| 1 | 1 | OVERHEAD LINES TO UNDERGROUND CABLE SYSTEM WORKS | BI01010001010000000000000515BI0100001110 | | |
|---|
| 2 | 1.01 | DGPS SURVEY WORK | BI01010001010000000000000515BI0100001111 | | |
|---|
| 3 | 1.02 | DGPS Survey, Submission of construction drawing of the Existing Electrical System and obtain NOC from various stakeholders:\n\nDetailed Survey of route alignment with covering of existing Distribution Sub-Station along with overhead Transmission/sub-transmission & distribution line , submission of route alignment, profile, final survey and DGPS survey with profile in details indicating road crossing, Electric poles, transformers and other equipment's as per specification. | BI01010001010000000000000515BI0100001112 | 0.7 | Km |
|---|
| 4 | 2 | ELECTRO-MECHANICAL WORKS | BI01010001010000000000000515BI0100001113 | | |
|---|
| 5 | 2.01 | 11kV UNDER GROUND DISTRIBUTION SYSTEM | BI01010001010000000000000515BI0100001114 | | |
|---|
| 6 | 2.02 | 11kV RING MAIN UNIT (RMU) | BI01010001010000000000000515BI0100001115 | | |
|---|
| 7 | 2.03 | 11kV RING MAIN UNIT : 3 way \nOut-Door type RMU, extensible type, at 11kV system volatge and breaking capacity 20kA for 3sec, system comprising of : \na) Two (2) Nos. 11kV, 630Amp. load break switched including earthing switches with making capacity, One (1) No. of VCB, 630A, all enclosed in SF6 filled robotically welded tank with non-magnetic/no-ferritic SS sheets having mechanical ON/OFF, earth indications with fault current indicator for XLPE Aluminium Cable upto 3Cx300Sq.mm. b) Cu Bus - Bar of 630 Amp. rating \nc) Incoming Isolators shall have FPI with electrical reset contact / facility.\nd) All necessary potential-free contacts for indications relevant to RMU monitoring and control.\ne) Capacitor Voltage Dividers serving live-line cable indicators in each LBS/Isolator. | BI01010001010000000000000515BI0100001116 | 4 | Each |
|---|
| 8 | 2.04 | 11kV RING MAIN UNIT : 4 way \nOut-Door type RMU, extensible type, at 11kV system volatge and breaking capacity 20kA for 3sec, system comprising of : \na) Three (3) Nos. 11kV, 630Amp. load break switched including earthing switches with making capacity, One (1) No. of VCB of 630A, all enclosed in SF6 filled robotically welded tank with non-magnetic/no-ferritic SS sheets having mechanical ON/OFF, earth indications with fault current indicator for XLPE Aluminium Cable upto 3Cx300Sq.mm. b) Cu Bus - Bar of 630 Amp. rating \nc) Incoming Isolators shall have FPI with electrical reset contact / facility.\nd) All necessary potential-free contacts for indications relevant to RMU monitoring and control.\ne) Capacitor Voltage Dividers serving live-line cable indicators in each LBS/Isolator. \n | BI01010001010000000000000515BI0100001117 | 2 | Each |
|---|
| 9 | 2.05 | 11kV RING MAIN UNIT : 5 way \nOut-Door type RMU, extensible type, at 11kV system volatge and breaking capacity 20kA for 3sec, system comprising of : \na) Four (4) Nos. 11kV, 630Amp. load break switched including earthing switches with making capacity, One (1) No. of VCB of 630A, all enclosed in SF6 filled robotically welded tank with non-magnetic/no-ferritic SS sheets having mechanical ON/OFF, earth indications with fault current indicator for XLPE Aluminium Cable upto 3Cx300Sq.mm. b) Cu Bus - Bar of 630 Amp. rating \nc) Incoming Isolators shall have FPI with electrical reset contact / facility.\nd) All necessary potential-free contacts for indications relevant to RMU monitoring and control.\ne) Capacitor Voltage Dividers serving live-line cable indicators in each LBS/Isolator. \n | BI01010001010000000000000515BI0100001118 | 3 | Each |
|---|
| 10 | 2.06 | Supply of following sizes TR-XLPE(E) 11KV insulated ISI marked and approved make. Aluminium conductor armoured cables suitable for working voltage upto 11000 volts as per specifications and approved make | BI01010001010000000000000515BI0100001119 | | |
|---|
| 11 | 2.07 | 3CX240 Sqmm. | BI01010001010000000000000515BI0100001120 | 1005 | RM |
|---|
| 12 | 2.08 | 3CX70 Sqmm. | BI01010001010000000000000515BI0100001121 | 90 | RM |
|---|
| 13 | 2.09 | Preparation of Cable Trench by HDD Method\nBoring and Supply & laying of 50 to 150mm dia HDPE pipe direct into the earth of 2500mm depth below the ground surface without effecting the existing road by manually digging/drilling horizontally or diagonically direction for road crossing /water supply line/Telecommunication line/Gas Pipe line etc. including excavation earth for entry pit as per direction of Engineer-in-charge | BI01010001010000000000000515BI0100001122 | 131.4 | RM |
|---|
| 14 | 2.1 | Laying of 11kV POWER CABLES-Through Existing HDPE/DWC pipe: Laying of 11kV TR-XLPE (E) Aluminium conductor armoured cables suitable for working voltage upto 33000Volts of below given sizes in HDPE/ DWC pipe (already laid) in above item, by manual method complete with necessary connections in an approved manner complete as required. | BI01010001010000000000000515BI0100001123 | | |
|---|
| 15 | 2.11 | 3CX240 Sqmm. | BI01010001010000000000000515BI0100001124 | 873.6 | RM |
|---|
| 16 | 2.12 | 3CX70 Sqmm. | BI01010001010000000000000515BI0100001125 | 90 | RM |
|---|
| 17 | 2.13 | Cable Termination - Indoor Type: \nSupply, Erection and commissioning of heat shrinkable type indoor termination along with necessary accessories to accommodate following sizes of 11kV TR-XLPE(E) aluminium cable complete with all kit contents including earth continuity connection along with 3 nos. crimpling type aluminium lugs / thimbles of suitable capacity including making joints etc. in an approved manner complete as required and as per specifications. | BI01010001010000000000000515BI0100001126 | | |
|---|
| 18 | 2.14 | 3CX240 Sqmm. | BI01010001010000000000000515BI0100001127 | 22 | Set |
|---|
| 19 | 2.15 | 3CX70 Sqmm. | BI01010001010000000000000515BI0100001128 | 8 | Set |
|---|
| 20 | 2.16 | Straight Through Joints: \nSupply, Erection and commissioning of heat shrinkable type Three Core H.T Cable straight through joints along with boots (SILCAB-T) to accommodate following sizes of 11kV TR-XLPE(E) aluminium cable complete with all kit contents including earth continuity connection along with 3 nos. crimpling type aluminium lugs / thimbles of suitable capacity including making joints etc.in an approved manner complete as required and as per specifications. | BI01010001010000000000000515BI0100001129 | | |
|---|
| 21 | 2.17 | 3CX240 Sqmm. | BI01010001010000000000000515BI0100001130 | 3 | Set |
|---|
| 22 | 2.18 | Cable Termination - Outdoor Type: \nSupply, Erection and commissioning of heat shrinkable type Outdoor termination along with necessary accessories to accommodate following sizes of 11kV TR-XLPE(E) aluminium cable complete with all kit contents including earth continuity connection along with 3 nos. crimpling type aluminium lugs / thimbles of suitable capacity including making joints etc. in an approved manner complete as required and as per specifications. | BI01010001010000000000000515BI0100001131 | | |
|---|
| 23 | 2.19 | 3CX240 Sqmm. | BI01010001010000000000000515BI0100001132 | 6 | Set |
|---|
| 24 | 2.2 | 3CX70 Sqmm. | BI01010001010000000000000515BI0100001133 | 2 | Set |
|---|
| 25 | 3 | Supply, Installation, Testing, & Commissioning of 3 Phase, 11/0.4kV, 50Hz oil immersed outdoor type Distribution Transformer DYN11, off-load tap changer of rating +5% to -5% @2.5%. Temp Rise - Oil/Winding 40/50 Deg cel. Losses and Impedance as per IS-1180:2014 Energy Efficiency Level-02, with all necessary fittings and accessories on existing structure complete as required of below givens ratings: | BI01010001010000000000000515BI0100001134 | | |
|---|
| 26 | 3.01 | 100kVA 11/0.4KV Distribution Transformer | BI01010001010000000000000515BI0100001135 | 1 | Nos. |
|---|
| 27 | 3.02 | 200kVA 11/0.4KV Distribution Transformer | BI01010001010000000000000515BI0100001136 | 2 | Nos. |
|---|
| 28 | 3.03 | 315kVA 11/0.4KV Distribution Transformer | BI01010001010000000000000515BI0100001137 | 1 | Nos. |
|---|
| 29 | 3.04 | Providing and erection of DP structure as per enclosed drawings including supply of poles, 10Kgf/cm2 100mm dia heavy duty finolex make PVC pipe for protection of cable, hot dipped structural sections for mounting transformers/RMU & chain pulley block and required clamps for fitting cables, structures, 100mm dia PVC pipe etc with all hardwares, suitable M.S. grill fencing with hinged door entry with suitable locking arrangement RMU/Transformer centra and its accessories such as clamps, hardwares, pipe etc with necessary muffing with PCC for commissioning of 11kV/400V Distribtion Transformers of different capacity as per approved drawings of engineer in charge including the dismentalling of pole mounted existing distribution transformer. | BI01010001010000000000000515BI0100001138 | 4 | Each |
|---|
| 30 | 3.05 | Pipe Earthing: \nEarthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal and salt as required. | BI01010001010000000000000515BI0100001139 | 26 | Set |
|---|
| 31 | 3.06 | Earth Strip: \nSupply and Erection of GI tape 25mm x 5 mm thick from earth electrode directly in ground and surface fixed with GI stapples of same size. | BI01010001010000000000000515BI0100001140 | 182 | RM |
|---|
| 32 | 3.07 | Copper Strip: \nSupply and Erection of GI tape 25mm x 5 mm thick from earth electrode directly in ground and fixed with brass nut bolts. | BI01010001010000000000000515BI0100001141 | 56 | RM |
|---|
| 33 | 3.08 | Supply and fixing of below given sizes HDPE pipe as per IS of different length as per requirement using for cable riser to overhead lines and other purpose, Pipe should be proper tie up with poles by the help of MS clamp and nuts bolts etc. | BI01010001010000000000000515BI0100001142 | | |
|---|
| 34 | 3.09 | 110 mm dia | BI01010001010000000000000515BI0100001143 | 24 | RM |
|---|
| 35 | 3.1 | 50 mm dia | BI01010001010000000000000515BI0100001144 | 12 | RM |
|---|
| 36 | 4 | LT UNDER GROUND DISTRIBUTION SYSTEM | BI01010001010000000000000515BI0100001145 | | |
|---|
| 37 | 4.01 | LV Distribution Box: \n\nSupply, Erection, Testing, Commossioning of L.T Distribution Box for the existing DT`s with the following switchgears and otehr necessary accessories and inbuilt padlocking facility, etc. required to complete the job as per specification and detailed technical parameters. | BI01010001010000000000000515BI0100001146 | | |
|---|
| 38 | 4.02 | 100 kVA DTR\n200A, 4P, 25KA MCCB with T/M release with following accessories:\nMultifunction Digital Meter with LCD display Ampere, Voltage Combined CTs, Control Fuses & Phase LED Lights.\nBUSBARS:\n4 Pole, Alum. With heat shrinkable sleeves in following capacities:\n300A, 400V, 50Hz. 25KA, 4 Strips, Aluminium with heat shrinkable sleeves.\nOUTGOINGS:\n100A, 4Pole MCCB-25KA with T/M protection - 2 Sets\n3 Phase 4 Wire energy meter - 2 nos. | BI01010001010000000000000515BI0100001147 | 1 | No. |
|---|
| 39 | 4.03 | 200 kVA DTR\n400A, 4P, 25KA MCCB with T/M release with following accessories:\nMultifunction Digital Meter with LCD display Ampere, Voltage Combined CTs, Control Fuses & Phase LED Lights.\nBUSBARS:\n4 Pole, Alum. With heat shrinkable sleeves in following capacities:\n500A, 400V, 50Hz. 25KA, 4 Strips, Aluminium with heat shrinkable sleeves.\nOUTGOINGS:\n160A, 4Pole MCCB-25KA with T/M protection - 3 Sets\n3 Phase 4 Wire energy meter - 3 nos. | BI01010001010000000000000515BI0100001148 | 2 | Nos. |
|---|
| 40 | 4.04 | 315 kVA DTR\n630A, 4P, 36KA MCCB with T/M release with following accessories:\nMultifunction Digital Meter with LCD display Ampere, Voltage Combined CTs, Control Fuses & Phase LED Lights.\nBUSBARS:\n4 Pole, Alum. With heat shrinkable sleeves in following capacities:\n800A, 400V, 50Hz. 36KA, 4 Strips, Aluminium with heat shrinkable sleeves.\nOUTGOINGS:\n160A, 4Pole MCCB-25KA with T/M protection - 5 Sets\n3 Phase 4 Wire energy meter - 5 nos. | BI01010001010000000000000515BI0100001149 | 1 | No. |
|---|
| 41 | 4.05 | Supply of following sizes 1.1KV Al. TR-XLPE insulated ISI marked and approved make. Aluminium conductor armoured cables suitable for working voltage upto 1100 volts as per specifications and approved make | BI01010001010000000000000515BI0100001150 | | |
|---|
| 42 | 4.06 | 1Core 185 Sqmm | BI01010001010000000000000515BI0100001151 | 4288 | Each |
|---|
| 43 | 4.07 | 4Core 70 Sqmm | BI01010001010000000000000515BI0100001152 | 295 | Each |
|---|
| 44 | 4.08 | 4Core 50 Sqmm | BI01010001010000000000000515BI0100001153 | 81 | Each |
|---|
| 45 | 4.09 | Preparation of Cable Trench by HDD Method:\n\nBoring and Supply & laying of 50 to 150mm dia HDPE pipe direct into the earth of 2500mm depth below the ground surface without effecting the existing road by moling / manually digging/drilling horizontally or diagonically direction for road crossing /water supply line/Telecommunication line/Gas Pipe line etc. including excavation earth for entry pit as per direction of engineer in charge | BI01010001010000000000000515BI0100001154 | 125.97 | RM |
|---|
| 46 | 4.1 | Laying of LV CABLES - Through HDPE/DWC pipe: \n\nLaying of 1.1kV TR-XLPE (E) Aluminium conductor armoured cables suitable for working voltage upto 1100Volts of below given sizes in n HDPE/DWC pipe (already laid) in above item, by manual method complete with necessary connections in an approved manner complete as required. | BI01010001010000000000000515BI0100001155 | | |
|---|
| 47 | 4.11 | 1Core 185 Sqmm | BI01010001010000000000000515BI0100001156 | 3860 | RM |
|---|
| 48 | 4.12 | 4Core 70 Sqmm | BI01010001010000000000000515BI0100001157 | 266 | RM |
|---|
| 49 | 4.13 | 4Core 50 Sqmm | BI01010001010000000000000515BI0100001158 | 73 | RM |
|---|
| 50 | 4.14 | Laying of LV CABLES - In Open Air: \n\nLaying of following size TR-XLPE(E) 1.1kV (LV) Aluminium conductor armoured cables suitable for working voltage upto 1100Volts, in open air (From Distribution Transformer to LTDB) including necessary connections digging in ordinary rocky soil and refilling with primary compaction of trenches including proper dressing of the cable in an approved manner complete as required. | BI01010001010000000000000515BI0100001159 | | |
|---|
| 51 | 4.15 | 1Core 185 Sqmm | BI01010001010000000000000515BI0100001160 | 215 | RM |
|---|
| 52 | 4.16 | 4Core 70 Sqmm | BI01010001010000000000000515BI0100001161 | 15 | RM |
|---|
| 53 | 4.17 | 4Core 50 Sqmm | BI01010001010000000000000515BI0100001162 | 5 | RM |
|---|
| 54 | 4.18 | LV CABLES - End Termination: \n\nSupply and Erection of Termination kits comprising of double brass compression gland and aluminium lugs. for 1100 V grade XLPE insulated PVC sheathed aluminium wire wound armouring for single core and galvanized steel strip wound armoured for multicore 'Aluminium conductor' power cable of the following sizes as per enclosed detailed specifications and relevent IS. | BI01010001010000000000000515BI0100001163 | | |
|---|
| 55 | 4.19 | 1Core 185 Sqmm | BI01010001010000000000000515BI0100001164 | 120 | Set |
|---|
| 56 | 4.2 | 4Core 70 Sqmm | BI01010001010000000000000515BI0100001165 | 24 | Set |
|---|
| 57 | 4.21 | 4Core 50 Sqmm | BI01010001010000000000000515BI0100001166 | 20 | Set |
|---|
| 58 | 4.22 | Supplying, Installation, testing and commissioning of OUTDOOR TYPE, compartmentalized, double door Feeder Pillars fabricated out of suitable size angle iron and flats and covered with 2mm thick cold rolled CRCA sheet, weather proof powder coated painting etc., complete with Al. Bus Bar, inter-connection with solid/stranded copper conductor wire/copper strips, glands neutral links, name plate and pad locking facility etc. including the following switchgears etc., complete as required with detailed specification: | BI01010001010000000000000515BI0100001167 | | |
|---|
| 59 | 4.23 | 6Way FP-TYPE A\nINCOMING:\n160A, 4P, 25KA MCCB with T/M release \nBUSBARS:\n4 Pole, Alum. With heat shrinkable sleeves in following capacities:\n200A, 415V, 50Hz. 25KA, 4 Strips, Aluminium with heat shrinkable sleeves.\nOUTGOINGS:\n10A, SPN MCB-10KA with T/M protection - 14 Sets\n32A, TPN MCB-10KA with T/M protection - 2 Sets\n125A, FP MCCB-25KA with T/M protection - 1 Set\n\n | BI01010001010000000000000515BI0100001168 | 3 | Nos. |
|---|
| 60 | 4.24 | 6Way FP-TYPE B\nINCOMING:\n125A, 4P, 25KA MCCB with T/M release \nBUSBARS:\n4 Pole, Alum. With heat shrinkable sleeves in following capacities:\n150A, 415V, 50Hz. 25KA, 4 Strips, Aluminium with heat shrinkable sleeves.\nOUTGOINGS:\n10A, SPN MCB-10KA with T/M protection - 14 Sets\n32A, TPN MCB-10KA with T/M protection - 2 Sets\n125A, FP MCCB-25KA with T/M protection - 1 Set\n\n | BI01010001010000000000000515BI0100001169 | 9 | Nos. |
|---|
| 61 | 4.25 | 6Way FP-TYPE C\nINCOMING:\n100A, 4P, 25KA MCCB with T/M release \nBUSBARS:\n4 Pole, Alum. With heat shrinkable sleeves in following capacities:\n150A, 415V, 50Hz. 25KA, 4 Strips, Aluminium with heat shrinkable sleeves.\nOUTGOINGS:\n10A, SPN MCB-10KA with T/M protection - 14 Sets\n32A, TPN MCB-10KA with T/M protection - 2 Sets\n100A, FP MCCB-25KA with T/M protection - 1 Set\n\n | BI01010001010000000000000515BI0100001170 | 6 | Nos. |
|---|
| 62 | 4.26 | 6Way FP-TYPE D\nINCOMING:\n63A, 4P, 16KA MCCB with T/M release \nBUSBARS:\n4 Pole, Alum. With heat shrinkable sleeves in following capacities:\n100A, 415V, 50Hz. 25KA, 4 Strips, Aluminium with heat shrinkable sleeves.\nOUTGOINGS:\n10A, SPN MCB-10KA with T/M protection - 14 Sets\n32A, TPN MCB-10KA with T/M protection - 3 Sets\n\n | BI01010001010000000000000515BI0100001171 | 10 | Nos. |
|---|
| 63 | 4.27 | Pipe Earthing: \nEarthing with G.I. earth pipe 4.5 metre long, 40 mm dia including accessories and providing masonry enclosure with cover plate having locking arrangement and watering pipe etc. with charcoal and salt as required. | BI01010001010000000000000515BI0100001172 | 56 | Set |
|---|
| 64 | 4.28 | 6SWG Earth Wire: \nProviding & laying earth connection from earth electrode with 6 SWG GI Wire from earth electrode | BI01010001010000000000000515BI0100001173 | 280 | RM |
|---|
| 65 | 4.29 | Erection/Mounting of LV Feeder Pillars on Road Lighting Poles/ any others structures | BI01010001010000000000000515BI0100001174 | 28 | Nos. |
|---|
| 66 | 4.3 | Service Cable Connection: | BI01010001010000000000000515BI0100001175 | | |
|---|
| 67 | 4.31 | Provision of Undergrounding Service Cable including excavation, refilling for each 1-Phase consumers with 2x6Sqmm Al. unarmoured cable in 20mm dia HDPE pipe | BI01010001010000000000000515BI0100001176 | 7840 | RM |
|---|
| 68 | 4.32 | Provision of Undergrounding Service Cable including excavation, refilling for each 3-Phase consumers with 4x6Sqmm Al. unarmoured cable in 20mm dia HDPE pipe | BI01010001010000000000000515BI0100001177 | 1120 | RM |
|---|
| 69 | 4.33 | MISCELLANEOUS WORK | BI01010001010000000000000515BI0100001178 | | |
|---|
| 70 | 4.34 | Dismantling of exisitng overhead network (including poles, conductors and other accessories) and shifting them to designated space as directed by department and Engineer-in-Charge. | BI01010001010000000000000515BI0100001179 | 2.5 | Km |
|---|
| 71 | 4.35 | CIVIL WORKS | BI01010001010000000000000515BI0100001180 | | |
|---|
| 72 | 4.36 | Civil Foundation work RMU: a) Earth work in excavation for ordinary rocky soil including disposal of excavated earth, lead up to 50 m and lift up to 1.5 m, disposed earth to be levelled and neatly dressed. b)Cement contrete 1:4:8 (1 cement : 4 coarse sand : 8 graded stone aggregate 40 mm nominal size) for foundation, plinth & barricating works c) Providing and laying in position specified grade of reinforced cement concrete, excluding the cost of centering, shuttering, finishing and reinforcement work for RCC raft 1:1:2 (1 cement : 1 coarse sand : 2 graded stone aggregate 20 mm nominal size) d) Steel reinforcement for R.C.C. work including straightening, cutting, bending, placing in position and binding etc. e) Centering and shuttering including strutting, propping etc. and removal of form for foundations & barricating works f)Providing 15mm thick cement plaster of mix 1:4 ( 1 cement : 4 fine sand) g)Rough iron and mild steel (using flats square bars tees and channels ladders grills grattings framed window guards iron door opendable or fixed staircase or parapet or any other type of railings gates and tree guards etc. including cost of screws and welding rods or bolts and nuts complete fixed in position. h) Providing and fixing of wire mesh jali around the RMU of size upto 8'x4' made out of wire mesh 1\"x1\"square including fixing in cement 1:2:4 including welding cutting etc. Complete in all respect i) Provision & fixing of 140mm. dia PVC pipes j) Provisiding & fixing of HT Danger board duly painted with enamel paint. | BI01010001010000000000000515BI0100001181 | 3 | Each |
|---|
| 73 | 5 | STREET LIGHT SYSTEM | BI01010001010000000000000515BI0100001182 | | |
|---|
| 74 | 5.01 | Octagonal Street Light Pole | BI01010001010000000000000515BI0100001183 | | |
|---|
| 75 | 5.02 | Supply, installation, testing and commissioning of following type of Octagonal Street Light Pole. The pole shaft shall have octagonal cross section and shall be continuously tapered with single longitudinal welding. There shall not be any circumferential welding of the pole shaft. The welding of the pole shaft shall be done by Submerged Welding process. All octagonal pole shafts shall be provided with the rigid flange plate of suitable thickness with provision for fixing 4 foundation bolts. The base plate shall be fillet welded to the pole shaft at two locations i.e. from inside and outside.The octagonal poles shall be bolted on a pre- cast foundation with a set of four foundation bolts for greater rigidity.Octagonal poles shall withstand the maximum wind speed of 180 km/hr. Maximum deflection of the poles considering top loading ie area and weight of fuxture shall meet the requirement of BS:5649 Part VI 1982. The materials of the pole as follows : Conforming to grade S355JO Base Plate:- Fe 410 Conforming to IS 226/ IS 2062, Foundation Bolts:- 6.8 Gr. As per IS 1367. The poles shall be hot dip galvanized as per IS 2629 / IS 2633 / IS 4759 standards with average coating thickness of 65 micron. The galvanizing shall be done in single dipping. Door opening :- The Octagonal poles shall have door of approximate 500 mm length at the elevation of 500 mm from the base plate. The door shall be vandal resistance and shall be weather proof to ensure safety of inside connection as approved by the Depts.. The door shall be flush with the exterior surface and shall have suitable locking arrangement. The pole shall be adequately strengthened at the location of the door compensate for the loss in section. There shall also be suitable arrangement for the purpose of earthing, Smart pack Junction box with 6 MCB & Terminals for mounting inside base compartment of Pole. | BI01010001010000000000000515BI0100001184 | | |
|---|
| 76 | 5.03 | 9m pole with inbuilt Junction box:\nSize of pole : Diameter : Dia 130 mm, Sheet thickness: 3 mm;Junction box: 6 MCB & Terminals for mounting inside base compartment of Pole. Base Plate Dimensions :- (L x B x 260 x 260 x 16, Foundation Bolt Size :- (no. x dia.) 4 x 24 Dia, Pitch Circle Dia.:- (PC 250 Bolt Length:- 750, Projected Bolt Length :-125 Anchor plate thickness :- 4 mm , Pole Foundation:- The foundation shall be done with ( Earth work 6.0 cubic Meters. RCC 1:1.5 : 3 proportion 0.65 cubic metres. Steel :- 23 Kg. Shuttering:- 4.6 square metres. | BI01010001010000000000000515BI0100001185 | 27 | Nos. |
|---|
| 77 | 5.04 | Supplying including fitting and fixing of Hot Dip galvanised arm bracket for installation of luminaries. \nHeader with top cap 300 mm long pipe of thickness 3mm with arrangement to fix on pole top with 3 Nos. of bolts. Armed shall be of 48.3mm out side dia and shall be 3.25mm thick. | BI01010001010000000000000515BI0100001186 | | |
|---|
| 78 | 5.05 | Single arm bracket 1500mm long for 3m to 10 metre. Poles | BI01010001010000000000000515BI0100001187 | 27 | Nos. |
|---|
| 79 | 5.06 | Light Fixtures | BI01010001010000000000000515BI0100001188 | | |
|---|
| 80 | 5.07 | Supply, installation, testing and commissioning of following type of LED Luminaires. The housing of the luminaries shall be Epoxy powder coated pressure die-cast aluminium and its cover shall be tempered protective toughened glass.It shall have inbuilt driver with THD <15%;Overvoltage protection,surge voltage protection etc as per IS 15885.The fixture shall have IP protection of IP66 and impact resistance of IK07.The fixture shall comply with Powerfactor>0.9;CRI>70;Colour Temperature >5500k;System Lumen Efficacy>100lm/W | BI01010001010000000000000515BI0100001189 | | |
|---|
| 81 | 5.08 | 140W LED Street light lumaries with and with the lumen level of 12000 lm. Philips Fixture Model no BRP322 LED 157 CW NR FG with Dimmable Driver or equivalent for Street lighting | BI01010001010000000000000515BI0100001190 | 27 | Nos. |
|---|
| 82 | 5.09 | Smart Lighting Control System | BI01010001010000000000000515BI0100001191 | | |
|---|
| 83 | 5.1 | Supply, installation, testing and commissioning of Smart Streetlight Switching Feeder Panel:- (Group Control with Dimming Control)\n(1) Rating 10KVA, \n(2)I/C & O/G Breaker :- 63A TPN MCB \n(3)Energy Meter :- 3Ph 10-60A Class 1 Accuracy Meter as per IS-13779 \n(4)Battery Back Up :6Hr \n(5)Communication Module:- Bidirectional GSM communication with server \n(6)SMPS for Communication Module \n(7)Theft alert \n(8)Data Backup :-days \n(9)Enclosure IP Protection:-IP54/65 \n(10) Measurement:-Voltage /current/Power factor/Active power/Apperent Power \n(11)Alerts:-Phasewise OC and SC Fault/Low pf/Phase wise over voltage/Group faliur of Light | BI01010001010000000000000515BI0100001192 | 1 | No. |
|---|
| 84 | 5.11 | LT Cables & Termination | BI01010001010000000000000515BI0100001193 | | |
|---|
| 85 | 5.12 | Supply, installation, testing and commissioning of 1100 Voltage grade,4C x 16sq mm A2XFY stranded Aluminium, XLPE insulated, inner and outer extruded PVC sheathed, galvanized Flat ARMORED cables laid in hume pipes/ trenches, Miscellaneous items such as clamp, cleat cable tags etc.are included in the scope. Removal of empty drums & making site normal as instructed by Client is included in the scope. | BI01010001010000000000000515BI0100001194 | 875 | RM |
|---|
| 86 | 5.13 | Supply, installation, testing and commissioning of Cable end terminations for 1100 Voltage grade, stranded Aluminium, XLPE insulated, inner and outer extruded PVC sheathed,galvanized steel round wire/ flat strip ARMORED power cables including stripping of cable insulation, supply and fixing of Aluminium lugs for aluminium cables for all phases and crimping the same to the conductor, supply and fixing of Double compression weather proof cable glands for 4C x 16sq mm. | BI01010001010000000000000515BI0100001195 | 54 | Nos. |
|---|
| 87 | 5.14 | Supply, installation, testing and commissioning of 3C X 2.5Sqmm flexible Copper conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Unarmoured, extruded PVC Type ST2 Sheathed, 650/1100 V grade as per IS 7098 (Part 1) 1988 . | BI01010001010000000000000515BI0100001196 | 243 | RM |
|---|
| 88 | 5.15 | Supply, installation, testing and commissioning of Termination of 3C X 2.5Sqmm flexible Copper conductor, XLPE Insulated, cores laid up, PVC tape inner sheathed, Unarmoured, extruded PVC Type ST2 Sheathed, 650/1100 V grade as per IS 7098 (Part 1) 1988. | BI01010001010000000000000515BI0100001197 | 54 | Nos. |
|---|
| 89 | 5.16 | Earthing | BI01010001010000000000000515BI0100001198 | | |
|---|
| 90 | 5.17 | Supplying & laying of 8 SWG G.I. earth from Earth Electrode (below G.L.) to electrical switch gears or electrical machineries including making necessary connection as approved, specified and directed by the deptt. and the Engineer-in-Charge. | BI01010001010000000000000515BI0100001199 | 1070.5 | RM |
|---|
| 91 | 5.18 | Supply and Laying of 25X6mm GI strip at a deth of 0.5m below ground as strip earth electrode, including termination/ interconnecting with GI Nut/Bolts, washer, Spring washer etc. as required. Jointing shall be done b yoverlapping & with two sets of Nut/ bolts and spring washer spaced at 50mm apart for earthing of the Street light panels. | BI01010001010000000000000515BI0100001200 | 14 | RM |
|---|
| 92 | 5.19 | Supply, installation & testing of G.I. earth station with perforated 50 mm dia and 3.00 Metre long heady duty G.I. pipe with necessary 50 mm dia. G.I. Fittings such as Socket, Tee, elbow, nipple and 65 mmx50 mm G.I. reducing socket for funnel including locking arrangement 300 mmx300 mmx6 mm hinged cover C.I. earth plate complete with digging of earth pit, construction of brick chamber and plastering of both inner & outer surface of wall. | BI01010001010000000000000515BI0100001201 | 9.9 | Nos. |
|---|
| 93 | 5.2 | Supply and providing of Extra salt 5 Kg and Charcoal 64 Kg in pipe Earth Station pit to provide low impedance ground in location of high soil resistivity as and when required and specified by the Deptt.and the Engineer-in-Charge. | BI01010001010000000000000515BI0100001202 | 9.9 | Nos. |
|---|
| 94 | 5.21 | Civil Works | BI01010001010000000000000515BI0100001203 | | |
|---|
| 95 | 5.22 | Supplying, laying of HDPE Pipe /DUCT IS 4984: 1995 as required in the existing trench, through micro tunneling, as directed and specified by the department. | BI01010001010000000000000515BI0100001204 | | |
|---|
| 96 | 5.23 | 50 mm PE63 GRADE PN4 | BI01010001010000000000000515BI0100001205 | 787.5 | RM |
|---|
| 97 | 5.24 | Horizontal Drilling (HDD) Method: \nBoring and Supply & laying of 50 to 150mm dia HDPE pipe direct into the earth of 2500mm depth below the ground surface without effecting the existing road by moling / manually digging/drilling horizontally or diagonically direction for road crossing /water supply line/Telecommunication line/Gas Pipe line etc. including excavation earth for entry pit as per direction of the Engineer-in-charge. | BI01010001010000000000000515BI0100001206 | 87.5 | RM |
|---|
| 98 | 5.25 | Dismantling of existing LED Street Light Fixtures of various wattages with Bracket from Electric pole including carring & handling charge for shifting to proper place as specified and directed by the deptt. and the Engineer-in-Charge. | BI01010001010000000000000515BI0100001207 | 25 | Nos. |
|---|
| 99 | 6 | OPERATION & MAINTENANCE | BI01010001010000000000000515BI0100001208 | | |
|---|
| 100 | 6.01 | Operation & Maintenance for 1st Year for Underground Electro-Mechanical Works | BI01010001010000000000000515BI0100001209 | 1 | Year |
|---|
| 101 | 6.02 | Operation & Maintenance for 1st Year for Street Lighting | BI01010001010000000000000515BI0100001210 | 1 | Year |
|---|
| 102 | 6.03 | Operation & Maintenance for 2nd Year for Underground Electro-Mechanical Works | BI01010001010000000000000515BI0100001211 | 1 | Year |
|---|
| 103 | 6.04 | Operation & Maintenance for 2nd Year for Street Lighting | BI01010001010000000000000515BI0100001212 | 1 | Year |
|---|
| 104 | 6.05 | Operation & Maintenance for 3rd Year for Underground Electro-Mechanical Works | BI01010001010000000000000515BI0100001213 | 1 | Year |
|---|
| 105 | 6.06 | Operation & Maintenance for 3rd Year for Street Lighting | BI01010001010000000000000515BI0100001214 | 1 | Year |
|---|
| 106 | 6.07 | Operation & Maintenance for 4th Year for Underground Electro-Mechanical Works | BI01010001010000000000000515BI0100001215 | 1 | Year |
|---|
| 107 | 6.08 | Operation & Maintenance for 4th Year for Street Lighting | BI01010001010000000000000515BI0100001216 | 1 | Year |
|---|
| 108 | 6.09 | Operation & Maintenance for 5th Year for Underground Electro-Mechanical Works | BI01010001010000000000000515BI0100001217 | 1 | Year |
|---|
| 109 | 6.1 | Operation & Maintenance for 5th Year for Street Lighting | BI01010001010000000000000515BI0100001218 | 1 | Year |
|---|