Provision Of Servo Stabilizer, Provision Of 1X40 Kva Ups For 59 Weu, Special Repairs To Lt/Oh Lines And Distribution System And Certain Minor Works Under Aor Of Age E/M Of Ge 862 Ews
Tender Value
40.50 Lakhs
Estimated cost
Bid Submission
25 Nov 2019
0 days left
EMD
81000
Bank guarantee accepted
Document Fee
500
Non-refundable
Tender Type
Online
Tender Overview
Organization
Tender ID
Competition Type
NCB
Bidding Type
Tender
Location / State
GE 862 EWS → Jammu And Kashmir
EMD Exemption
Not Available
Quantity
Not Available
Website
Contact Person
Address
Project Description
Provision Of Servo Stabilizer, Provision Of 1X40 Kva Ups For 59 Weu, Special Repairs To Lt / Oh Lines And Distribution System And Certain Minor Works Under Aor Of Age E / M Of Ge 862 Ews
BOQ
| Name of Work: Provn of Servo stabilizer, Provn of 1x40 KVA UPS for 59 WEU, Spl repairs to LT/OH lines and distribution system and certain minor works under AOR of AGE E/M of GE 862 EWS | |||||
|---|---|---|---|---|---|
| Sl.No. | Item Description | Item Code / Make | Quantity | Units | |
| 1 | 1 | Servo Voltage Stabilizer for automatic operation, three phase naturally oil cooled indoor type & designed for input variation between 340 V to 460 V with output voltage stabilized at 415 with accuracy ± 2.5% and speed of correction 8 Volts per second of capacity 300 KVA complete all as specifed and directed. | 1 | Each | |
| 2 | 2 | Servo Voltage Stabilizer for automatic operation, three phase naturally oil cooled indoor type & designed for input variation between 340 V to 460 V with output voltage stabilized at 415 with accuracy ± 2.5% and speed of correction 8 Volts per second of capacity 200 KVA complete all as specifed and directed. | 1 | Each | |
| 3 | 3 | Supply, laying and testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor 1100 volts grade of size 95 sqmm 3½ core complete all as specified and directed. | 70 | RM | |
| 4 | 4 | Supply, laying and testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor 1100 volts grade of size 185 sqmm 3½ core complete all as specified and directed. | 80 | RM | |
| 5 | 5 | Earthing complete with galvanized steel earth plate electrode of size 60cm X 60 cm X 6 mm buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5 m below the normal ground level connected to GI earth strip 32 X 6 mm dia as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, protected by GI pipe light grade 15mm bore from earth plate to main switch board/panel, watering pipe 20mm dia with wire mesh and funnel to top all as shown on electrical plate No 3 of SSR Part-I connected to earth test point electrode, PCC pit with RCC cover, etc and testing on completion complete all as specified and directed.\nNote No 1 :- The unit rate shall also include for earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I.\nNote No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required | 4 | Each set | |
| 6 | 6 | Excavation in trenches not exceeding 1.5 m wide and not exceeding 1.5 m depth for laying of cable, foundation of poles or sturts and getting out in any type of soil complete all as specified and directed. | 363 | CUM | |
| 7 | 7 | Excavation in trenches exceeding 1.5 m depth but not exceeding 3.00m depth for laying of cable, foundation of poles or struts and getting out in any type of soil complete all as specified and directed. | 1 | CUM | |
| 8 | 8 | Returning, filling in, including spreading leveling watering and well ramming in layers not exceeding 25 cm thick complete all as specified and as directed | 176 | CUM | |
| 9 | 9 | Removing excavated material not exceeding 50 m and depositing where directed at a level not exceeding 1.5 m above the starting point complete all as specified and directed by Engineer-in-Charge. | 200 | CUM | |
| 10 | 10 | Sand cushioning to underground cable, provided with a layer 8 cm before and 15 cm after laying and stretching jointing and testing the cable complete all as specified and as directed\nNote: Punned thickness of sand shall be measured.\n | 136 | CUM | |
| 11 | 11 | Brick covering with width equal to length of brick as mechanical protection to cable using sub class ‘B’ bricks laid flat, size 230mm x 115mm x 75mm, complete all as specified and as directed | 14130 | Each | |
| 12 | 12 | Supply, installation, testing and commissioning for 'ON' line UPS 40 KVA three phase with 100 AH battery 12 Volt-32 Nos, DC-circuit breaker, Battery rack, connectors, links etc, for one hour back up of the following specification. Make : APC/SUKAM BEC/Front LINE/Microtex/Birla Yamha | 1 | Each | |
| 13 | 12.01 | Technology\nIGBT based high frequency pulse with modulation operated inverter, Charger SCR Bridge constant Voltage/Current type with current limit for protection of battery | |||
| 14 | 12.02 | Input Voltage\n380 to 440 volt (AC mains) three phase input | |||
| 15 | 12.03 | Input frequenty\n50 HZ + 6% | |||
| 16 | 12.04 | Output frequenty\n50 HZ + 0.5% | |||
| 17 | 12.05 | Harmonic Distortion\n< 5% THD AT FULL LOAD | |||
| 18 | 12.06 | Output Waveform at Full load\nPure Sine Wave | |||
| 19 | 12.07 | Crest Factor : 3:1 | |||
| 20 | 12.08 | Load Power Factor : 0.8 lagging to unity | |||
| 21 | 12.09 | Over Load : 110 % for 10 Min | |||
| 22 | 12.1 | Inverter Efficiency : > 85 % | |||
| 23 | 12.11 | Prtection : Spikes - RFI EMI fuse protection for charger and inverter, Battery low shut down, overload & short ckt output over voltage | |||
| 24 | 12.12 | Inverter : Overlaod, short circuit, over voltage & under voltage | |||
| 25 | 12.13 | Rectifier/Charger- Over load, short circuit, Line interference | |||
| 26 | 12.14 | Battery : Overcharging and over discharging | |||
| 27 | 12.15 | Input/Output : Input/Output MCB | |||
| 28 | 12.16 | Indication : Input and output voltage and circuit indicators mains on inverter on UPS on battery, battery low, output low, output high overload and inverter trip | |||
| 29 | 12.17 | Audio Alarm : Battery low voltage, output low output high , overload battery high and inverter trip | |||
| 30 | 12.18 | Audiable noise : less than 45 DBA at 1.0 meter | |||
| 31 | 12.19 | Battery Voltage : 360 DC voltage | |||
| 32 | 12.2 | Type of cooling : Forced air cooling | |||
| 33 | 12.21 | Battery complete Dischare : Inverter should cut off automatically | |||
| 34 | 12.22 | Mains to battery transfer time : Zero time | |||
| 35 | 12.23 | Battery : 10 AH 12 Volts = 32 Nos | |||
| 36 | 12.24 | Efficiency : > 90 % in inverter mode | |||
| 37 | 13 | Supply, laying and testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor 1100 volts grade of size 70 sqmm 3½ core complete all as specified and directed. | 920 | RM | |
| 38 | 14 | MCCB 63 Amp, 3 Pole 50 HZ 415 V with rupturing capacity 35 KA complete all as specified and directed by Engineer-in-Charge. | 1 | Each | |
| 39 | 15 | Sheet metal enclosure MCB distribution board three pole & neutral 240 volts 4 way with IP-43 IK-09 protection double door complete with appropriate size bus bar and neutral link,fixed flush in wall including chases wall for fixing DB and making good distributed wall surfaces to match with existing specification complete all as specified and as directed by Engr-in-Charge. | 2 | Each | |
| 40 | 16 | MCB single pole 240 volts any rating from 5 to 30 amps, with rupturing capacity 10 KA, including providing thimble for out going cables. | 24 | Each | |
| 41 | 17 | MCB TPN 415 volts any rating 63 amps, with rupturing capacity 10 KA, including providing thimble for out going cables complete all as specified and as directed by Engr-in-Charge. | 2 | Each | |
| 42 | 18 | Sub main wiring complete with 4 runs of 10 sqmm single core PVC insulated unsheathed FRLS cable 1100 volts grade multi stranded copper conductor cable along with two run of 6 sqmm single core PVC insulated FRLS cable 1100 volts grade multi stranded copper conductor as earth continuity conductor drawn through and incl rigid PVC conduit and conduit accessories fixed on wall/floor/ceiling etc all as specified and as directed. Note: Six runs of cable and one run of conduit shall be measured as one unit. | 50 | RM | |
| 43 | 19 | Earthing complete with galvanized steel earth plate electrode of size 60cm X 60 cm X 6 mm buried directly in ground (earth pit not less than 2.25m deep below the normal ground level) with top edge of plate not less than 1.5 m below the normal ground level connected to GI earth strip 25 X 4 mm dia as earth lead by means of bolts, nuts, check nuts and washers of galvanized iron or steel, protected by GI pipe light grade 40mm bore all as shown on electrical plate No 3 of SSR Part-I connected to earth test point electrode, PCC pit with RCC cover, watering pipe 20mm dia, funnel with wire mesh etc and testing on completion complete all as specified and directed.\nNote No 1 :- The unit rate shall also include for earth work in hard/dense soil, PCC (1:3:6) type C1 chamber, RCC 1:2:4 type B-1 cover 50 mm thick reinforced with 8 mm dia TMT bar @ 150 mm c/c both ways, funnel with watering pipe 20 mm dia medium grade, GI protection pipe light grade 40 mm dia and wire mesh complete in addition to item No 1 (a) to (e) of preamble (Notes) under sub-heading earthing, specified on Serial Page No 389 of SSR Part –I.\nNote No 2 :- Earthing strip and GI protection pipe beyond 7.5 m will be measured and paid separately if required | 4 | Each set | |
| 44 | 20 | Dismantling and taking down broken LT PCC electric pole/struts of any size including embeded portion of PCC complete all as specified and directed by Engineer-in-Charge | 8 | Each | |
| 45 | 21 | Replacement of LT overhead lines on existing poles with 1100V grade LT Aerial Bunched cable having three power core and one neutral-cum-messenger core of stranded compacted circular Aluminum Black coloured XLPE insulated & core indentification by ridges, one, two, three and four respectively. One street lighting Core of stranded, compacted Circular Aluminum conductor, (Ph Wire + St light wire+ messenger-cum-neutral wire (3x95 sqmm+1x16sqmm +1x70 sqmm). Messenger-Cum-Neutral wire should be of stranded compacted circular Aluminum Alloy Conductor conforming to IS 8130/1984, IS-398 (Part-IV)/1979 and IS-14255/1995 with upto date amendments, if any including accessories required for hanging and existing connections ie Anchor Clamp (3-Bolts and 2 Bolt type), Eye hook with suspension clamp Assembly, pole clamp, insulation piercing connectors with cover or PG connectors with insulation cover, Water proof pre-insulated Hexagonal Compression Connectors & Lugs etc complete all as specified and directed by Engineer-in-Charge | 275 | RM | |
| 46 | 22 | Replacement of LT overhead lines on existing poles with 1100V grade LT Aerial Bunched cable having three power core and one neutral-cum-messenger core of stranded compacted circular Aluminum Black coloured XLPE insulated & core indentification by ridges, one, two, three and four respectively. One street lighting Core of stranded, compacted Circular Aluminum conductor, (Ph Wire + St light wire+ messenger-cum-neutral wire (3x70 sqmm+ 1x 16 sqmm+1x50 sqmm). Messenger-Cum-Neutral wire should be of stranded compacted circular Aluminum Alloy Conductor conforming to IS 8130/1984, IS-398 (Part-IV)/1979 and IS-14255/1995 with upto date amendments, if any including accessories required for hanging and existing connections ie Anchor Clamp (3-Bolts and 2 Bolt type), Eye hook with suspension clamp Assembly, pole clamp, insulation piercing connectors with cover or PG connectors with insulation cover, Water proof pre-insulated Hexagonal Compression Connectors & Lugs etc complete all as specified and directed by Engineer-in-Charge | 300 | RM | |
| 47 | 23 | Supply and errect in truly vertical position steel tubular swaged pole 09 mtr long with cast iron base plate 6mm thick, finial taper plug, bolts, nuts and screws as specified type 410 SP-31, including painting one under coat with anti corrosive primer and two coats of aluminium paint and in the botton above ground level alternative white & black strips of 30 cm width upto 1.5 mtr above ground level and marking pole No complete all as specifed and directed. \nNote :- Earth work, excavation and PCC in foundation, coping etc be measureed and paid separately under respective items. | 10 | Each Job | |
| 48 | 24 | PCC 1:4:8 (normal mix) type D-2 using 40mm graed crushed stone aggregates, as in foundation filling and mass concrete of poles and stay/installation paths complete all as specified and directed. | 0.5 | CUM | |
| 49 | 25 | PCC 1:3:6 (normal mix) type C-1 using 20mm graded crushed stone aggregate as in coping of poles and the like complete including weathering, slightly rounded or chamfered angles and throating all as specified and directed. | 7 | CUM | |
| 50 | 26 | PCC 1:2:4 (normal mix) type B-1 using 20mm graded crushed stone aggregate as in coping of poles and the like complete including weathering, slightly rounded or chamfered angles and throating all as specified and directed. | 1 | CUM | |
| 51 | 27 | Dismantling ACSR conductor complete all as specified and directed by Engineer-in-Charge. | 3 | Qtl | |
| 52 | 28 | Cross Arms, bracings, supports, clamps (including stya clamps, clamps for fixing GI tubes for passing through of cables) and back plates fabricated out of standrd steel sections including nuts, bolts, washers, welding, bending cold or hot, drilling holes for botls in any shape or size as directed and inclusive of providing two coats of aluminum paint over a coat of primer after preparation of steel surfaces including taking down old complete all as specified and directed. | 1 | Qtl | |
| 53 | 29 | Earthing complete with galvanised cast iron earth plate electrode of size 600x600x6mm thick as earth electrode with top edge of the earth plate not less than 2.25mtr below ground level using GI wire 4mm dia as earth continuity conductor connected to earth plate by means of GI thimbles nuts bolts washers all as directed including providing earth wire protection pipe GI light grade15mm dia from earth plate to main switch board/panel, watering pipe 20mm dia with wire mesh and funnel at top, earth pit and RCC pit cover in PCC 1:3:6 adequate quantity of charcoal dust and salt all around the earth plate, earth work in any type of soil removing surplus excavated material all as required at site and specified in EP No 3 of SSR part I 2009. | 4 | Each set | |
| 54 | 30 | GI pipe 50mm dia light grade (ISI marked) with all fitting laid in trenches or on pole, crossing of roads, fixed on wall for protection of cable complete all as specified and directed. | 10 | RM | |
| 55 | 31 | Service cable 10 sqmm 2 core 1100 volts grade heavy duty cable PVC insulated stranded aluminum conductor, served with an inner sheathing of PVC tape and overall PVC sheathed in service connections suspended by insulating hangers not more than 1 mtr apart including 4mm suspension wire or drawn in and including medium grade non metalic rigid PVC donduit as per site requiredment, flat or circular complete all as specified and directed. | 200 | RM | |
| 56 | 32 | Bus bar chamber of suitable size with 4 strips 200 amps bus bar aluminum alongwith MCCB of 100 Amps, FP Adjustable type duly connected to aluminum strip at incoming side with suitable space for 2 incoming cables and outgoing of 2 cables. Bus bar fixed on insulators in zig-zag positions, clearance in each strip and clearance at both side should not be less than 125mm with sufficient working space, height of bus bar chamber not less than 1 mtr, mounted MS angle 50x50x6mm, made of CRCA sheet 2mm thick outdoor type, powder coated, both side opending, shutter in two halves, cable opening from bottom side with indicators R, Y, B hinges through out the length of shutter with half turn locking arrangement, including grouting in PCC, complete all as specified and directed by Engineer-in-charge. Note : Size of Bus Bar should not be less than 600 MM x 900mm x 350mm. Make of Bus bar should be CPRI approved | 5 | Each | |
| 57 | 33 | Sheet metal terminal box of size 30cm x 30cm x 15cm made out of 2 mm thick CRCA sheet, factory made powder coated consisiting of aluminium bus bar of size 20 x 3mm - 04 Nos and MCB SP 10 Amps-01 No complete all as specified and directed. | 25 | Each | |
| 58 | 34 | Supply and fix cable 4 sqmm 2 core flat 1100 volt grade heaby duty cable PVC insulated stranded aluminum conductor, served with inner sheathing of PVC tape and overall PVC sheathed in for connection of street light from junction box, drawn in and including medium grade ISI marked non metalic rigid PVC conduit as per site requirement complete all as specified and directed. | 320 | RM | |
| 59 | 35 | Supply, laying and testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor 1100 volts grade of size 10 sqmm 4 core complete all as specified and directed. | 900 | RM | |
| 60 | 36 | Supply, laying and testing cable XLPE insulated screened PVC bedded, galvanized steel strip or wire armoured, electric power cables (heavy duty) with stranded aluminium conductor 1100 volts grade of size 50 sqmm 3.5 core complete all as specified and directed. | 350 | RM | |
| 61 | 37 | Voltage Stabilizer for automatic operation, single phase naturally air cooled indoor type & designed for input variation between 150 to 280 with output voltage stabilized at 240 volts with accuracy ± 10% 50 Hz of capacity 5 KVA complete all as specifed and directed. | 6 | Each | |
| 62 | 38 | Sub main wiring complete with 2 single core PVC insulated unsheathed FRLS cable 1100 volts grade multi stranded copper conductor cable of size 6 x 2 sqmm along with one single core PVC insulated unseathed FRLS flexible copper conductor cable greent colour of size 4 sqmm as earth continuity conductor drawn through and non metalic rigid PVC conduit medium grade and conduit accessories fixed on wall/floor/ceiling etc all as specified and as directed. | 168 | RM | |
| 63 | 39 | Sheet metal enclosure with socket plug top and with one MCB single pole 40 Amps complete all as specified Make: Havells/Legrand/ABB | 6 | Each | |
| 64 | 40 | Rotational moulded polythylene water storage tank (ISI marked) with float valve, plastic lid cover, double layered, cylindrical vertical with closed top hoisted and fixed in position of capacity 5000 ltrs and making connections inlcuding suitable GI wash out, over flow, nipple and including ball valve of PTMT with epoxy coated Aluminium rod & high density plastic ball screwed for iron pipe and fixed. (minium weight 15mm-142 gms complete all as specifed and directed. | 2 | Each | |
| 65 | 41 | Cutting the exisitng tubing and inserting new tee of suitable size including necessary screwing, threading, tail pieces, short pieces, jointing materila etc complete all as specified and directed. | 1 | Each Job | |
| 66 | 42 | GI tubing medium grade 25 mm bore galvanized iron with all fittings such as bends, socket, Tee, Elbow, union, Nipple, short pieces and fixed to walls, ceilings or laid in floors complete all as specifed and directed. | 6 | RM | |
| 67 | 43 | Gun-metal, globe or gate valves 25mm bore , with iron wheel head, screwed both ends for iron pipe and fixed complete all as specified and directed. | 1 | Each | |
| 68 | 44 | PCC 1:2:4 (normal mix) type B-2 using 40mm graded crushed stone aggregate as in mass concrete complete all as specified and directed. | 1.5 | CUM | |
| 69 | 45 | Note:- The contract sum arrived after deduction of amount of Sch of credit as listed in tender Documents. |
AI Tender Summary
Tender Timeline
Nov 04, 2019
11:30 IST
Tender Published
Tender notice published.
CompletedNov 25, 2019