | Supply & fixing in replacement MCB three pole 415 volt, 40 Amp, 50 HZ, with 10 KA rupturing capacity 'C' series all as specified & directed by Engineer-in- charge. Make:- Havells/L&T/Indo Asian / C&S Electric / Hager | 12 | Each | |
25 | 24 | M&L submain wiring with three single core FRLS PVC insulated unsheathed multistranded copper conductor cables of size 4 Sqmm FRLS PVC insulated copper conductor one run green insulation copper conductor cable as earth continuity drawn in and including medium grade PVC rigid non metelic conduit not less than 25mm dia with necessary conduit fittings concaeled in wall including cutting chases and making good the disturbed surface to match the existing surface including taking down existing submain wiring complete all as specified and directed by Engineer-in- charge. | 270 | RM | |
26 | 25 | M&L submain wiring with three single core FRLS PVC insulated unsheathed multistranded copper conductor cables of size 4 Sqmm FRLS PVC insulated copper conductor one run green insulation copper conductor cable as earth continuity drawn in and including medium grade PVC rigid non metelic conduit not less than 25mm dia with necessary conduit fittings concaeled in wall including cutting chases and making good the disturbed surface to match the existing surface complete all as specified and directed by Engineer-in- charge. | 75 | RM | |
27 | 26 | S&F in replacement panel mounted voltmeter three phase incl with CTs/ PT ratio 4 digit display , class 1.0 in 96X96 Sq mm flush mounted case suitable for APFC Panel complete all as specified and directed by Engineer-in- charge. Make:-Neptune/Havells/L&T/Indo Asian | 15 | Each | |
28 | 27 | S&F in replacement panel mounted Ammeter three phase incl with CTs/ PT ratio 4 digit display, class 1.0 in 96X96 Sq mm flush mounted case suitable for APFC Panel complete all as specified and as directed by Enginner- in- Charge.Make:-Neptune/Havells/L&T/Indo Asian | 10 | Each | |
29 | 28 | S&F in replacement of indicator lamp in red, yellow and blue colour with lamp holder multi LED type complete including wiring with copper conductor cable of suitable size complete all as specified and as directed by Enginner- in- Charge. | 10 | Set of Three | |
30 | 29 | S&Fin replacement of slector switch complete including wiring with copper conductor cable of suitable size complete all as specified and as directed by Enginner- in- Charge. | 10 | Set of Three | |
31 | 30 | Supplying, laying, jointing and testing XLPE insulated screened PVC bedded galvanised steel strip or wire armored heavy duty electric power cable 1100 volts grade with stranded aluminium conductor cross sectional area 120 sqmm 3.5 core laid in trenches/ ducts/ along poles/ through pipes including taking out existing cable complete all as specified & directed by Engineer-in- charge. Make: Havells / Finolex / Polycab / CCI | 105 | RM | |
32 | 31 | Supplying, laying, jointing and testing XLPE insulated screened PVC bedded galvanised steel strip or wire armored heavy duty electric power cable 1100 volts grade with stranded aluminium conductor cross sectional area 95 sqmm 3.5 core laid in trenches/ ducts/ along poles/ through pipes including taking out existing cable complete all as specified & directed by Engineer-in- charge. Make: Havells / Finolex / Polycab / CCI | 95 | RM | |
33 | 32 | Supplying, laying, jointing and testing XLPE insulated screened PVC bedded galvanised steel strip or wire armored heavy duty electric power cable 1100 volts grade with stranded aluminium conductor cross sectional area 70 sqmm 3.5 core laid in trenches/ ducts/ along poles/ through pipes including taking out existing cable complete all as specified & directed by Engineer-in- charge. Make: Havells / Finolex / Polycab / CCI | 110 | RM | |
34 | 33 | Excavation in trenches n. exc. 1.5 metre wide for foundations, laying cables and similar works n. exc. 1.5 m deep and getting out in soft/ loose soil complete all as specified & directed by Engineer-in-charge. | 263 | Cum | |
35 | 34 | Excavation in trenches n. exc. 1.5 metre wide for foundations, laying cables and similar works exc. 1.5 m and n. exc. 3.0 m deep and getting out in soft/ loose soil complete all as specified & directed by Engineer-in-charge. | 0.65 | Cum | |
36 | 35 | Returning filling in including spreading, levelling, watering and well ramming in layers not exceeding 25cm thick complete all as specified & directed by Engineer-in-charge. | 156.02 | Cum | |
37 | 36 | Removal of excavated surplus spoil to a distance n. exc. 50m and depositing where directed at level not exceeding 1.5 m above the starting point complete all as specified & directed by Engineer-in-charge . | 106.98 | Cum | |
38 | 37 | M & L brick protection with old size sub class 'B' bricks laid flat across the route of underground cable all as specified and directed by Engineer-in-Charge. | 8.6 | Per 1000 No. | |
39 | 38 | M & L sand cushioning for under ground cable 23cm thick (one layer of 8cm thickness before laying the cable and other layer of 15cm thickness after laying the cable) all as specified and directed by Engineer-in-Charge. | 89.05 | Cum | |
40 | 39 | M&L for painting of panel board inner & outer complete with synthetic enamel paint by spraying including filling cavaties with filler one coat after cleaning all dust/rust including writing the Distribution/Panel Number and panel details all as directed by Engr-in-Charge. Note: The Quoted rates are inclusive of white wash to fountation of Panel Board/ Painting to Angle Frames complete all as specified and directed by Engineer-in-Charge. | 17 | Each Job | |
41 | 40 | Supplying, erecting and fixing in position 8.5 metre long steel tubular swaged pole type 410 SP-22 complete with cast iron base plate, finial taper plug, bolts, nuts & screws conforming to IS-2713 (Part- I & III) of 1980 and painting the pole with two coats of aluminum paint over a coat of primer including black and white strips 30cm each upto 1.5 metre from top of PCC foundation block and numbering of poles in 80mm high white and yellow letter using synthetic enamel paint over base etc complete all as specified and directed by Engineer-in-Charge | 12 | Each | |
42 | 41 | S&F junction box made out of steel of size 300mm x300mmx150mm complete with 100 amp 3 phase and one neutral rated copper bus bar with MS clamp of size 35x6mm and MCB single pole 6 amp inside box and fixed on pole with MS clamp nut bolts and washer etc complete all as specified and directed by Engineer-in-Charge. | 12 | Each | |
43 | 42 | S&F 1100 volt grade heavy duty single core cable FRLS PVC insulated PVC sheathed with stranded copper conductor wire of size 2x2.5 sqmm and 1x2.5 sqmm for connection purpose, ISI marked drawing through 20mm dia with PVC pipe / conduit etc complete all as specified and directed by Engineer-in-Charge. | 365 | RM | |
44 | 43 | Supplying, laying, jointing and testing XLPE insulated screened PVC bedded galvanised steel strip or wire armored heavy duty electric power cable 1100 volts grade with stranded aluminium conductor cross sectional area 25 sqmm 4 core laid in trenches/ ducts/ along poles/ through pipes complete all as specified & directed by Engineer-in- charge. | 755 | RM | |
45 | 44 | S&F MCCB of current rating 100 Amp 50 Hz having thermal magnetic release with adjustable thermal range,ICS=ICU=100%, 4 pole, 415 volts, AC, 16 KA rupturing capacity all as specified & directed by Engineer-in- charge. | 1 | Each | |
46 | 45 | Supply and fixing security light bracket made of 40mm dia GI light grade pipe 1.2 metre long bend to shape including fixing on pole with suitable size of flat iron clamps, nut, bolt etc. complete all as specified and directed. | 12 | Each | |
47 | 46 | S&F LED street light luminarie of 100 watt in epoxy powder coated pressure die-cast aluminium housing of standard size, heat resistant toughned clear glass fixed with SS screws controlled with potted CVCC type, BIS marked electronic driver of approved brand only in housing having protection against over voltage, short circuit and open circuit and surge protection against lightening of 5 KV minimum in circuit and 5 KV outside the driver but inside the fixure with IP-66, Class-1 protection for LED and control gear compartments with high power LED cips of rating 2.5 to 3 watt (maximum) with colour temperature 5700 K (Max) with secondary optics modular independent lenses provided with casing and caping to minimize glare and for beter distribution of light suitable for voltage band 120 volts to 270 volt, power factor 0.95 (minimum) having efficacy 100 lumens/ watt. Brand name should be embossed on fixture to ensure Indian brand only. Make :- Havells, Crompton, Philips, Bajaj | 12 | Each | |
48 | 47 | M & L PCC (1:4:8) type D-2 using 40mm graded stone aggregate as in foundation of electric poles, struts, PCC block including necessary form work and fair finish to exposed surfaces without using extra cement etc. complete all as specified and directed by Engineer-in-Charge. | 0.65 | Cum | |
49 | 48 | M&L PCC (1:3:6) type C-2 using 40mm graded stone aggregate as in coping, stay assembly and struts PCC blocks including necessary form work and fair finishing the exposed surface without using extra cement complete all as specified and directed by Engineer-in-Charge. | 6 | Cum | |
50 | 49 | M&L PCC (1:2:4) type B-1 using 20mm graded stone aggregate as in coping of poles etc. with slightly rounded or chamfered angles including necessary form work and fair finishing the exposed surface without using extra cement complete all as specified and directed by Engineer-in-Charge. | 0.68 | Cum | |
51 | 50 | Supply and fixing connecting and testing energy efficient Water heater storage vertical type powder coated metal body adjustable thermostate megnesium anode for extra protection from corrosion and leakage. Unique temprature idicator dial electricdriven, single phase ,2000 W, 230 volt ,capacity 25 litres .BEE 5 star rated with accessories such as thermostste switch having adjustable knob for tempature setting heating element puessure safty valves indicators including fixing of MS bolts nuts in wall of suitable size complete all as specified and directed by Engineer-in-Charge.\n MAke :- Havells cat part No. GHWAMGTWH025 Crompton greaves / Bajaj\nNote:- i).Incl with incoming and out going water hose(hot & Cold water) | 19 | Each | |
52 | 51 | M&L point wiring complete with 4 Sqmm (nominal cross section area) FRLS PVC insulated unsheathed multistranded copper conductor cable in and including concealed heavy duty PVC conduit including cutting chases in walls and making good the disturbed surface with all jointing accessories including provision of 3mm thick bakelite sheet top cover on new sunken boxes fixed with new brass screws & washers including 4 Sqmm FRLS, PVC insulated unsheathed stranded copper conductor wire as earth continuity to common earth and connecting to earth dolly for one light point/ bell point controlled by one switch or one fan point controlled by one switch through regulator complete all as specified & directed by Engineer-in- charge. | 19 | Per Point | |
53 | 52 | Supply & fixing switch socket combination two-in-one,3 pin, 5 and 15 Amp flush type universal complete all as specified & directed by Engineer - in - Charge.Make: Havells (Reo) / SSK (Top line or Touch / Anchor (Penta) | 19 | Each | |
54 | 53 | Supply & fixing bib tap cast copper alloy with crutch or butterfly handles, screwed down, screwed for iron pipe or for brass ferrule 15mm bore minimum weight 500gms complete, all as specified & directed by Engineer-in-charge. | 19 | Each | |
55 | 54 | Supply & fixing steel water tubes of size 15mm bore (medium grade) galvanised with all fittings and fixed complete to walls and ceiling or laid in floors/ concealed in walls including making good to all distrub surfaces complete, all as specified & directed by Engineer-in-charge. | 170 | RM | |
56 | 55 | Supply & fixing stop valve cast copper alloy screwed down, high pressure with crutch or butterfly handle, screwed both ends for iron pipe or brass ferrule 15mm bore minimum weight 400gms complete all as specified & directed by Engineer-in-charge. | 19 | Each | |
57 | 56 | Earthing complete with galvanised steel earth plate electrode 60 cm x 60 cm x 6mm thick burried directly in ground vertically to a depth not less than 2.25 metre below ground level with top edge of earth plate at a depth of not less than 1.5 metre below ground level, earth plate surrounded by 15cm thick and packed layer of charcoal dust and common salt, connected to earth lead of GI wire 4 mm dia (8 SWG) by means of bolts, nuts and washers of the earth wire.galvanised iron or steel and thimbles and other end of the earth wire connected to earthing test point and protected by galvanised iron pipe light grade 15mm dia and water pipe 20mm dia GI light grade with funnel and wire mesh, PCC chamber in cement concrete (1:3:6) type C-1 and CI cover with frame, 150 mm,filling of black cotton soil in earth pit up to ground level PCC chamber recessed for including RCC cover including all necessary Exacavation &earth work ,earth wire connected to O/H continous earth wire on pole ,testing the earthing after completion all as shown in MES Schedule (Part-I) including dismantling existing earthing complete. \nNotes :- (i) Outer edge of earth pit will be 1.50 metre away from the outer edge of PCC chamber. (ii) GI wire upto DBs earth connection is included in this item. (iii) Water pipe shall be provided in slantling position (iv) Earth wire and protection pipe upto 7.50m length is icluded in the unit rate | 4 | Each |
Copyright © 2024 · All Rights Reserved. Terms of Usage | Privacy Policy
For Tender Information Services Visit : TenderDetail